Megger DCM305E User Manual

DCM305E
Earth Leakage Clampmeter
User manual P 2 Benutzerhandbuch P17 Manuel utilisateur P33 Guía del usuario P49 Gebruikershandleiding P65
G Read First G Safety Information
To ensure safe operation and service of the meter, follow these instructions.
Failure to observe warnings can result in severe injury or death.
■ Avoid working alone so assistance can be rendered.
■ Do not use the clamp meter if the instrument looks damaged
■ Do not use the clamp meter if the tester is not operating properly or if it is wet.
■ Use the clamp meter only as specified in the instruction card or the protection provided by the clamp meter may be impaired.
■ Ensure hands are kept behind the barrier / hand guard when making measurements.
■ Special precautions are necessary when operating in situations where exposed live parts at dangerous voltages may be encountered. Personal protective equipment (not supplied with the instrument) should be used.
■ Use caution with voltages above 30 V AC RMS, or 60 V DC. These voltages pose a shock hazard.
2
megger.com
CAT IV
Measurement category IV: Equipment connected between the origin of the low-voltage mains supply outside the building and the consumer unit.
CAT III
Measurement category III: Equipment connected between the consumer unit and the electrical outlets.
CAT II
Measurement category II: Equipment connected between the electrical outlets and the user’s equipment.
Symbols as marked on the instrument and instruction card
F G t
g a c
Risk of electric shock
See instruction card
Equipment protected by double or reinforced insulation
Low battery
Earth
AC measurement
Conforms to EU directives
Application around hazardous exposed live conductors is permitted
Do not discard or throw away this product
G Caution
Take sufficient care not to apply shock, excessive vibration or force to the jaw If the meter is used in the vicinity of equipment that generates large
electromagnetic fields, the display may become unstable or the measurements may be subject to large errors.
megger.com
3
Power Off / On
■ The instrument displays battery capacity when powering up. Replace batteries when 0% is displayed.
Auto Power Off Enable / Disable
4
megger.com
Auto Hold Enable / Disable
In the AUTOHOLD mode, if the measured value remains within ±10 counts over 10 measuring cycles the instrument will beep 3 times; the measured value will be held on the display and “AUTOHOLD” will be displayed.
Subsequently if the measured value changes by ±10 counts, the instrument will beep; “AUTOHOLD” will disappear and the instrument will revert to displaying the new readings until the next AUTOHOLD conditions are met.
Note: When the AUTOHOLD activates, the displayed reading will be held for 3 seconds if the clamp jaws are removed from the conductor/s. During this time the HOLD key may be pressed to hold the reading indefinitely.
Auto Backlight
The Auto backlight on the display activates automatically when the instrument is used in very poor light locations
megger.com
5
AC Current
G CAT III 300 V with respect
to earth for the jaw.
Barrier for hand guard.
G Do not hold the
instrument above the barrier.
Leakage Current Measurement
Recommended applications of instrument with respect to conductors.
Note: Measurements made on the earth conductor only will indicate current in the earth conductor but not the entire installation.
6
megger.com
Single / 1 phase
Single / 1 phase
3 wire / 3 phase
3 wire / 3 phase
megger.com
7
4 wire / 3 phase + neutral
Data Hold
Note: Data Hold beep guard The internal sounder will beep continuously with the LCD display flashing in
the Data Hold mode when the measured signal is 50 counts larger than the LCD reading.
8
megger.com
Peak Hold
(forcing into the manual range mode)
Low Pass Filter
(forcing into the manual range mode)
■ The cut-off frequency of the low pass filter is about 100 Hz with an attenuation characteristic of approximately -24 dB / octave.
megger.com
9
Auto Range / Manual Range
10
megger.com
Comparator
Select a limit level
Confirm the limit level
Comparing
■ The instrument offers 3 limit values (0.25 mA, 0.5 mA and 3.5 mA)
■ The internal sounder will beep continuously with the LCD display flashing when measured value exceeds the confirmed limit level.
megger.com
11
Auto Hold
12
megger.com
Auto Power Off
Battery Replacement
Maintenance
Do not attempt to repair this meter. It contains no user-serviceable parts. Repair or serving should only be performed by qualified personnel.
Cleaning
Periodically wipe the case with a dry cloth and detergent, do not use abrasives or solvents.
WEEE Directive
The crossed out wheeled bin symbol on the instrument and on the batteries is a reminder not to dispose of them with general waste at the end of their life.
Megger is registered in the UK as a Producer of Electrical and Electronic equipment. The registration No is; WEE/DJ2235XR.
Users of Megger products in the UK may dispose of them at the end of their useful life by contacting B2B Compliance at www.b2bcompliance.org.uk or by telephone on 01691 676124.
Users of Megger products in other parts of the EU should contact their local Megger company or distributor.
megger.com
13
Battery Disposal
Batteries in this product are classified as Portable Batteries under the Batteries Directive. Please contact Megger Ltd for instructions on the safe disposal of these batteries.
