Measurement CB-COM-7021 User Manual

CD-7021/CB7021P
&
CB-7022, CB-7024
User’s Manual
Copyright Sept., 2000. All rights are reserved.
CB-7021, CB-7022, CB-7024 User’s Manual
1
Table of Contents
1.1 More Information.......................................6
1.2 Pin Assignment ..........................................7
1.3 Specifications ..........................................10
1.4 Block Diagram ........................................12
1.5 Jumper Setting .........................................14
1.6 Wire Connection......................................14
1.7 Quick Start ..............................................15
1.8 Default Setting ........................................15
1.9 Calibration ...............................................16
1.10 Configuration Tables .............................22
2. Command.......................................................26
2.1 %AANNTTCCFF ...................................29
2.2 $AA2 .......................................................30
2.3 $AA5 .......................................................31
2.4 $AAF .......................................................32
2.5 $AAM......................................................33
2.6 ~AAO(Data) ............................................34
2.7 #AA(Data) ...............................................35
2.8 $AA0 .......................................................37
2.9 $AA1 .......................................................38
2.10 $AA3VV ...............................................39
2
CB-7021, CB-7022, CB-7024 User’s Manual
2.11 $AA4 .....................................................40
2.12 $AA6 .....................................................41
2.13 $AA7 .....................................................42
2.14 $AA8 .....................................................43
2.15 #AAN(Data) ..........................................45
2.16 $AA0N ..................................................47
2.17 $AA1N ..................................................48
2.18 $AA3NVV.............................................49
2.19 $AA4N ..................................................50
2.20 $AA6N ..................................................51
2.21.1 $AA7N ...............................................52
2.21.2 $AA7N ...............................................53
2.22 $AA8N ..................................................54
2.23 $AA9N ..................................................56
2.24 $AA9NTS..............................................57
2.25 ~** .........................................................58
2.26 ~AA0 .....................................................59
2.27 ~AA1 .....................................................60
2.28 ~AA2 .....................................................61
2.29 ~AA3EVV.............................................62
2.30 ~AA4 .....................................................64
2.31 ~AA4N ..................................................65
2.32 ~AA5 .....................................................66
2.33 ~AA5N ..................................................67
CB-7021, CB-7022, CB-7024 User’s Manual
3
3. Application Note............................................68
3.1 INIT* pin Operation.................................68
3.2 Module Status .......................................... 68
3.3 Dual Watchdog Operation ........................69
3.4 Reset Status..............................................69
3.5 Analog Output..........................................69
3.6 Slew Rate Control ....................................70
3.7 Current Readback.....................................71
HM CB COM 7021-24.p65
4
CB-7021, CB-7022, CB-7024 User’s Manual
CB-7021, CB-7022, CB-7024 User’s Manual
5
1. Introduction
CB-7000 is a family of network data acquisition and
control modules. They provide analog-to-digital, digital-to-analog,
digital input/output, timer/counter and other functions. These
modules can be remote controlled by a set of commands. The basic
features of CB-7021, CB-7021P, CB-7022 and CB-7024 are given
as following:
l 3000 VDC isolated analog output.
l Programmable PowerOn Value of analog output.
l Programmable slew rate.
l Software calibration.
The CB-7021 is an analog output module with 12-bit reso-
lution and current readback function. The CB-7021P is similar with
CB-7021 but with 16-bit resolution. The CB-7022 is the dual channel
version of CB-7021. The CB-7024 is a 4-channel analog output
module, and supports bipolar voltage outputs.
1.1 More Information
Refer to “CB-7000 Bus Converter User Manual” chap-
ter 1 for more information as following:
1.1 CB-7000 Overview
1.2 CB-7000 Related Documentation
6
1.3 CB-7000 Command Features
1.4 CB-7000 System Network Configuration
1.5 CB-7000 Dimension
CB-7021, CB-7022, CB-7024 User’s Manual
1.2 Pin Assignment
CB-7021, CB-7022, CB-7024 User’s Manual
7
8
CB-7021, CB-7022, CB-7024 User’s Manual
CB-7021, CB-7022, CB-7024 User’s Manual
9
1.3 Specifications
CB-7021
Analog Output
Output Channel: 1
Output Type: mA, V
Accuracy: ±0.1% of FSR
Resolution: ±0.02% of FSR
Readback Accuracy: ±1% of
FSR
Zero Drift:
Voltage output: ±30µV/°C
Current output: ±0.2µA/°C
CB-7021P
Analog Output
Output Channel: 1
Output Type: mA, V
Accuracy: ±0.02% of FSR
Resolution: ±0.002% of FSR
Readback Accuracy: ±1% of
FSR
Zero Drift:
Voltage output: ±10µV/°C
Current output: ±0.2µA/°C
Span Temperature Coefficient:
±25ppm/°C
Programmable Output Slope:
0.125 to 1024 mA/Second
0.0625 to 512 V/Second
Voltage Output: @ 10 mA max.
