MEGGER LT300 Installation Manual

LT300
High current loop testers
High current loop tester
Single and 3 phase testing
16 Hz to 400 Hz operation
CATIV 300 V applications
Two wire lead set or mains plug leads
Tough armoured case
Built-in cover
LT300
High Current Loop Testers
DESCRIPTION
The LT300 offers high current loop testing over a wide range of frequencies and supply voltages with simple, fast, two wire operation.
It has a large clear display that aids visibility in poor conditions.
wo models are available:
LT300-EN-00 - with red/green leads
T300-EN-BS - with BS1363 mains plug lead
L
The high current loop test provides fast accurate and stable results with a resolution to 0.01 on the 20 range.
equency range
Fr
Supply frequency is indicated upon connection to the
. This will automatically set to the measured supply
supply frequency either 16 Hz, 50/60 Hz or 400 Hz. T commence automatically.
Loop Impedance measurement:
wo loop impedance ranges are provided.
T 20 - Resolution to 0.01 200 - Resolution to 0.1
Supply voltage:
Operational supply range extends from 50 V to 550 V (400 V @ 16 Hz), with a warning for voltages over 330 V high­lighting accidental phase to phase connections on a nominal 230 V system.
esting will
Single Phase CATIV 300 V phase to earth, as well as 550 V phase to phase applications (400 V @ 16 Hz)
GENERAL
The instrument is housed in a rubber armoured case with a built-in cover to protect the display when not in use.
The IP54 weatherproof rating provides excellent protection in adverse conditions.
The instrument is supplied with either a two wire (red/green) lead set, or a mains plug test lead for access to wall sockets, a certificate of test and a hard carry case.
LT300
High Current Loop Testers
SPECIFICATION
Voltage measurement range
Voltage range: 0 V to 550 V (400 V @ 16 Hz) Accuracy: ±5% ±2 V
Loop test operating frequencies
16 Hz 15 Hz to 18 Hz
50/60 Hz 40 Hz to 70 Hz
400 Hz 260 Hz to 490 Hz
Test currents
20 Range 200 Range
550 V 27 A 2.7 A
230 V 12 A 1.2 A
115 V 6 A 0.6 A
50 V 3 A 0.3 A
Loop test accuracy
Loop resistance:
0 to 19.99 (20 range) ±5% ±0.03 0 to 199.9 (200 range) ±5% ±0.5
EMC
In accordance with IEC61326 including amendment No.1
Weight: 980gms (2.16lb)
Dimensions: 203 x 148 x 78mm ( 8 x 5.8 x 3 in)
Environmental
Operating temperature: -10°C to +60°C
Storage temperature: -25°C to +70°C
Humidity: 90%RH @+40°C
Maximum altitude: 2,000 m
Dust and water: IP54
Battery: 8 x AA (LR6) alkaline or NiMH rechargeable cells.
Safety
Meets the requirements of 300 V CA Phase to Phase (400 V @ 16 Hz).
EN61557
Complies with the following parts of EN61557,Electrical safety in low voltage systems up to 1000 V a.c. and 1500 V d.c. Equipment for testing, measuring or monitoring of protective measures:
t1 - General Requirements
ar
P Part3 - Loop resistance
TIV phase to ear
th or 550 V
ORDERING INFORMA
Item (Qty)
High current loop tester with red/green lead set LT300-EN-00
High current loop tester with BS1363 mains plug lead LT300-EN-BS
Included Accessories
Red/green 2 wire test lead set (LT300-EN-00) 6220-784 Mains plug test lead (BS1363) (LT300-EN-BS) 6220-810
TION
Order Code
Loading...