MEGAFLO Compact 2d, Compact 4d, Compact 8d, Compact 10d, Compact 2i User Manual

...
Page 1
Important
Please read & understand all these instructions before commencing installation.
Please leave this manual with the customer for future reference
Megaflo Compact
Unvented Direct & Indirect
Hot Water Cylinders
Page 2
Contents
1. Introduction 3
1.1 General 3
1.2 Symbols used 3
1.3 Abbreviations 3
1.4 Liabilities 3
2. Safety 4
2.1 General safety warnings 4
3. Technical specications 5
4. Description of the product 10
4.1 General description 10
4.2 Operation principle 10
4.3 Main components 10
4.4 Standard delivery 10
4.5 Storage and Handling 10
5. Before installation 12
5.1 Installation regulations 12
5.2 Installation requirements 12
5.3 Choice of location 12
6. Installation 13
6.1 General 13
6.2 Water connections 13
6.3 Electrical connections 19
6.4 Filling the installation 22
7. Commissioning 23
7.1 General 23
7.2 Checklist before commissioning 23
7.3 Commissioning procedure 23
7.4 Benchmark 23
8. Operation 24
8.1 General 24
9. Maintenance 25
9.1 General 25
9.2 Standard inspection & maintenance operations 25
10. Troubleshooting 27
10.1 Fault nding 27
11. Decommissioning 28
11.1 Decommissioning procedure 28
12. Spare parts 29
12.1 Spare parts list 29
Benchmark checklist 34
Commissioning & service records 35
Warranty 36
Benchmarktm places responsibilities on both manufacturers and installers. The purpose is to ensure that customers are provided with the correct equipment for their needs, that it is installed, commissioned and serviced in accordance with the manufacturer’s instructions by competent persons and that it meets the
requirements of the appropriate Building Regulations and relevant electrical qualications. The Benchmarktm
Checklist can be used to demonstrate compliance with Building Regulations and should be provided to the customer for future reference. Installers are required to carry out installation, commissioning and servicing work in accordance with the Benchmarktm Code of Practice which is available from the Heating and Hotwater Industry Council who manage and promote the Scheme. Visit www.centralheating.co.uk for more information. IMPORTANT NOTE TO USER: PLEASE REFER TO THE COMMISSIONING SECTION, PAGE 23 FOR IMPORTANT INFORMATION WITH RESPECT TO THE BENCHMARK SCHEME
Page 3
1. Introduction
1.1 General
The following instructions are offered as a guide to the user and installer.
The installation must be carried out by a competent plumbing and electrical installer in accordance with Building Regulation G3 (England and Wales), Technical Standard P3 (Scotland) or Building Regulation P5 (Northern Ireland) and the Water Fitting Regulations (England and Wales) or Water Byelaws (Scotland).
1.2 Symbols used
In these instructions, various risk levels are employed to draw the user’s attention to particular information. In doing so we wish to safeguard the user, avoid hazards and guarantee the correct operation of the appliance.
DANGER
Risk of a dangerous situation causing serious physical injury.
WARNING
Risk of dangerous situation causing slight physical injury.
CAUTION
Risk of material damage.
Signals important information.
1.3 Abbreviations
` T&P - Temperature & Pressure relief valve ` PRV - Pressure Reducing Valve ` ERV - Expansion relief valve
1.4 Liabilities
Manufacturers liability
Our products are manufactured in compliance with the requirements of the various applicable European Directives.
This appliance complies with the requirements of the CE marking directive.
In the interest of UK customers, we are continuously endeavouring to make improvements in product
quality. All the specications stated in this document
are therefore subject to change without notice.
Our liability as the manufacturer may not be invoked in the following cases:
` Failure to abide by the instructions on using the
appliance.
` Faulty or insufcient maintenance of the
appliance.
` Failure to abide by the instructions on installing the
product.
Installer's liability
The installer is responsible for the installation and the commissioning of the appliance. The installer must respect the following instructions:
` Read and follow the instructions given in the
manuals provided with the appliance.
` Carry out installation in compliance with the
prevailing legislation and standards.
` Perform the initial start up and carry out any checks
necessary. ` Complete the commissioning checklist. ` Explain the installation to the user. ` If maintenance is necessary, warn the user of the
obligation to check the appliance and maintain it in
good working order. ` Give all the instruction manuals to the user.
Users liability
To guarantee optimum operation of the appliance, the user must respect the following instructions:
` Read and follow the instructions given in the
manuals provided with the appliance. ` Call on qualied professionals to carry out
installation and initial start up. ` Get your installer to explain your installation to you. ` Have your required checks and services done. ` Keep the instruction manuals in good condition and
close to the appliance.
This appliance can be used by children aged
from 8 years and above and persons with reduced physical sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.
Children must be supervised to ensure they do not play with the appliance.
Page 4
2. Safety
2.1 General safety warning
- Water may drip from the discharge pipe of the pressure-relief device and this pipe must be left open to the atmosphere; (see page 18 for more details)
-the pressure-relief device is to be operated regularly to remove lime deposits and to verify that it is not blocked; (see page 18 for more details)
- How hot water can be drained. (see page 25 for more details)
- The type or characteristics of the pressure-relief device and how to connect it; (see Figure 4 page 9 )
- A discharge pipe connected to the pressure­relief device is to be installed in a continuously downward direction and in frost free environment; (see page 18 for details)
Details on how to set the temperature controls for both immersion heaters and boiler controls can be found in section “Installation Instructions, page 20.
WARNING TO USER
` If this unvented water heater develops
a fault, such as a ow of water from
the discharge pipe, switch the heater off and contact the installer.
` Do not remove or adjust any component
or part of this unvented water heater ; contact installer
` DO NOT bypass the thermal cut-out(s)
in any circumstances.
WARNING
` Only competent persons having
received adequate training are permitted to work on the appliance and the installation.
` Do not tamper with any of the safety
valves or controls supplied with the cylinder.
` Before any work, switch off the mains
supply to the appliance.
` Do not switch on if there is a possibility
that the water in the cylinder is frozen.
DANGER
This cylinder is unvented and as such becomes pressurised when in operation. The combination of pressurisation and hot water could lead to serious physical injury if the safety instructions in this manual are not adhered to.
CAUTION
Do not operate immersion heaters until the
cylinder has been lled with water.
WARNING
When handling the unit, take appropriate precautions for the weight of the unit. Weights can be found in section 3, Tables 1&2, pages 5&6.
CAUTION
Annual maintenance is recommended by a competent person.
Page 5
3. Technical specications
Table 1: Technical data - Indirect Cylinders
Notes: 1: at 3 bar water inlet pressure 2: at 80°C - +/- 2°C 3: Although the primary coil pressure rating is 1.0MPa (10bar) the 2 port zone valve and coil compression nuts supplied with
the cylinder are only rated at 0.86MPa (8.6 bar). If the cylinder is to be plumbed into a system delivering 1.0MPa (10 bar) a suitable 2 port zone valve and the coil compression nuts will have to be sourced.
