Mect TPAC1008 User Manual

Page 1
USER’S MANUAL for
TPAC1008 series
Operator panel
ME7030_05
Page 2
TPAC1008 Operator panel Mect srl
ME7030_05 04/16
Page 3
TPAC1008 Operator panel Mect srl
ME7030_05 04/16
INDEX
1. Introduction .............................................................................................................. 1
1.1. Staff skill ............................................................................................................ 1
1.2. Simbols ............................................................................................................... 1
1.3. Terms ................................................................................................................. 1
1.4. Security .............................................................................................................. 2
1.5. Reference manuals ............................................................................................. 2
2. System description ................................................................................................... 2
2.1. Specification....................................................................................................... 4
3. Hardware Installation............................................................................................... 5
3.1. Mechanical dimensions ...................................................................................... 5
3.2. Panel mount........................................................................................................ 8
3.2.1. Distance ........................................................................................................ 8
4. TPAC1008 wiring .................................................................................................... 9
4.1. Connections ........................................................................................................ 9
4.2. Power supply .................................................................................................... 11
4.2.1. Isolation ...................................................................................................... 11
4.2.2. System power supply ................................................................................. 11
4.2.3. Digital output power supply ....................................................................... 11
4.2.4. Fuse ............................................................................................................ 11
4.3. Digital input/output wiring .............................................................................. 12
4.4. Analogue input wiring ..................................................................................... 12
4.5. Analogue output wiring ................................................................................... 14
4.6. CanOpen wiring ............................................................................................... 15
4.7. ModBus wiring ................................................................................................ 17
5. Peripherals ............................................................................................................. 18
5.1. USB .................................................................................................................. 18
5.2. Ethernet ............................................................................................................ 18
6. PLC and HMI ........................................................................................................ 18
6.1. System variables .............................................................................................. 19
Page 4
TPAC1008 Operator panel Mect srl
ME7030_05 04/16
1
1. Introduction
To grant a fast setup of the device please follow carefully the information in this manual.
1.1. Staff skill
Products described in this manual are devoted to PLC programmers or automation experts only. MECT S.r.l. declines any responsibility about malfunctioning or damage caused by incorrect use of MECT devices, due to noncompliance to this manual information. MECT S.r.l has an help desk.
1.2. Simbols
Danger Follow this advice to avoid people injury.
Warning Follow this advice to protect the device.
Caution Follow this advice to have a more effective performance.
ESD ( Electrostatic discharge) Danger: possibly damage due to Electrostatic discharge.
Note Step to follow for a correct installation.
Additional information
1.3. Terms
PLC: TPAC1008 Terminals: MPNC020; MPNC030 System: PLC (TPAC1008) with terminals
Page 5
TPAC1008 Operator panel Mect srl
ME7030_05 04/16
2
1.4. Security
Attention Switch off devices before connecting them.
ESD (Electrostatic discharge) Modules have electronic components that can be damaged by. electrostatic discharge. Be sure to be connected to ground when handle the devices.
The instrument has no power switch and no internal fuse, but it powers on immediately after connecting a correct power supply input (check the power supply value on the instrument label). Keep the power supply line as short as possible and keep it separate from other power lines. For security reasons it is necessary to have a 2 section power switch with a fuse near the instrument and easily replaceable. Avoid the presence of other power actuators in the same control panel, high humidity, excessive heat and corrosive gas. Instruments must have a power supply from security transformers or SELV transformers.
1.5. Reference manuals
ME7028 Mect configurator ME7041 Quick Start
2. System description
TPAC1008 is a device composed by a PLC and a HMI with touch-screen monitor 7” width and 800 x 480 pixel resolution with 262.000 colors. TPAC1008 has digital and analogue input and output, field bus CanOpen and Modbus, and a 100Mbit/s Ethernet. The device can be applied in horizontal or in vertical design with the option "V" (see following pictures).
Page 6
TPAC1008 Operator panel Mect srl
ME7030_05 04/16
3
Figure 1: Front view TPAC1008 (horizontal version)
Figure 2: Front view TPAC1008 (vertical version)
Page 7
TPAC1008 Operator panel Mect srl
ME7030_05 04/16
4
2.1. Specification
TPAC1008 is based on a multiprocessor system. PLC and HMI are based on a 454MHz ARM9, I/O interface and I/O acquisition is based on a Cortex M3 processor. The 2 systems on different boards communicate over a CAN channel.
