Megger BM100/4, BM101/4 User Manual

500 V. Analogue Insulation & Continuity Testers
M BM100/4 and BM101/4
User Guide Guide de l’utilisateur Gebrauchsanleitung Guía del usuario
SAFETY WARNINGS
Safety Warnings and precautions m u s t be read and understood before the instrument is used. They m u s t
be observed during use. The circuit under test must be de-energised and
isolated before Insulation, Resistance, or Continuity tests are made.
During an insulation test, the circuit must not be touched.
After insulation tests, capacitive circuits must be allowed to discharge before disconnecting the test
leads. Test leads, including prods and crocodile clips must
be in good order; clean, and with no broken or cracked insulation.
Replacement fuses must be of the correct type and rating.
BM 100/4 Only
U.K. Safety Authorities recommend the use of fused test leads when measuring voltage on high energy systems.
When making a voltage measurement, the 'T est' push
must not be pressed.
NOTE
T H E I N S T R U M E N T S M U S T O N Y B E U S E D B Y S U I TA B LY T R A I N E D A N D C O M P E T E N T P E R S O N S
.
Symbols used on the instrument
Caution: Refer to accompanying notes. Equipment protected throughout by Double Insulation
(Class II). Equipment complies with relevant EU Directives
Refer to Safety Warnings before using the instrument
OPERATION
Preliminary Test lead check
1. Before each use of the instrument, inspect the test leads to confirm that their condition is good, with no damaged or broken insulation.
2. Insert the red and black test leads, terminated with the appropriate prods or clips, to their respective ‘+’ and ‘-’ terminal sockets.
3. Short the test lead prods or clips together. Set the selector switch to ‘2 ’ .
4. Press the ‘Test’ push. Check that the instrument reads zero. If a higher resistance reading is obtained check all connections. If the reading remains high, suspect that the test leads may be at fault, or that the 2A non replaceable fuse has ruptured.
Continuity Testing
1. Set the selector switch to ‘2
’, or ‘200 ’, as appropriate.
2. Connect the test leads across the isolated item / circuit under test.
3. Press and hold the ‘Test’push button; allow the needle to settle. There is a separate scale for each range so each reading is direct. Take the reading from the appropriate scale of the instrument.
4. Release the ‘Test’ push button and disconnect the test leads.
Insulation Testing
1. Set the selector switch to ‘200 M.’
2. Connect the R e d test lead to earth, equipment frame, or cable sheath etc.
3. Connect the Black test lead to the circuit under test or cable core.
4. Confirm that Voltage is not indicated on the instrument. (BM100/4 only)
5. Press and hold the ‘Test’ push; allow needle to settle, and take the reading from the top scale of the instrument.
6. Release the ‘Test’ push button.
7. Wait a few moments before disconnecting the test leads, to allow any circuit capacitance to discharge. The BM100/4 will automatically monitor the discharge on its Voltage range, indicating when it is safe to remove the test leads.
Resistance Testing (BM101/4 only)
1. Set the selector switch to the 1M resistance range.
2. Connect the test leads across the isolated item / circuit under test.
3. Press and hold the ‘Test’ push button, allow the needle to settle. Take the reading from the 1M range scale.
4. Release the ‘Test’ push button and disconnect the test leads.
SPECIFICATION
Range:
BM100/4 BM101/4
Insulation 0,01 - 200 M 0,01 - 200 M Resistance - 0,01 - 1 M Continuity (¡) 0,01 - 200 0,01 - 200
(¡¡) 0,01 - 2 0,01 - 2
Insulation Test Voltage: 500V d.c. 500V d.c. Open Cct. Terminal Voltage:
Insulation Range <600V d.c. <600V d.c.
(>500V at 0,5M) >500V at 0,5M)
Resistance Range - 53V d.c.(nom.) Continuity Ranges (¡) 0,76V d.c.(nom.) 0,76V d.c.(nom)
(¡¡) 4,7V d.c.(nom.) 4,7V d.c.(nom)
Typical Terminal Characteristics Limiting value curve
Short Cct.Terminal Current:
Insulation Range 1,6 mA 1,6 mA Resistance Range - 325 µA Continuity Ranges (¡) 12,3 mA 12,3 mA
(¡¡) 217 mA 217 mA
Movement: Robust Taut Band type. 250 µA F.S.D. A.C. Voltage Measurement (BM100/4 only):
The Voltage range is automatically selected when the switch is in any position and the ‘Test’ push button is not pressed. When connected across the circuit under test, the BM100/4 will indicate if the circuit is energised (a.c. or d.c.), and measure a.c.voltage up to 600 V.
Voltmeter Input Impedance: 330 k Automatic Discharge: Capacitive circuits are automatically
discharged via an internal (<500k) resistor, when the ‘Test' push button is released following an insulation test.
Accuracy (at 20°C): ± 2,5% of scale length on all ranges (e.g.± 1,9 mm
on Insulation range). Insulation range is marked with a white band (Class 1,5 as VDE 0413). Other ranges are Class 3.
Humidity: Operation: 90% R.H.max. at 20°C
Temperature Range: Operation: -5°C to + 40°C
80% R.H. max.at 35°C
Storage 95% R.H. max. at 35°C
Storage -20°C to + 70°C
Temperature Coefficient: ±0,1% per °C Power Supply: Single 9V Alkaline battery I.E.C. 6 LR61 type Current consumption: 110 mA max on Insulation
40mAmax on Resistance 220 mA max on 2 range
Battery life: Not less than 1800, 5 second operations on 2 range. Battery Condition Test: The battery condition test position checks the
battery voltage on a simulated load, when the ‘Test’ push button is pressed. The instrument pointer should deflect clockwise to within the ‘Battery Check’ arc on the scale. Remove the battery if the instrument is not to be used for an extended period of time.
Battery Replacement:
For safety reasons, the battery compartment must not be opened if the test leads are connected. To remove the battery cover, release the screw in the centre of the cover and lever the cover upwards.
Replaceable Fuse: 500 mA, 250V. H.B.C. type (F) (20mm. x 5mm)
To check this fuse, open circuit the test leads, switch to the 200
range and press the ‘Test’ push button. A reading of <200 indicates a ruptured fuse. Located in the battery compartment, this fuse can be replaced by the user. The replacement fuse must be of the correct type and rating.To replace the fuse, disconnect the test leads, remove the battery cover by releasing the screw in the centre of the cover and levering the cover upwards. Aspare fuse is clipped onto the battery cover.
Non Replaceable Fuse: 2A - 500 V H.B.C. type (F) 50 kA. Fitted for overall safety protection, this fuse is not replaceable by the user. No response from the instrument to an insulation test, with the leads shorted together is likely to mean that this fuse has ruptured. The instrument must be returned to the manufacturer, or an approved agent for repair.
Safety: Meets the requirements for double insulation to IEC1010-1
(1995) EN61010-1 (1995) to installation Category III***, 300 V phase to earth (ground) and 500 V phase to phase, without the need for separately fused test leads. If required, fused test leads are available as an optional accessory. Indicates circuit discharge after insulation test, 600 V Category II **.
*** Relates to transient overvoltage likely to be found in fixed
installation wiring. ** Relates to transient overvoltage likely to
be found in portable equipment and appliances.
E.M.C. In accordance with IEC61326 including amendment No.1 Standards: BS 7430 (1992) - VDE 0413 (1982) Weight: 485g Dimensions: 175 mm x 95 mm x 57 mm. Cleaning: Wipe disconnected instrument with a clean cloth dampened
with soapy water or Isopropyl Alcohol (IPA).
Loading...
+ 8 hidden pages