Megger CM500 User Manual

User Guide
M
CM500 Multi-Function Installation Tester
Safety Warnings 3
Initial Setup 4
General Description 6
Features, Controls and Connections 8
Operation 10
Backlight 10
Switched probe
SP2 10
Checking Earth Potential 10
Voltage and Frequency Measurement 10
Polarity Indication 11
Determining Phase Sequence 12
Continuity Testing and Low Resistance measurement 12
Test Lead Resistance Nulling 12
Low Resistance Continuity measurement 13
Low input resistance voltmeter 13 5Threshold 13
Insulation Testing and High Resistance measurement 14
Loop Impedance Measurement 15
Bonded Metalwork Testing 16
Prospective Short Circuit Current (PSCC) 17
PFC measurement accuracy 17
Earth Loop Resistance measurement at 15 mA 17
RCD Testing 18
Auto Sequence RCD Test 22
Earth Resistance Measurement 24
Earth Electrode Resistance Measurement 24
Condition and Warning Indication 26
Test Results, Storage, Deletion and Retrieval 27
Serial Cable Connections 30
Specification 31
Accessories 35
Publications 36
Basic and Service Error calculation 37
Repair and Warranty 39
Symbols used on the instrument
Caution: Refer to accompanying notes
Equipment protected throughout by Double or reinforced Insulation (Class
II)
Equipment complies with current EU Directives
Complies with IEC / EN 61557
2
Contents
3
SAFETY WARNINGS
Q Safety Warnings and Precautions must be read and understood before the instrument is used. They must be observed
during use.
Q The circuit under test must be switched off, de-energised and isolated before test connections are made when carrying
out insulation and continuity tests.
Q Continuity of protective conductors and earthed equipotential bonding of new or modified installations must be verified
before carrying out an earth fault loop impedance test, or RCD test.
Q Circuit connections and exposed metalwork of an installation or equipment under test must not be touched.
Q Do not move the rotary selector switch position while a test is in progress.
Q The LCD ‘neon’ voltage indicators cannot reveal a Neutral - Earth reversal.
Q After insulation tests, capacitive circuits must be allowed to discharge before disconnecting test leads.
Q The instrument should not be used if any part of it is damaged.
Q Test leads, probes and crocodile clips must be in good order, clean and with no broken or cracked insulation.
Q U.K. Safety Authorities recommend the use of fused test leads when measuring voltage on high energy systems.
Q Replacement fuses must be of the correct type and rating.
NOTE
THE INSTRUMENT MUST ONLY BE USED BY SUITABLY TRAINED AND COMPETENT PERSONS
Read this page before using the CM500.
Your
CM500 has been set up as shown on the label on the
front of this User Guide:-
The
first line gives the setting, which modifies the way the
instrument behaves.
The second line gives the printer report language. This may be Language 1, which is English, or Language 2 which is the language noted on the third line of the label.
Instrument Setup
The instrument setup mode allows you to change the setting, the printer speed and the printer report language.
To display the current setup modes:-
1. Press and hold the
backlight key, then turn the rotary
selector switch from the from ‘OFF’ position to the ‘RCL’ position. The code (printer speed) is displayed.
2. Release the
backlight key.
3. Toggle the
I key to scroll through and display the current
setup modes. as follows:-
To change the Printer speed
1. Toggle the I key to scroll through and display the
code.
2. Press the
SAVE key. The current speed setting is
displayed.
3. Toggle the
RCL keys until the required speed setting is
displayed.
4. To save the new setting, press the
SAVE key. The bleeper
sounds and is displayed. To abort the new setting, press the
EXIT key. is displayed.
To select the Printer language
1. Toggle the I key to scroll through and display the
code.
Initial Setup
4
2. Press the SAVE key. The current printer report language is displayed as 1 (English) or 2 (as given on the type label on the previous page).
Note:- Language 2 can be changed using the CM500 Setup Disk supplied.
3. Toggle the
I key until the required language setting is
displayed.
4. To save the new setting, press the
SAVE key. The bleeper
sounds and is displayed. To abort the new setting, press the
EXIT key. is displayed.
To select the Setting
1. Toggle the I key to scroll through and display the code.
2. Press the
SAVE key. The current setting is displayed as A
(Continental Europe) or b (U.K.).