Current Load Resistance:
Internal power: 500 ohms
External 24V: 1050 ohms
Isolation: 3000VDC
Power Supply
Span Temperature Coefficient:
±5ppm/°C
Programmable Output Slope:
0.125 to 1024 mA/Second
0.0625 to 512 V/Second
Voltage Output: @ 10 mA max.
Current Load Resistance:
Internal power: 500 ohms
External 24V: 1050 ohms
Isolation: 3000VDC
Power Supply
Input: +10 to +30VDC
Consumption: 1.8 W.
10
CB-7021, CB-7022, CB-7024 User’s Manual
Input: +10 to +30VDC
Consumption: 1.8 W.
CB-7022
CB-7024
Analog Output
Output Channel: 2
Output Type: mA, V
Accuracy: ±0.1% of FSR
Resolution: ±0.02% of FSR
Readback Accuracy: ±1% of
FSR
Zero Drift:
Voltage output: ±30µV/°C
Current output: ±0.2µA/°C
Span Temperature Coefficient:
Analog Output
Output Channel: 4
Output Type: mA, V
Accuracy: ±0.1% of FSR
Resolution: ±0.02% of FSR
Zero Drift:
Voltage output: ±30µV/°C
Current output: ±0.2µA/°C
Span Temperature Coefficient:
±20ppm/°C
Programmable Output Slope:
±25ppm/°C
Programmable Output Slope:
0.125 to 1024 mA/Second
0.0625 to 512 V/Second
Voltage Output: @ 10 mA max.
Current Load Resistance:
Internal power: 500 ohms
External 24V: 1050 ohms
Isolation: 3000VDC
Channel-to-channel isolation
Power Supply
0.125 to 2048 mA/Second
0.0625 to 1024 V/Second
Voltage Output: @ 5 mA max.
Current Load Resistance:
External 24V: 1050 ohms
Isolation: 3000VDC
Power Supply
Input: +10 to +30VDC
Consumption: 2.3 W.
Input: +10 to +30VDC
Consumption: 3.0 W.
CB-7021, CB-7022, CB-7024 User’s Manual
11
1.4 Block Diagram
12
CB-7021, CB-7022, CB-7024 User’s Manual
CB-7021, CB-7022, CB-7024 User’s Manual
13
1.5 Jumper Setting
Jumper-select the current output power supply of CB-7021/21P:
1. Select internal power of module. The default setting can drive
a load of up to 500 ohms.
2. Select external power of module: can drive larger load. With
24V power, it can drive 1050 ohms.
Jumper select the current output power supply of CB-7022:
1. JP1 for channel 0 setting, and JP2 for channel 1 setting.
2. Select internal power: 500 ohms load max.
3. External power: 1050 ohms with external +24VDC power.
1.6 Wire Connection
CB-7021/21P/22 Voltage Output Wire Connection
14
CB-7021, CB-7022, CB-7024 User’s Manual
CB-7021/21P/22 Current Output Wire Connection
CB-7024 Voltage Output Wire Connection
CB-7024 Current Output Wire Connection
1.7 Quick Start
Refer to “CB-7000 Bus Converter User Manual” and
Getting Started” for more detail.
1.8 Default Setting
Default setting for CB-7021, CB-7021P, CB-7022 and CB-7024:
l Address: 01
l Analog Output Type: 0 to +10V
l Baud rate: 9600 bps
l Checksum disable, change immediate, engineer unit format
l CB-7021, CB-7021P, CB-7022 jumper setting: internal power.
CB-7021, CB-7022, CB-7024 User’s Manual
15
1.9 Calibration
Don’t Perform Calibration Until You Understand Procedure.
