MEGAFLO 2sf, 6sf, 8sf, 4sf Instructions Manual

Megaflo Compact SystemReady
Hot Water Cylinders
Unvented Indirect
Important
Please read & understand all these instructions before commencing installation.
Please leave this manual with the customer for future reference
2
Contents
1. Introduction................................................................................................. 3
1.1 General......................................................................................................3
1.2 Symbols used ............................................................................................ 3
1.3 Abbreviations ........................................................................................... 3
1.4 Liabilities ................................................................................................... 3
2. Safety ........................................................................................................... 4
2.1 General safety warnings ........................................................................... 4
3. Technical specifications .............................................................................. 5
3.1 Technical data ........................................................................................... 5
3.2 Dimensions ............................................................................................... 6
3.3 Electrical diagram(s) .................................................................................. 7
4. Description of the product ......................................................................... 8
4.1 General description ................................................................................... 8
4.2 Operation principle ................................................................................... 8
4.3 Main components ..................................................................................... 8
4.4 Standard delivery ...................................................................................... 8
5. Before installation ...................................................................................... 8
5.1 Installation regulations .............................................................................. 8
5.2 Installation requirements ........................................................................... 8
5.3 Choice of location .................................................................................... 9
5.4 Transport .................................................................................................. 9
6. Installation ................................................................................................ 10
6.1 General .................................................................................................. 10
6.2 Water connections .................................................................................. 11
6.3 Electrical connections .............................................................................. 18
6.4 Filling the installation .............................................................................. 19
7. Commissioning .......................................................................................... 20
7.1 General .................................................................................................. 20
7.2 Checklist before commissioning .............................................................. 20
7.3 Commissioning procedure ...................................................................... 20
8. Operation .................................................................................................. 21
8.1 General .................................................................................................. 21
9. Maintenance ............................................................................................. 22
9.1 General .................................................................................................. 22
9.2 Standard inspection & maintenance operations ....................................... 22
10. Troubleshooting ...................................................................................... 23
10.1 Fault finding ......................................................................................... 23
11. Decommissioning .................................................................................... 24
11.1 Decommissioning procedure ................................................................. 24
12.1 Spare parts list ...................................................................................... 25
Benchmark checklist ..................................................................................... 30
Commissioning & service records.................................................................31
Warranty ........................................................................................................ 32
THE BENCHMARK SCHEME
Benchmark places responsibilities on both manufacturers and installers. The purpose is to ensure that customers are provided with the correct equipment for their needs, that it is installed, commissioned and serviced in accordance with the manufacturer’s instructions by competent persons and that it meets the requirements of the appropriate Building Regulations and relevant electrical qualifications. The Benchmark Checklist can be used to demonstrate compliance with Building Regulations and should be provided to the customer for future reference. Installers are required to carry out installation, commissioning and servicing work in accordance with the Benchmark Code of Practice which is available from the Heating and Hotwater Industry Council who manage and promote the Scheme. Visit www.centralheating.co.uk for more information.
3
1. Introduction
1.1 General
The following instructions are offered as a guide to the user and installer.
The installation must be carried out by a competent plumbing and electrical installer in accordance with Building Regulation G3 (England and Wales), Technical Standard P3 (Scotland) or Building Regulation P5 (Northern Ireland) and the Water Fitting Regulations (England and Wales) or Water Byelaws (Scotland).
1.2 Symbols used
In these instructions, various risk levels are employed to draw the user’s attention to particular information. In doing so we wish to safeguard the user, avoid hazards and guarantee the correct operation of the appliance.
DANGER
Risk of a dangerous situation causing serious physical injury.
WARNING
Risk of dangerous situation causing slight physical injury.
CAUTION
Risk of material damage.
Signals important information.
1.3 Abbreviations
` T&P - Temperature & Pressure Relief Valve ` PRV - Pressure Reducing Valve ` ERV - Expansion Relief Valve
1.4 Liabilities
Manufacturers liability
Our products are manufactured in compliance with the requirements of the various applicable European Directives.
This appliance complies with the requirements of the CE marking directive.
In the interest of UK customers, we are continuously endeavouring to make improvements in product quality. All the specifications stated in this document are therefore subject to change without notice.
Our liability as the manufacturer may not be invoked in the following cases:
` Failure to abide by the instructions on using the
appliance. ` Faulty or insufficient maintenance of the appliance. ` Failure to abide by the instructions on installing the
product.
Installer's liability
The installer is responsible for the installation and the commissioning of the appliance. The installer must respect the following instructions:
` Read and follow the instructions given in the manuals
provided with the appliance. ` Carry out installation in compliance with the
prevailing legislation and standards. ` Perform the initial start up and carry out any checks
necessary. ` Complete the commissioning checklist. ` Explain the installation to the user. ` If maintenance is necessary, warn the user of the
obligation to check the appliance and maintain it in
good working order. ` Give all the instruction manuals to the user.
Users liability
To guarantee optimum operation of the appliance, the user must respect the following instructions:
` Read and follow the instructions given in the manuals
provided with the appliance. ` Call on qualified professionals to carry out installation
and initial start up. ` Get your installer to explain your installation to you. ` Have your required checks and services done. ` Keep the instruction manuals in good condition and
close to the appliance.
This appliance can be used by children aged
from 8 years and above and persons with reduced physical sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.
Children must be supervised to ensure they do not play with the appliance.
4
2. Safety
2.1 General safety warnings
WARNING TO USER
` If water discharges from the
Temperature/Pressure Relief /Expansion Relief Valve on the cylinder shut down the boiler/immersion heaters. Do not turn off any water supply. Contact a competent installer for unvented water heaters to check the system.
` Do not tamper with any of the safety
valves fitted to the system. If a fault is suspected contact a competent installer.
` DO NOT bypass the thermal cut-out(s) in
any circumstances.
WARNING
` Only competent persons having received
adequate training are permitted to work on the appliance and the installation.
` Do not tamper with any of the safety
valves or controls supplied with the cylinder.
` Before any work, switch off the mains
supply to the appliance and the water mains.
` Do not switch on if there is a possibility
that the water in the cylinder is frozen.
DANGER
This cylinder is unvented and as such becomes pressurised when in operation. The combination of pressurisation and hot water could lead to serious physical injury if the safety instructions in this manual are not adhered to.
CAUTION
Do not operate immersion heaters until the appliance has been filled with water.
WARNING
When handling the appliance, take appropriate precautions for the weight of the unit. Weights can be found in section 3, table 1, page 5.
CAUTION
Annual maintenance is recommended by a competent person.
- Water may drip from the discharge pipe of the pressure-relief device and this pipe must be left open to the atmosphere; (see page 17 for more details)
-The pressure-relief device is to be operated regularly to remove lime deposits and to verify that it is not blocked; (see page 22 for more details)
- How hot water can be drained. (see page 22 for more details)
- The type or characteristics of the pressure­relief device and how to connect it; (see Figure 9, page 13 and Figure 10, page 14 for details)
- A discharge pipe connected to the pressure­relief device is to be installed in a continuously downward direction and in frost free environment; (see page 17 for details)
Details on how to set the temperature controls for both immersion heaters and boiler controls can be found in section Installation Instructions, and Figure 16, page 19.
