DCM1500
1500 A TRMS clamp meter
DC and AC current up to 1500 A
True RMS measurement for greater accuracy
Large jaw size safely assists with uninsulated
conductor measurements
750 VAC and 1000 VDC
Resistance, continuity and frequency
Peak, min/max and data-hold functions
DCM1500
1500 A TRMS clamp meter
DESCRIPTION
Measuring up to 1500 A ac or dc the DCM1500 also offers 750 Vac
and 1000 Vdc ranges making the instrument ideal for use in the
installation, maintenance, monitoring or checking of large a.c. or
d.c. electrical systems and equipment.
The large clear digits of the numeric display are complemented by
the high-resolution digital bar graph, useful for indicating trending
and fluctuation of measurement. The backlight assists use in poorly
lit areas such as distribution cupboards and corners of switchrooms;
and the data-hold feature enables use on difficult access cables
where otherwise the display may be impossible to see.
Min/Max hold provides the ability to store the maximum and
minimum d.c. or rms values over a period of time. While storage is
taking place, either the present, maximum or minimum value can
be displayed. Peak hold stores the maximum and minimum peak
value of an a.c. signal at a 10 ms sample rate. The auto-off feature
automatically places the meter in power-save mode after 30 minutes
from power-on, but this can be disabled if required for min/max
measurements.
Using the Relative mode (REL), a stable value can be stored, the
instrument zeroed at that point, and then any variation from that
value is displayed as a direct measurement relative to it.
The DCM1500 is safety rated to IEC 61010-1 CAT IV 600 V, and is
drop-tested to 1.2 m onto a hard floor. It is supplied with test leads
and a carry case, and a full 1-year manufacturer’s warranty.
APPLICATIONS
The DCM1500 is designed to be used on electrical systems and
equipment where there is a need to measure current, volts,
resistance and frequency. It is therefore intended for use while
installing, maintaining, fault-finding or monitoring those systems.
The tactile barrier below the jaws of the instrument ensures a safe
working distance for the operator’s hand when measuring current
on live uninsulated conductors, although additional personal
protection must still be used.
The min/max and peak-hold enable maximum load currents from
equipment to be identified such as start-up currents to motors and
heaters.
With the added benefit of d.c. current measurement, it can also
be used in applications including domestic power generation from
solar panels and wind-turbines; battery monitoring; automotive
uses for charging and load circuits; electric vehicle servicing such
as fork-lift trucks; lift maintenance; UPS commissioning, servicing
and maintenance; electro-plating plants and welding equipment
servicing.
True RMS Measurement
By using True RMS measurement techniques the DCM1500 avoids
the errors which can occur when non-sinusoidal waveforms created
by today’s complex loads are measured using traditional average
sensing clamp meters.
1
1500 A TRMS clamp meter
SPECIFICATIONS
Accuracy is ±(% reading + number of digits) at 23°C ± 5°C, less than 80% R.H.
AC current
Range Resolution Accuracy Frequency Response Overload Protection
400 A 0.1 A ±(1.5% reading + 5 digits)* 50 Hz ~ 60 Hz 1500 A rms
1000 A 1 A ±(1.9% reading + 7 digits) 50 Hz ~ 60 Hz 1500 A rms
1500 A 1 A ±(2.5% reading + 7 digits) 50 Hz ~ 60 Hz 1500 A rms
400 A 0.1 A ±(1.9% reading + 5 digits)* 61Hz ~ 400 Hz 1500 A rms
1000 A 1 A ±(2.5% reading + 7 digits) 61 Hz ~ 200Hz 1500 A rms
1500 A 1 A ±(3.0% reading + 7 digits) 61 Hz ~ 200 Hz 1500 A rms
AC Conversion Type: * add 2 digits to accuracy when reading less 15% of full scale.
AC Conversions are ac-coupled, true rms responding, calibrated to the rms value of a sine wave input. Accuracies
are given for sine wave at full scale and non-sine wave below half scale. For non-sine wave add the following Crest
Factor corrections:
For Crest Factor of 1.4 to 2.0, add 1.0% to accuracy.
For Crest Factor of 2.0 to 2.5, add 2.5% to accuracy.
For Crest Factor of 2.5 to 3.0, add 4.0% to accuracy.
Max.CF 2 @ 600A
1.5 @ 1500A
DC current
Range Resolution Accuracy Over voltage protection
400 A 0.1 A ±(1.0% reading + 3 digits) AC 1000 A for 1 min
1000 A 1 A ±(1.9% reading + 7 digits) AC 1000 A for 1 min
1500 A 1 A ±(2.5% reading + 7 digits) AC 1000 A for 1 min
Position Error: Add ±1% of LCD reading
DCM1500
AC voltage (auto-ranging)
Range Resolution Accuracy Over voltage protection
400 V 100 mV ±(1.0% reading + 5 digits) 750 V rms
50 Hz ~ 500 Hz*
750 V 1 V ±(1.0% reading + 5 digits) 750 V rms
50 Hz ~ 500 Hz*
* add 2 digits to accuracy when reading less 15% of full scale.
Input Impedance: ≥1 MΩ// less than 100pF.
AC Conversion Type:
AC Conversions are ac-coupled, true rms responding, calibrated to the rms value of a sine wave input. Accuracies are given
for sine wave at full scale and non-sine wave below half scale.
For non-sine wave add the following Crest Factor corrections:
For Crest Factor of 1.4 to 2.0, add 1.0% to accuracy.
For Crest Factor of 2.0 to 2.5, add 2.5% to accuracy.
For Crest Factor of 2.5 to 3.0, add 4.0% to accuracy.
Max.CF 2 @ 600V
1.5 @ 750V
DC voltage (auto-ranging)
Range Resolution Accuracy Over voltage protection
400 V 100 mV ±(0.7% reading + 2 digits) 1000 V rms
1000 V 1 V ±(0.7% reading + 2 digits) 1000 V rms
Input impedance: ≥ 1 MΩ
Resistance and continuity
Range Resolution Accuracy Over voltage protection
0 – 400 Ω 100 mΩ ±(1.0% reading + 3 digits) 600 V rms
Continuity check: buzzer sounds when resistance< 30 Ω
Frequency
Range Resolution Accuracy Over voltage protection
20 – 400 Hz 1 Hz ±(0.1% reading + 2 digits) AC /DC 1000 A for 1 min
Sensitivity: 3 A rms for < 400 Hz
2