3. Toggle the I key until the required setting is displayed.
4. To save the new setting, press the
SAVE key. The bleeper
sounds and is displayed. To abort the new setting, press the
EXIT key. is displayed.
CM500 Setup Disk
The program on the disk enables the second printer language to be changed into any of the separate languages. The program may be run directly from disk. Connect the PC to the instrument via a serial lead.
for DOS type: a:\cm500set and press: Return.
for Windows™ 3.1 or 3.11:
1. From the Program Manager options, select: File
2. From the options given, select: Run.
3. Type:
a:\cm500set and press: Return.
For Windows™ 95:
1. Select the Start menu.
2. Select the
Run option.
3. Type:
a:\cm500set and press: Return.
Follow the instructions given by the program.
5
The MEGGER CM500 Multi-function Installation Tester is a compact instrument designed to perform all of the functions required by the electrical contractor to fully test domestic, commercial and industrial wiring. Specially designed to comply with U.K., European and other International wiring regulations and standards, the
CM500 may be used on all single and three phase systems with rated voltages up to 300 Volts a.c. rms to earth/ground.
Measured values are indicated on a large backlit analogue/digital LCD and may also be stored in internal memory for later recall to the display, direct printing via a standard serial printer, or downloaded to a PC for storage, analysis and report generation.
The
CM500 is supplied as standard in a protective test and carry case, and with the necessary mains plug lead and 2-wire lead set required to commence testing. Optional accessories include the SP2, a 2-wire lead set with test switch built into one of the probes providing remote operation, and a 5 metre 2-wire lead set for increased accessibility.
Key Features
No Trip loop Impedance test
Storage of test results in memory
Direct serial printer driver output
RS-232 Output for PC storage
Recall stored results to the display
RCD Ramp test function
Analogue arc and digital display.
Selectable backlight
Optional switchable probe (SP2)
Test Capability
Insulation
Test voltages of 250V, 500V and 1000V.
Continuity testing
Fast bleeper Test lead resistance nulling Automatic polarity reversal (
Setting A)
Loop Testing
Operates regardless of mains polarity (Setting A) Two wires only needed for testing Automatic test start on voltage detection Direct indication of short circuit current. Phase - phase, phase - neutral & phase - earth tests Simple earth electrode test
RCD Tests
Tests selective (delayed) general and d.c. sensitive RCDs. Two wires only needed for testing Contact voltage and loop resistance displayed. Selectable test current for programmable devices
Supply voltage and frequency measurement
Phase sequence indication
Mains outlet polarity indication
Application
The CM500 may be be connected live to earth or between live conductors of systems that have a rated voltage of 300V a.c. rms to earth and an installation (overvoltage) Category
III or lower.
This means that the
CM500 may be connected to any fixed wiring of a building installation, but not to primary supply circuits such as overhead cables. To maintain user safety and ensure accurate measurements, only use the test leads supplied or
General Description
6
recommended for use with this instrument. The
CM500 is fuse protected to 440V 10kA. The maximum current which could flow through this fuse in the case of a fault is limited to 10 kA by the impedance of the test leads. There is a fuse accessible in the battery compartment which protects the Insulation and Continuity range. If warning of a ruptured fuse is given during a test, and if the warning symbol is present when attempting to carry out an insulation test with the test leads shorted together, this fuse must be replaced by another fuse of the same type and rating i.e. 500 mA (F) 500 V H.B.C. 10 kA.
Fuse Replacement
To replace the fuse, disconnect the test leads, switch the instrument Off and with a screwdriver, loosen the captive screw holding the battery compartment cover in place. Remove the cover. Depress the fuseholder slightly, and turn a quarter turn anti-clockwise to release. Remove the holder and replace the fuse with one of the correct size and rating. Relocate the fuse holder, depress and turn a quarter turn clockwise. Replace and re-secure the cover.
Battery Replacement
When the low battery symbol appears, the cells are nearly exhausted and should be replaced as soon as possible. When the battery is exhausted, the instrument will not perform tests and the cells must be replaced. Use Alkaline cells IEC LR6 (AA) or 1,5 V nickel cadmium cells only.
To install or replace the cells,
disconnect the test leads, switch
the instrument Off and loosen the captive screw holding the battery compartment cover in place. Remove the cover, lift out and disconnect the battery holder to access the cells. Ensure that the replacement cells are fitted with the correct polarity, in
accordance with the symbols on the battery holder moulding.
