Megger DC Data sheet

5 and 15 kV DC Dielectric Test Sets
5 and 15 kV DC Dielectric Test Sets
n
Continuously variable test voltage
n
Rugged field construction
n
Compact and portable
15 kV model
DESCRIPTION
Dielectric test sets measure leakage current while applying a dc voltage at or above the insulation system’s operating level. This measurement aids in determining the insulation system’s ability to withstand overvoltages such as lightning strikes and switching surges.
APPLICATIONS
Megger portable dc dielectric test sets check the electrical insulation quality of motors, power cables, switchgear, insula­tors, transformers and capacitors. Typical applications include acceptance and maintenance testing of critical equipment used by electrical utility substations and industrial plant distri­bution systems. Power apparatus manufacturers may also use the equipment to perform QA/QC production tests.
The test sets can be used to perform step-voltage and proof tests which, when incorporated into a routine maintenance program, can aid in predicting potential failure before break­down occurs.
Two models are available; a 5-kV unit for testing equipment rated 2.5 kV and below, and a 15-kV model for use on equip­ment rated 7.5 kV and below. Both are suitable for testing power cable, switchgear and rotating machinery in accor­dance with IEEE, ICEA, NEMA and ANSI guidelines.
Because Megger dc dielectric test sets act like full-wave recti­fied units, they also are suitable for applications involving vacuum bottles.
DC vs AC High-Potential Testing
Direct current high-potential testing provides several advan-
tages over alternating current. Direct current test equipment uses far less power, provides fast charging of highly capacitive test samples, can be easily transported to the test site and costs less. Additionally, the dc test can detect incipient break­down without the possibility of damage to good insulation.
FEATURES AND BENEFITS
n
Compact and portable
n
Air insulated, uses no oil
n
±2% accuracy
n
Leakage current measurement as low as 0.1 mA
n
Continuously variable test voltage with zero-start safety
interlock
n
Fast charging of high-capacitance samples
n
Current guard circuit for highly accurate measurements
n
Strip chart recorder for hard copies (optionally available)
Safety and Reliability
n
Input and output line circuit breaker
n
Output current overload relay
n
Zero-start interlock for high-voltage output
n
Switch control and indicating lights for high-voltage ON/
OFF on the 15-kV model
n
Full circuit breaker protection
SPECIFICATIONS
Input
120 Vac, 50/60 Hz
Output
Cat. No. 220005
Voltage (maximum): 0 to 5 kVdc, negative with respect to ground Current (maximum): 5 mA continuous
Metering
Kilovoltmeter: 4-in. (102-mm) taut band with two ranges, 0 to 2.5 and 0 to 5 kV Current Meter: 4-in. (102-mm) taut band with four ranges, 0 to 5/50/500 µA and 5 mA
Cat. No. 220015
Voltage: 0 to 15 kVdc, negative with respect to ground Current: 2 mA continuous Short Circuit: 12 mA max., limited by circuit breaker
Metering
Kilovoltmeter: 4-in. (102-mm) taut band with two ranges, 0 to 7.5 and 0 to 15.0 kV Current Meter: 4-in. (102-mm) taut band with four ranges, 0 to 5/50/500 µA and 5 mA
Accuracy
±2% of full scale
Temperature Range
0 to 122° F (–17.7 to +50° C) operating
5 and 15 kV DC Dielectric Test Sets
5 kV model
CAT. NO.
220005
220015
Model
5 kV
15 kV
Test Voltage
Range*
0 to 2.5 kVdc
0 to 5 kVdc
0 to 7.5 kVdc 0 to 15 kVdc
Max. Power
System Voltage
2.5 kVac
(phase-to-phase)
7.5 kVac
(phase-to-phase)
* Negative polarity with respect to ground
ORDERING INFORMATION
Item (Qty) Cat. No.
DC Dielectric Test Sets
5 kV 220005
15 kV 220015
Included Accessories
Ground connection cable, 10 ft [3 m] 4702
kV/MΩ test record graph paper (100-sheet pad) 220000
Power cord, Cat. No. 220015 17032
Instruction manual, Cat. No. 220005 AVTM22-5JB
Instruction manual, Cat. No. 220015 AVTM22-15JA
Output Current (120-Vac input)
5 mA continuous
5 mA for 12 min; 2 mA continuous
Dimensions
9.4 H x 13.5 W x 10 D in.
24.8 H x 34.3 W x 25.4 D cm
12 H x 20.5 W x 13 D in.
30.5 H x 52 W x 33 D cm
Weight
20.5 lb
(9.3 kg)
35.2 lb (16 kg)
Item Cat. No.
Optional Accessories
High-voltage resistance discharge stick 222070-62
Internal voltage stabilizer, Cat. No. 220015 only Add –50
Special cable lengths Add –56
“The Lowdown on High-Voltage DC Testing” AVTM22P-1
UK
Archcliffe Road, Dover CT17 9EN England T (0) 1 304 502101 F (0) 1 304 207342
UNITED STATES
4271 Bronze Way Dallas, TX 75237-1019 USA T 1 800 723 2861 T 1 214 333 3201 F 1 214 331 7399
OTHER TECHNICAL SALES OFFICES
Norristown USA, Toronto CANADA, Mumbai INDIA, Trappes FRANCE, Sydney AUSTRALIA, Madrid SPAIN and The Kingdom of BAHRAIN.
ISO STATEMENT
Registered to ISO 9001:2000 Reg no. Q 09250
Registered to ISO 14001 Reg no. EMS 61597
5_15KV_DCTS_DS_en_V13
www.megger.com Megger is a registered trademark
Loading...