4:Tested to EN 12897:2016
2i
4i
6i
8i
10i
Max direct kW rating 3 3 3 3 3
Immersion heat up times (Btm immersion, 3kW)
139 167 179 208 252
Coil surface area (m²) 0.51
Coil heat up times
15l/min 33.1 40.1 43.0 45.1 52.8
30l/min
26.9 30.2 34.8 37.7 46.7
45/min 25.0 28.8 32.3 34.2 41.7
Coil rating (kW) ²
15l/min 13.1 12.7 13.7 14.3 14.8
30l/min 16.3 16.3 17.1 17.3 17.4
45l/min 17.6 17.7 18.8 19.1 19.0
Pressure drop through
coil
15l/min 0.004 MPa (0.04 Bar)
30l/min 0.013 MPa (0.13 Bar)
45l/min 0.031 MPa (0.31 Bar)
Heat loss (kW/24hrs) 1.58 1.59 1.82 1.97 2.16
Weight empty (kg) 31 34 37 42 46
Weight full (kg) ¹
168 190 217 238 283
Volume (Litres) ¹
137 155 178 195 233
Mixed water delivery to 40°C
1
168 188 218 238 281
Max mains pressure 1.6 MPa (16 Bar)
Max design pressure 0.8 MPa (8 Bar)
Operating pressure/PRV set pressure
0.3 MPa (3 Bar)
Max primary pressure ³ 1.0 MPa (10 Bar)
Expansion relief valve setting 0.8 MPa (8 Bar)
T&P valve setting
90°C +/- 5°C/1.0 MPa (10 Bar)
T&P Part number
7034796
Immersion heater electrical rating 3.0 kW@240V/2.8kW@230V ~
ErP Data
Model(s) 2i 4i 6i 8i 10i
Energy efciency class C C C C C
Standing loss W 65.8 66.3 75.8 82.1 90.0
Storage volume V in Litres 137 155 178 195 233
Technical parameters in accordance with European Commission regulations 814/2013 and 812/2013
Page 6
2d
4d
6d
8d
10d
Max direct kW rating 6 6 6 6 6
Immersion heat up times (Btm immersion, 3kW)
139 175 193 205 267
Immersion heat up times (Top immersion, 3 kW)
65 83 87 89 96
Immersion heat up times (Both immersions, 6kW)
62 79 88 90 98
Heat loss (kW/24hrs) 1.53 1.59 1.80 1.97 2.22
Mixed water delivery to 40°C
1
168 188 218 238 281
Weight empty (kg) 25 31 34 38 46
Weight full (kg) ¹ 165 183 216 237 282
Volume (Litres) ¹ 140 152 182 199 236
Max mains pressure 1.6MPa (16 Bar)
Max design pressure
0.8 MPa (8 Bar)
Operating pressure/PRV set pressure 0.3 MPa (3 Bar)
Expansion relief valve setting 0.8 MPa (8 Bar)
T&P valve setting
90°C +/- 5°C/1.0 MPa (10 Bar)
T&P Part number
7034796
Immersion heater electrical rating 3.0 kW@240V/2.8kW@230V ~
ErP Data
Suppliers model identier 2d 4d 6d 8d 10d
Storage volume V in Litres 140 152 182 199 236
Mixed water at 40°C V40 in Litres 155 180 217 168 273
The declared load prole M L L L XL
The water heating energy efciency class of the model C C C C C
The water heating efciency in % 37 38 38 38 38
The annual electricity consumption in kWh
1397 2729 2697 2666 4379
Daily fuel consumption Q in kWh
6.52 12.66 12.47 12.29 20.20
The thermostat temperature settings of the water heater as placed on the market by the supplier.
60°C
Specic precautions that shall be taken when the water
heater is assembled, installed or maintained and disposed of at end of life.
See pages 3 to 39
Notes: 1: at 3 bar water inlet pressure 2:Tested to EN 60379:2004
3: Energy efciency tested to EN50440
Table 2: Technical data - Direct Cylinders
Technical parameters in accordance with European Commission regulations 814/2013 and 812/2013
Page 7
General information:
Outer casing
White pre-coated corrosion protected steel body shell. Polypropylene top and base mouldings. ABS electrical controls housings and enclosures.
Water container
Duplex stainless steel. 100% pressure tested to 1.6MPa
(16 bar).
Connections
Pipe connections accept 22mm outside diameter pipe (compression nuts and olives supplied). Thread rate is 3/4" BSP parallel to accept standard 3/4" BSP female
ttings if required.
Thermal insulation
CFC/HCFC free re retardant expanded polyurethane
foam with zero ozone depletion potential. It has a Global Warming Potential (GWP) of 3.1.
Safety Features
Direct models: Manually re-settable thermal cut-out on
each immersion heater. Factory tted combined T&P and
Expansion Relief Valve.
Indirect models: Manually re-settable thermal cut-out on immersion heater. Manually re-settable thermal cut-out for primary heating - must be wired in conjunction with 2 port
motorised valve supplied. Factory tted T&P/Expansion
Relief Valve.
Page 8
Figure 1: General dimensions - Direct models
Figure 2: General dimensions - Indirect models
Size DIMENSIONS
(mm)
A B C
2i N/A 728 1130
4i N/A 883 1256
6i N/A 1008 1413
8i 900 1084 1515
10i 1110 1309 1766
Table 3: Dimensions Direct Cylinders
Size DIMENSIONS
(mm)
A B C
2d 668 782 1130
4d 680 883 1256
6d 805 1008 1413
8d 900 1084 1515
10d 1110 1309 1766
424
394
316
355
A
B
C
47°
27°
32°
92
553
30°
355
394
A
B
C
553
32°
30°
92
Table 4: Dimensions Indirect Cylinders
Page 9
Figure 3: Schematic installation details
TO HOT OUTLET
DISCHARGE PIPE
DRAIN COCK
TUNDISH
T&P and RELIEF VALVE
PRIMARY FLOW
RETURN
PRIMARY
ELEMENT/CONTROLS HOUSING
1/2” BSP SENSOR POCKET ASSEMBLY LONG
BALANCED COLD WATER
CONNECTION (IF REQUIRED)
MAINS WATER
SUPPLY
3 BAR PRESSURE REDUCING VALVE
STOP COCK (IF USED IN THIS POSITION)
MIXING VALVE
Combination T&P/ERV
T&P = temperature and pressure
ERV = Expansion relief valve
Mains water
supply
90° Tundish
T&P
actuation knob
ERV
actuation knob
D2 Pipe
Figure 4: Combination T&P/ERV
Page 10
10
4. Description of the product
4.1 General description
This appliance is a purpose designed unvented water heater. The unit has a stainless steel inner vessel, which ensures an excellent standard of corrosion resistance. The outer casing is a combination of resilient thermoplastic mouldings and pre-painetd corrosion proofed steel. All products are insulated with CFC free polyurethane foam to give good heat loss protection.
The appliance is supplied complete with all the necessary safety and control devices needed to allow connection to the cold water mains. All these components are preset and should not be tampered with.
4.2 Operation principle
The unvented cylinder is used to heat and store hot water for use in domestic applications.
Depending on the model the water can be heated
directly using factory tted Immersion heater(s) or
indirectly through a coil in the unit using an indirect heat source.
To provide pressure to the tap or shower an unvented water heater uses the incoming mains water pressure. To do this the water heater is sealed and not vented. However, when the volume of water is heated it expands and without any room for expansion could cause the water heater to rupture and fail. The water heater requires no separate expansion vessel to accommodate this expansion as it incorporates an internal air gap.
4.3 Main components
See Figure 3 on page 9
4.4 Standard delivery
The delivery includes:
` Cylinder incorporating factory tted immersion
heater(s) and thermal controls and factory tted
combination T&P/Expansion relief valve
` Instructions (inc benchmark commissioning
checklist & service record)
` Warranty card
` Cold water control pack
` Pressure reducing valve ` Isolation valve ` Mixer valve ` Mixer valve connection pipe ` Tundish ` Drain valve ` Nut and olive kit
` Immersion spanner ` 2 port zone valve (indirect only) ` Wiring centre (indirect only)
Check all components are supplied in the pack and advise your supplier if any are missing
4.5 Storage and Handling
If the unit is to be stored before installation it must be placed upright on a secure, level surface and be in a dry, frost free environment. The support surface must be capable of supporting the packaged weight of the unit, the packaged weights are displayed on the carton label.
Please take care when handling a packaged cylinder. The units are heavy and must only be moved manually using safe working practices. The package weights of each unit are displayed on the carton label. Take note of the unit weights when deciding on a safe
lifting method. DO NOT use the factory tted T&P/
Expansion Relief Valve to lift or manoeuvre the unit.
Page 11
11
Figure 5: Typical system installation schematic (not to scale)
Balanced cold water
draw-off
Combined Temperature
and Pressure Relief valve
with Expansion Relief
Valve / Check Valve
0.3 Mpa/3 bar Pressure Reducing
Valve and Strainer.
(Stop cock can be fitted
here)
MCWS to Kitchen
(unbalanced cold
mains supply)
Mains Cold Water
Supply
KEY
MCWS = Mains Cold Water Supply
HWS = Hot Water Service
SC = Stop Cock / Isolating Valve
DOC = Drain Off Cock
Discharge pipe to atmosphere
(see page 18 “Discharge Pipework”)
Isolating / Regulating
Valves, as required
Mixed HWS supply
Balanced HWS and
MCWS to bathrooms,
showers, cloakrooms,
etc
DOC DOC
DOC
DOC
SC
SC
Tundish
Mixing valve
Page 12
12
5. Before installation
WARNING
Installation of the appliance must be carried
out by a qualied engineer in accordance
with prevailing and national regulations as listed below.
` Building Regulations G3 ` The Building Standards (Scotland) ` The Building Regulations (Northern
Ireland) ` I.E.E Electrical Regs ` UK Water Regulations
5.2 Installation requirements
Water supply
In an unvented system the pressure and owrate is
directly related to the incoming water supply. For this reason it is recommended that the maximum water demand is assessed and the water supply checked to ensure this demand can be satisfactorily met.
` We suggest the minimum supply requirements
should be 0.15MPa (1.5 bar) pressure and 20 litres
per minute ow rate. However, at these values outlet ow rates may be poor if several outlets are
used simultaneously.