Carefully re-connect the battery holder to the plug, replace the battery holder in the compartment, and re-secure the cover. Remove the cells if the instrument is not going to be used for any extended period of time. Stored results are retained when the battery is disconnected.
Test Leads
All test leads form part of the measuring circuit of the instrument and must not be modified or changed in any way, or be used with any other electrical instrument or appliance. The power cord supplied with the
CM500 is a test lead that forms part of the measuring circuit of the instrument. The overall length of this lead must not be altered. If the power cord plug is not suitable for your type of socket outlets, do not use an adaptor. You may change the plug once only by cutting the cord as close to the plug as possible and fitting a suitable plug.
The colour code of the cord is:
Earth (Ground) Yellow/Green Neutral Blue Phase (Line) Brown
Note:
A plug severed from the power cord must be destroyed, as
a plug with bare conductors is hazardous in a live socket outlet.
7
Incorrect battery cell polarity can cause electrolyte leakage, resulting in damage to the instrument.
8
Features, Controls and Connections
Press I and TYPE key to:
Select test parameters
Enter test result identification
Auto Shut-off Operates after 5 minutes of inactivity by the instrument
(30 seconds in Bleeper mode)
Turn Rotary Selector Switch to:
Select test position
Select Download (RCL)
Select ‘OFF’
Press TYPE key to:
Select test voltage (M)
Select type of RCD
Delete data (in combination with
I key)
Insulation test positions
Continuity test position
VAR test selection
Push TEST
button to:
• Initiate the selected test
• Repeat selected test
Touch finger to Earth Test Pad to:
• Check potential between the Earth connection and your finger
Press key to:
• Display other test results
Press and hold key to:
• Save test results
RCD test selection
Backlight key
Continuity Bleeper position
Lead resistance null position
Recall / Download position
‘OFF’ position
150mA 40ms test selection
Loop test selection
9
Fuse
Ruptured
Low Battery
voltage indication
3 Phase
sequence
RCD Test
Selection
RCD Type Selection
Lead resistance
null ‘On’
Over / Under
Range
Excessive
Noise
Single Phase
Polarity indication
Plug polarity
Thermal
Trip operated
Touch button -
Earth >100 V.
CM500 Display
CM500 Connections
Backlight
The display backlight gives a clear display of measurements in poor lighting conditions. The backlight will briefly operate when the
CM500 is switched on. To switch the backlight on, press the
key. Press the key again to switch the backlight off. To conserve battery power, the backlight will automatically switch off after a period of 15 seconds (if the battery voltage is low, this period is automatically reduced).
Auto Shut - Off
To extend battery life and reduce unnecessary drainage, the CM500 uses advanced battery management techniques, switching functions off when they are not required. For example, if an external voltage of 25 V or less is applied, no value is displayed unless the backlight is switched on. After a period of inactivity by the instrument, the
CM500 will switch itself off, preceded by a series of bleeps. To switch the instrument back on, press any key.
Switched Probe SP2
This is an accessory which can be used anywhere that the 2-wire lead set is specified in this User Guide. The press button probe duplicates the function of the
TEST key on the instrument,
allowing quick and easy testing.
Checking Earth Potential
To quickly distinguish live and earth, this feature provides display indication if a voltage greater than 100 V exists between the earth connection and your finger.
1. In any switch position except
OFF, RCL and () ,
connect the earth connection (black for the 2-wire lead set, green for the 3-wire lead set) to earth.
2. Touch a finger to the metal pad on the front panel. This is safe and will not endanger you.
3. If a voltage greater than 100 V exists between the finger (normally at earth potential) and the earth wire, the warning symbol is displayed.
Voltage and Frequency Measurement
The CM500 will display the supply voltage and frequency in all switch positions except
() , RCL and OFF. The DISPLAY
key will alternate between voltage and frequency.
Power plug connection
1. Insert the power cord plug into an installation socket.
2. Supply voltage and polarity are displayed.
3. Press
DISPLAY to alternate between supply voltage and
frequency.
2-wire lead set connection
If an installation socket is not available, use the 2-wire lead set.
1. Connect the red and black leads to the two conductors to be tested.
2. Voltage between the leads and polarity are displayed.
Note:- Though displayed, when using the 2-wire test set, ‘neon’
Operation
10
The SP2 probe test key circuit is hazardous live during a test. It is safe in normal use.