CB-7021/21P Current Output Calibration Sequence:
1. Set the jumper 1 to internal power and connect milliammeter
to module’s current output. If a milliammeter in not available,
use Volt Meter with shunt resistor (250 ohms, 0.1%). Calculate
the output current by the Volt Meter value (I = V/250).
2. Warm-Up for 30 minutes.
3. Setting type to 30. (0 to 20 mA) Refer Sec. 2.1.
4. Program output for 4 mA. Refer Sec. 2.7.
5. Check the meter and trim the output until
4 mA match by apply trim command. Refer Sec. 2.10.
6. Preform 4 mA Calibration Command. Refer Sec. 2.8.
7. Program output for 20 mA. Refer Sec. 2.7.
8. Check the meter and trim the output until
20 mA obtained by trim command. Refer Sec. 2.10
9. Perform 20 mA Calibration Command. Refer Sec. 2.9.
16
CB-7021, CB-7022, CB-7024 User’s Manual
CB-7021/21P Voltage Output Calibration Sequence:
1. Connect voltmeter to module’s voltage output.
2. Warm-Up for 30 minutes.
3. Set type to 32. (0 to 10V) Refer Sec. 2.1.
4. Program output for 10V. Refer Sec. 2.7.
5. Check Refer Sec. 2.13.
CB-7021, CB-7022, CB-7024 User’s Manual
17
CB-7022 Current Output Calibration Sequence:
1. Set the jumper to internal power and connect milliammeter to
module’s current output channel 0. If a milliammeter is not avail-
able, use a Volt Meter with shunt resistor (250 ohms, 0.1%),
and calculate the mA by the Volt Meter value (I = V/250).
2. Warm-Up for 30 minutes.
3. Set output type to 0. (0 to 20mA) Refer Sec. 2.24.
4. Program output for 4 mA. Refer Sec. 2.15.
5. Check the meter and trim the output for
4 mA match by using trim command. Refer Sec. 2.18.
6. Preform 4 mA Calibration Command. Refer Sec. 2.16.
7. Program output 20 mA. Refer Sec. 2.15.
8. Check the meter and trim the output until
20 mA match by using trim command. Refer Sec. 2.18.
9. Perform 20 mA Calibration Command. Refer Sec. 2.17.
10. Repeat step 1 to 9 for channel 1.
18
CB-7021, CB-7022, CB-7024 User’s Manual
CB-7022 V oltage Output Calibration Sequence:
1. Connect voltmeter to module’s voltage output.
2. Warm-Up for 30 minutes.
3. Set output type to 2. (0 to 10V) -> Refer Sec. 2.24.
4. Program output 10V. -> Refer Sec. 2.15.
5. Check the meter and trim the output for
10V match by using trim command.-> Refer Sec. 2.18.
6. Perform 10V Calibration Command. -> Refer Sec. 2.21.
7. Repeat step 1 to 6 for channel 1.
CB-7021, CB-7022, CB-7024 User’s Manual
19
CB-7024 Current Output Calibration Sequence:
1. Connect meter and external power source to module’ s
current output channel 0.
2. Warm-Up for 30 minutes.
3. Set type to 30. (0 to 20 mA) -> Refer Sec. 2.1.
4. Program output for 0 mA. -> Refer Sec. 2.15.
5. Check the meter and trim the output for
0 mA match by using trim command. -> Refer Sec. 2.18.
6. Perform 0 mA Calibration Command. -> Refer Sec. 2.16.
7. Program output for 20 mA. -> Refer Sec. 2.15.
8. Check the meter and trim the output for
20 mA match by using trim command. -> Refer Sec. 2.18.
9. Perform 20 mA Calibration Command. -> Refer Sec. 2.17.
10. Repeat 1 to 9 for channel 1, 2, and 3.
20
CB-7021, CB-7022, CB-7024 User’s Manual
CB-7024 Current Output Calibration Sequence:
1. Connect meter to module’s voltage output channel 0.
2. Warm-Up for 30 minutes.
3. Setting type to 33. (10 to 10V) -> Refer Sec. 2.1.
4. Output 10V. -> Refer Sec. 2.15.
5. Check the meter and trim the output for
10V match by using trim command. -> Refer Sec. 2.18.