` A 22mm cold water supply is recommended,
however, if a smaller supply exists, which provides
sufcient ow, this may be used (although more ow noise may be experienced).
` The higher the available pressure and ow rate the
better the system performance.
` See tables 1&2 on pages 5&6 for cylinder operating
pressures. This is controlled by the Pressure Reducing valve (PRV)
Outlet/terminal ttings (taps, etc.)
` The appliance can be used with most types of
terminal ttings.
` Outlets situated higher than the appliance will give
outlet pressures lower than that at the appliance, a 10m height difference will result in a 1 bar pressure reduction at the outlet.
` All ttings, pipework and connections must have a
rated pressure of at least 8 bar at 80°C.
Limitations
The appliance should not be used in association with any of the following:
` Solid fuel boilers or any other boiler in which the
energy input is not under effective thermostatic control, unless additional and appropriate safety measures are installed.
` Ascending spray type bidets or any other class 1
back syphonage risk requiring that a type A air gap be employed.
` Steam heating plants unless additional and
appropriate safety devices are installed.
` Situations where maintenance is likely to be
neglected or safety devices tampered with.
` Water supplies that have either inadequate
pressure or where the supply may be intermittent.
` Situations where it is not possible to safely pipe
away any discharge from the safety valves.
` In areas where the water consistently contains a
high proportion of solids, e.g. suspended matter that could block the strainer, unless adequate
ltration can be ensured.
` In areas where the water supply contains chloride
levels that exceed 250mg/l.
5.3 Choice of location
The appliance must be vertically oor mounted.
Although location is not critical, the following points should be considered:
` The appliance should be sited to ensure minimum
dead leg distances, particularly to the point of most frequent use.
` Avoid siting where extreme cold temperatures will
be experienced. All exposed pipe work should be insulated.
` The discharge pipework from the safety valves
must have minimum fall of 1:200 from the appliance and terminate in a safe and visible position as per G3 requirements
` Access to associated controls and immersion
heaters must be available for the servicing and maintenance of the system. Where these controls are installed against a wall a minimum distance of 250mm must be left (see Fig. 6).
` Note of the overall height of the appliance in relation
to the ceiling height and ensure that access and space is available for piping/connections to the outlet.
` Ensure that the oor area for the appliance is level
and capable of permanently supporting the weight when full of water (see Tables 1&2, pages 5&6 for weights).
` The tundish should be installed away from electrical
components.
Figure 6: Siting the appliance
WALL
Min 250mm
Min 250mm
5.1 Installation regulations
Page 13
13
` The draining tap supplied should be installed in
the cold water supply to the cylinder between the expansion valve and the heater at as low a level as possible.
` It is recommended that the outlet point of the drain
pipework be at least 1 metre below the level of the base of the appliance (this can be achieved by attaching a hose to the drain tap outlet spigot).
` Hot water distribution pipework should be 22mm
pipe with short runs of 15mm pipe to terminal
ttings such as sinks and basins. Pipe sizes may
vary due to system design
Mixing valve
` The mixing valve should be installed at the hot
outlet point of the appliance using the copper tube
supplied. (see gure 7 below). The mixing valve will
reduce the hot water outlet temperature to approx 55°C, further temperature control will be required for
outlets such as showers and baths
` The mixing valve can be installed in any orientation
providing the pipe from the tank outlet to the H port of the valve is no more than 500mm long and has no
other connections attached.
` Where the application dictates water to be
delivered at 60°C, a mixing valve pre-set at 60°C is available as an accessory (see page 29) note the overall mixed water volume would decrease
6. Installation
6.1 General
After reading the previous sections in this booklet and choosing a suitable location for the appliance please install, paying attention to the following water, electrical and commissioning sections.
Boiler selection (Indirect units only)
` The boiler should have a control thermostat and non
self-resetting thermal cut-out and be compatible with unvented storage water heaters.
` Where use of a boiler without a thermal cut-out
is unavoidable a “low head” open vented primary circuit should be used. The feed and expansion cistern head above the cylinder should not exceed
2.5m.
` Can be a sealed system or open vented type -
maximum primary pressure 10 bar.
` The boiler cannot be vented through the cylinder.
6.2 Water connections
WARNING
` Under no circumstances should the
factory fitted Temperature/Pressure/ Expansion Relief Valve be removed other than by a competent person. To do so will invalidate any warranty or claim.
` The cold water controls MUST be
fitted on the mains water supply to the appliance.
` No control or safety valves should be
tampered with or used for any other purpose.
` The discharge pipe should not be blocked
or used for any other purpose.
` The tundish should not be located
adjacent to any electrical components.
` The mixing valve supplied is factory pre-
set to give a water temperature of approx 55°C. Do not dismantle or attempt to adjust
Refer to the installation schematic (Fig 3, page 9) for
details on the pipework layout. Specic details for the
discharge pipework layout is also provided in Figure 10 on page 18.
` All connections accept 22mm outside diameter
pipe (compression nuts and olives supplied). The thread rate is 3/4" BSP Male parallel to accept
standard 3/4" BSP Female ttings if required.
` The Cold Water Inlet Control kit supplied
incorporates a full ow isolating valve which will
enable the appliance to be isolated from the mains supply for maintenance or servicing.
` The location of the unit should allow access to the
Combination T&P/ERV to allow re-charging of the internal air gap when necessary.
Hot water from
cylinder
Cold water from
Mains
Mixed water
Mixer Valve
Copper tube
H
M
C
Figure 7: Mixing valve layout
Page 14
14
Cold water control pack
CAUTION
` Flush supply pipework before
connection to remove all ux and debris prior to tting the inlet controls.
Failure to do this may result in irreparable damage to the controls and will invalidate any warranty.
` The cold water control pack can be connected
anywhere on the cold water cylinder supply.
` The Control pack incorporates the pressure
reducing valve and isolation valve ` The pressure setting is set to 0.3MPa/3.0 bar. ` The valve can be tted in any orientation to suit
the installation as long as the valve is installed with
the direction of ow arrows pointing in the correct
direction.
` The Expansion Relief has been incorporated into
the T&P valve for ease of installation
` No other valves should be placed between the cold
pressure reducing valve and the appliance.
Primary circuit control
` The 2 port motorised valve supplied with the
appliance MUST be tted on the primary ow to the
appliance heat exchanger and wired such that in the event of the appliance overheating it will close the primary circuit.
` Primary circulation to the appliance heat exchanger
must be pumped; gravity ow to the appliance heat
exchanger WILL NOT WORK.
` It is recommended that an air bleed or automatic
air vent is incorporated in the primary return pipe work close to the unit.
` Boiler ow temperature should be set to 80°C
(peak temperature not to exceed 88°C)
Figure 9: Cold water controls
Isolation valve to be paired with Reducing valve
3 bar Pressure
Reducing Valve
Isolation valve
Figure 8: Pressure Reducing Valve
Mains in
22mm compression connections
Outlet to Megao
Take note of ow
direction
Pressure reducing valve
cartridge (3 bar)
Page 15
15
Secondary circulation
If secondary circulation is required it is recommended
that it be connected to the cylinder as shown (see g
10).
` The secondary return pipe should be in 15mm pipe
and incorporate a check valve to prevent backow.
` A suitable WRAS approved circulation pump will
be required. ` On large systems, due to the increase in system
water content, it may be necessary to t an
additional expansion vessel to the secondary
circuit. This should be done if the capacity of the
secondary circuit exceeds 10 litres.
Pipe capacity (copper): 15mm O.D. = 0.13 l/m (10 litres = 77m) 22mm O.D. = 0.38 l/m (10 litres = 26m) 28mm O.D. = 0.55 l/m (10 litres = 18m)
Note: Plastic pipe capacities may be reduced due to thicker wall sections.
In direct electric installations where a secondary
circulation is required particular attention should be paid by the installer to maintain the returning water temperature (guidelines state that a minimum of 55°C return temperature is advisable). Factors such as,
but not limited to, secondary circulation ow rates,
minimising heat loss of all secondary circuit pipework and timed operation during periods of high demand are critical to the correct operation and longevity of the heating element(s) and thermostats.
Secondary circulation is not recommended for
direct electric units using off-peak tariffs where the secondary circulation is not controlled in conjunction with the heat source as performance can be affected.
Figure 10: Secondary circulation schematic
Cold Water Inlet
T
o Hot
Outlets
Check Valve
Swept Tee
Secondary Return
Secondary
Circulation Pump
Page 16
16
Discharge
It is a requirement of Building Regulation G3 that any discharge from an unvented system is conveyed to where it is visible, but will not cause danger to persons in or about the building. The tundish and discharge pipes
should be tted in accordance with the requirements
and guidance notes of Building Regulation G3. The G3 Requirements and Guidance section 3.50 - 3.63 are reproduced in the following sections of this manual. For discharge pipe arrangements not covered by G3 Guidance advice should be sought from your local
Building Control Ofcer. Any discharge pipe connected
to the pressure relief devices (expansion valve and temperature/pressure relief valve) must be installed in a continuously downward direction and in a frost free environment.