5
3. Technical specifications
3.1 Technical data:
Notes:
1. Indirect cylinders tested in accordance with BS EN 12897:2006.
2. Heat up time from cold through 45°C, based on a flow temperature of 80°C +/- 2°C & normal volume.
Table 1: Technical data - Indirect
Model(s) 2sr 4sr 6sr 8sr
Energy efficiency class C C C C
Storage volumes V in Litres 137 155 178 195
Standing loss in W 65.8 66.3 75.8 82.1
Table 2: Technical parameters in accordance with European Commission regulations 814/2013 and 812/2013
2sf
4sf
6sf
8sf
Max direct kW rating 3 3 3 3
Immersion heat up times (Btm immersion, 3kW)
139 167 179 208
Coil surface area (m²) 0.51
Coil heat up times
15l/min 33.1 40.1 43.0 45.1
30l/min
26.9 30.2 34.8 37.7
45/min 25.0 28.8 32.3 34.2
Coil rating (kW) ²
15l/min 13.1 12.7 13.7 14.3
30l/min 16.3 16.3 17.1 17.3
45l/min 17.6 17.7 18.8 19.1
Pressure drop through
coil
15l/min 0.004 MPa (0.04 Bar)
30l/min 0.013 MPa (0.13 Bar)
45l/min 0.031 MPa (0.31 Bar)
Heat loss (kW/24hrs) 1.58 1.59 1.82 1.97
Weight empty (kg) 41 46 50 53
Weight full (kg) ¹
178 201 228 248
Volume (Litres) ¹
137 155 178 195
Mixed water delivery to 40°C
1
168 188 218 238
Max mains pressure 1.6 MPa (16 Bar)
Max design pressure 0.8 MPa (8 Bar)
Operating pressure/PRV set pressure
0.3 MPa (3 Bar)
Max primary pressure ³ 1.0 MPa (10 Bar)
Expansion relief valve setting 0.8 MPa (8 Bar)
T&P valve setting
90°C +/- 5°C/1.0 MPa (10
Bar)
T&P Part number
7034796
Immersion heater electrical rating
3.0 kW@240V/2.8kW@230V ~
6
3.2 Dimensions and connections
Figure 1: General dimensions - SystemReady
Table 3: General dimensions table - SystemReady
Size DIMENSIONS (mm)
A B C
2sr N/A 728 1130
4sr N/A 883 1256
6sr N/A 1008 1413
8sr 900 1084 1515
355
A
B
C
316
423
619
689
759
350
285
285415
7
Figure 2: Schematic wiring diagram - basic 2 x 2 port valve system
3.3 Electrical diagram
KEY Br BROWN Bl BLUE G GREY O ORANGE W WHITE GY GREEN/YELLOW DHW DOMESTIC HOT WATER HTG HEATING L LIVE N NEUTRAL EARTH
BOILER
(DHW)
ZONE VALVE
WIRING CENTRE
123
9 10
L N
G
Br Bl O
GY
2
1
3
L N
L
N
PUMP
INDIRECT
THERMAL CONTROLS
(SUPPLIED FITTED)
FUSED (3 AMP) MAINS SUPPLY
N.B. A DOUBLE POLE ISOLATING SWITCH MUST BE INSTALLED IN THE MAINS SUPPLY
NOTES
1. ALL EARTH CONNECTIONS MUST BE LINKED BACK TO THE EARTH TERMINALS IN THE WIRING CENTRE
2. ALL NEUTRAL CONNECTIONS MUST BE LINKED BACK TO THE NEUTRAL TERMINALS IN THE WIRING CENTRE
3. ASSUMES BASIC BOILER
4. THE 22MM MOTORISED VALVES DO NOT HAVE A WHITE WIRE
5. THE ABOVE DIAGRAM IS FOR GUIDANCE ONLY, THE MANUFACTURER ACCEPTS NO LIABILITY FOR ANY LOSS OR DAMAGE ARISING FROM ANY ERRORS OR OMISSIONS THAT MAY BE INADVERTENTLY CONTAINED WITHIN THIS DIAGRAM. THE VARIOUS EQUIPMENT MANUFACTURERS SHOULD BE CONSULTED TO CONFIRM THE CORRECT OPERATION OF THEIR PRODUCTS WITHIN THE SYSTEM
11
13
12
14
15 16
N
N
N
N
(SUPPLIED FITTED)
(SUPPLIED FITTED)
PROGRAMMER - HEATING ZONE
1
& DOMESTIC HOT WATER
(SUPPLIED)
L N
HTG
DHW
ON
ON
4 3
5 6
ROOM SENSOR
(SUPPLIED)
N
HEATING ZONE 1VALVE
G
Br
Bl
O
GY
N
(SUPPLIED FITTED)
W
HEATING ZONE 2 VALVE
G
Br
Bl
O
GY
N
W
PROGRAMMABLE
ROOM THERMOSTAT
FOR ZONE 2
1
2
45
678
8
5.1 Installation regulations
5.2 Installation requirements
Water supply
In an unvented system the pressure and flowrate is directly related to the incoming water supply. For this reason it is recommended that the maximum water demand is assessed and the water supply checked to ensure this demand can be satisfactorily met.
` We suggest the minimum supply requirements
should be 0.15MPa (1.5 bar) pressure and 20 litres per minute flow rate. However, at these values outlet flow rates may be poor if several outlets are used simultaneously.
` A 22mm cold water supply is recommended,
however, if a smaller supply exists, which provides sufficient flow, this may be used (although more flow noise may be experienced).
` The higher the available pressure and flow rate the
better the system performance.
` See table 1 on page 5 for appliance operating
pressures. This is controlled by the Pressure Reducing Valve.
` The water supply must be of wholesome water
quality (Fluid Category 1 as defined by the Water Supply Regulations 1999).
Outlet/terminal fittings (taps, etc.)
` The appliance can be used with most types of
terminal fittings.
` Outlets situated higher than the appliance will give
outlet pressures lower than that at the heater, a 10m height difference will result in a 1 bar pressure reduction at the outlet.
` All fittings, pipe work and connections must have a
rated pressure of at least 8 bar at 80°C.
4. Description of the product
4.1 General description
This appliance is a purpose designed unvented water heater. The unit has a stainless steel inner vessel, which ensures an excellent standard of corrosion resistance. The outer casing is a combination of resilient thermoplastic mouldings and pre-coated steel. All products are insulated with CFC free polyurethane foam to give good heat loss protection. The appliance is supplied complete with all the necessary safety and control devices needed to allow connection to the cold water mains. All these components are preset and should not be tampered with.
4.2 Operation principle
The unvented cylinder is used to heat and store hot water for use in domestic applications. The water can be heated indirectly through a coil in the unit using an indirect heat source, or directly via back up immersion heater.
4.3 Main connections
See Figure 4: Main connections on page 10
4.4 Standard delivery
The delivery includes:
` Cylinder ` Factory fitted
` Immersion heater(s) and thermal controls ` Combination Temperature and Pressure Relief
Valve (set at 90ºC / 1 Mpa (10bar)) with Expansion
Relief valve (set at 0.8Mpa (8Bar)) ` Indirect thermostat and thermal cut-out ` Tundish ` Drain valve ` Wiring centre ` 2 x 2 Port motorised valve ` Lock shield flow balancing valve ` Filling Loop
` Automatic air vent ` 3 bar Pressure Reducing Valve (incorporating strainer) ` Isolating valve ` Mixing valve ` Mixing valve connection pipe ` Literature pack
` Instructions (inc benchmark commissioning
checklist & service record)
` Warranty card Check all components are supplied in the pack and advise your supplier if any are missing
5. Before installation
WARNING
Installation of the appliance must be carried out by a qualified engineer in accordance with prevailing and national regulations as listed below.
` Building Regulations G3 ` The Building Standards (Scotland) ` The Building Regulations (Northern
Ireland) ` I.E.E Electrical Regs ` UK Water Regulations
9
Limitations
The appliance should not be used in association with any of the following:
` Solid fuel boilers or any other boiler in which the
energy input is not under effective thermostatic control, unless additional and appropriate safety measures are installed.