Continuity of the
SP2 probe non replaceable fuse must be
confirmed (by testing in the Bleeper range) before making any
measurement.
indication is invalid and should be ignored.
3. Press
DISPLAY to alternate between supply voltage
and frequency.
3-wire lead set connection
If an installation socket is not available and it is necessary to connect to all three conductors, use the 3-wire lead set.
1. On a single phase system connect the red lead to phase, the black to neutral and the green to earth.
2. Supply voltage and polarity are displayed.
3. Press
DISPLAY to alternate between supply voltage and
frequency.
Note: For connection to a three phase system, see ‘Determining Phase Sequence’.
When connected, the instrument will display the supply voltage indicated in the following table:
Polarity Indication
If connected to a single phase power supply by a plug or by the 3-wire lead set, three LCD ‘neons‘ marked
L-PE, N-PE and L-N
respectively will indicate supply polarity. If a voltage is detected between their respective two wires, the ‘neon’(s) will activate. A ‘neon’ will usually flash if one connection is open circuit.
Note:- The presence of a voltage between phase and earth does not prove earth continuity, as the earth could have a high resistance and a voltage would still be measured. To test earth continuity refer to the sections on loop resistance or RCD testing.
If
Setting A is set, the CM500 will automatically switch Line and
Neutral as appropriate, when in any of
LOOP, Re (earth) or RCD
test functions. This enables a test to be performed without inverting the plug connections. The live terminal of the wall
socket is identified by the addition of a separate symbol adjacent to the ’neons’. The Phase / Neutral reversal and symbol display does not occur in Setting A Insulation and Continuity ranges, and does not occur in Setting b.
Setting A - LOOP, Re (earth) and RCD
11
Mode
RCD Tests (all Currents)
Loop Resistance
Continuity
Insulation
Download to PC
Off
Switch Position
Voltage Display
L-PE
L-N
L-PE
L-PE
L-N L-N L-N
L-N
N-PE
No Display
Off
RCL
(M
) L-N
(M) N-PE
(M
) L-PE
(Loop) L-PE/Re
() R ()
()
(Loop) L-L/L-N
(RCD) positions
Normal Supply
L-PE N-PE
L-N
L-N Reversed
Neutral Live
Neutral
Open Circuit
Earth
Open Circuit
Operation (Contd.)
12
Setting A - Mand , and Setting b
Determining Phase Sequence
When connected to all conductors of a three phase system, the CM500 automatically displays the sequence of phase rotation.
Connect the
CM500 as follows:­Line 1 Red phase Red lead Line 2 Yellow phase Green lead Line 3 Blue phase Black lead
If connected as above, the symbol is displayed when the
sequence is 1:2:3, or Red-Yellow-Blue. The symbol is displayed when the sequence is 1:3:2, or Red-Blue-Yellow. If one of the lines is faulty, neither of the symbols is displayed and the normal ‘neon’ polarity indication is shown.
To measure the phase to phase voltages, the following switch positions are used:-
Switch position Voltage Shown
(M) L-PE Red and Green Leads V
1-2
(M) L-N Red and Black leads V
1-3
(M) N-PE Black and Green leads V
2-3
Continuity Testing, Low Resistance and kMeasurement
The CM500 will measure low resistance from 0.01to 99.9 and will automatically change range to kup to 99.9 kusing the 2-wire lead set. Up to 10 of test lead resistance may be subtracted using the test lead resistance nulling range. Measurement is displayed on the large digital display, and the analogue scale from 0 to 20 , or 0 to 20 k.
In
Setting A, automatic polarity reversal is carried out with the
CM500 measuring resistance with both positive and negative current flow. Normally the average of the two results will be displayed.
Test Lead Resistance Nulling
The CM500 measures total resistance between its terminals, including the resistance of the test leads. The value of the test leads can be automatically nulled.
1. Firmly short the ends of the test leads together.
2. Select () lead resistance null position.
3. Press the
TEST key. The test leads are checked.
4.
0.00 Ω is displayed to confirm that a new lead value has been stored.
CM500 will automatically display any voltage over 25 V
between the two test leads, and inhibit testing if >5 V.
Normal Supply
L-PE N-PE
L-N
Normal Supply
Neutral Live
Neutral
Open Circuit
Earth
Open Circuit
Loading...
+ 28 hidden pages