Megger LT300 Specifications

LT300
High current loop testers

High current loop tester

Single and 3 phase testing

16 Hz to 400 Hz operation


Two wire lead set or mains plug leads

Tough armoured case
LT300
High current loop testers
DESCRIPTION
The LT300 offers high current loop testing over a wide range of frequencies and supply voltages with simple, fast, two wire operation.
It has a large clear display that aids visibility in poor conditions.
Two models are available:
LT300-EN-00 - with red/green leads
LT300-EN-BS - with BS1363 mains plug lead
LT300-EN-FS - with fused red/green leads
The high current loop test provides fast accurate and stable results with a resolution to 0.01 Ω on the 20 Ω range.
Frequency range
Supply frequency is indicated upon connection to the supply. This will automatically set to the measured supply frequency either 16 Hz, 50/60 Hz or 400 Hz. Testing will commence automatically.
Loop Impedance measurement:
Two loop impedance ranges are provided.
20 Ω - Resolution to 0.01 Ω
200 Ω - Resolution to 0.1 Ω
Supply voltage:
Operational supply range extends from 50 V to 550 V (400 V @ 16 Hz), with a warning for voltages over 330 V highlighting accidental phase to phase connections on a nominal 230 V system.
Single Phase CATIV 300 V phase to earth, as well as 550 V phase to phase applications (400 V @ 16 Hz)
GENERAL 1
The instrument is housed in a rubber armoured case with a built-in cover to protect the display when not in use.
The IP54 weatherproof rating provides excellent protection in adverse conditions.
The instrument is supplied with either a two wire (red/green) lead set, or a mains plug test lead for access to wall sockets, a certificate of test and a hard carry case.
SPECIFICATION
Voltage measurement range
Voltage range: 0 V to 550 V (400 V @ 16 Hz)
Accuracy: ±5% ±2 V
Loop test operating frequencies
16 Hz 15 Hz to 18 Hz, 33 Hz, 29 Hz to 337 Hz
50/60 Hz 40 Hz to 70 Hz, 125 Hz, 100 Hz to 142 Hz
400 Hz 260 Hz to 498 Hz
Test currents
20 ½ Range 200 ½ Range
550 V 27 A 2.7 A
230 V 12 A 1.2 A
115 V 6 A 0.6 A
50 V 3 A 0.3 A
Loop test accuracy
Loop resistance:
0 to 19.99 ½ (20 ½ range) ±5% ±0.03 ½
0 to 199.9 ½ (200 ½ range) ±5% ±0.5 ½
Environmental
Operating temperature: -10°C to +60°C
Storage temperature: -25°C to +70°C
Humidity: 90%RH @+40°C
Maximum altitude : 2,000 m
Dust and water: IP54
Battery: 8 x AA (LR6) alkaline or NiMH
rechargeable cells.
Safety
Meets the requirements of IEC61010-1 300 V CATIV phase to earth
or 550 V Phase to Phase (400 V @ 16 Hz).
EN61557
Complies with the following parts of EN61557,Electrical safety in low voltage systems up to 1000 V a.c. and 1500 V d.c. Equipment for testing, measuring or monitoring of protective measures:
Part1 - General Requirements
Part3 - Loop resistance
EMC
In accordance with IEC61326-1
Weight: 980gms (2.16lb)
Dimensions: 203 x 148 x 78mm ( 8 x 5.8 x 3 in)
LT300