Testing the quality of the grounding system has been a critical part of any
electrical maintenance program for many years. Ground electrodes are
used to provide a safe path to earth for the dissipation of fault currents,
lightning strikes, static charges and EMF/RFI signals. Over time, ground
systems deteriorate due to either environmental conditions or catastrophic
events (like lightning strikes). Alternatively, facility expansion may change
needs in the installed ground system.
The risks from ground system deterioration include potentially deadly
electrical shocks, plant-wide equipment damage, disruption in the
performance of sensitive electrical equipment, heat build-up and
eventually fire on a single piece of electrical equipment and disruption
in digital communication service. Grounding systems present a unique
challenge because they are out of site, buried beneath the soil. The
only way to ensure that the system remains capable of dissipating fault
currents is to measure its resistance periodically.
Good grounding protects people and equipment and improves the
performance of sensitive electronic equipment. The bonding to the
ground system is also a critical part of the system. Testing the quality
of grounds and bonding should be an active part of any electrical
maintenance strategy. Ground (or earth) testing is done to determine the
effectiveness of the ground system and connections to protect personnel
and equipment and ensure optimal equipment performance. Fall of
potential (and its variants) was the only method of testing ground system
integrity until the 1980s. Clamp-on, or stake-less, ground testing first
appeared in the 1980s and has gained in popularity and acceptance in the
years since its introduction.
This booklet will focus on the clamp-on method of ground testing and
is designed to give the reader a better understanding of the test method
and where it can and cannot be used. Factors that a technician may
want to consider when selecting a clamp-on ground tester will also be
addressed. Please refer to Megger’s booklet “Getting Down to Earth” for
further information on fall of potential tests and soil resistivity tests.
2 1-866-254-0962 www.megger.com
Clamp-On Testing versus Fall of Potential Testing
Fall of Potential Testing
As mentioned, clamp-on, or stake-less, ground testing is a relatively
new method of determining the quality of a ground system. The fall of
potential method dates back to the 1930s and is based on the research
of H.B. Dwight. It is the most accurate way of measuring and confirming
ground rod resistance, but it has several major disadvantages. The basic
methodology follows. This booklet will not go into the theory or math
behind this method.
Proper fall of potential testing involves placing a current probe in the soil
at a distance from the ground electrode being tested (please note that
the ground electrode must be disconnected from the system). The actual
distance is determined by the size of the ground electrode/system. The
ground tester is then connected to the ground electrode under test, the
current probe and a potential probe. The potential probe is placed in the
soil at distances of 10%, 20%, 30%, up to 90% of the distance between
the ground electrode and the current probe and a reading is taken at
each location. The readings are then plotted against the distances and the
point where the curve flattens is the approximate resistance of the ground
electrode (see figure below).
Guide to Clamp-on Ground Testing 3
The fall of potential method is extremely reliable, as the results can be
checked by testing at different current probe distances. This built-in proof
capability means that results do not have to be accepted on faith. The
operator has complete control of the test set-up. This method can be
used on any size ground system as long as the current probe can be
placed far enough from the ground system under test. It conforms to IEEE
81 and is IEEE approved. In an ideal world, fall of potential would be the
only method used. Unfortunately, nothing is ideal and this method has
three important disadvantages:
1. It is exceedingly time consuming and labor intensive. Temporary probes
must be placed and moved. Cables must be run. Readings must be
taken and plotted.
2. The operator must disconnect the ground electrode to make the test.
As a result, the system is not protected during the test. The ground
electrode must then be reconnected after the test, which, in addition
to being time consuming, leaves the possibility for error if it is poorly
bonded.
3. In real-world situations, space constraints can make it difficult to place
the remote probes.
Clamp-On Testing
The clamp-on ground tester is an effective and time-saving method when
used correctly because the user does not have to disconnect the ground
system to make a measurement or place probes in the ground. The theory
behind this method and the methodology itself will be covered in more
detail later in this booklet. The method is based on Ohm’s Law, where
R (resistance) = V (voltage) / I (current). The clamp includes a transmit coil,
which applies the voltage and a receive coil, which measures the current.