Water may drip from the discharge pipe of the pressure relief device. This pipe must be left open to the atmosphere. The pressure relief device is to be operated regularly to remove lime deposits and to verify that it is not blocked.
G3 REQUIREMENT
“...there shall be precautions...to ensure that the hot water discharged from safety devices is safely conveyed to where it is visible but will not cause danger to persons in or about the building.”
The following extract is taken from the latest G3 Regulations
Discharge pipes from safety devices
Discharge pipe D1
3.50 Each of the temperature relief valves or combined
temperature and pressure relief valves specied in
3.13 or 3.17 should discharge either directly or by way of a manifold via a short length of metal pipe (D1) to a tundish.
3.51 The diameter of discharge pipe (D1) should be not less than the nominal outlet size of the temperature relief valve.
3.52 Where a manifold is used it should be sized to accept and discharge the total discharge from the discharge pipes connected to it.
3.53 Where valves other than the temperature and pressure relief valve from a single unvented hot water system discharge by way of the same manifold that is used by the safety devices, the manifold should be
factory tted as part of the hot water storage system
unit or package.
Tundish
3.54 The tundish should be vertical, located in the same space as the unvented hot water storage system
and be tted as close as possible to, and lower than,
the valve, with no more than 600mm of pipe between the valve outlet and the tundish (see Fig 11, page 18).
Note: To comply with the Water Supply (Water Fittings) Regulations, the tundish should incorporate a suitable air gap.
3.55 Any discharge should be visible at the tundish. In addition, where discharges from safety devices may not be apparent, e.g. in dwellings occupied by people with impaired vision or mobility, consideration should be given to the installation of a suitable safety device to warn when discharge takes place, e.g. electronically operated.
Discharge pipe D2
3.56 The discharge pipe (D2) from the tundish should:
(a) have a vertical section of pipe at least 300mm long below the tundish before any elbows or bends in
the pipework (see g. 11); and
(b) be installed with a continuous fall thereafter of at least 1 in 200.
3.57 The discharge pipe (D2) should be made of:
(a) metal; or
(b) other material that has been demonstrated to be capable of safely withstanding temperatures of the water discharged and is clearly and permanently marked to identify the product and performance standard (e.g. as
specied in the relevant part of BS 7291).
3.58 The discharge pipe (D2) should be at least one pipe size larger than the nominal outlet size of the safety device unless its total equivalent hydraulic resistance
exceeds that of a straight pipe 9m long, i.e. for discharge pipes between 9m and 18m the equivalent resistance
length should be at least two sizes larger than the
nominal outlet size of the safety device; between 18 and 27m at least 3 sizes larger, and so on; bends must be taken into account in calculating the ow resistance.
See Fig 11, Table 6 and the worked example.
Note: An alternative approach for sizing discharge
pipes would be to follow Annex D, section D.2 of BS 6700:2006 Specication for design, installation, testing
and maintenance of services supplying water for domestic use within buildings and their curtilages.
3.59 Where a single common discharge pipe serves
more than one system, it should be at least one pipe size larger than the largest individual discharge pipe (D2) to be connected.
3.60 The discharge pipe should not be connected to a soil discharge stack unless it can be demonstrated that the soil discharge stack is capable of safely withstanding temperatures of the water discharged, in which case, it should:
(a) contain a mechanical seal, not incorporating a water trap, which allows water into the branch pipe without allowing foul air from the drain to be ventilated
through the tundish;
(b) be a separate branch pipe with no sanitary
appliances connected to it;
Page 17
17
Worked example of discharge pipe sizing
Fig. 11: shows a G1/2 temperature relief valve with a discharge pipe (D2) having 4 No. elbows and length of 7m from the tundish to the point of discharge.
From Table 6: Maximum resistance allowed for a straight length of 22mm copper discharge pipe (D2) from a G1/2 temperature relief valve is 9.0m.
Subtract the resistance for 4 No. 22mm elbows at 0.8m each = 3.2m
Therefore the permitted length equates to: 5.8m
5.8m is less than the actual length of 7m therefore calculate the next largest size.
Maximum resistance allowed for a straight length of 28mm pipe (D2) from a G1/2 temperature relief valves equates to 18m.
Subtract the resistance of 4 No. 28mm elbows at 1.0m each = 4.0m
Therefore the maximum permitted length equates to: 14m
As the actual length is 7m, a 28mm (D2) copper pipe will be satisfactory.
(c) if plastic pipes are used as branch pipes carrying discharge from a safety device they should be either
polybutylene (PB) to Class S of BS 7291-2:2006 or cross linked polyethylene (PE-X) to Class S of BS 7291-3:2006; and
(d) be continuously marked with a warning that no sanitary appliances should be connected to the pipe.
Note:
1. Plastic pipes should be joined and assembled with
ttings appropriate to the circumstances in which they are used as set out in BS EN ISO 1043-1.
2. Where pipes cannot be connected to the stack it may be possible to route a dedicated pipe alongside or in close proximity to the discharge stack.
Termination of discharge pipe
3.61 The discharge pipe (D2) from the tundish should terminate in a safe place where there is no risk to persons in the vicinity of the discharge.
3.62 Examples of acceptable discharge arrangements are:
(a) to a trapped gully with the end of the pipe below a
xed grating and above the water seal; (b) downward discharges at low level; i.e. up to
100mm above external surfaces such as car parks, hard standings, grassed areas etc. are acceptable providing that a wire cage or similar guard is positioned
to prevent contact, whilst maintaining visibility; and
(c) discharges at high level: e.g. into a metal hopper and metal downpipe with the end of the discharge pipe clearly visible or onto a roof capable of withstanding high temperature discharges of water and 3m from any plastic guttering system that would collect such discharges.
3.63 The discharge would consist of high temperature
water and steam. Asphalt, roong felt and non-
metallic rainwater goods may be damaged by such discharges.
Page 18
18
Valve
Outlet Size
Minimum Size Of
Discharge Pipe
D1
Minimum Size Of
Discharge Pipe D2
From Tundish
Maximum Resistance
Allowed, Expressed As A
Length Of Straight Pipe
(I.E. No Elbows Or Bends)
Resistance
Created By Each
Elbow Or Bend
G1/2 15mm
22mm 28mm 35mm
up to 9m up to 18m up to 27m
0.8m
1.0m
1.4m
G3/4 22mm
28mm 35mm 42mm
up to 9m up to 18m up to 27m
1.0m
1.4m
1.7m
G1 28mm
35mm 42mm 54mm
up to 9m up to 18m up to 27m
1.4m
1.7m
2.3m
Table 5: Sizing of copper discharge pipe (D2) for common temperature relief valve outlet sizes
Safety device
(e.g. Temperature
relief valve)
Metal discharge pipe (D1) from
Temperature relief valve to tundish
Tundish
Discharge below
fixed grating
(Building Regulation
G3 section 3.61 gives
alternative points
of discharge)
Fixed grating
Trapped
gully
600mm maximum
300mm
minimum
Discharge pipe (D2) from tundish,
with continuous fall. See Building
Regulation G3 section 3.56,
Table 1 and worked example
Figure 11: Typical discharge pipe arrangement (extract from Building Regulation G3 Guidance Section 3.50)
Page 19
19
6.3 Electrical connections
In case of difculty contact service support; contact
details are available on page 40 of this booklet.
WARNING
` Disconnect from the mains electrical
supply before removing any covers.
` Never attempt to replace the
immersion heater(s) other than with the recommended immersion heater(s).
` DO NOT bypass the thermal cut-out(s)
in any circumstances.
` All electrical wiring should be carried
out by a competent electrician and be in accordance with the latest I.E.E Wiring Regulations.
` Each circuit must be protected by a
suitable fuse and double pole isolating switch with a contact separation of at least 3mm in both poles.
` DO NOT operate the immersion
heaters until the appliance has been
lled with water.
DIRECT models
` The immersion heater and controls are accessed
by removing the Control Cover (see Fig 12).
` Unscrew the large screw on the cover using a at
ended screwdriver.
` Lift from the bottom of the cover at the point
indicated on Fig 12 until cover comes away freely.