` Ascending spray type bidets or any other class 1 back
syphonage risk requiring that a type A air gap be employed.
` Steam heating plants unless additional and
appropriate safety devices are installed.
` Situations where maintenance is likely to be neglected
or safety devices tampered with.
` Water supplies that have either inadequate pressure
or where the supply may be intermittent.
` Situations where it is not possible to safely pipe away
any discharge from the safety valves.
` In areas where the water consistently contains a high
proportion of solids, e.g. suspended matter that could block the strainer, unless adequate filtration can be ensured.
` In areas where the water supply contains chloride
levels that exceed 250mg/l.
` Gravity circulation primaries.
5.3 Choice of location
The cylinder must be vertically floor mounted. Although location is not critical, the following points should be considered:
` The appliance should be sited to ensure minimum
dead leg distances, particularly to the point of most frequent use.
` Avoid siting where extreme cold temperatures will
be experienced. All exposed pipe work should be insulated.
` The discharge pipe work from the safety valves must
have minimum fall of 1:200 from the appliance and terminate in a safe and visible position as per G3 regulations.
` Access to associated controls and immersion heaters
must be available for the servicing and maintenance of the system. Where these controls are installed against a wall a minimum distance of 250mm must be left.
` Ensure that the floor area for the appliance is level
and capable of permanently supporting the weight when full of water (see table 1, page 5 for weights).
` The tundish should be installed away from electrical
components.
5.4 Transport
If the unit is to be stored before installation it must be placed upright on a secure, level surface and be in a dry, frost free environment. The support surface must be capable of supporting the packaged weight of the unit, the packaged weights are displayed on the carton label.
Please take care when handling a packaged appliance. The appliance is heavy and must only be moved manually using safe working practices. The package weights of each unit are displayed on the carton label. Take note of the unit weights when deciding on a safe lifting method. DO NOT use the factory fitted T&P/ Expansion Relief Valve to lift or manoeuvre the unit.
WALL
Min 250mm
Min 250mm
Figure 3: Siting the appliance
10
6. Installation
6.1 General
After reading the previous sections in this booklet and choosing a suitable location for the appliance please install, paying attention to the following water, electrical and commissioning sections.
Boiler selection
` Ideally the boiler should be a system type boiler
incorporating the primary circulating pump, primary expansion vessel and Pressure Relief device, a non system boiler can be used however suitable controls must be incorporated into the primary circuit according to manufaturers instructions.
Figure 4: Typical installation schematic (not to scale)
` The boiler should have a control thermostat and non
self-resetting thermal cut-out and be compatible with unvented storage water heaters.
` Should be a sealed system - maximum primary
pressure 3 bar.
` The primary flow from the boiler must be pumped.
Gravity circulation will not work due to the special design of the primary heat exchanger. It is recommended that the automatic air vent supplied is incorporated in the primary return pipework close to the unvented system.
` The boiler cannot be vented through the cylinder.
TO HOT OUTLET
DISCHARGE PIPE
DRAIN COCK
T&P and EXPANSION RELIEF VALVE
BALANCED COLD WATER CONNECTION (IF REQUIRED)
MIXING VALVE
PRIMARY FLOW
PRIMARY RETURN
3 BAR PRESSURE REDUCING VALVE WITH STOP COCK
TUNDISH
ELEMENT CONTROLS
MAINS WATER
SUPPLY
11
6.2 Water connections
WARNING
` Under no circumstances should the
factory fitted Temperature/Pressure/ Expansion Relief Valve be removed other than by a competent person. To do so will invalidate any warranty or claim.
` The cold water controls MUST be
fitted on the mains water supply to the appliance.
` No control or safety valves should be
tampered with or used for any other purpose.
` The discharge pipe should not be blocked
or used for any other purpose.
` The tundish should not be located
adjacent to any electrical components.
Refer to the installation schematic (fig 11, page 14) for details on the pipe work layout. Specific details for the discharge pipe work layout are also provided in figure 12 on page 17, see also Figure 6 page 12 for Primary circuit schematic
` The connection points to the heating system are
in 22mm O/D copper pipe for 2sr, 4sr, 6sr, and 8sr units.
` All pipe fittings are made via 22mm compression
fittings directly to the unit (nuts and olives supplied).
` Solder fittings can be used, but extreme care must be
taken to ensure the external finish of the appliance casing is not damaged by heat.
` Push fit type fittings can be used for connection to
the copper pipes.
` The cold water inlet control kit supplied with the
appliance incorporates a full flow isolating valve which will enable the appliance to be isolated from the mains supply for maintenance or servicing.
` It is recommended that the outlet point of the drain
pipework be at least 1 metre below the level of the base of the appliance (this can be achieved by attaching a hose to the drain tap outlet spigot).
Mixing valve
` The mixing valve should be installed at the hot
outlet point of the appliance using the copper tube supplied.(see figure 5) The mixing valve will reduce the hot water outlet temperature to approx 55°C,
further temperature control will be required for outlets such as showers and baths
` The mixing valve can be installed in any orientation
providing the pipe from the tank outlet to the H port of the valve is no more than 500mm long and has no other connections attached
` Where the application dictates water to be delivered
at 60°C, a mixing valve pre-set at 60°C is available as an accessory (see page 25) note the overall mixed
water volume would decrease
Cold water control pack
CAUTION
` Flush supply pipe work before
connection to remove all flux and debris prior to fitting the inlet controls. Failure to do this may result in irreparable damage to the controls and will invalidate any warranty.
` The cold water control pack can be connected
anywhere on the cold water cylinder supply.
` The Control pack incorporates the Pressure Reducing
Valve and Isolation valve
` The pressure setting is set to 0.3Mpa/3.0 bar. It is not
adjustable.
` The valve can be fitted in any orientation to suit
the installation as long as the valve is installed with the direction of flow arrows pointing in the correct direction.
` The Expansion Relief has been incorporated into the
T&P Valve for ease of installation
` No other valves should be placed between the cold
pressure reducing valve and the appliance.
` Where discharge pipework is difficult to attain, the
local building control officer from the local council should be sought for advice as this falls under G3 guidelines and is not down to the manufacturer for unvented systems
Primary circuit control
` Primary circulation to the cylinder heat exchanger
must be pumped; gravity circulation WILL NOT WORK.
` It is recommended that the automatic air vent
supplied is incorporated in the primary return pipe work close to the unit.
` Boiler flow temperature should be set to 80° (peak
temperature to primary heat exchanger 88°C).
` See Fig 6 page 12 for example installation schematic,
consult boiler manufatuers installation manual for further guidance. Other primary system valves may be required
Hot water from
cylinder
Cold water from
Mains
Mixed water
Mixer Valve
Copper tube
H
M
C
Figure 5: Mixing valve layout
12
Secondary circulation
If secondary circulation is required it is recommended that it be connected to the appliance as shown (see fig
7).
` The secondary return pipe should be in 15mm pipe
and incorporate a check valve to prevent backflow.
` A suitable WRAS approved circulation pump will be
required.
` On large systems, due to the increase in system
water content, it may be necessary to fit an additional expansion vessel to the secondary circuit. This should be done if the capacity of the secondary circuit exceeds 10 litres.
Pipe capacity (copper): 15mm O.D. = 0.13 l/m (10 litres = 77m) 22mm O.D. = 0.38 l/m (10 litres = 26m) 28mm O.D. = 0.55 l/m (10 litres = 18m)
Note: Plastic pipe capacities may be reduced due to thicker wall sections.
