31
tech
Table 2 - Fault Finding Chart
FAULT POSSIBLE CAUSE REMEDY
No hot water flow 1. Mains supply off 1. Check and open stop cock
2. Strainer blocked 2. Turn off water supply.
Rem ove strainer and clean (see
Section 9.3)
3. Cold W ater Combination
Valve incorrec tly fitted
3. Check and refit as required
W ater from hot taps is
cold
1. DIRECT immersion
heater not switched on
1. Check and switch on
2. DIRECT immersion
heater thermal cut-out has
operated
2. Check. Reset by pushing
button. (See Diagram 11)
3. INDIRECT programm er
set to Central Heating only
3. Check. Set to a Domestic
Hot W ater programm e
4. INDIRECT boiler not
working
4. Check boiler operation. If fault
is suspected consult boiler
manufacturer's instructions
5. INDIRECT thermal cut-
out has operated
5. Check. Reset by pushing
button on cut-out. Check
operation of indirect thermostat
(see Diagram 13)
6. INDIRECT motorised
valve not connected
correctly
6. Check wiring and/or plumbing
connections to m otorised valve
(see Diagrams 14 & 15)
7. SO LAR insuffic ient solar
gain with no auxiliary
heating switched on
7. Check auxiliary heat source
is switched on and is controlled
to provide heat gain if no solar
output is available.
W ater disc harges 1. INTERMITTENTLY
from Expansion Relief
Valve
Ex pansion volume has
reduced within Ex pansion
Vessel
1. See Section 9.6 for recharging procedure
2. CONTINUALLY
a. Cold W ater Combination
Valve Press ure Reducer not
working correctly
a. Check pressure from Cold
W ater Combination Valve. If
greater than 3 bar replac e
Pressure Reducer cartridge
b. Expansion Valve seat
damaged.
b. Rem ove E xpansion Valve
cartridge. Check condition of
seat. If nec essary fit new
Expansion Valve cartridge.
W ater disc harges from
T&P Relief Valve
1. Therm al control failure
NOTE water will be very hot
1. Switch off power to
imm ersion heater(s), shut down
boiler and solar prim ary circuit.
DO NOT turn off water supply.
W hen discharge stops check
all thermal controls, replace if
faulty.