Advanced Earth (Ground) Tester
 High resolution of 1 mΩ, ideal for large earth
(ground) systems
 Versatile test modes
 High accuracy for earth (ground) electrode grid and
soil resistivity tests
 Rechargeable battery power that can last all day
with a fast re-charge (up to 10 hours)
 Robust instrument with IP65 protection
 Automatic test frequency selection, with filters
and high current features
 Diagnostic trace display
 Data storage
 Large colour display that shows numeric and
graphical results
DET2/3
Advanced earth (ground) tester
DESCRIPTION
The Megger® DET2/3 automatic earth (ground) test instrument is robust, compact and designed to measure earth Electrode Resistance and Soil Resistivity. It provides a full range of test methods and excels at the four terminal method of measurement, which eliminates the resistance of the current circuit from the measurement.
Soil Resistivity measurements are used to establish the optimum electrode design and site, as well as archaeological and geological investigations.
FEATURES
High accuracy earth
The DET2/3 provides accurate 1 mΩ resolution measurements of earth (ground) electrode resistance.
With its microprocessor controlled system it provides a flexible and ‘user-friendly’ approach to earth tests by the provision of excellent error detection capabilities and full test information shown on a large colour display.
Test frequency, test voltage and filtering can be quickly and easily adjusted so that adverse conditions, which can influence the test, can be overcome.
A wide band of test frequencies, with a resolution of 0.5 Hz, can be used to eliminate errors caused by noise in the earth.
(ground) measurements
The DET2/3 also includes an automatic frequency selection feature that scans for frequencies with the lowest noise level and then runs
a test at that frequency.
Continuity measurements and bonding
n Single resistance range: One fully automatic range from
0.01 Ω to 1.0 kΩ
n Display: Three digit display
n Accuracy: ±3% (±2 digits)
n Short circuit current: 200 mA continuity test currents
n Lead null: Lead resistance compensation (NULL) operates with
a lead resistance up to 10 Ω
Trace display and data storage
Utilising the latest processors, the DET2/3 can provide a live trace of its measurements, which graphically shows the amount of noise from the system under test - a powerful diagnostic tool for the expert earth (ground) test engineer.
Use of the latest processors and a large internal memory allows for immediate calculations of resistivity (Wenner or Schlumberger method) and the ability to save a complete day’s worth of test results.
Test result data can be downloaded directly through a USB flash drive or straight to a Windows PC running PowerDB™ software.
DET2/3
Advanced earth (ground) tester
Weatherproof and rugged
The DET2/3 is sealed to IP54 standard, which provides weatherproofing during operation (case lid open). When the case lid is closed its protection standard is to IP65 (water and dust damage).
The case is made of a tough and light copolymer polypropylene, which can withstand the rough and tumble of outdoor use.
Portable power
An internal Li-ion battery provides for a full day of tests. The Li-ion battery has a fast recharge facility that allows a flat battery to provide an afternoon of tests, if charged during a lunch break. The DET2/3 can also operate from a standard 12 V DC battery supply.
SPECIFICATION
2, 3 and 4 pole resistance measurements
Range 0.001 Ω to 20.00 kΩ auto range
Display Four digit display
Accuracy at 23 °C ±2 °C
±0.5% of reading ±2 digits
3P ±10 mΩ
2P ±20 mΩ
Operational uncertainty ±2% of reading, ±2 digits
(meets IEC61557 operational uncertainty requirement with readings over 10 mΩ) when spike resistances are below 100 Ω ±5% of reading ±2 digits ±10 mΩ (meets IEC61557 operational uncertainty requirement with readings over 10 mΩ)
Test standards BS 7430 (Earthing) BS 62305 (Lightning) BS EN50122 (Railway)
IEEE Standard 81
Test frequency 10 Hz to 200 Hz in steps of
0.5 Hz
Test current 50 mA max.
Maximum output voltage Less than 50 V rms
Maximum interference Up to 50 V pk to pk
Temperature coefficient < ±0.1% per °C over operating
temp
3 and 4 pole ART (selective) resistance measurements
Range 0.01 Ω to 10.00 kΩ Auto range
Accuracy ±5% of reading ±3 digits at
23 °C ±2 °C
Stakeless resistance measurement
Range 0.01 Ω to 200 Ω
Accuracy ±7% accuracy, ±3 digits
Leakage current
Range 0.00 A to 2.00 A
Accuracy ±5% (±3 digits)
Instrument specifications
Display 4.3 inch QWVGA, daylight viewable backlit colour
Operating temperature and humidity
-10 to 40 °C
90% RH max at 40 °C
Storage temperature -20 to 60 °C
IP rating IP54 operational (lid open), IP65 storage (lid closed)
Measurement rating CAT IV 300 V
Power supply Internal Li-ion battery or
external 12-18 V, 65 W, DC supply
Battery life Up to 10 hrs use
Battery charging time Fast recharge to 50%,
3 hrs for 100%
Safety Meets IEC 61010
EMC Meets IEC 61326
Dimensions L 315 x W 285 x H 181 mm
(12.4 x 11.2 x 7.1 in)
Weight 4.5 kg (9.9 lb)
Data download To PC through USB 2.0
Data storage On board 500 record storage
downloadable as *.txt
USB type A Data download to USB drive
USB type B Data download to PC
Secondary measurement display Noise, voltage and current Resistivity calculation Wenner: PE = 2 π a R
Schlumberger: PE = π b (b+a) R
a
Test modes Internally set 2P, 3P, ART (Selective), 4P, Stakeless (clamp) modes
Aux inputs MCC1010, MVC1010
RoHS compliant Yes
W
ACCESSORIES
MCC1010 and MVC1010
n For Stakeless tests
n For ART tests
Cable reels with spike
n Sturdy handle and a smooth unwind and wind action n Cable ‘feed through’ n 20 m, 30 m, 50 m, 60 m or 100 m cables n Attachable 25 cm (10”) earth spike n Spike can be hammered into the ground n Unique daisy-chain feature to create longer lengths
Continuity test cables and clips
n 1.4 m cables n 2 wire connection cable n Crocodile clips n Probes
Accessories bag
n Holds a full suite of accessories n Water resistant n Toughened bottom for outdoor use