Technical Manual for the
Horn – DB3-ULC
Please note that every care has been taken to ensure the accuracy of our
technical manual. We do not, however, accept responsibility for damage,
loss or expense resulting from any error or omission. We reserve the right
to make alterations in line with technical advances and industry standards.
© Cooper MEDC 2012 11/12

1. INTRODUCTION
These horn units have been designed for use in harsh environmental conditions.
2. INSTALLATION
General
When installing and operating explosion-protected electrical equipment, requirements for selection, installation and operation should be referred to eg. IEC
60079-14 worldwide and the ‘National Electrical Code’ in North America.
Additional national and/or local requirements may apply.
Ensure that all nuts, bolts and fixings are secure.
Ensure that only the correct UL listed stopping plugs are used to blank off unused
gland entry points and that the NEMA/IP rating of the unit is maintained.
The DB3 is mounted via 2 x Ø 0.354” (9 mm) fixing holes in the ‘u’ shaped
stirrup/mounting bracket. The fixing holes have been designed to accept an M6
screw or bolt. MEDC recommend the use of stainless steel screws.
The elevation of the unit can be adjusted by loosening the 2 x M6 screws which
fasten the stirrup to the horn. The unit can then be adjusted by rotating to the
required position and then tightening the M6 screws. The DB3 should be positioned such that debris, dust or water cannot settle in the re-entrant horn.
Cable Termination
CAUTION: Before removing the cover assembly, ensure that the power to the
unit is isolated.
Unscrew the 6 off screws holding the cover to the unit. Twist the cover gently
clockwise and anti-clockwise, whilst pulling it away from the unit. Remove to gain
access to the interior of the base.
Cable termination should be in accordance with specifications applying to the
application. MEDC recommend that all cables and cores should be fully identified.
Ensure that only correct UL Listed cable glands are used and that the assembly is
shrouded and correctly earthed.
11/

12 © Cooper MEDC 2012
4. MAINTENANCE
During the working life of the unit, little or no maintenance is required. However,
if abnormal or unusual environmental conditions occur due to plant damage or
accident etc., then visual inspection is recommended.
If a fault should occur, it is recommended that the unit be returned to MEDC for
repair. All parts are replaceable.
If you have acquired a significant quantity of units, it is recommended that spares
are also made available. Please discuss your requirements with the Technical
Sales Engineers at MEDC.
5. CERTIFICATION/APPROVALS
Please refer to marking on the unit for specific approval details.
• ULlistedforusein ClassI,Zone1,AExdIICT5.
USA (USL) and Class I, Division 2, Groups A, B, C & D.
Canada (CNL) Class II, Division 2, Groups F & G.
• ULStandards UL2279&UL464.
• ULCStandards CAN/ULC-S525-07
6. CERTIFIED TEMPERATURE
–55°C to +70°C
–67°F to +158°F
11/
© Cooper MEDC 2012
GENERAL ARRANGEMENT
All cable glands should be of an equivalent NEMA/IP rating to that of the unit
and integrated with the unit such that this rating is maintained.
Once termination is complete, carefully push the cover back onto the unit, avoiding damage to the mating surfaces. Tighten the 6 off cover screws evenly, to
ensure maintenance of the required gap between the cover and enclosure.
3. OPERATION
The unit is initiated directly from the power source.
For all versions, a 5-way DIL switch selects the tone required from the list shown.
The DB3P includes two 5-way DIL switches to select any two tones from the list.
These units can be switched between any two of the tones listed by either:-
· Reversing the polarity of the power supply, or
· By a 3 wire common +ve system, switching between the two –ve lines.
1011/16"
271mm
Ø 45/8" / 117mm
Ø 6
11
/16" / 170mm
FIXING HOLE Ø
1
/2" /
FIXING HOLES Ø ALL 11/32" / 9mm (2 POS.)
2 x
1
/2" NPT ENTRIES MAX
7
19
/32"
193mm
1
3
/16"
30mm
1
3
/16"
30mm
POSITION 2 IS USED IF ONLY 1 x 1/2" NPT ENTRY REQUIRED
2
3
/32"
53mm
ALL DIMENSIONS IN INCHES AND MILLIMETERS
11/12

12 © Cooper MEDC 2012
SWITCH TONE Nom O/P
TONE FREQ/DESCRIPTION SETTING DESCRIPTION (dB(A)
12345 @1M)
1 Alt Tones 800/970 Hz at 1/4 sec 11111 114
2 Sweeping 800/970 Hz at 7Hz 11110 Fast Sweep(LF) 114
3 Sweeping 800/1000 Hz at 1 Hz 11101 Med Sweep(LF) 114
4 Continuous at 2850 Hz 11100 109
5 Sweeping 2400-2850 Hz at 7 Hz 11011 Fast Sweep 114
6 Sweeping 2400-2850 Hz at 1 Hz 11010 114
7 Slow Whoop 11001 Slow Whoop 115
8 Sweep 1200-500 Hz at 1 Hz 11000 Din Tone 115
9 Alt Tones 2400/2850 Hz at 2 Hz 10111 111
10 Int Tone of 970 Hz at 1 Hz 10110 Back-Up Alarm(LF) 114
11 Alt Tones 800/970 Hz at 7/8 Hz 10101 114
12 Int Tone at 2850 Hz at 1Hz 10100 Back Up Alarm(HF) 109
13 970Hz at 1/4 sec on 1 sec off 10011 114
14 Continuous at 970 Hz 10010 114
15 554Hz for 100mS / 440 Hz for 400mS 10001 French Fire Sound 101
16 Int 660 Hz 150 mS on 150 mS off 10000 Swedish Fire Alarm 106
17 Int 660 Hz 1.8 sec on 1.8 sec off 01111 Swedish Fire Alarm 106
18 Int 660 Hz 6.5 sec on 13 sec off 01110 Swedish Fire Alarm 104
19 Continuous 660 Hz 01101 Swedish Fire Alarm 106
20 Alt 554/440 Hz at 1 Hz 01100 Swedish Fire Alarm 100
21 Int 660 Hz at 7/8 Hz 01011 Swedish Fire Alarm 106
22 Int 2850 Hz 150 mS on 100 mS off 01010 Pelican Crossing 109
23 Sweep 800-970 Hz at 50 Hz 01001 Low Freq Buzz 113
24 Sweep 2400-2850 Hz at 50 Hz 01000 High Freq Buzz 112
25 3 970Hz pulses 0.5on/0.5off, 1.5 off 00111 113
26 3 2850Hz pulses 0.5on/0.5off, 1.5 off 00110 109
27 Int 3100 Hz 0.32s on / 0.68s off 00101 110
28 Spare/Customer Tone 00100
29 Spare/Customer Tone 00011
30 Spare/Customer Tone 00010
31 Spare/Customer Tone 00001
32 Spare/Customer Tone 00000
11/
© Cooper MEDC 2012
Rated SPL directional characteristics as measured in ULC 525, clause 7.3.1
Nominal output @ nominal power/3m - 102dB(A)
AUDIBLE
SIGNAL
3m DEVICE 3m
P6 P1
P2
P5 P3
P4
90º
(REF.)
POINT ANGLE SPL dB(A)
REF. 90º 102.0
P1 0º 93.7
P2 (-6 dB) 30º 96.0
P3 (-3 dB) 50º 99.0
P4 (-3 dB) 105º 99.0
P5 (-6 dB) 130º 96.0
P6 180º 91.7