Cold Water Inlet
T
o Hot
Outlets
Check Valve
Swept Tee
Secondary Return
Secondary
Circulation Pump
Figure 7: Secondary circulation schematic
M
M
1
2
3
4
5
6
7
8
9
1 System boiler complete
2 SystemReady Unit
3 Filling loop assembly
4 Lockshield balancing valve
5 DHW Motorised valve
6 Drain off cock
7 CH motorised valve
8 Tapping for Zone 2 CH motorised valve
9 CH circuit
Figure 6: Primary circuit schematic
13
Figure 8: 3 bar Pressure Reducing Valve
Mains in
22mm compression connections
Outlet to Megao
Take note of ow
direction
Pressure reducing valve
cartridge (3 bar)
Combination T&P/ERV
T&P = Temperature and Pressure
ERV = Expansion Relief Valve
Mains water
supply
90° Tundish
T&P
actuation knob
ERV
actuation knob
D2 Pipe
Figure 9: Isolation and 3 bar pressure reducing valve
Figure 10: Combination T&P/Expansion Relief Valve
Isolation valve to be paired with Reducing valve
3 bar Pressure
Reducing Valve
Isolation valve
14
Figure 11: Schematic installation diagram.
Balanced cold water
draw-off
Combined Temperature
and Pressure Relief valve
with Expansion Relief
Valve / Check Valve
0.3 Mpa/3 bar Pressure Reducing
Valve and Strainer.
(Stop cock can be fitted
here)
MCWS to Kitchen
(unbalanced cold
mains supply)
Mains Cold Water
Supply
KEY
MCWS = Mains Cold Water Supply
HWS = Hot Water Service
SC = Stop Cock / Isolating Valve
DOC = Drain Off Cock
Discharge pipe to atmosphere
(see page 18 “Discharge Pipework”)
Isolating / Regulating
Valves, as required
Mixed HWS supply
Balanced HWS and
MCWS to bathrooms,
showers, cloakrooms,
etc
DOC DOC
DOC
DOC
SC
SC
Tundish
Mixing valve
15
Discharge
It is a requirement of Building Regulation G3 that any discharge from an unvented system is conveyed to where it is visible, but will not cause danger to persons in or about the building. The tundish and discharge pipes should be fitted in accordance with the requirements and guidance notes of Building Regulation G3. The G3 Requirements and Guidance section 3.50 - 3.63 are reproduced in the following sections of this manual. For discharge pipe arrangements not covered by G3 Guidance advice should be sought from your local Building Control Officer. Any discharge pipe connected to the pressure relief devices (expansion valve and temperature/pressure relief valve) must be installed in a continuously downward direction and in a frost free environment.
Water may drip from the discharge pipe of the pressure relief device. This pipe must be left open to the atmosphere. The pressure relief device is to be operated regularly to remove lime deposits and to verify that it is not blocked.
G3 REQUIREMENT
“...there shall be precautions...to ensure that the hot water discharged from safety devices is safely conveyed to where it is visible but will not cause danger to persons in or about the building.”
The following extract is taken from the latest G3 Regulations
Discharge pipes from safety devices
Discharge pipe D1
3.50 Each of the temperature relief valves or combined temperature and pressure relief valves specified in 3.13 or 3.17 should discharge either directly or by way of a manifold via a short length of metal pipe (D1) to a tundish.
3.51 The diameter of discharge pipe (D1) should be not less than the nominal outlet size of the temperature relief valve.
3.52 Where a manifold is used it should be sized to accept and discharge the total discharge from the discharge pipes connected to it.
3.53 Where valves other than the temperature and pressure relief valve from a single unvented hot water system discharge by way of the same manifold that is used by the safety devices, the manifold should be factory fitted as part of the hot water storage system unit or package.
Tundish
3.54 The tundish should be vertical, located in the same space as the unvented hot water storage system and be fitted as close as possible to, and lower than, the valve, with no more than 600mm of pipe between the valve outlet and the tundish (see fig 12).
Note: To comply with the Water Supply (Water Fittings) Regulations, the tundish should incorporate a suitable air gap.
3.55 Any discharge should be visible at the tundish. In addition, where discharges from safety devices may not be apparent, e.g. in dwellings occupied by people with impaired vision or mobility, consideration should be given to the installation of a suitable safety device to warn when discharge takes place, e.g. electronically operated.
Discharge pipe D2
3.56 The discharge pipe (D2) from the tundish should:
(a) have a vertical section of pipe at least 300mm long below the tundish before any elbows or bends in the pipework (see fig. 12 page 17); and (b) be installed with a continuous fall thereafter of at least 1 in 200.
3.57 The discharge pipe (D2) should be made of: (a) metal; or (b) other material that has been demonstrated to be capable of safely withstanding temperatures of the water discharged and is clearly and permanently marked to identify the product and performance standard (e.g. as specified in the relevant part of BS 7291).
3.58 The discharge pipe (D2) should be at least one pipe size larger than the nominal outlet size of the safety device unless its total equivalent hydraulic resistance exceeds that of a straight pipe 9m long, i.e. for discharge pipes between 9m and 18m the equivalent resistance length should be at least two sizes larger than the nominal outlet size of the safety device; between 18 and 27m at least 3 sizes larger, and so on; bends must be taken into account in calculating the flow resistance. See Fig 12, Table 4 and the worked example.
Note: An alternative approach for sizing discharge pipes would be to follow Annex D, section D.2 of BS 6700:2006 Specification for design, installation, testing and maintenance of services supplying water for domestic use within buildings and their curtilages.
3.59 Where a single common discharge pipe serves more than one system, it should be at least one pipe size larger than the largest individual discharge pipe (D2) to be connected.
3.60 The discharge pipe should not be connected to a soil discharge stack unless it can be demonstrated that the soil discharge stack is capable of safely withstanding temperatures of the water discharged, in which case, it should:
(a) contain a mechanical seal, not incorporating a water trap, which allows water into the branch pipe without allowing foul air from the drain to be ventilated through the tundish; (b) be a separate branch pipe with no sanitary appliances connected to it;
16
(c) if plastic pipes are used as branch pipes carrying discharge from a safety device they should be either polybutylene (PB) to Class S of BS 7291-2:2006 or cross linked polyethylene (PE-X) to Class S of BS 7291-3:2006; and (d) be continuously marked with a warning that no sanitary appliances should be connected to the pipe.
Note:
1. Plastic pipes should be joined and assembled with fittings appropriate to the circumstances in which they are used as set out in BS EN ISO 1043-1.
2. Where pipes cannot be connected to the stack it may be possible to route a dedicated pipe alongside or in close proximity to the discharge stack.
Termination of discharge pipe
3.61 The discharge pipe (D2) from the tundish should terminate in a safe place where there is no risk to persons in the vicinity of the discharge.
3.62 Examples of acceptable discharge arrangements are:
(a) to a trapped gully with the end of the pipe below a fixed grating and above the water seal; (b) downward discharges at low level; i.e. up to 100mm above external surfaces such as car parks, hard standings, grassed areas etc. are acceptable providing that a wire cage or similar guard is positioned to prevent contact, whilst maintaining visibility; and (c) discharges at high level: e.g. into a metal hopper and metal downpipe with the end of the discharge pipe clearly visible or onto a roof capable of withstanding high temperature discharges of water and 3m from any plastic guttering system that would collect such discharges.
3.63 The discharge would consist of high temperature water and steam. Asphalt, roofing felt and non-metallic rainwater goods may be damaged by such discharges.
Worked example of discharge pipe sizing
Fig. 12: shows a G1/2 temperature relief valve with a discharge pipe (D2) having 4 No. elbows and length of 7m from the tundish to the point of discharge.
