These safety warnings are provided to ensure the safety of personnel and proper operation of the instrument.
Safety warnings and precautions must be read and understood before the MCC1010 / MVC1010 is used. They must be
observed during use.
Do not leave the MCC1010/MVC1010 connected to the system under test when not in use.
Do not touch circuit connections and exposed metalwork of the installation or equipment under test.
Always keep your hand behind the tactile barrier.
Do not use the MCC1010/MVC1010 or connect it to any external system if it shows any visible signs of damage or if it
has been stored for prolonged periods in unfavourable conditions.
Do not use the MCC1010/MVC1010 or connect it to any external system if the casing is open or any parts of the case
are missing.
Do not use the MCC1010/MVC1010 or connect it to any external system if the MCC1010/ MVC1010 lead is damaged
in any way.
Always connect the MCC1010/MVC1010 to the compatible Megger earth testing product before clamping it around
the item being tested.
Always inspect the compatible Megger earth testing product, MCC1010/MVC1010 and connection cable prior to every
use. Replace any defective parts immediately.
Always use extreme caution when clamping around bare conductors: under fault conditions, potentially high voltages
and currents may be present and may pose a shock hazard.
NOTE: THE INSTRUMENT MUST ONLY BE USED BY SUITABLY TRAINED AND COMPETENT PERSONS.
Users of this equipment and/or their employers are reminded that National Health and Safety Legislation requires them
to carry out valid risk assessments of all electrical work so as to identify potential sources of electrical danger and risk of
electrical injury such as inadvertent short circuits. Where the assessments show that the risk is significant then the use of
fused test leads may be appropriate.
The safety warnings provided in this document are indicative of safe practice and shall not be considered exhaustive.
Additionally, they are not intended to replace local safety procedures where the instrument is being used.
Symbols used on the MCC1010/MVC1010 are:
Icon Description
Caution: refer to User Guide
Equipment protected throughout by Double Insulation
Equipment complies with current EU directives.
Do not dispose of in the normal waste stream.
Equipment can be clamped around and removed from hazardous live conductors
(IEC 61010-2-032 Type A clamp)
CAT IV
600 V
Note: The safety warnings provided in this document are indicative of safe practice and shall not be considered exhaustive.
Additionally, they are not intended to replace local safety procedures where the instrument is being used.
Overvoltage category IV is for equipment installed at or near the origin of the electrical supply
to a building 600 V refers to the rms phase-to-earth voltage that this instrument can withstand
to the over- voltage category IV rating
www.GlobalTestSupply.com
Page 4
Introduction
Introduction
Thank you for purchasing the Megger MCC1010 / MVC1010.
For your own safety and to get the maximum benefit from your instrument, please ensure that you read and understand the
safety warnings and instructions in this manual before attempting to use the instruments.
This user manual describes the operation and functions of the MCC1010 / MVC1010:
MCC1010
MVC1010
Megger Instruments Limited reserves the right to change the specification of these instruments at any time without prior
notice.
The MCC1010 is a conventional AC current transformer (CT). For correct operation its output must be loaded with a burden
resistor of appropriate value, which the attached instrument must provide. The voltage developed across the burden resistor
is directly proportional to the primary AC current and the secondary output current is 1000 times smaller than the primary
current.
The MVC1010 is used as a voltage transformer and is designed to work with compatible Megger earth testing products
only. The secondary winding is driven by an AC waveform with a suitable peak value, usually as high as possible, but low
enough not to activate the built-in overvoltage protection circuit.
The MVC1010 has a ratio of 1000:1 so that the voltage induced in a primary wire/cable will be 1000 times lower than
the voltage driving the secondary coil. This reduced primary voltage drives current in the loop under test. The value of the
current will be directly proportional to the loop impedance according to Ohm’s law.
Preparations for use
Inspection
Before each use of the instrument, visually inspect the instrument case, test leads and connectors to confirm that their
condition is good, with no damaged or broken insulation.
Preventive instrument maintenance
1. The MCC1010 / MVC1010 series of instruments require very little maintenance.
2. Test leads should be checked before use to ensure there is no damage.
3. When necessary, the instrument can be cleaned with a damp cloth. Clamp heads must be kept clean.
4. Do not use alcohol-based cleaners, as these may leave a residue.
The instrument contains static sensitive devices, and care must be taken in handling the printed circuit board. If an
instrument’s protection has been impaired it should not be used, but sent for repair by suitably trained and qualified
personnel. The protection is likely to be impaired if for example, it shows visible damage, fails to perform the intended
measurements, has been subjected to prolonged storage under unfavourable conditions, or has been subjected to severe
transport stresses.
NEW INSTRUMENTS ARE GUARANTEED FOR 1 YEAR FROM THE DATE OF PURCHASE BY THE USER.
Note: Any unauthorized prior repair or adjustment will automatically invalidate the Warranty.
Calibration, repair and spare parts
For service requirements for Megger Instruments contact:
Megger operate fully traceable calibration and repair facilities, ensuring your instrument continues to provide the high
standard of performance and workmanship you expect. These facilities are complemented by a worldwide network of
approved repair and calibration companies, which offer excellent in-service care for your Megger products.
Returning your product to Megger - UK and USA service centres
1. When an instrument requires recalibration, or in the event of a repair being necessary, a Returns Authorisation (RA)
number must first be obtained from one of the addresses shown above. You will be asked to provide the following
information to enable the Service Department to prepare in advance for receipt of your instrument, and to provide the
best possible service to you.
Model, e.g. MCC1010 / MVC1010
Serial number, to be found on the underside of the case or on the calibration certificate.
Reason for return, e.g. calibration required, or repair.
Details of the fault if the instrument is to be repaired.
2. Make a note of the RA number. A returns label can be emailed or faxed to you if you wish.
3. Pack the instrument carefully to prevent damage in transit.
4. Ensure the returns label is attached, or that the RA number is clearly marked on the outside of the package and on
any correspondence, before sending the instrument, freight paid, to Megger. Copies of the original purchase invoice
and packing note should be sent simultaneously by airmail to expedite clearance through customs. In the case of
instruments requiring repair outside the warranty period, an immediate quotation can be provided when obtaining the
RA number.
Approved Service Centres
A list of Approved Service Centres may be obtained from the UK address above,
Hereby, Megger Instruments Limited declares that radio equipment manufactured by Megger Instruments Limited described
in this user guide is in compliance with Directive 2014/53/EU. Other equipment manufactured by Megger Instruments
Limited described in this user guide is in compliance with Directives 2014/30/EU and 2014/35/EU where they apply.