` The immersion heater thermostat is factory set at
57oC. This is set for eco mode. To maximise water availability the thermostat should be set to maximum during commissioning (see Fig 14). Should this require adjustment see Fig 14 for details of how to adjust the temperature setting. Each immersion heater has its own individual thermostatic control. The thermostat incorporates a thermal cut-out that will switch off the immersion heater in the event of a thermostat failure. The thermal cut-out reset button position is also shown on Fig 14.
` Replace the Control Cover(s) before operating.
To do this tilt the cover and align the top two lugs with the holes in the housing as indicated on Fig
12. Hinge the cover downwards and rmly press
the cover until it "snaps" back into place. Secure
by tightening the screw on the cover using a at
ended screwdriver. DO NOT OVER TIGHTEN
` Where the Megao's are tted with two immersion
heaters. Each immersion heater is rated 3kW at 240V ~ 1ph
` The immersion heater(s) should be wired in
accordance with Fig 13. The immersion heater(s) MUST be earthed. The supply cable should be a minimum 1.5mm² 3 core HO5 VV-F sheathed cable and must be routed through the cable entry ports
provided with the outer sheath of the cable rmly
secured using the cable securing bar provided.
Figure 12: Immersion heater cover removal and replacement
Figure 13: Wiring schematic - DIRECT models
N
L
Direct Wiring Layout
1.5mm² 3 Core HO5 VV-F sheathed cable
LIFT OFF
REPLACE
LIFT FROM THIS POINT
LUGS
Page 20
20
` The immersion heater and indirect controls MUST
be earthed. The supply cable for the immersion heater should be a minimum 1.5mm² 3 core HO5 VV-F sheathed cable and must be routed through the right hand cable entry port provided, with the
outer sheath of the cable rmly secured using the
cable securing bar provided. The cable connecting the indirect control to the heating system must be an appropriate size for the maximum load of the heating controls and should be routed in the controls housing through the left hand cable entry port and secured using the cable securing bar provided.
` The immersion heater and boiler control
thermostats are factory set at 57oC and 70°C . See Fig 14 for details of how to adjust the temperature setting. The immersion heater and indirect controls each has its own individual thermostatic control. The thermostats incorporate a thermal cut-out that will switch off in the event of a thermostat failure. The thermal cut-out reset button position is also shown on Fig 14.
` Replace the Control Cover(s) before operating.
To do this tilt the cover and align the top two lugs with the holes in the housing as indicated on Fig
12. Hinge the cover downwards and rmly press
the cover until it "snaps" back into place. Secure
by tightening the screw on the cover using a at
ended screwdriver. DO NOT OVER TIGHTEN
Space and heating systems controls
` The controls provided with the cylinder will ensure
the safe operation of the unit within the central heating system. Other controls will be necessary to control the space heating requirements and times that the system is required to function.
` The cylinder is compatible with most heating
controls, examples of electrical circuits are shown in Figures. 16 & 17. However, other systems may be suitable, refer to the controls manufacturers instructions, supplied with the controls selected, for
alternative system wiring schemes.
INDIRECT models
` The indirect controls and back-up immersion heater
are accessed by removing the Control Cover (see Fig 12).
` Unscrew the large screw on the cover using a at
ended screwdriver.
` Lift from the bottom of the cover at the point
indicated on Fig 12 until cover comes away freely.
` The back up immersion heater should be wired
in accordance with the instructions given for DIRECT models. The immersion heater cannot be controlled by the boiler control or space heating programmer, it must be connected with its own dedicated electrical supply circuit.
` The immersion heater and indirect thermal controls
should be wired in accordance with Fig 15
Figure 15: Wiring schematic - INDIRECT models
Figure 14: Thermostat adjustment
L
N
1 2 3
Control Housing Details
Immersion connections
1.5mm² 3 Core HO5 VV-F sheathed cable
Indirect control wiring
SPINDLE POSITIONS
= MINIMUM TEMP
= MAXIMUM TEMP 70°C
= APPROX 57 °C
ROTATE SPINDLE CLOCKWISE FOR TEMPERATURE INCREASE AND COUNTER CLOCKWISE FOR TEMPERATURE DECREASE
TEMPERATURE ADJUSTING SPINDLE
THERMAL CUT-OUT RESET BUTTON
Page 21
21
Figure 16: Wiring schematic - 2 x 2 Port valve heating system
Figure 17: Wiring schematic - 2 Port valve in conjunction with 3 port mid-position valve heating system
L N
N L
N L
G GY
1 2 3
L N
HTG
ON
DHW
ON
Pump
Boiler
Zone valve (HTG)
Megaflo (DHW)
zone valve
(Supplied)
Wiring centre
(Supplied)
Programmer
Megaflo indirect
thermal controls
(Supplied fitted)
1 3 2
Room stat
NOTES:
1. A DOUBLE POLE ISOLATING SWITCH MUST BE INSTALLED IN THE MAINS SUPPLY.
2. ALL EARTH CONNECTIONS MUST BE LINKED BACK TO THE MAINS EARTH SUPPLY.
3. USE COPPER LINKS SUPPLIED TO MAKE CONNECTIONS BETWEEN TERMINALS.
4. DO NOT MOUNT WIRING CENTRE ON CYLINDER.
5. THE ABOVE DIAGRAM IS FOR GUIDANCE ONLY, HEATRAE SADIA ACCEPT NO LIABILITY FOR ANY LOSS OR DAMAGE ARISING FROM ANY ERRORS OR OMISSIONS. THAT MAY BE INADVERTENTLY CONTAINED WITHIN THIS DIAGRAM. THE VARIOUS EQUIPMENT MANUFACTURERS SHOULD BE CONSULTED TO CONFIRM THE CORRECT OPERATION OF THEIR PRODUCTS WITHIN THE SYSTEM.
KEY Bl BLUE Br BROWN G GREY O ORANGE GY GREEN/YELLOW DHW DOMESTIC HOT WATER HTG HEATING
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Bl Br O
G GYBl Br O
L N
N L
N L
Bl W G O GY
1 2 3
L N
HTG
ON
DHW
ON
Pump
Boiler
3-Port mid position valve
Megaflo (DHW) 2-Port
valve (Supplied)
Wiring centre
(Supplied)
Programmer
Megaflo Indirect
thermal controls (Supplied fitted)
1 3 2
Room sta
NOTES:
1. A DOUBLE POLE ISOLATING SWITCH MUST BE INSTALLED IN THE MAINS SUPPLY.
2. ALL EARTH CONNECTIONS MUST BE LINKED BACK TO THE MAINS EARTH SUPPLY.
3. ASSUMES BASIC BOILER WITH EXTERNAL PUMP.
4. USE COPPER LINKS SUPPLIED TO MAKE CONNECTIONS BETWEEN TERMINALS.
5. DO NOT MOUNT WIRING CENTRE ON CYLINDER.
6. THE ABOVE DIAGRAM IS FOR GUIDANCE ONLY, HEATRAE SADIA ACCEPT NO LIABILITY FOR ANY LOSS OR DAMAGE ARISING FROM ANY ERRORS OR OMISSIONS. THAT MAY BE INADVER TENTLY CONTAINED WITHIN THIS DIAGRAM. THE VARIOUS EQUIPMENT MANUFACTURERS SHOULD BE CONSULTED TO CONFIRM THE CORRECT OPERATION OF THEIR PRODUCTS WITHIN THE SYSTEM.
KEY Bl BLUE Br BROWN G GREY O ORANGE GY GREEN/YELLOW DHW DOMESTIC HOT WATER HTG HEATING
W WHITE
DHW
OFF
1
2 3 4 5 6 7
8
9
10
11 12
13 14
15
16
Bl
Br
G
O GY
Page 22
22
6.4 Filling the appliance
` Ensure the drain cock is CLOSED. ` Open a hot tap furthest from the appliance. ` Open the mains stop cock. ` Open the isolating valve by turning the blue handle
so it is parallel with the direction of ow. It should
be fully opened, partial opening will restrict the inlet
ow rate.
` Allow the appliance to ll. When water ows from
the tap, allow to run for a few minutes to thoroughly
ush through any residue, dirt or swarf, then close
the tap.
` Open successive hot taps to purge the system of
air.
` Check all connections and system pipes for water
tightness.
WARNING
Should the Megaflo be used in conjunction with a boiler or external controls that control the water temperature via a sensor connected to the cylinder, it should be noted that the factory fitted indirect thermostat and thermal cut-out MUST NOT be disconnected or bypassed. To do so would invalidate the product approvals and warranty and it would not comply with Building Regulations. Should this method of control be adopted the Megaflo Indirect thermostat should be set at maximum and the cylinder control temperature set at 68oC to avoid the thermostat over-riding the boiler control. Where the boiler or external controls do not directly power the 2 Port Motorised Valve supplied with the Megaflo, the wiring should ensure that in the event of the thermal cut-out on the Megaflo Indirect controls operating power will be interrupted to the 2 Port Motorised Valve such that it closes and prevents flow of the primary heating fluid around the Megaflo primary heat exchanger coil. For further details of wiring the boiler, or external controls consult the manufacturer’s installation instructions.