6. Perform −10V Calibration Command. -> Refer Sec. 2.16.
7. Program output for 10V. Refer Sec. 2.15.
8. Check the meter and trim the output for
10V match by using trim command.-> Refer
Sec. 2.18.
9. Perform 10V Calibration Command. -> Refer Sec. 2.17.
10. Repeat 1 to 9 for channel 1, 2 and 3.
CB-7021, CB-7022, CB-7024 User’s Manual
21
1.10 Configuration Tables
Baud rate Setting (CC)
edoC30405060708090A0
etarduaB0021004200840069002910048300675002511
Analog Output Type Setting (TT)
edoCepyT031323334353F3
tuptuO.niMAm0Vm4V0V01-V0V5--
tuptuO.xaMAm02Am02V01+V01+V5+V5+-
etoN42/P12/1207-IroFylno4207-IroF
Data Format Setting (FF)
76543210
01*2*3*
*1: Checksum Bit: 0=Disable, 1=Enable
*2: Slew Rate Control:
for CB-7021/21P and CB-7024, Refer Sec. 3.6 for de-
tails
for CB-7022, set to 0
2207-IroF
ylno
22
*3: 00 = Engineering Unit Format
01 = Percent of Span Format (For CB-7021/21P/22)
10 = Hexadecimal Format (For CB-7021/21P/22)
CB-7021, CB-7022, CB-7024 User’s Manual
4207-IdnaP12/1207-IrofetaRwelS
dnoceS/VdnoceS/AmdnoceS/VdnoceS/Am
0000etaidemmI00010.80.61
10005260.0521.010010.610.23
0100521.052.001010.230.46
110052.05.011010.460.821
00105.00.100110.8210.652
10100.10.210110.6520.215
01100.20.401110.2150.4201
11100.40.811110.42010.8402
etoNylno4207-Irofsi1111gifnocehT
edoCepyTegnaRtuptuOtamroFataD.xaM.niM
tinUreenignE000.02000.00
03Am02ot0
13Am02ot4
23V01ot0
napSfo%00.001+00.000+
lamicedaxeHFFF0000
tinUreenignE000.02000.40
napSfo%00.001+00.000+
lamicedaxeHFFF0000
tinUreenignE000.01000.00
napSfo%00.001+00.000+
lamicedaxeHFFF0000
P12/1207-IroftamroFataDdnaepyTtuptuOgolanA
CB-7021, CB-7022, CB-7024 User’s Manual
23
2207-IroftamroFataDdnaepyTtuptuOgolanA
epyTtuptuOegnaRtuptuOtamroFataD.xaM.niM
tinUreenignE000.02000.00
0Am02ot0
1Am02ot4
2V01ot0
napSfo%00.001+00.000+
lamicedaxeHFFF0000
tinUreenignE000.02000.40
napSfo%00.001+00.000+
lamicedaxeHFFF0000
tinUreenignE000.01000.00
napSfo%00.001+00.000+
lamicedaxeHFFF0000
4207-IroftamroFataDdnaepyTtuptuOgolanA
edoCepyTegnaRtuptuOtamroFataD.xaM.niM
03Am02ot0tinUreenignE000.02+000.00+
13Am02ot4tinUreenignE000.02+000.40+
23V01ot0tinUreenignE000.01+000.00+
33V01+ot01-tinUreenignE000.01+000.01-
43V5+ot0tinUreenignE000.50+000.00+
24
53V5+ot5-tinUreenignE000.50+000.50-
CB-7021, CB-7022, CB-7024 User’s Manual
DA Configuration of CB-7022 Analog Output T ype (T)
0 0 mA to 20 mA current output
1 4 mA to 20 mA current output
2 0V to 10V voltage output
Slew Rate Control (S)
0 Immediate change
1 0.0625V/Second or 0.125 mA/Second
2 0.125V/Second or 0.25 mA/Second
3 0.25V/Second or 0.5 mA/Second
4 0.5V/Second or 1.0 mA/Second
5 1.0V/Second or 2.0 mA/Second
6 2.0V/Second or 4.0 mA/Second
7 4.0V/Second or 8.0 mA/Second
8 8.0V/Second or 16 mA/Second
9 16V/Second or 32 mA/Second
A 32V/Second or 64 mA/Second
B 64V/Second or 128 mA/Second
C 128V/Second or 256 mA/Second
D 256V/Second or 512 mA/Second
E 512V/Second or 1024 mA/Second
CB-7021, CB-7022, CB-7024 User’s Manual
25
2. Command
Command Format: (Leading)(Address)(Command)[CHK](cr) Response Format: (Leading)(Address)(Data)[CHK](cr)
[CHK] 2-character checksum (cr) end-of-command character, character returns(0x0D)
Calculate Checksum:
1. Calculate ASCII sum of all characters of command (or
response) string except the character returns(cr).
