Megger 210600 User Manual

Page 1
M 210600
Insulation &
Low Resistance Tester
User Guide
SAFETY WARNINGS
Safety Warnings and Precautions must be read and understood
before the instrument is used. They must be observed during use.
isolated
before Insulation or Continuity tests are made.
Circuit connections must not be touched during a test.The test button must not be pressed while connecting the test
leads or while changing ranges. (May cause ‘
Live Circuit
Warning‘ to become inoperable).
The ‘Test’ button must not be pressed when making a voltage test.The Default Voltmeter, ’Live Circuit Warning‘ and Automatic
discharge
are additional safety features and should not be
regarded as a substitute for normal safe working practice.
The 210600 is protected for connection to Power distribution
systems up to 300 V
Line - Ground, and 500 V Line - Line for
Installation Category
III*.
It is recommended that fused test leads are used when measuring
voltage on high energy systems.
After insulation tests, capacitive circuits must be allowed to
discharge
before disconnecting the test leads.
Test leads, prods and alligator clips must be in good order; clean,
and with no broken or cracked insulation.
Replacement fuses must be of the correct size, type and rating.
Symbols used on the instrument
Caution: risk of electric shock
Caution: refer to accompanying notes
Equipment protected throughout by Double Insulation (Class
II)
NOTE
THE INSTRUMENT MUST ONLY BE USED BY SUITABLY TRAINED AND COMPETENT
PERSONS.
Page 2
OPERATION
Live Circuit Warning
The live circuit warning indicator will illuminate if 60 V or more is detected at the terminals. Testing should be aborted if lit.
Default Voltage measurement
The 210600 will act as a direct reading default voltmeter (0 to 600 V a.c./d.c.) in the ‘Standby’ mode (when switched ‘On’, and any of the Insulation test positions is selected). The ‘Test’ push must not be pressed when making a voltage test. Note:- The 210600 is internally fuse protected to 500 V. For fuse protection with supplies above 500 V, use Fuse Probe Kit FPK5.
1. Turn the instrument ‘
On’ by pressing the ‘On‘/‘Off‘ switch-button once.
2. Select any Insulation test position with the rotary selector switch. ’
V’is
displayed.
3. Carefully connect the test leads to the circuit under test.
Do not press
the ‘Test’ push.
4. Read the voltage measurement directly from the display.
5. Carefully disconnect the test leads and turn the instrument ‘
Off‘ by
pressing the ‘On‘/‘Off‘ switch-button once.
Low Resistance measurement (kΩ)
1. Turn the instrument ‘On’ by pressing the ‘On /’Off ‘switch-button once.
2. Select
kΩ with the rotary selector switch.
3. Ensure that all test leads are clean and in good condition, and connect them to the
isolated circuit under test.
4. Press the ‘
Test’ push and read the measurement directly from the
display.
5. Disconnect the test leads and turn the instrument ‘
Off‘ by pressing the
On‘/‘Off‘ switch-button once.
Insulation Testing (MΩ)
Automatic circuit discharge is effective when the ‘Test‘ push is released, and decaying voltage is displayed until the circuit is discharged.
1. Turn the instrument ‘
On’ by pressing the ‘On‘/‘Off‘ switch-button once.
2. Ensure that all test leads are clean and in good condition, and connect them to the
isolated circuit under test.
3. Select the required test voltage with the rotary selector switch.
4. Press the ‘
Test’ push and read the measurement directly from the
display. Overrange is indicated by ‘ ’.
5. Release the ‘
Test’ push and monitor any displayed voltage to confirm
when any discharging voltage decays to zero.
6. When the circuit has discharged, disconnect the test leads and turn the instrument ‘
Off‘ by pressing the ‘On‘/‘Off‘ switch-button once.
Low
Battery
Refer to Safety Warnings before using the instrument
DISPLAY FEATURES
Live Circuit Warning
Page 3
Using the Guard Terminal
For basic insulation tests and where there is little possibility of surface leakage affecting the measurement, it is unnecessary to use the guard terminal. In cable testing, there may be surface leakage paths across the insulation between the bare cable and the external sheathing due to the presence of moisture or dirt. Where it is required to remove the effect of this leakage, particularly at high testing voltages, a bare wire may be bound tightly around the insulation and connected via the third test lead to the guard terminal ‘G’.