For disposal of batteries in other parts of the EU contact your local distributor. Megger is registered in the UK as a producer of batteries. The registration number is BPRN01235. For Further information see www.megger.com
Specifications
General Specifications
LCD display digits : 6000 count large scale LCD readout.
Measuring rate : 5 times / sec.
Over range display : Shows the real value for “100 A”
and shows “OL” for other ranges.
Automatic power off time : Approximately 20 minutes after power on without operations.
Low battery indicator :
the indicator
Power requirement : 1.5 V x 2 batteries AAA / LR03
Battery type and life : Alkaline 60 hours.
is displayed. Replace the battery when
appears in the display.
Environmental Conditions
Indoor Use.
Pollution degree : 2
Calibration : One year calibration cycle.
Operating temperature : 0°C ~ 30 °C (≤ 80% RH)
30°C ~ 40 °C (≤ 75% RH) 40°C ~ 50 °C (≤ 45% RH)
Storage temperature : -20 to +60 °C, 0 to 80% RH (batteries not fitted).
Operating altitude : 2000 m (6562 ft)
Conductor Size : 40 mm diameter.
Shock vibration : No shock, No vibration to the jaw tips.
Temperature coefficient : 0.2 x (Specified accuracy) / °C,
< 18 °C, > 28 °C
EMC : EN 61326-1
Overvoltage category : IEC 61010-1 300 V CAT III
Accuracy is ±(% reading + number of digits) at 23 °C ± 5 °C < 80% RH.
14
megger.com
AC Current
Range Resolution Accuracy
* 6 mA 0.001 mA 0A ~ 10A
60 mA 0.01 mA
600 mA 0.1 mA
6 A 0.001 A
60 A 0.01 mA
100 A 0.1 A
* Digit rolling ±3 digits.
Frequency Response (61~400 Hz) :
0A ~ 10A ±(2% reading + 11 digits) 10 ~ 50A ±(10% reading + 11 digits) 50 ~ 100A ±(35% reading + 11 digits)
Position Error: ±1% of reading.
Additional Accuracy by Crest Factor (C.F.):
Add 1.0% for C.F. 1.4 ~ 2.0. Add 2.5% for C.F. 2.0 ~ 2.5. Add 4.0% for C.F. 2.5 ~ 3.0.
Max. Crest Factor: 1.6 for 6000 ~ 5000 digits
2.0 for 5000 ~ 3000 digits
3.0 for 3000 ~ 0 digits
Influence of external magnetic field of adjacent wires :
0.04% typical value.
±(1% reading + 8 digits)
10 ~ 50A ±(2% reading + 10 digits)
50 ~ 100A ±(10% reading + 10 digits)
Low Pass Filter
Range Resolution Accuracy
* 6 mA 0.001 mA 0A ~ 10A
60 mA 0.01 mA
600 mA 0.1 mA
6 A 0.001 A
60 A 0.01 A
100 A 0.1 mA
* Digit rolling ±3 digits.
Attenuation characteristic: approximately –24 dB/octave
Cut-off frequency : 100 Hz
±(2% reading + 8 digits)
10 ~ 50A ±(3% reading + 10 digits)
50 ~ 100A ±(12% reading + 10 digits)
megger.com
15
Limited Warranty
This meter is warranted to the original purchaser against defects in material and workmanship for 1 year from the date of purchase. During this warranty period, manufacturer will, at its option, replace or repair the defective unit, subject to verification of the defect or malfunction.
This warranty does not cover fuses, disposable batteries, or damage from abuse, neglect, accident, unauthorised repair, alteration, contamination, or abnormal conditions of operation or handling.
Any implied warranties arising out of the sale of this product, including but not limited to implied warranties of merchantability and fitness for a particular purpose, are limited to the above. The manufacturer shall not be liable for loss of use of the instrument or other incidental or consequential damages, expenses, or economic loss, or for any claim or claims for such damage, expense or economic loss. Some states or countries laws vary, so the above limitations or exclusions may not apply to you.
Megger Limited Archcliffe Road Dover Kent CT17 9EN Tel: +44 (0) 1304 502 101 Fax: +44 (0) 1304 207 342 www.megger.com
DCM305E
Leckstromzange für Ableitstrom
Benutzerhandbuch
G Zuerst lesen
G Sicherheitsinformationen
Für eine sichere Bedienung und eine sichere Wartung des Messgeräts bitte diese Anweisungen beachten.
Eine Nichtbeachtung der Warnhinweise kann zu schweren Verletzungen oder zum Tod führen.
■ Niemals alleine arbeiten, sodass im Notfall Hilfe geleistet werden kann.
■ Leckstromzange nicht benutzen, wenn das Gerät beschädigt aussieht
■ Leckstromzange nicht benutzen, wenn das Messgerät nicht ordnungsgemäß funktioniert oder wenn es nass ist.