2. Mask the sum of string with 0ffh. Example:
Command string: $012(cr)
Sum of string = ‘$’+‘0’+‘1’+‘2’ = 24h+30h+31h+32h = B7h The checksum is B7h, and [CHK] = “B7”
Command string with checksum: $012
B7(cr)
Response string: !01300600(cr)
Sum of string: ‘!’+‘0’+‘1’+‘3’+‘0’+‘0’+‘6’+‘0’+‘0’ = 21h+30h+31h+33h+30h+30h+36h+30h+30h = 1ABh The checksum is ABh, and [CHK] = “AB”
Response string with checksum: !01300600AB(cr)
steSdnammoClareneG
dnammoCesnopseRnoitpircseDnoitceS
FFCCTTNNAA%AA!noitarugifnoCeludoMteS 1.2.ceS 2AA$FFCCTTNNAA!noitarugifnoCdaeR 2.2.ceS 5AA$SAA!sutatSteseRdaeR 3.2.ceS
26
FAA$)ataD(AA!noisreVerawmriFdaeR 4.2.ceS MAA$)ataD(AA!emaNeludoMdaeR 5.2.ceS
)ataD(OAA~AA!emaNeludoMteS 6.2.ceS
CB-7021, CB-7022, CB-7024 User’s Manual
steSdnammoCtuptuOgolanAP12/1207-I
dnammoCesnopseRnoitpircseDnoitceS
)ataD(AA#> eulaVgolanAtuptuO 7.2.ceS 0AA$AA!noitarbilaCAm4 8.2.ceS 1AA$AA!noitarbilaCAm02 9.2.ceS
VV3AA$AA!noitarbilaCmirT 01.2.ceS 4AA$AA!eulaVnOrewoPteS 11.2.ceS 6AA$)ataD(AA!kcabdaeReulaVtsaL 21.2.ceS 7AA$AA!noitarbilaCV01 31.2.ceS 8AA$)ataD(AA!kcabdaeRtnerruC 41.2.ceS
steSdnammoCtuptuOgolanA2207-I
)NlennahcdeicificepsrofdnammocllA(
dnammoCesnopseRnoitpircseDnoitceS
)ataD(NAA#> eulaVgolanAtuptuO 51.2.ceS N0AA$AA!noitarbilaCAm4 61.2.ceS N1AA$AA!noitarbilaCAm02 71.2.ceS
VVN3AA$AA!noitarbilaCmirT 81.2.ceS N4AA$AA!eulaVnOrewoPteS 91.2.ceS N6AA$)ataD(AA!kcabdaeReulaVtsaL 02.2.ceS N7AA$AA!noitarbilaCV01 1.12.2.ceS N8AA$)ataD(AA!kcabdaeRtnerruC 22.2.ceS N9AA$STAA!noitarugifnoCADdaeR 32.2.ceS
STN9AA$AA!noitarugifnoCADteS 42.2.ceS
CB-7021, CB-7022, CB-7024 User’s Manual
27
steSdnammoCtuptuOgolanA4207-I
)NlennahcdeicificepsrofsdnammocllA(
dnammoCesnopseRnoitpircseDnoitceS
)ataD(NAA#> eulaVgolanAtuptuO 51.2.ceS N0AA$AA!noitarbilaCV01-/Am0 61.2.ceS N1AA$AA!noitarbilaCV01/Am02 71.2.ceS
VVN3AA$AA!noitarbilaCmirT 81.2.ceS N4AA$AA!eulaVnOrewoPteS 91.2.ceS N6AA$)ataD(AA!kcabdaeReulaVtsaL 02.2.ceS N7AA$AA!eulaVnOrewoPdaeR 2.12.2.ceS N8AA$)ataD(AA!kcabdaeReulaVtnerruC 22.2.ceS
steSdnammoCdetaleRgodhctaWtsoH
dnammoCesnopseRnoitpircseD noitceS
**~esnopseRoNKOtsoH 52.2.ceS
0AA~SSAA!sutatSeludoMdaeR 62.2.ceS 1AA~AA!sutatSeludoMteseR 72.2.ceS
godhctaWtsoHdaeR
2AA~VVAA!
eulaVtuoemiT
godhctaWtsoHteS
VVE3AA~AA!
eulaVtuoemiT
4AA~)ataD(AA!eulaVefaSdaeR 03.2.ceS
foeulaVefaSdaeR
N4AA~)ataD(AA!
