DLRO10HD QUICK START GUIDE
P1
C1
Line input
Line input
fuse
Line
connected
indicator
Power and
mode
selector
switch
Contrast adjust
Current flow
indicator
Measurement terminals
P2
C2
Probe LED indicator plug/socket
HV warning indicator
Backlight ON/OFF
Test active indicator
Test START/STOP
Range selector switch
Line voltage connected
Battery level
Over temperature
Noise present
Refer to user guide warning
High voltage warning
G SAFETY WARNINGS
nThese safety warnings must be read and understood before the instrument is used.
nWhenever possible, circuits should be de-energised before testing.
If it is impossible to de-energise the circuit, (e.g. high voltage batteries cannot be switched off while their connections are tested) the user must be aware of the dangers. The instrument terminals will become live when connected to the circuit. Therefore when used on hazardous voltages the Megger
terminal cover (part number 1002-390) must be used.
nTesting inductive circuits can be hazardous. Following testing an inductive load it must be discharged
before disconnecting the test leads. Refer to the User Guide for more information.
BASIC GUIDE TO OPERATION
n This instrument can operate from battery or line voltage. The battery will charge when line voltage is connected. n Display backlight is turned on by pressing the backlightJ button and contrast is adjusted by
repetitively pressing contrast
n Fasten leads to respective measurement terminals ensuring C and P terminals are not swapped. n Attach test leads to unit under test if applicable to lead set being used. n Select highest resistance range on the range selector switch. n Turn on instrument by rotating power and mode switch to desired position. n Adjust measurement range as required
MODES
Automatic modes - bidirectional
and undirectional current flow
Normal mode - test current
applied in both directions
Instrument is off in this
position
C
button.
Continuous mode - test current applied in both directions, test repeated at 3 seconds intervals
Inductive mode - test current applied in one direction only
Part no. 2000-436 Artwork V04