Page 23
23
7. Commissioning
7.1 General
After lling the installation with water in the previous
section please follow the following steps to complete the installation of the unit.
7.2 Checklist before commissioning
` Check all water connections for leaks and rectify
as necessary. ` Turn off mains water supply. ` Remove the pressure reducing valve head work to
access the strainer mesh, clean and re-t.
` Turn the water supply back on. ` Manually open, for a few seconds, each relief valve
in turn, checking that water is discharged and runs
freely through the tundish and out at the discharge
point. ` Ensure that the valve(s) reseat satisfactorily.
7.3 Commissioning procedure
Direct units
` Switch on electrical supply to the immersion
heater(s) and allow the water heater to heat up to
normal working temperature, factory set to 57°C
but for maximum hot water availability reset to
70°C (see Fig 14, page 20). ` Adjust the temperature by inserting a at bladed
screwdriver in the adjustment spindle on front of the
immersion heater (ELEMENT) control thermostat
and rotating (see Fig. 14 page, 20 for details
of how to adjust). The adjustment represents a
temperature range of 10°C to 70°C. ` Check the operation of thermostat(s) and that no
water has issued from the Expansion Relief Valve
or Temperature/Pressure Relief Valve during the
heating cycle. ` The mixing valve tted to the hot water outlet will
reduce the outlet temperature to approx 55°C. It is not adjustable
Indirect units
` Fill the indirect (primary) circuit following the boiler
manufacturer’s commissioning instructions.
` To ensure the cylinder primary heat exchanger is
lled, the 2 port motorised valve (supplied) should
be manually opened by moving the lever on the motor housing to the MANUAL setting. When the primary circuit is full return the lever to the AUTOMATIC position.
` Switch on the boiler, ensure the programmer is set
to Hot Water and allow the cylinder to heat up to a normal working temperature, 70°C.
` If necessary adjust the temperature by inserting a
at bladed screwdriver in the adjustment spindle
on front of the indirect (BOILER) thermostat and rotating (see Fig. 14, page 20 for details of how to adjust). The adjustment represents a temperature range of 10°C to 70°C, setting less than 70°C will reduce the amount of available hot water.
` Check the operation of thermostat(s) and that no
water has issued from the Expansion Relief Valve or Temperature/Pressure Relief Valve during the heating cycle.
` The mixing valve tted to the hot water outlet will
reduce the outlet temperature to approx 55°C. It is not adjustable
7.4 Benchmark
The appliance is covered by the Benchmark Scheme which aims to improve the standards of installation and commissioning of domestic heating and hot water systems in the UK and to encourage regular servicing
to optimise safety, efciency and performance.
Benchmark is managed and promoted by the Heating and Hotwater Industry Council. For more information visit www.centralheating.co.uk.
Please ensure that the installer has fully completed the Benchmark Checklist (see page 34) of this manual and that you have signed it to say that you have received a full and clear explanation of its operation. The installer is legally required to complete a commissioning checklist as a means of complying with the appropriate Building Regulations (England & Wales).
All installations must be notied to Local Area Building
Control either directly or through a Competent Persons Scheme. A Building Regulations Compliance
Certicate will then be issued to the customer who should, on receipt, write the Notication Number on the
Benchmark Checklist.
This product should be serviced regularly to optimise
its safety, efciency and performance. The service
engineer should complete the relevant Service Record on the Benchmark Checklist after each service. The Benchmark Checklist may be required in the event of any warranty work.
WARNING
` If the unit is to be left unused following
installation and commissioning e.g. unocupied properties, the water heater
should be drained or regularly ushed
through with fresh mains water once a week.
` When placing the unit into service,
the procedure for lling the unit and
the system checks below should be observed.
WARNING
DO NOT operate the immersion heaters or primary circuit until the appliance has been filled with water.
Page 24
24
8.1 General
8. Operation
Temperature controls – direct units immersion
heater(s)
` A combined thermostat and thermal cut-out is
provided for each immersion heater tted. The
thermostat is factory set to give a water storage temperature of approx. 57oC, however it can be set to control between 10oC and 70oC. For maximum hot water availabilty its advisable to set the thermostat to 70°C during commissioning.
` To access the thermostat open the controls housing
cover (see Fig 12, page 19)- DISCONNECT THE ELECTRICAL SUPPLY BEFORE OPENING THE COVER(S).
` Temperature adjustment is made by rotating the
adjustment spindle on the top of the thermostat. The adjustment represents a temperature range of 10°C to 70°C (see page 20, Fig 14 for method of adjustment).
` Maximum working temperature is 70°C.
DO NOT bypass the thermal cut-out(s) in any circumstances.
Temperature controls - indirect units
` A combined thermostat and thermal cut-out is
provided for the control of the external boiler. The thermostat is factory set to give a water storage temperature of approx. 70oC, however it can be set to control between 10oC and 70oC. Adjustments can only be made by opening the controls covers.
` To access the thermostat open the controls housing
cover (see Fig 12, page 19)- DISCONNECT THE ELECTRICAL SUPPLY BEFORE OPENING THE COVER(S).
WARNING
` If water discharges from the Temperature
& Pressure relief valve on the cylinder shut down the heat source and/or switch off the immersion heater(s). DO NOT turn off the water supply. Contact a competent installer for unvented water heaters to check the system.
` DO NOT tamper with any of the safety
valves tted to the system. If a fault is
suspected contact a competent installer.
` Disconnect from the mains electrical
supply before removing any covers.
` DO NOT bypass the thermal cut-out(s)
in any circumstances.
` All electrical wiring should be carried
out by a competent electrician and be in accordance with the latest I.E.E Wiring Regulations.
` Temperature adjustment is made by rotating the
adjustment spindle on the top of the thermostat. The adjustment represents a temperature range of 10°C to 70°C (see page 20, Fig 14 for method of
adjustment). ` Maximum working temperature is 70°C. ` The boiler thermostat and thermal cut-out must
be wired in series with the 2 port motorised zone
valve supplied to interrupt the ow of primary water
around the heat exchanger coil when the control
temperature has been reached. ` The controls tted to the cylinder will affect the
temperature of the stored water only, other
controls will be provided in the system for time
and temperature control of the space heating
requirements. Consult the instructions provided
with those controls for details of adjustments.
DO NOT bypass the thermal cut-out(s) in any circumstances.
Mixing Valve
The hot water outlet is tted with a factory pre-set
mixing valve which limits the temperature of the hot water to approx 55°C. Scalding can still occur at this temperature so further temperature control may be required at shower and bath outlets
Flow performance
When initially opening hot outlets a small surge in
ow may be noticed as pressures stabilise. This is
quite normal with unvented systems. In some areas cloudiness may be noticed in the hot water. This is due to aeration of the water, is quite normal and will quickly clear.
Operational faults
Operational faults and their possible causes are detailed in the Fault Finding section (page 27) of this book. It is recommended that faults should be checked by a competent installer
Page 25
25
9. Maintenance
9.1 General
Maintenance requirements
Unvented hot water systems have a continuing maintenance requirement in order to ensure safe working and optimum performance. It is essential that the relief valve(s) are periodically inspected and manually opened to ensure no blockage has occurred in the valves or discharge pipework.
Similarly cleaning of the strainer element and replacement of the air in the internal expansion volume will help to prevent possible operational faults.
The maintenance checks described below should be performed by a competent person on a regular basis, e.g. annually to coincide with boiler maintenance.
After any maintenance, please complete the relevant Service Interval Record section of the Benchmark
Checklist on page 35 of this document.
9.2 Standard inspection & maintenance operations
Inspection
The immersion heater boss can be used as an access for inspecting the cylinder internally.
Safety valve operation
CAUTION
Water discharged may be very hot!
` Manually operate the Temperature/Pressure Relief
Valve for a few seconds (Fig. 4 page 9)
` Check water is discharged and that it ows freely
through the tundish and discharge pipework. ` Check valve reseats correctly when released. ` Repeat the above procedure for the Expansion
Relief Valve. (Fig. 4 page 9)
Strainer
` Turn off the isolating valve prior to the Pressure
Reducing Valve or the main stop cock to the
system. ` Open the lowest hot tap in the system to relieve the
system pressure. ` Using a spanner unscrew the Pressure Reducing
Valve cartridge and remove the housing. The
strainer will be removed with the cartridge. (see Fig
18 page 30) ` Wash any particulate matter from the strainer
under clean running water. ` Replace the strainer and screw the Pressure
Reducing Valve cartridge into the moulded housing. ` Close hot tap, turn on isolating valve or main stop
cock to the system. Check for leaks.