From Table 4 page 17: Maximum resistance allowed for a straight length of 22mm copper discharge pipe (D2) from a G1/2 temperature relief valve is 9.0m.
Subtract the resistance for 4 No. 22mm elbows at 0.8m each = 3.2m
Therefore the permitted length equates to: 5.8m
5.8m is less than the actual length of 7m therefore calculate the next largest size.
Maximum resistance allowed for a straight length of 28mm pipe (D2) from a G1/2 temperature relief valves equates to 18m.
Subtract the resistance of 4 No. 28mm elbows at 1.0m each = 4.0m
Therefore the maximum permitted length equates to: 14m
As the actual length is 7m, a 28mm (D2) copper pipe will be satisfactory.
17
Valve Outlet
Size
Minimum Size Of
Discharge Pipe D1
Minimum Size Of
Discharge Pipe D2 From
Tundish
Maximum Resistance
Allowed, Expressed As A
Length Of Straight Pipe (I.E.
No Elbows Or Bends)
Resistance Created
By Each Elbow Or
Bend
G1/2 15mm
22mm 28mm 35mm
up to 9m up to 18m up to 27m
0.8m
1.0m
1.4m
G3/4 22mm
28mm 35mm 42mm
up to 9m up to 18m up to 27m
1.0m
1.4m
1.7m
G1 28mm
35mm 42mm 54mm
up to 9m up to 18m up to 27m
1.4m
1.7m
2.3m
Table 4: Sizing of copper discharge pipe (D2) for common temperature relief valve outlet sizes
Safety device
(e.g. Temperature
relief valve)
Metal discharge pipe (D1) from
Temperature relief valve to tundish
Tundish
Discharge below
fixed grating
(Building Regulation
G3 section 3.61 gives
alternative points
of discharge)
Fixed grating
Trapped
gully
600mm maximum
300mm
minimum
Discharge pipe (D2) from tundish,
with continuous fall. See Building
Regulation G3 section 3.56,
Table 1 and worked example
Figure 12: Typical discharge pipe arrangement (extract from Building Regulation G3 Guidance Section 3.50)
Notes:
1) Discharge pipe-work D2 can now be a plastic pipe but only pipes that have been tested to a minimum 110°C must be used.
2) Discharge pipe D2 can now be plumbed in the soil stack but only soil stacks that can handle temperatures of 99°C or greater should be used.
18
6.3 Electrical connections
In case of difficulty contact service support; contact details are available on page 36 of this booklet.
WARNING
` Disconnect from the mains electrical
supply before removing any covers.
` Never attempt to replace the immersion
heater(s) other than with genuine manufacturers components. Using other manufacturers components may invalidate the warranty on the cylinder.
` DO NOT bypass the thermal cut-out(s) in
any circumstances. All electrical wiring should be carried out by a competent electrician and be in accordance with the latest I.E.E Wiring Regulations.
` Each circuit must be protected by a
suitable fuse and double pole isolating switch with a contact separation of at least 3mm in both poles.
` DO NOT operate the immersion heaters
until the appliance has been filled with water.
Space and heating systems controls
` The controls provided with the cylinder will ensure
the safe operation of the unit within the central heating system.
` Connections to the various system components is
made via the wiring centre fitted to the front of the cylinder and the terminal identification labels within the wiring centre to aid in connecting the various external system components such as the mains supply, programmer and boiler.
Back up immersion heater
` The back up immersion heater should be wired in
accordance with fig 14 and 15, page 19.
` The immersion heater thermostat is factory set at
57oC. This is set for eco mode, To maximise water availability the thermostat should be set to maximum during commissioning (see Fig 16 page 19). Should this require adjustment see Fig 16 for details of how to adjust the temperature setting. Each immersion heater has its own individual thermostatic control. The thermostat incorporates a thermal cut-out that will switch off the immersion heater in the event of a thermostat failure. The thermal cut-out reset button position is also shown on Fig 16.
LIFT OFF
REPLACE
LIFT FROM THIS POINT
LUGS
Access to Control Unit:
Disconnect from mains supply before removing any covers.
Removing the Control Cover.
` Unscrew the large screw using a flat ended screw
driver.
` Lift from bottom of cover at point indicated until
cover comes away freely.
Replacing the Control Cover:
` Tilt and align the top 2 lugs in the holes indicated. ` Firmly press the cover until it "snaps" back in place. ` Tighten the large screw.
WARNING
` Do not over tighten
Figure 13: Cover Access
19
WARNING
Should the Megaflo be used in conjunction with a boiler or external controls that control the water temperature via a sensor connected to the cylinder, it should be noted that the factory fitted indirect thermostat and thermal cut-out MUST NOT be disconnected or bypassed. To do so would invalidate the product approvals and warranty and it would not comply with Building Regulations. Should this method of control be adopted the Megaflo Indirect thermostat should be set at maximum and the cylinder control temperature set at 68oC to avoid the thermostat over-riding the boiler control. Where the boiler or external controls do not directly power the 2 Port Motorised Valve supplied with the Megaflo, the wiring should ensure that in the event of the thermal cut-out on the Megaflo Indirect controls operating power will be interrupted to the 2 Port Motorised Valve such that it closes and prevents flow of the primary heating fluid around the Megaflo primary heat exchanger coil. For further details of wiring the boiler, or external controls consult the manufacturer’s installation instructions.
Figure 15: Direct wiring schematic
Figure 14: Indirect wiring schematic
L
N
1 2 3
Control Housing Details
Immersion connections
1.5mm² 3 Core HO5 VV-F sheathed cable
Indirect control wiring
N
L
1.5mm
²
3 Core HO5 VV-F sheathed cable
Immersion heater connections
6.4 Filling the appliance
` Ensure the drain cock is CLOSED. ` Open a hot tap furthest from the cylinder. ` Open the isolating valve on the 3 bar Pressure
Reducing Valve by turning the blue handle on the stop cock (if fitted in this position) so that it lies parallel to the direction of flow. Open the mains stop cock to fill the unit. When water discharges from the tap, allow to run for a few minutes to thoroughly flush through any residue, dirt or swarf, then close the tap.
` Open successive hot taps to purge the system of air.
SPINDLE POSITIONS
= MINIMUM TEMP
= MAXIMUM TEMP
= APPROX 60 °C
A
ROTATE SPINDLE CLOCKWISE FOR TEMPER ATURE INCREASE AND COUNTER CLOCKWISE FOR TEMPER TURE DECREASE
TEMPERATURE ADJUSTING SPINDLE
THERMAL CUT-OUT RESET BUTTON
Figure 16: Boiler and Immersion controls
20
WARNING
` If the unit is to be left unused following
installation and commissioning e.g. unoccupied properties, the water heater should be drained or regularly flushed through with fresh mains water once a week.
` When placing the unit into service, the
procedure for filling the unit and the system checks above should be observed.
7.2 Checklist before commissioning
` Check all water connections for leaks and rectify as
necessary. ` Turn off mains water supply. ` Remove the pressure reducing valve head work to
access the strainer mesh, clean and re-fit. ` Turn the water supply back on. ` Manually open, for a few seconds, each Relief Valve
in turn, checking that water is discharged and runs
freely through the tundish and out at the discharge
point. ` Ensure that the valve(s) re-seat satisfactorily.