■ Leckstromzange nur für die in der Bedienungsanleitung beschriebenen Arbeiten verwenden, sonst kann der Schutz durch die Leckstromzange evtl. nicht gewährleistet sein.
■ Sicherstellen, dass die Hände während des Messvorgangs hinter der Griffbegrenzung / dem Handschutz gehalten werden.
■ Besondere Vorsicht ist erforderlich bei Arbeiten in Bereichen, in denen frei liegende, spannungsführende Bauteile mit gefährlichen Spannungen vorhanden sein können. Es muss persönliche Schutzausrüstung verwendet werden (wird nicht zusammen mit dem Gerät geliefert).
■ Vorsichtig sein bei Spannungen über 30V AC EFF oder 60V DC. Bei diesen Spannungen besteht die Gefahr eines Stromschlags.
18
megger.com
CAT IV
Messkategorie IV: Gerät ist zwischen der Niederspannungs-Netzanschlussquelle außerhalb des Gebäudes und dem Verbrauchergerät angeschlossen.
CAT III
Messkategorie III: Gerät ist zwischen dem Verbrauchergerät und den Steckdosen angeschlossen.
CAT II
Messkategorie II: Gerät ist zwischen den Steckdosen und den Anlagen des Anwenders angeschlossen.
Symbole, wie sie auf dem Gerät und in der Bedienungsanleitung erscheinen
F G t
g a c
Risiko eines elektrischen Schlags
Siehe Bedienungsanleitung
Gerät ist mit einer doppelten oder verstärkten Isolierung geschützt
Niedriger Batterieladestand
Masse
AC-Messung
Entspricht den EU-Richtlinien
Anwendung in der Umgebung gefährlicher freiliegender, stromführender Leiter ist zulässig
Dieses Produkt nicht entsorgen oder wegwerfen
G Vorsicht
Achten Sie genügend darauf, keine Erschütterung, übermäßige Vibration oder Kraft auf die Zange auszuüben
Wenn das Messgerät in der Nähe von Geräten verwendet wird, die elektromagnetische Felder verursachen, kann die Anzeige schwanken oder es kann bei der Messung zu groben Fehlern kommen.
megger.com
19
Aus-/Einschalten
Drücken Sie
Drücken Sie> 3 Sekunden
■ Das Gerät zeigt den Batterieladestand beim Einschalten an. Tauschen Sie die Batterien aus, wenn 0% angezeigt wird.
Autom. Ausschalten aktivieren/deaktivieren
Drücken Sie> 3 Sekunden
Drücken Sie <3 Sekunden
20
megger.com
Auto-Halten aktivieren/deaktivieren
Drücken Sie <5 Sekunden
Drücken Sie >5 Sekunden
Wenn der gemessene Wert im AUTOHOLD-Modus über 10 Messzyklen hinweg im Bereich ±10Zähler bleibt, piept das Gerät 3 Mal; der gemessene Wert wird in der Anzeige beibehalten und „AUTOHOLD“ wird angezeigt.
Wenn sich anschließend der gemessene Wert um ±10Zähler ändern, piept das Gerät; „AUTOHOLD“ wird nicht mehr angezeigt, und das Gerät zeigt jetzt die neuen Messergebnisse an, bis die nächsten AUTOHOLD-Bedingungen für das Auto-Halten erfüllt werden.
Hinweis: Wenn die AUTOHOLD-Funktion aktiviert wird, wird das angezeigte Messergebnis 3Sekunden lang gehalten, wenn die Zangenbacken von den Leitern entfernt werden. Während dieser Zeit können Sie die HOLD-Taste drücken, um das Messergebnis unendlich lang anzuzeigen.
Autom. Hintergrundbeleuchtung
Die automatische Hintergrundbeleuchtung der Anzeige wird automatisch aktiviert, wenn das Gerät an Orten mit schlechter Beleuchtung verwendet wird
megger.com
21
Strom (AC)
G CATIII 300V in
Bezug auf Masse für die Zange.
Begrenzung für den Handschutz.
G Das Gerät
nicht oberhalb der Begrenzung halten.
Messung des Ableitstroms
Empfohlene Anwendungsbereiche des Geräts in Bezug auf Leiter.
BELASTUNG
Hinweis: Messungen, die am Erdungsleiter vorgenommen werden, zeigen
den Strom im Erdungsleiter, nicht jedoch in der gesamten Anlage an.
22
megger.com
BELASTUNG
Single / 1 Phase
Single / 1 phase
BELASTUNG
megger.com
3 Draht / 3 Phase
3 wire / 3 phase
23
Daten-Halten
BELASTUNG
4 wire / 3 phase + neutral
4 Draht / 3 Phase + Neutralleiter
Drücken Sie
Hinweis: Warnpiepen bei Daten-Halten
Der eingebaute Summer gibt einen kontinuierlichen Piepton aus, gleichzeitig blinkt die LCD-Anzeige, wenn das gemessene Signal im Daten-Halten-Modus 50Zähler größer ist als das LCD-Ergebnis.
24
megger.com
Loading...