Descaling immersion heater(s)
CAUTION
DO NOT use a sharp implement as damage to the element surface could be caused.
Turn off the mains water supply, isolate the electrical supply and turn off boiler
` Attach a hosepipe to the drain cock having sufcient
length to take water to a suitable discharge point below the level of the unit.
` Open a hot tap close to the unit and open drain
cock to drain unit.
` Open the cover(s) to the immersion heater
housing(s) and disconnect wiring from immersion heater(s) thermostat(s).
` Unscrew the immersion heater backnut using the tool
supplied and withdraw the immersion heater from the cylinder. Take care when removing the immersion heater from the cylinder and work within safe working practices.
` Carefully remove any scale from the surface of the
element(s).
` Ensure sealing surfaces are clean and seals are
undamaged, if in doubt t a new gasket (spare part
number 7035165)
` Replace immersion heater(s), making sure the
gasket is correctly tted and does not become
displaced as the immersion heater is replaced.
` Rewire, check, close and secure immersion heater
housing cover(s).
Re-commissioning
` Check all electrical and plumbing connections are
secure. Close the drain cock.
` With a hot tap open, turn on the cold water supply
and allow appliance to rell.
` DO NOT switch on the immersion heater(s) or
boiler until the appliance is full.
` When water ows from the hot tap allow to ow
for a short while to purge air and ush through any
disturbed particles.
` Close hot tap and then open successive hot taps in
system to purge any air.
` When completely full and purged check system for
leaks.
` The heating source (immersion heater(s) or boiler)
can then be switched on.
Page 26
26
Expansion volume re-charge
The air volume within the product will periodically require recharging to ensure expanded water is accommodated within the system. A discharge of water INTERMITTENTLY from the expansion valve will indicate the air volume has reduced to a point where it can no longer accommodate the expansion.
To recharge the air volume:-
` Turn off the heat source to the cylinder via
programmers / immersion isolation switch(es). ` Turn off the water supply to the cylinder by turning
off the isolating valve on the 3 bar pressure
reducing valve if tted at this point. Turn the handle
so that it lies at 90° to the direction of ow.
` Open the lowest hot tap. ` Hold open the temperature / pressure relief valve
until water ceases to run from the tap and gurgling
noise at the valve stops, (see g 4, page 9)
` Close the temperature / pressure relief valve. ` Turn on the isolating valve at the cold water
combination valve by turning the handle so it lies
parallel to the direction of ow, when water ows
from the hot tap, close tap. ` The air volume will be automatically recharged
as the unit rells. If after following the above
actions water still discharges from the expansion
relief valve, further advice should be sought from
a competent installer or the Megao service
department.
http://www.baxi.co.uk/information-and-advice/how-to­videos.htm
Page 27
27
10. Troubleshooting
` After servicing, complete the relevant Service
Interval Record section of the Benchmark Checklist
located on page 35 of this document. ` Any spare parts used MUST be authorised parts. ` Disconnect the electrical supply before removing
any electrical equipment covers. ` NEVER bypass any thermal controls or operate
system without the necessary safety valves.
The fault nding chart (table 6, below) will enable operational faults to be identied and their possible causes rectied. Any work carried out on the unvented
appliance and its associated controls MUST be carried out by a competent installer for unvented water heating systems. In case of doubt contact service support. (see
page 40 for details)
Spare Parts
A full range of spare parts are available for the cylinder range (Table 7, page 29). Refer to the technical data label on the unit to identify the model installed and ensure the correct part is ordered. You will need to quote the serial number, which is printed on the data label.
Table 6: Fault nding chart
WARNING
Do not tamper with any of the safety valves or controls supplied with the cylinder as this will invalidate any warranty. Water contained in the cylinder may be very hot, especially following a thermal control failure. Caution must be taken when drawing water from the unit.
NEVER bypass any thermal controls or operate system without the necessary safety valves.
10.1 Fault nding
Important
` Servicing should only be carried out by competent
persons in the installation and maintenance of unvented water heating systems.
Fault Possible cause Remedy
No hot water 1. Mains water supply off. 1. Check and open stop cock.
2. Strainer blocked. 2. Turn off water supply. Remove strainer and clean ( see page 25 for details).
3. Pressure reducing valve
incorrectly tted.
3. Check and ret as required.
Water from hot taps is cold
1. Immersion heater not switched
on.
1. Check and switch on.
2. Immersion heater thermal cut-
out has tripped.
2. Check. Reset by pushing button (Figure 14, page 20).
3. Indirect programmer set to
central heating only.
3. Check. Set programmer to a hot water programme.
4. Indirect boiler not working. 4. Check boiler operation. If fault is suspected consult boiler manufacturers instructions.
5. Indirect thermal cut-out has
tripped.
5. Check. Reset by pushing button. Check operation of indirect thermostat (Figure 15, page 20).
6. Indirect motorised valve not
connected correctly.
6. Check wiring and/or plumbing connections to motorised valve (see Figures 16 & 17, page 21).
Water discharges from expansion relief valve
1. Intermittently. Air volume in the
cylinder has reduced
1. See page 26 for details on how to test and recharge.
2. Continually. 3 bar pressure
reducing valve is not working correctly.
2. Check pressure from 3 bar Pressure Reducing Valve. If greater than 3 bar replace Pressure Reducing Valve.
3. Continually. Expansion valve
seat damaged.
3. Replace combined T&P/Expansion relief valve assembly
Water discharges from the T&P valve intermittently
1. Air volume in the cylinder has
reduced
1. See page 26 for details on how to test and recharge.
2. 8 bar expansion relief valve
faulty.
2. Check valve and replace if necessary
Water discharges from the T&P valve continually
1. Thermal control failure. Note
water will be very hot.
1. Switch off power supply to immersion heater(s) and shut down the boiler. DO NOT turn off the water supply. When discharge stops check all thermal controls, replace if faulty.
Milky water 1 Oxygenated water. 1. Water from a pressurised system releases oxygen bubbles
when owing. The milkiness will disappear after a short
while.
Page 28
28
11. Decommissioning
11.1 Decommissioning procedure
` Isolate electrical supplies and make safe ` Isolate the water supply ` Drain the appliance ` Drain the primary circuit (indirect only) ` Remove appliance ` Cap pipework
Environmental information
Products are manufactured from many recyclable materials. At the end of their useful life they should be disposed of at a Local Authority Recycling Centre in
order to realise the full environmental benets.
Insulation is by means of an approved CFC/HCFC free polyurethane foam with an ozone depletion factor of zero.
WEEE Declaration
Disposal of Waste Equipment by Users in Private Households in the European Union.
This symbol on the product indicates that this product must not be disposed of with your other household waste. Instead, it is your responsibility to dispose of your waste equipment by handing it over to a designated collection point for the recycling of waste electrical equipment. The separate collection and recycling of your waste equipment at the time of disposal will help to conserve natural resources and ensure that it is recycled in a manner that protects human health and the environment. For more information about where you can drop off your waste equipment for recycling,
please contact your local city ofce, your household
waste disposal service or the company where this product was purchased.
Page 29
29
ITEM DESCRIPTION PART NUMBER
1 Cold water inlet control kit (NOT SHOWN) 70 347 97
2 3 bar Pressure reducing valve - Complete 95 605 886
3 Immersion heater gasket 70 351 65
4 Immersion heater key spanner (NOT SHOWN) 95 607 861
5 Immersion heater blanking plate (NOT SHOWN) 95 605 881
6 90° Tundish (NOT SHOWN) 70 342 07
7 T&P/ERV combination valve 70 347 96
8 Set of compression nuts and olives (NOT SHOWN) 95 607 838
9 Drain valve 1/4 turn (NOT SHOWN) 95 605 051
10 Swept tee joint (for secondary return) (NOT SHOWN) 95 605 812
11 Direct combined thermostat / thermal cut-out 70 316 88
12 Direct mounting plate 95 607 929
13 3 way terminal block 95 607 932
14 Element - Incoloy (Bent, lower) 95 606 984
15 Immersion heater backnut - Plastic (Black) 95 605 132
16 Indirect combined thermostat / thermal cut-out 70 316 89
17 Controls cover 70 316 73
18 Indirect mounting plate 95 607 931
19 6 way terminal block 95 607 933
20 2 port motorised valve (22mm compression connections)(NOT SHOWN) 95 605 819
21 1/2" BSP Sensor Pocket Assembly Long 70 325 79
22 Element - Incoloy (Straight, upper) 95 606 986
23 Mixer valve (55°C) - Standard 70 373 07
24 Mixer valve (60°C) - Accessory 70 373 06
12. Spare parts
Table 7: Spare parts list
12.1 Spare parts list
A full range of spare parts are available for the Megao Compact range. Refer to the Technical Data label on the unit
to identify the model installed and ensure the correct part is ordered.