7.3 Commissioning procedure
Indirect units
` Ensure the filling loop hose is connected at both ends
and is tight. ` Fill the indirect (primary) circuit following the boiler
manufacturer’s commissioning instructions. ` Open the isolating valves at either end of the filling
loop and allow to fill from the mains inlet supply. ` To ensure the appliance primary heat exchanger is
filled, both of the 2 port motorised valves (supplied)
should be manually opened by moving the lever on
the motor housing to the MANUAL setting. When
the primary circuit is full return the lever to the
AUTOMATIC position. ` Air can be vented from the primary heating coil by
unscrewing the small dust cap on the auto air vent
by half a turn. ` The primary system should be pressurised to the
minimum pressure required by the boiler (usually 1
bar), the pressure gauge fitted should be used to
ensure the correct system pressure is set. ` When full and pressurised, the filling loop isolating
valves should be closed, the pipe disconnected and
the caps replaced. The levers on the motorised valves
should be returned to the Auto position. ` Check primary circuit for leaks and rectify as necessary
Switch on the boiler, ensure the programmer is set to
Hot Water and allow the cylinder to heat up to a
normal working temperature (70oC recommended).
7. Commissioning
7.1 General
After filling the installation with water in the previous section please follow the following steps to complete the installation of the unit.
WARNING
DO NOT operate the immersion heaters or primary circuit until the appliance has been filled with water.
Direct Heating
` Switch on electrical supply to the immersion heater
and allow the appliance to heat up to normal working temperature, factory set to 57°C but for maximum water availability reset to 70°C (see Fig 16 page 19).
` The adjustment represents a temperature range of
10°C to 70°C.
` Check the operation of thermostat and that no
water has issued from the Expansion Relief Valve or Temperature/Pressure Relief Valve during the heating cycle.
Benchmark
The cylinder is covered by the Benchmark Scheme which aims to improve the standards of installation and commissioning of domestic heating and hot water systems in the UK and to encourage regular servicing to optimise safety, efficiency and performance.
Benchmark is managed and promoted by the Heating and Hotwater Industry Council. For more information visit www.centralheating.co.uk.
All installations must be notified to Local Area Building Control either directly or through a Competent Persons Scheme. A Building Regulations Compliance Certificate will then be issued to the customer who should, on receipt, write the Notification Number on the Benchmark Checklist.
This product should be serviced regularly to optimise its safety, efficiency and performance. The service engineer should complete the relevant Service Record on the Benchmark Checklist after each service.
The Benchmark Checklist may be required in the event of any warranty work.
21
8.1 General
WARNING
` If water discharges from the
Temperature/Pressure/Expansion Relief Valve on the cylinder shut down the heat source. Do not turn off any water supply. Contact a competent installer for unvented water heaters to check the system.
` Do not tamper with any of the safety
valves fitted to the system. If a fault is suspected contact a competent installer.
` DO NOT bypass the thermal cut-out(s) in
any circumstances.
Please ensure that the installer has fully completed the Benchmark Checklist (page 30) of this manual and that you have signed it to say that you have received a full and clear explanation of its operation. The installer is legally required to complete a commissioning checklist as a means of complying with the appropriate Building Regulations (England & Wales).
Flow performance
When initially opening hot outlets a small surge in flow may be noticed as pressures stabilise. This is quite normal with unvented systems. In some areas cloudiness may be noticed in the hot water. This is due to aeration of the water, is quite normal and will quickly clear.
Operational faults and their possible causes are detailed in the Fault Finding section (page 24) of this book. It is recommended that faults should be checked by a competent installer.
8. Operation
Temperature controls - indirect units
` A combined thermostat and thermal cut-out is
provided for the control of the external boiler. The
thermostat is factory set to give a water storage
temperature of approx. 70oC, however it can be set
to control between 10oC and 70oC. Adjustments can
only be made by opening the controls covers. ` To access the thermostat open the controls
housing cover (see Fig 13, page 18)- DISCONNECT
THE ELECTRICAL SUPPLY BEFORE OPENING THE
COVER(S). ` Temperature adjustment is made by rotating the
adjustment spindle on the top of the thermostat.
The adjustment represents a temperature range of
10°C to 70°C (see page 19, Fig 16 for method of
adjustment). ` Maximum working temperature is 70°C. ` The boiler thermostat and thermal cut-out must
be wired in series with the 2 port motorised zone
valve supplied to interrupt the flow of primary water
around the heat exchanger coil when the control
temperature has been reached.
http://www.baxi.co.uk/information-and-advice/how-to­videos.htm
` The controls fitted to the cylinder will affect
the temperature of the stored water only, other controls will be provided in the system for time and temperature control of the space heating requirements. Consult the instructions provided with those controls for details of adjustments.
Temperature controls – Back up immersion heater
` The immersion heater is fitted with a thermostat
which is fitted in the centre of the heater plate and a cut-out which is fitted to the side of the thermostat.
` Access to the thermostat can be made by opening
the immersion heater cover - DISCONNECT THE ELECTRICAL SUPPLY BEFORE OPENING THE COVER.
` Temperature adjustment is made by rotating the
adjustment knob on the top of the thermostat. The adjustment represents a temperature range of 10°C to 70°C.
` Maximum working temperature is 70°C. In very hard
water areas limit to 60/65°C.
Expansion Volume
The air volume within the product will periodically require recharging to ensure expanded water is accommodated within the system. A discharge of water INTERMITTENTLY from the expansion valve will indicate the air volume has reduced to a point where it can no longer accommodate the expansion.
To recharge the air volume:-
` Turn off the heat source to the appliance via
programmers / immersion isolation switch(es).
` Turn off the water supply to the appliance by turning
off the isolating valve on the 3 bar Pressure Reducing Valve if fitted at this point. Turn the handle so that it lies at 90° to the direction of flow. See figure 9
page 13. ` Open the lowest hot tap. ` Hold open the Temperature/Pressure Relief Valve
until water ceases to run from the tap and gurgling
noise at the valve stops. (see fig 10 page 13) ` Close the Temperature / Pressure Relief Valve. ` Turn on the isolating valve at the Pressure Reducing
Valve by turning the handle so it lies parallel to the
direction of flow, when water flows from the hot
tap, close tap. ` The air volume will be automatically recharged as the
unit refills. If after following the above actions water
still discharges from the Expansion Relief Valve,
further advice should be sought from a competent
installer or the Megaflo service department.
22
9. Maintenance
9.1 General
Maintenance requirements
Unvented hot water systems have a continuing maintenance requirement in order to ensure safe working and optimum performance. It is essential that the relief valve(s) are periodically inspected and manually opened to ensure no blockage has occurred in the valves or discharge pipework. Maintenance of this appliance should only be carried out by a suitably qualified person. Failure to do so could invalidate the warranty.
Similarly cleaning of the strainer element and replacement of the air in the product will help to prevent possible operational faults.
The maintenance checks described below should be performed by a competent person on a regular basis, e.g. annually to coincide with boiler maintenance.
After any maintenance, please complete the relevant Service Interval Record section of the Benchmark
Checklist on page 30 of this document.
9.2 Standard inspection & maintenance operation
Inspection
The immersion heater boss can be used as an access for inspecting the cylinder internally.
Safety valve operation
WARNING
Water discharged may be very hot!
` Manually operate the Temperature/Pressure Relief
Valve for a few seconds. (see fig 10 page 13)
` Check water is discharged and that it flows freely
through the tundish and discharge pipe work. ` Check valve reseats correctly when released. ` Repeat the above procedure for the Expansion Relief
Valve. (see fig 10 page 13)
Strainer
` Turn off the isolating valve prior to the Pressure
Reducing Valve or the main stop cock to the system. ` Open the lowest hot tap in the system to relieve the
system pressure. ` Using a spanner unscrew the pressure reducing
cartridge and remove the moulded housing. The
strainer will be removed with the cartridge. ` Wash any particulate matter from the strainer under
clean running water. ` Replace the strainer and screw the Pressure Reducing
Valve cartridge into the moulded housing.