Table 1
PLC Hardware characteristics
PLC Processor
ARM926JE 454MHz
128MB
FLASH
128MB
Non volatile variables
On FLASH memory
Real Time Clock
Yes with rechargeable battery
Screen 7”
TFT 800 x 480 pixel 262k colors
Touch screen
Resistive 4 wires
Ethernet
10Mbit/s - 100Mbit/s self recognition
USB
Host 2.0
I/O hardware characteristics
Processor
Cortex-M3 72MHz
PLC software characteristics
OS
LINUX 2.35
PLC
IEC61131-3
Graphics
Based on QT library
CAN
CanOpen 2.0
ModBus
Modbus RTU master
Storage memory
Possibility of history storage
Page 8
TPAC1008 Operator panel Mect srl
ME7030_05 04/16
5
3. Hardware Installation
In the following figures see the TPAC1008 dimensions.
3.1. Mechanical dimensions
Side view
Figure 3
Rear view
Figure 4
Side view
Figure 5
Page 9
TPAC1008 Operator panel Mect srl
ME7030_05 04/16
6
Technical specification
Table 2
Mechanical
Material
Polycarbonate, Polyamide 6.6
Dimensions W x L x H
195 mm x 145 mm x 60.5 mm
Mounting plate
139mm x 189mm
Installation
Panel installation
Environmental conditions
Operative temperature
0 °C ... 55 °C
Storage Temperature
-20 °C ... +85 °C
Relative Humidity
5 % a 95 % no condensation
Electric isolation
Air clearance
According to IEC 60664-1
Pollution According to IEC 61131-2
2
Protection
Rear protection
IP 20
Front protection
IP65
EMC
EMC according to EN 61000-6-2 (2001)
Test specification
Values
Class
Criterion
EN 61000-4-2 ESD
4 kV/8 kV (contact/air)
2/3
B
EN 61000-4-3 electromagnetic fields
10 V/m 80 MHz ... 1 GHz
3
A
EN 61000-4-4 burst
1 kV/2 kV (data/supply)
2/3
B
EN 61000-4-5 surge
Data:
-/- (line/line)
B
1 kV (line/earth)
2
DC supply:
0.5 kV (line/line)
1
B
0.5 kV (line/earth)
1
AC supply:
1 kV (line/line)
2
B
2 kV (line/earth)
3
EN 61000-4-6 RF disturbances
10 V/m 80 % AM (0.15 ... 80 MHz)
3
A
Emissions according to EN 61000-6-4 (2001)
Test specification
Limit
values/IQPI
Frequency
Range
Distance
Page 10
TPAC1008 Operator panel Mect srl
ME7030_05 04/16
7
EN 55011 (AC supply, conducted)
73 dB (µV)
500 kHz ... 30 MHz
EN 55011 (radiated) 40 dB (µV/m)
30 MHz ... 230
10 m
47 dB (µV/m)
230 MHz ... 1
10 m
Emissions according to EN 61000-6-3 (2001)
Test specification
Limit
values/IQPI
Frequency
Range
Distance
EN 55022 (AC supply, conducted)
66 ... 56 dB
150 kHz ... 500
56 dB (µV)
500 kHz ... 5
60 dB (µV)
5 MHz ... 30
EN 55022 (DC supply/data, conducted)
40 ... 30 dB
150 kHz ... 500
30 dB (µA)
500 kHz ... 30
EN 55022 (radiated) 30 dB (µV/m)
30 MHz ... 230
10 m
37 dB (µV/m)
230 MHz ... 1
10 m
Digital input
8
Input Range 0 - 24Vdc +/- 15%
Digital output
12
Max current for each digital output: 500mAdc@24Vdc Analogue input
4
PT100, TCJ, TCK,TCT, 0-10Vdc,4(0)-20mA
Analogue output
2
0-10Vdc, 4(0)-20mA
Power
10 W no load
Attention Install the device in a panel with no more than 55 °C.
Page 11
TPAC1008 Operator panel Mect srl
ME7030_05 04/16
8
3.2. Panel mount
3.2.1. Distance
System must be installed with a space for heat dissipation and cabling. Avoid cabling superimposing to avoid EMC problems.
Figure 6A: Horizontal mounting
Figure 6B: Vertical mounting
Page 12
TPAC1008 Operator panel Mect srl
ME7030_05 04/16
9
4. TPAC1008 wiring
4.1. Connections
In the following figure see the wiring diagram with the available I/O.
Figure 7: Pinout PLC
M4 connection terminal is the expansion board terminal, and can be different according to different available models.