Page 30
30
Pressure Reducing
Valve Cartridge (3 Bar)
Strainer Mesh
3 Bar Pressure Reducing Valve - Complete
2
Figure 18: Pressure Reducing Valve exploded view
Figure 19: Mixing valve assembly
Hot water from
cylinder
Cold water from
Mains
Mixed water
Mixer Valve
23
24
Page 31
31
14
15
19
11
16
7
17
3
21
18
Figure 20: Indirect controls - exploded view
Page 32
32
11
13
13
11
7
15
3
22
15
3
14
17
17
12
12
Figure 21: Direct controls - exploded view
Page 33
33
Spares Stockists
Advanced Water Co.Ltd. Unit D5 Enterprise Way Vale Park, Evesham Worcs WR11 1GS Tel: 01386 760066 Fax: 01386 760077
Electric Water Heating Co. 2 Horsecroft Place Pinnacles Harlow Essex CM19 5BT Tel: 0845 0553811 E-Mail: sales@ewh.co.uk
SPD Special Product Division Units 9 & 10 Hexagon Business Centre
Springeld Road
Hayes Middlesex UB4 0TY Tel: 020 8606 3567
Parts Center Tel: 0845 270 9800 www.partscenter.co.uk
Newey & Eyre Unit 3-5 Wassage Way Hampton Lovett Ind. Estate Droitwich, Worcestershire WR9 0NX Tel: 01905 791500 Fax: 01905 791501
UK Spares Ltd Unit 1155 Aztec West Almondsbury Bristol BS32 4TF Tel: 01454 620500
William Wilson Ltd Unit 3A 780 South Street Whiteinch Glasgow G14 0SY Tel: 0141 434 1530
Alternatively contact your local supplying merchant or wholesale branch
Page 34
34
Benchmark checklist
Page 35
35
Commissioning &
service records
Page 36
36
Warranty
The Megao Compact Warranty provides unrivalled levels
of customer support and peace of mind in the unlikely event that a problem arises from a manufacturing defect. It is supported by a large nationwide team of company-
employed eld-based engineers and our own call centre,
which is open 363 days a year.
The Megao Compact Warranty covers Megao Compact
cylinders against corrosion for 25 years from date of original purchase.
The cold water inlet valve (and expansion vessel, where
supplied) is covered by a ve year warranty from the date of purchase of the Megao Compact product, that includes
both parts and labour. All other components, including any
other valves, ttings and controls supplied with the Megao
Compact are covered by a two year warranty from the
date of purchase of the Megao Compact product, that
includes both parts and labour.
In the case of the Megao Compact Systemready, Megao Compact Systemt appliances, the supplied pumps and motorized valves ( where tted ) are also covered by this
two year warranty.
Incoloy immersion heaters ( where tted ) are covered by a
two year warranty.
Outside of the UK
These warranties are valid for installations within the United Kingdom.
For installation in the Republic of Ireland please contact Baxi Potterton Myson (Ireland) Limited on 00353 (0) 1 4590870
For installations outside of the United Kingdom and the
Republic of Ireland, please telephone Megao Export on
+44 1603 420271 for further details of the warranty terms and conditions applicable.
This warranty is valid provided that:
• The Megao Compact product has been installed by
a competent installer in accordance with the instructions contained in the installation instructions and in compliance with all relevant laws, guidance, codes of practice and regulations in force at the time of installation.
• The Megao Compact product has not been modied or
tampered with in any way, other than by a Heatrae Sadia or Baxi Customer Support approved engineer.
• The Megao Compact product has not been subject to
damage by scale.
• The Megao Compact product and any part or parts of the Megao product (whether factory tted or otherwise)
have not been repaired or replaced other than by a Baxi Customer Support approved engineer and any replacement
parts used on the Megao Compact product are authorised Megao Compact spare parts.
• The factory tted Temperature /Pressure & Expansion
Relief Valve has not been tampered with or removed.
• The Megao Compact product has not been subject to
misuse or neglect.
• The Megao Compact product has only been used for
the storage of wholesome water. Should another substance be put through the product, the warranty will be invalid unless it is part of a disinfectant procedure carried out in accordance with BS EN 806.
• The Megao Compact product has not been subjected to
frost or freezing temperatures.
• The Benchmark™ commissioning checklist service
record, included in the Megao Compact installation
instructions has been completed.
• Regular maintenance has been carried in accordance with the requirements set out in the maintenance section of the installation instructions, by a competent person, an approved engineer from Heatrae Sadia or any other part of the Baxi Groups Customer Support approved engineer ing team.
• Access is available, at reasonable times and upon
reasonable notice, to the Megao Compact product to allow
for any inspection repair or replacement.
• The product is registered within 60 days of purchase. This can be done by telephone, online or by using the registration form provided with the product.
• Evidence of purchase (for example a receipt or delivery note) and date of supply is submitted when making a claim.
• The Megao Compact product has not been affected
by any cause beyond our reasonable control including,
without limitation: an act of God, explosion, ood, re or
accident; war or civil disturbance; strike, industrial action or stoppages of work; any form of government intervention; a third party act or omission including theft or malicious damage; failure by you to give us a correct delivery address or notify us of any change of address.
.
If any of the following situations occur, the Megao
Compact Warranty will NOT apply:
• Any wilful or accidental damage caused by your negligence
• Damage caused as a result of scale.
• Installation not in line with the installer and user manuals provided,
• Failure to comply with installation instructions (whether oral or in writing),
• Misuse of the Megao Compact product or alteration of the Megao product not in accordance with the
requirements set out above.
• Defects which are reported to us outside of the warranty
period on 0344 8711535 or Megaoservice@baxi.co.uk
Page 37
37
• Any third party repair or replacement costs unless those costs have been agreed and authorised by Baxi Customer Support or Heatrae Sadia in writing prior to incurring the costs.
Claims
Defects should be reported to us as soon as you are aware of them. Please report defect to us by contacting
0344 871 1535 or Megaoservice@baxi.co.uk .
Notes Heatrae Sadia accepts no liability for any third party
damage. These warranties do not affect your statutory rights and
remedies in relation to the Megao Compact products.
Annual service
Annual services are available from Baxi Customer Support, the service division of Heatrae Sadia.
Please contact Baxi Customer Support on 0344 871 1535 for details.
Megao Compact 25 year warranty is the period during which the rst owner of the Megao Compact or a new
build home continues to own the property. Should the property be sold, the new owner and any subsequent owners will receive a 25 year warranty from the date the
original owner purchased the Megao Compact or a new home with a Megao Compact installed.
The Megao Compact warranty is conditional on the
installation being carried out in accordance with the installation instructions supplied with the product. These warranties do not affect your statutory rights. Full terms and conditions of these warranty packages are available on
request or via www.heatraesadia.com/Megao
Megao may introduce modications to their products
from time to time. Consequentially the details given in this brochure are subject to alteration without notice.
Contacts
Specication Advice Hotline
T: 01603 420220 F: 01603 420229
E: specier@heatraesadia.com
www.heatraesadia.com
Heatrae Sadia*, Hurricane Way, Norwich, Norfolk, NR6 6EA
* Heatrae Sadia is a trading name of Baxi Heating UK Limited, Brooks House, Coventry Road, Warwick, CV34 4LL
Page 38
38
NOTES:
Page 39
39
NOTES:
Page 40
40
Customer service
Telephone: 0344 8711535
Facsimile: 0344 8711528
E-mail: megaoservice@baxi.co.uk
Megao
Hurricane Way Norwich Norfolk NR6 6EA
Important notice to installations outside of the UK.
References to legislation, legal requirements, regulations, building regulations benchmark, spares stockists, guarantees and warranty are ONLY APPLICABLE WITHIN THE UK.
For local legislation, legal requirements, regulations, building regulations outside of the UK, contact your local Authority.
For spares stockists, guarantees and warranty outside the UK, contact your local supplier or,
Export Sales
T: +44 (0)1603 420271
F: +44 (0)1603 420199
E: export.sales@heatraesadia.com
7034800_issue _1
The HWA Charter’s Code of Practice requires that all members adhere to the following:
• Tosupplytforpurposeproductsclearlyandhonestlydescribed
To supply products that meet, or exceed appropriate standards and building and water regulations
To provide pre and post sales technical support
To provide clear and concise warranty details to customers
© 2016
Loading...