` Close hot tap, turn on isolating valve or main stop
cock to the system. Check for leaks.
Descaling immersion heater - Draining appliance
` Turn off the mains water supply, isolate the electrical
supply and turn off boiler
` Attach a hosepipe to the drain cock having sufficient
length to take water to a suitable discharge point below the level of the unit.
` Open a hot tap close to the unit and open drain
cock to drain unit. If water fails to drain vent the unit manually by opening the temperature and pressure relief valve, there is no need to drain the primary circuit.
` Open the cover(s) to the immersion heater housing
and disconnect wiring from immersion heater thermostat.
` Unscrew the immersion heater backnut and withdraw
the immersion heater from the appliance. A key spanner is supplied with the product for easy removal and tightening of the immersion heater. Over time the immersion heater gasket may become stuck to the mating surface. To break the seal insert a round shafted screwdriver into one of the pockets on the immersion heater and gently lever up and down. Take care when lifting the immersion heater out of the cylinder and work within safe working practices.
` Carefully remove any scale from the surface of the
element.
CAUTION
DO NOT use a sharp implement to scrape off scale as damage to the element surface could be caused.
` Ensure sealing surfaces are clean and seals are
undamaged, if in doubt fit a new gasket. (spare part number 7035165)
` Replace immersion heater, making sure not to trap
the gasket.
` Rewire, check, close and secure immersion heater
housing cover.
Re-commissioning
` Check all electrical and plumbing connections are
secure. Close the drain cock.
` With a hot tap open, turn on the cold water supply
and allow unit to refill.
` DO NOT switch on the immersion heater or boiler
until the unit is full.
` When water flows from the hot tap allow to flow
for a short while to purge air and flush through any disturbed particles.
` Close hot tap and then open successive hot taps in
system to purge any air.
` When completely full and purged check system for
leaks.
` The heating source (immersion heater or boiler) can
then be switched on.
23
10. Troubleshooting
` Disconnect the electrical supply before removing any
electrical equipment covers.
` NEVER bypass any thermal controls or operate system
without the necessary safety valves.
Fault Possible Cause Remedy
No hot water flow
Mains water supply off Check and open stop cock
Strainer blocked Turn off water supply. Remove strainer and clean
Pressure Reducing Valve incorrectly fitted Check and refit as required
Water from hot tap
is cold
Indirect programmer set to central
heating only
Check, set to domestic hot water programme
Indirect boiler not working Check boiler operation. If fault is suspected
consult boiler manufacturer’s instructions
Indirect thermal cut-out has operated Check, reset by pushing button on thermostat.
Check operation of indirect thermostat
Indirect motorised valve not connected
correctly
Check wiring and/or plumbing connections to
motorised valve
Immersion heater not switched on Check and switch on
Immersion heater thermal cut-out has
operated
Check, reset by pushing button on thermostat
Water discharges
from Expansion
Valve
Intermittently
Air volume in product has reduced
See page 24 for re-charging of Air volume
Continually
Cold water Pressure Reducer not working
correctly.
Expansion valve seat damaged
Check pressure from Pressure Reducing Valve. If
greater than 3bar replace Pressure Reducing Valve.
Fit new T&P/Expansion Relief valve
Water discharges
from T&P Relief
Valve
Thermal control failure
CAUTION: Water will be very hot!
Switch off power to immersion heater and shut
down boiler.
DO NOT turn off water supply. When discharge
stops check all thermal controls, replace if faulty
Milky water
Oxygenated water Water from a pressurised system releases oxygen
bubbles when flowing. The milkiness will
disappear after a short while
Table 5: Fault finding chart
WARNING
Do not tamper with any of the safety valves or controls supplied with the appliance as this will invalidate any warranty. Water contained in the appliance may be very hot, especially following a thermal control failure. Caution must be taken when drawing water from the unit.
10.1 Fault finding
Important
` After servicing, complete the relevant Service Interval
Record section of the Benchmark Checklist located on pages 30 and 31 of this document.
` Servicing should only be carried out by competent
persons in the installation and maintenance of unvented water heating systems.
` Any spare parts used MUST be authorised parts.
The fault finding chart (table 5, below) will enable operational faults to be identified and their possible causes rectified. Any work carried out on the unvented water heater and its associated controls MUST be carried out by a competent installer for unvented water heating systems. In case of doubt contact service support.
Spare Parts
A full range of spare parts are available for the appliance (table 6, page 25). Refer to the technical data label on the unit to identify the model installed and ensure the correct part is ordered. You will need to quote the serial number, which is printed on the data label.
24
11. Decommissioning
11.1 Decommissioning procedure
` Isolate electrical supplies and make safe ` Isolate the water supply ` Drain the cylinder ` Drain the primary circuit (indirect only) ` Remove cylinder ` Cap pipework
Environmental information
Products are manufactured from many recyclable materials. At the end of their useful life they should be disposed of at a Local Authority Recycling Centre in order to realize the full environmental benefits.
Insulation is by means of an approved CFC/HCFC free polyurethane foam with an ozone depletion factor of zero.
WEEE Declaration
Disposal of Waste Equipment by Users in Private Households in the European Union.
This symbol on the product indicates that this product must not be disposed of with your other household waste. Instead, it is your responsibility to dispose of your waste equipment by handing it over to a designated collection point for the recycling of waste electrical equipment. The separate collection and recycling of your waste equipment at the time of disposal will help to conserve natural resources and ensure that it is recycled in a manner that protects human health and the environment. For more information about where you can drop off your waste equipment for recycling, please contact your local city office, your household waste disposal service or the company where this product was purchased
25
Table 6: Spares
12.1 Spare parts list
A full range of spare parts are available for the appliance. Refer to the Technical Data label on the unit to identify the model installed and ensure the correct part is ordered.
ITEM DESCRIPTION SPARES NUMBER
1 Cold water inlet control kit - Complete (NOT SHOWN) 70 316 90 2 3 bar Pressure Reducing Valve - Complete 95 605 886 3 Immersion heater gasket 70 351 65 4 Immersion heater key spanner (NOT SHOWN) 95 607 861 5 Immersion heater blanking plate (NOT SHOWN) 95 605 881 6 90° Tundish 70 342 07 7 T&P/ERV combination valve 70 347 96 8 Set of compression nuts and olives (NOT SHOWN) 95 607 838
9 Drain valve 1/4 turn 95 605 051 10 22mm Manifold 70 316 93 11 Direct combined thermostat / thermal cut-out 70 316 88 12 Wiring centre 95 612 702 13 Filling loop and connection 95 607 096 14 Element - Incoloy (Bent, lower) 95 606 984
15 Immersion heater backnut - Plastic (Black) 95 605 132 16 Indirect combined thermostat / thermal cut-out 70 316 89 17 Controls cover 70 316 73 18 Indirect mounting plate 95 607 931 19 6 way terminal block 95 607 933 20 2 port motorised valve (22mm compression connections) 95 605 819 21 1/2" BSP Sensor Pocket Assembly Long 70 325 79 22 Automatic air vent (NOT SHOWN) 95 605 050 23 Mixer valve (55°C) - Standard 70 373 07 24 Mixer valve (60°C) - Accessory 70 373 06
12. Spare parts
26
Pressure Reducing
Valve Cartridge (3 Bar)
Strainer Mesh
3 Bar Pressure Reducing Valve - Complete
2
Figure 17: Exploded view of 3bar pressure reducing valve
Figure 18: Mixing valve
Hot water from
cylinder
Cold water from
Mains
Mixed water
Mixer Valve
23
24
27
Figure 19: SystemReady exploded view
13
20
10
06
09
20
12
28
14
15
19
11
16
7
17
3
21
18
Figure 20: Indirect exploded view
29
NOTES.