The guard terminal is at the same potential as the negative terminal. Since the leakage resistance is effectively in parallel with the resistance to be measured, the use of the guard causes the current flowing through surface leakage to be diverted from the measuring circuit. The instrument therefore reads the leakage of the insulator, ignoring leakage across its surface.
SPECIFICATION
Insulation Ranges
Measuring Ranges: 0 - 1.999Mat all test voltages
19.99 Mat all test voltages
199.9 Mat all test voltages 1999 Mat 500 V and 1000 V d.c. test voltages Fully auto - ranging at all voltages
Test Voltages (d.c.): 100 V; 250 V; 500 V; 1kV Test V. Accuracy: ±5% at open circuit
Short Cct. Current: 1.2 mA nominal Accuracy (73.4°F ± 3.6˚F): <500 M: ± 3% ±2 digits
500 Mto 1999 M: ± 5% ±2 digits
Temp. Co-efficient: <500 MΩ: 86˚F, ±0.06% per °F, >86˚F ± 0.14% per ˚F
500 Mto 1999 MΩ: ≤86˚F ± 0.11% per ˚F, >86˚F, ±0.28% per °F,
Hum Rejection: Within twice the normal accuracy if the noise current
does not exceed 1 mA for the 1 kV range, or 0.5 mA for the other ranges and is within 45 Hz to 65 Hz.
Low resistance Range
Measuring Range: 0 - 1.999 k
19.99 k
Open Cct. Voltage: 4.3 V nominal Accuracy (73.4°F ± 3.6˚F):± 2% of reading ± 1digit
1100
1000
900 800 700 600 500 400 300 200 100
0
0.01
0.1
1
10
100
1000
10000
100000
Terminal Characteristics
Leakage path
to ‘+’ve
terminal
to ‘G’
terminal
to ‘-’ve
terminal
Tightly bound bare wire
Page 4
M
Archcliffe Road Dover
Kent CT17 9EN Tel: +44 (0) 1304 502100 England Fax: +44 (0) 1304 207342
PO Box 9007 Valley Forge PA 19484-9007 Tel: +1 (610) 676-8500 U.S.A. Fax: +1 (610) 676-8610
4271 Bronze Way Dallas TX 75237-1017 Tel: +1 (800) 723-2861 (U.S.A. only) U.S.A. Tel: +1 (214) 330-3203 (International)
Fax: +1 (214) 337-3038
110 Milner Avenue, Unit 1 Scarborough ON M1S 3R2 Tel: +1 (800) 567-0286 Canada Fax: +1 (416) 298-0848
This instrument is manufactured in the United Kingdom. The company reserves the right to change the specification or design without prior notice. Megger is a registered trademark.
Part No. 6172-373 - Edition 4 - Printed in England - 11HH www.megger.com
Page 5
Short Cct. Current: 2.75 mA nominal Temp. Coefficient: ±0.06% per °F
Default Voltage measurement
Range: 0 - 600 V a.c. / d.c. (effective on Insulation ranges
with ‘Test’ push not pressed) Input impedance: 300 kto 1 Mdepending on input voltage Discharge Rate: A 1 µF capacitor will discharge to a safe level in 2 s Accuracy: ±2% of reading ± 1 digit d.c. or a.c. at 45 Hz to 65 Hz Temp. Coefficient: ±0.06% per °F