Page 13
TPAC1008 Operator panel Mect srl
ME7030_05 04/16
10
Table 3
TPAC1008 01
Analogue input
N° 4
Input type
Resolution
Note
420 mA
0.01mA
Input impedance 9
0V
0.005V
Input impedance 1M
thermocouples J(0°C – 600°C), T(0°C – 400°C), K(0°C – 1200°C)
1°C
Cold junction compensation PT100 r -40.0°C – 200.0°C
0.1°C
PT100 E
-40°C-800°C
1°C
Analogue output
N° 2
Output type
Resolution
Note
420 mA
0.005mA
Max Impedance: 400
0-10V
0.003V
Min Impedance: 1K
Input (rpm)
N° 1
Input type
Resolution
Note
rpm
Max Frequency 1kHz (60000 rpm)
Digital Input/Encoder input
N°8
Input type
Resolution
Note
PNP
Max Frequency 500Hz
input 2 and 3 can be used as incremental encoder input Fmax 40kHz D2: A input D3: B input
Digital output
N°12
Output type
Resolution
Note
PNP
Max Frequency 500Hz
Max 500mA for each output. 2 A max total load
Power supply
24Vdc 15% 400mA
I/O power supply
24Vdc 15%
CANOpen 1 channel
Max Bit rate: 1Mbit/sec
Cycle time: 10msec
USB A
2.0
Ethernet
Bit rate: 100Mbit/sec
Serial output
RS485 full duplex (by hardware configuration)
Page 14
TPAC1008 Operator panel Mect srl
ME7030_05 04/16
11
4.2. Power supply
4.2.1. Isolation
Device has no galvanic isolation between input, output and power supply.
4.2.2. System power supply
TPAC1008 has a 24VDC (-15% +20 %) according to the scheme in the figure. System is protected against reverse power supply. As shown in the figure, the digital outputs must have a separate power supply respect the main power supply of the instrument.
4.2.3. Digital output power supply
TPAC1008 digital outputs must have a separate power supply respect the main power supply of the instrument to avoid consequences on control system due to I/O problems.
4.2.4. Fuse
System has no internal fuse , so is suggested the use of an external 1A fuse for the panel power supply, and an external 3A delayed fuse for the I/O power supply.
Figure 8
Attention A wrong value for the power supply can cause a damage to the device.
Page 15
TPAC1008 Operator panel Mect srl
ME7030_05 04/16
12
4.3. Digital input/output wiring
The digital I/Os are PNP type, the wiring must follow the scheme below.
Figure 9
Each digital output can source a 500mA max, and the total current can be lower than 2A.
4.4. Analogue input wiring
By means of the PLC program the TPAC1008 can be configured to connect several analogue input type. Configuration is done by the setup of a system variable in the PLC program. Configuration can be set up and modified in any moment.
Configuring input as thermocouple it is possible to connect up to 4 of the following type:
J (0°C – 600°C), K(0°C – 1200°C) T (0°C – 400°C)
Page 16
TPAC1008 Operator panel Mect srl
ME7030_05 04/16
13
thermocouple
Figure 10
TPAC1008 can be connected to PT100. 2 different scales are possible:
 –40.0 °C to 200.0°C  –40 °C to 800°C
The scale –40.0°C to 200.0°C has a resolution of 0.1°C. The scale –40°C to 800°C has a resolution of 1°C.
Figure 11
Page 17
TPAC1008 Operator panel Mect srl
ME7030_05 04/16
14
Configuring input as 0V or 4m is possible to connect up to 4:
Figure 12
4.5. Analogue output wiring
2 analogue output channels are available. See in the figure the current analogue output wiring.
Figure 13
Page 18
TPAC1008 Operator panel Mect srl
ME7030_05 04/16
15
See in the figure the voltage analogue output wiring.
Figure 14
4.6. CanOpen wiring
Can interface on TPAC1008 is on M1 terminal board on pins:
Table 4
Pin
Segnale
1
CAN H
2
CAN L
3
GND
Example of a wiring of a system composed by:
MPNC010 MPNC020 MPNC030
TPAC1008
Page 19
TPAC1008 Operator panel Mect srl
ME7030_05 04/16
16
Figure 15
Cable type
Cable between TPAC1008 and CANopen slave must be a shielded twisted pair, and to avoid external disturbances the shield must be connected to both 0V of the communicating systems. The cable length is a function of the baud rate as follows.