30
Benchmark checklist
31
Commissioning &
service records
32
Warranty
The Megao Compact Warranty provides unrivalled levels
of customer support and peace of mind in the unlikely event that a problem arises from a manufacturing defect. It is supported by a large nationwide team of company-
employed eld-based engineers and our own call centre,
which is open 363 days a year.
The Megao Compact Warranty covers Megao Compact
cylinders against corrosion for 25 years from date of original purchase.
The cold water inlet valve (and expansion vessel, where
supplied) is covered by a ve year warranty from the date of purchase of the Megao Compact product, that includes
both parts and labour. All other components, including any
other valves, ttings and controls supplied with the Megao
Compact are covered by a two year warranty from the
date of purchase of the Megao Compact product, that
includes both parts and labour.
In the case of the Megao Compact Systemready, Megao Compact Systemt appliances, the supplied pumps and motorized valves ( where tted ) are also covered by this
two year warranty.
Incoloy immersion heaters ( where tted ) are covered by a
two year warranty.
Outside of the UK
These warranties are valid for installations within the United Kingdom.
For installation in the Republic of Ireland please contact Baxi Potterton Myson (Ireland) Limited on
00353 (0) 1 4590870
For installations outside of the United Kingdom and the
Republic of Ireland, please telephone Megao Export on
+44 1603 420271 for further details of the warranty terms and conditions applicable.
This warranty is valid provided that:
• The Megao Compact product has been installed by
a competent installer in accordance with the instructions contained in the installation instructions and in compliance with all relevant laws, guidance, codes of practice and regulations in force at the time of installation.
• The Megao Compact product has not been modied or
tampered with in any way, other than by a Heatrae Sadia or Baxi Customer Support approved engineer.
• The Megao Compact product has not been subject to
damage by scale.
• The Megao Compact product and any part or parts of the Megao product (whether factory tted or otherwise)
have not been repaired or replaced other than by a Baxi Customer Support approved engineer and any replacement
parts used on the Megao Compact product are authorised Megao Compact spare parts.
• The factory tted Temperature /Pressure & Expansion
Relief Valve has not been tampered with or removed.
• The Megao Compact product has not been subject to
misuse or neglect.
• The Megao Compact product has only been used for
the storage of wholesome water. Should another substance be put through the product, the warranty will be invalid unless it is part of a disinfectant procedure carried out in accordance with BS EN 806.
• The Megao Compact product has not been subjected to
frost or freezing temperatures.
• The Benchmark™ commissioning checklist service
record, included in the Megao Compact installation
instructions has been completed.
• Regular maintenance has been carried in accordance with the requirements set out in the maintenance section of the installation instructions, by a competent person, an approved engineer from Heatrae Sadia or any other part of the Baxi Groups Customer Support approved engineer ing team.
• Access is available, at reasonable times and upon
reasonable notice, to the Megao Compact product to allow
for any inspection repair or replacement.
• The product is registered within 60 days of purchase. This can be done by telephone, online or by using the registration form provided with the product.
• Evidence of purchase (for example a receipt or delivery note) and date of supply is submitted when making a claim.
• The Megao Compact product has not been affected
by any cause beyond our reasonable control including,
without limitation: an act of God, explosion, ood, re or
accident; war or civil disturbance; strike, industrial action or stoppages of work; any form of government intervention; a third party act or omission including theft or malicious damage; failure by you to give us a correct delivery address or notify us of any change of address.
.
If any of the following situations occur, the Megao
Compact Warranty will NOT apply:
• Any wilful or accidental damage caused by your negligence
• Damage caused as a result of scale.
• Installation not in line with the installer and user manuals provided,
• Failure to comply with installation instructions (whether oral or in writing),
• Misuse of the Megao Compact product or alteration of the Megao product not in accordance with the
requirements set out above.
• Defects which are reported to us outside of the warranty
period on 0344 8711535 or Megaoservice@baxi.co.uk
33
• Any third party repair or replacement costs unless those costs have been agreed and authorised by Baxi Customer Support or Heatrae Sadia in writing prior to incurring the costs.
Claims
Defects should be reported to us as soon as you are aware of them. Please report defect to us by contacting
0344 871 1535 or Megaoservice@baxi.co.uk .
Notes Heatrae Sadia accepts no liability for any third party
damage. These warranties do not affect your statutory rights and
remedies in relation to the Megao Compact products.
Annual service
Annual services are available from Baxi Customer Support, the service division of Heatrae Sadia.
Please contact Baxi Customer Support on 0344 871 1535 for details.
Megao Compact 25 year warranty is the period during which the rst owner of the Megao Compact or a new
build home continues to own the property. Should the property be sold, the new owner and any subsequent owners will receive a 25 year warranty from the date the
original owner purchased the Megao Compact or a new home with a Megao Compact installed.
The Megao Compact warranty is conditional on the
installation being carried out in accordance with the installation instructions supplied with the product. These warranties do not affect your statutory rights. Full terms and conditions of these warranty packages are available on
request or via www.heatraesadia.com/Megao
Megao may introduce modications to their products
from time to time. Consequentially the details given in this
brochure are subject to alteration without notice.
Contacts
Specication Advice Hotline
T: 01603 420220 F: 01603 420229
E: specier@heatraesadia.com
www.heatraesadia.com
Heatrae Sadia*, Hurricane Way, Norwich, Norfolk, NR6 6EA
* Heatrae Sadia is a trading name of Baxi Heating UK Limited, Brooks House, Coventry Road, Warwick, CV34 4LL
34
Spares Stockists
Electric Water Heating Co. 2 Horsecroft Place Pinnacles Harlow Essex CM19 5BT Tel: 0845 0553811 E-Mail: sales@ewh.co.uk
SPD Special Product Division Units 9 & 10 Hexagon Business Centre Springfield Road Hayes Middlesex UB4 0TY Tel: 020 8606 3567
Parts Center Tel: 0344 292 7057 www.partscenter.co.uk
Newey & Eyre Unit 3-5 Wassage Way Hampton Lovett Ind. Estate Droitwich, Worcestershire WR9 0NX Tel: 01905 791500 Fax: 01905 791501
UK Spares Ltd Unit 1155 Aztec West Almondsbury Bristol BS32 4TF Tel: 01454 620500
Alternatively contact your local supplying merchant
or wholesale branch or use our online stockist finder
at www.interpartspares.co.uk
35
NOTES.
Customer service
Telephone: 0344 8711535
Facsimile: 0344 8711528
E-mail: megaoservice@baxi.co.uk
Megao
Hurricane Way Norwich Norfolk NR6 6EA
Important notice to installations outside of the UK.
References to legislation, legal requirements, regulations, building regulations benchmark, spares stockists, guarantees and warranty are ONLY APPLICABLE WITHIN THE UK.
For local legislation, legal requirements, regulations, building regulations outside of the UK, contact your local Authority.
For spares stockists, guarantees and warranty outside the UK, contact your local supplier or,
Export Sales
T: +44 (0)1603 420271
F: +44 (0)1603 420199
E: export.sales@heatraesadia.com
7034802_issue _01
The HWA Charter’s Code of Practice requires that all members adhere to the following:
• Tosupplytforpurposeproductsclearlyandhonestlydescribed
To supply products that meet, or exceed appropriate standards and building and water regulations
To provide pre and post sales technical support
To provide clear and concise warranty details to customers
© 2016
Loading...