General Specifications
Overload rating: The 210600 is protected for connection to Power
distribution systems up to 300 V Line - Ground, and
500 V Line - Line for Installation Category III*.
Temp. Range:
Operating: 23°F to 122°F Storage: 4°F to 158°F
Humidity:
Operating: 70% RH at 68°F, 60% RH at 95°F, 50% RH at 104°F
for measurements <200 M
Storage: 95% RH at 95°F
Display: 31⁄2 digit L.C.D. Maximum reading 1999 Automatic Discharge: Capacitive circuits are automatically discharged when
the ‘Test‘ push is released following an insulation test Power Supply: 6 x 1.5 V AA( Alkaline) type cells Battery life: Typically 2100 x 5 second operations (worst case) Note:- Battery cells should not be left in an instrument which may remain
unused for extended periods of time. Low Battery Indicator: The low battery indicator symbol will appear
when the battery cells are exhausted. Battery Replacement: The rear cover must not be opened if the test leads
are connected. To remove the rear cover, release the screw at the bottom of the cover and lift the cover upwards.To avoid the possibility of shock, do not press the ‘Test‘ push when changing batteries.
Fuses: 2 x 500 mA 500 V (F) H.B.C.10 kA min 11⁄4“ x 1⁄4 To check the
+ve fuse, short the +ve and -ve test leads and press the ‘Test
push. An ‘ ’ reading indicates that the
+ve fuse has ruptured.
Fuse Replacement: Held in screw type holders located in the base of the
instrument. Use a flat blade screwdriver to release the center part of each fuse holder. Remove the fuses and test each in turn. Replace with fuse(s) of the correct type, size and rating.
Weight: 2.2 lb (including batteries) Dimensions: 7” x 5” x 5” Cleaning: Wipe disconnected instrument with a clean cloth dampened with
soapy water or Isopropyl Alcohol (IPA)
*Relates to transient overvoltage likely to be found in fixed installation wiring.
0.5A(F) 500V HBC(10 kA)
Guard fuse
Positive fuse
Page 6
ACCESSORIES
Supplied Part Number
User Guide 6172-373 Battery - 6 x 1.5 V AA(Alkaline) type
Test Record Card (5 supplied)
Optional
Carrying case 217740 Fuses 500 mA, 500 V (F) H.B.C. (pack of 5) 6121-289 Fused probe kit FPK4 6111-287 Test lead set comprising:-
1 black, 1 red, 1 green test lead, with alligator clips 6220-436
Test Record cards (Pack of 20) 6111-216 Publication - ‘A Stitch in Time’ AVTM21-P8B
REPAIR AND WARRANTY
The instrument contains static sensitive devices, and care must be taken in handling the printed circuit board. If an instrument’s protection has been impaired it should not be used, but sent for repair by suitably trained and qualified personnel. The protection is likely to be impaired if for example; it shows visible damage; fails to perform the intended measurements; has been subjected to prolonged storage under unfavourable conditions, or has been subjected to severe transport stresses.
NEW INSTRUMENTS ARE GUARANTEED FOR 1 YEAR
FROM THE DATE OF PURCHASE BY THE USER.
Note:
Any unauthorized prior repair or adjustment will automatically invalidate
the Warranty.
INSTRUMENT REPAIR AND SPARE PARTS
For service requirements for Megger Instruments contact :-
Megger Limited or Megger
Valley Forge Corporate Center Archcliffe Road 2621 Van Buren Avenue Dover Norristown, PA 19403 Kent, CT17 9EN U.S.A. England
Tel: +1 (610) 676-8579 Tel: +44 (0) 1304 502243 Fax: +1 (610) 676-8625 Fax: +44 (0) 1304 207342
or an approved repair company.
Approved Repair Companies
A number of independent instrument repair companies have been authorised for repair work on most Megger instruments, using genuine Megger spare parts. Consult the Appointed Distributor / Agent regarding spare parts, repair facilities, and advice on the best course of action to take.
Returning an Instrument for Repair
If returning an instrument to the manufacturer for repair, it should be sent freight pre-paid to the appropriate address. Acopy of the invoice and of the packing note should be sent simultaneously by airmail to expedite clearance through Customs. Arepair estimate showing freight return and other charges will be submitted to the sender, if required, before work on the instrument commences.
MeterCenter
2046 West Peninsula Circle Chandler, AZ 85248 Telephone (480) 659-8351 Toll Free (800) 230-6008 Fax (480) 659-8361
Loading...