Table 5
Baud rate
Bus Lenght
1 Mbit/s
10 m
800 kbit/s
50 m
500 kbit/s
100 m
250 kbit/s
250 m
125 kbit/s
500 m
50 kbit/s
1000 m
Terminal resistance
Inside the TPAC1008 there is a resistance of 120 to terminate properly the bus on the master side. To configure the CAN communication see the TPAC tutorial.
Page 20
TPAC1008 Operator panel Mect srl
ME7030_05 04/16
17
4.7. ModBus wiring
ModBus on TPAC1008 is a 4 wire RS485 serial line, on the M2 terminal board on pins:
Table 6
Pin
Segnale
Description
11
GND
12
TX +
Line + Tx
13
TX -
Line - Tx
14
RX +
Line + Rx
15
RX -
Line - Rx
Example of a wiring of a system composed by:
TPLC005 MPNC020 MPNC030 TPAC1008
wire
Figure 16
Page 21
TPAC1008 Operator panel Mect srl
ME7030_05 04/16
18
5. Peripherals
5.1. USB
TPAC1008 has an USB 2.0 host for:
software update. data storage: datalogger. Connect USB peripherals as printers, mouse, etc.
Specific connection of external peripherals are implemented on request.
5.2. Ethernet
TPAC1008 has a 10/100Mbit/s ethernet port with autoconfiguration, with direct or inverse connection cable.
TAPC1008, by ethernet, can be controlled by a personal computer, it is possible to control the I/O of TPAC1008 by means of a program on a PC.
6. PLC and HMI
To program TPAC1008 it is necessary to develop 2 software. A PLC program written with the PLC program IDE software. A human machine interface program (HMI) written with Qt Creator.
A PLC program can be written using one of the following standard IEC 61131-3 languages:
Table 7
FBD
Functional Block Diagram
Graphic
Contact scheme
LD
Ladder
Graphic
Ladder scheme
SFC
Sequential Function Chart
Graphic
State diagram
ST
Structured Text
Text
Pascal-like language
IL (AWL)
Instruction List
Text
Assembler-like language
The 2 programming environment (PLC and HMI) are for windows OS.
Page 22
TPAC1008 Operator panel Mect srl
ME7030_05 04/16
19
6.1. System variables
Here some system variables available for PLC program. Table 8
Variable name
Number
Type
Description
PLC_StatusReg
-
UINT
Firmware revision
PLC_AnInConf_1 PLC_AnInConf_2 PLC_AnInConf_3 PLC_AnInConf_4
4
UINT
Analogue input configuration:
0 not configured 1 current 2 voltage 3 TCJ 4 TCK 5 TCT 6 PT100E 7 PT100R
Ex°: ch1 = TCT
PLC_AnInConf_1 := 5;
PLC_AnOutConf_1 PLC_AnOutConf_2
2
UINT
Analogue output configuration:
0 not configured 1 current 2 voltage
Ex°: ch1= not configured
PLC_AnOutConf_1 := 0;
PLC_DigIn_1 PLC_DigIn_2 PLC_DigIn_3 PLC_DigIn_4 PLC_DigIn_5 PLC_DigIn_6 PLC_DigIn_7 PLC_DigIn_8
8
INT
Digital input value
PLC_AnIn_1 PLC_AnIn_2 PLC_AnIn_3 PLC_AnIn_4
4
INT
Analogue input value
PLC_Tamb
-
INT
Temperature of cold junction
PLC_EncoderLo
-
UINT
Reading encoder (lower part)
PLC_EncoderHi
-
UINT
Reading encoder (upper part)
PLC_DigOut_1 PLC_DigOut_2
12
INT
Digital output value
Page 23
TPAC1008 Operator panel Mect srl
ME7030_05 04/16
20
PLC_DigOut_3 PLC_DigOut_4 PLC_DigOut_5 PLC_DigOut_6 PLC_DigOut_7 PLC_DigOut_8 PLC_DigOut_9 PLC_DigOut_10 PLC_DigOut_11 PLC_DigOut_12
PLC_AnOut_1 PLC_AnOut_2
2
INT
Analogue output value
PLC_EncEnable
-
UINT
Enable encoder:
0: disable encoder 1: enable bidirectional
encoder
Ex°: Encoder = disable
PLC_EncEnable := 0;
PLC_EncoderReset
-
UINT
Encoder reset
After that the variables are available in read / write mode as described in the program tutorial. The system can use 5472 interchange variables between HMI and automation (at maximum) which include: internal variables, interchange variables on Modbus network, retentive variables. The variables are defined by a software “Mect Suite”.