The instrument applies a known voltage to a complete circuit, measures
the resulting current flow and calculates the resistance (see figure on next
page).
4 1-866-254-0962 www.megger.com
The clamp-on method requires a complete electrical circuit to measure.
The operator has no probes and therefore cannot set up the desired test
circuit. The operator must be certain that earth is included in the return
loop. The clamp-on tester measures the complete resistance of the path
(loop) that the signal is taking. All elements of the loop are measured in
series. The method assumes that only the resistance of the ground
electrode under test contributes significantly. Based on the math behind
the method (to be reviewed later), the more returns, the smaller the
contribution of extraneous elements to the reading and, therefore, the
greater the accuracy.
The major advantage of the clamp-on method is that it is quick and
easy. The ground electrode does not have to be disconnected from the
system to take the measurement and no probes need to be driven and
no cables connected. In addition, it includes the bonding and overall
connection resistance. Good grounding must be complemented by
“bonding”, having a continuous low-impedance path to ground. Fall of
potential measures only the ground electrode, not the bonding (leads
must be shifted to make a bonding test). Because the clamp-on uses the
grounding conductor as part of the return, an “open” or high resistance
bond will show up in the reading. The clamp-on ground tester also allows
Guide to Clamp-on Ground Testing 5
the operator to measure the leakage current flowing through the system.
If an electrode has to be disconnected, the instrument will show whether
current is flowing to indicate whether it is safe to proceed.
Unfortunately, the clamp-on ground tester is often misused in applications
where it will not give an effective reading. The clamp-on method is
effective only in situations where there are multiple grounds in parallel. It
cannot be used on isolated grounds as there is no return path. Therefore,
it cannot be used for installation checks or commissioning new sites.
It also cannot be used if an alternate lower resistance return exists not
involving the soil (such as with cell towers). Unlike with fall of potential
testing, there is no way of proofing the result, meaning the results must
be taken on “faith.” The clamp-on ground tester does fill a role as one
tool that the technician could have in his “bag”, but not the only tool.
Clamp-On Ground Testing Theory and Methodology
Understanding how and why the clamp-on method works helps in
understanding where it will and will not operate, and how to optimize its
use. As mentioned, the clamp-on test method is based on Ohm’s Law
(R = V/I). Understanding Ohm’s law and how it applies to series and
parallel circuits is the first step to understanding how and why a clamp-on
ground tester works. The following graphics will show a series circuit, a
parallel circuit and a series-parallel circuit, and the math used to determine
the total current and resistance.
Series Circuit
In a series circuit, total current and total resistance are calculated as
follows: It = I1 = I2 = I
Rt = R1 + R2 + R
6 1-866-254-0962 www.megger.com
3
3
Parallel Circuit
In a parallel circuit, total current and total resistance are calculated as
follows:
It = I1 + I2 + I
3
Rt = 1/ (1/R1 + 1/R2 + 1/R3)
Parallel-Series Circuit
In a parallel-series circuit, total current and total resistance are calculated
as follows:
It = I1 + I2 = I3 = I4 + I
5
Rt = 1/ (1/R1 + 1/R2) + 1/ (1/R3 + 1/R4)
Guide to Clamp-on Ground Testing 7
Clamp-On Test Methodology
The head of a clamp-on
ground tester includes two
cores (see figure at right). One
core induces a test current
and the other measures how
much was induced. The input
or primary voltage of the
test current inducing core is
kept constant, so the current
actually induced into the test
circuit is directly proportional
to the loop resistance.
The important thing to
remember with clamp-on
testing is that clamp-on
ground testers effectively
make loop resistance
measurements. Clamp-on
measurements are loop
measurements. For the clamp-on method to work there must be a seriesparallel resistance path (and the lower the better). The more electrodes or
ground paths in the system the nearer the measurement gets to the actual
electrode under test’s true resistance. The following figure shows a pole
ground configuration, one of the most effective applications of the clampon ground tester.
8 1-866-254-0962 www.megger.com
Loading...
+ 22 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.