NlennahC
82.2.ceS
92.2.ceS
13.2.ceS
28
5AA~AA!eulaVefaSteS 23.2.ceS
lennahCfoeulaVefaSteS
N5AA~AA!
N
CB-7021, CB-7022, CB-7024 User’s Manual
33.2.ceS
2.1 %AANNTTCCFF
Description: Set module Configuration Syntax: %AANNTTCCFF[CHK](cr)
% Delimiter character AA Address of setting module (00 to FF) NN New address for setting module (00 to FF)
TT New type for setting module (Ref Sec. 1.10) CC New baud rate for setting module (Ref Sec. 1.10) FF New data format for setting module (Ref Sec. 1.10)
When changing the baud rate or checksum, short the
INIT* pin to ground.
Response: Valid Command: !AA[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax error or communication error may get no re­sponse.
! Delimiter for valid command ? Delimiter for invalid command. While changing baud rate
or checksum setting without shorting INIT* to ground, the
module will returns an invalid command message.
AA Address of response module (00 to FF)
Example:
Command: %0102300600 Receive: !02
Change address from 01 to 02, returns successful.
Related Command: Sec. 2.2 $AA2 Related Topics: Sec. 1.10 Configuration Tables, Sec. 3.1 INIT* pin Operation
CB-7021, CB-7022, CB-7024 User’s Manual
29
2.2 $AA2
Description: Read Configuration Syntax: $AA2[CHK](cr)
$ Delimiter character
AA Address of reading module (00 to FF)
2 Command for reading configuration
Response: Valid Command: !AA TTCCFF[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax error or comm. error may get no response.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of response module (00 to FF)
TT Type code of module (reference Sec. 1.10) CC Baud rate code of module (reference Sec. 1.10) FF Data format of module (reference Sec. 1.10)
Example:
Command: $012 Receive: !01300600
Read configuration of module in address 01, which is an CB-
7021 module, returns analog output 0 to 20 mA, baud rate
9600bps, no checksum, engineering unit format and output
change immediate.
Related Command: Sec. 2.1 %AANNTTCCFF Related Topics: Sec. 1.10 Configuration Tables, Sec3.1 INIT* pin Operation
30
CB-7021, CB-7022, CB-7024 User’s Manual
2.3 $AA5
Description: Read Reset Status Command: $AA5[CHK](cr)
$ Delimiter character
AA Address of reading module (00 to FF)
5 Command for reading reset status
Response: Valid Command: !AAS[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax or communication error may get no
response.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of response module (00 to FF)
S Reset status, 1 = the module is been reset; 0 = the
module is not been reset.
Example:
Command: $015 Receive: !011
Read address 01 reset status, returns first read.
Command: $015 Receive: !010
Read address 01 reset status, returns no reset occurred.
Related Topics: Sec3.4, Reset Status
CB-7021, CB-7022, CB-7024 User’s Manual
31
2.4 $AAF
Description: Read Firmware Version Syntax: $AAF[CHK](cr)
$ Delimiter character
AA Address of reading module (00 to FF)
F command for reading firmware version
Response: Valid Command: !AA(Data)[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax error or communication error may get no re-
sponse.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of response module (00 to FF)
(Data) firmware version of module
Example:
Command: $01F Receive: !01A2.0
Read address 01 firmware version, returns version A2.0.
Command: $02F Receive: !01B1.1
Read address 02 firmware version, returns version B1.1.
32
CB-7021, CB-7022, CB-7024 User’s Manual
2.5 $AAM
Description: Read Module Name Syntax: $AAM[CHK](cr)
$ Delimiter character
AA Address of reading module (00 to FF)
M Command for reading module name
Response: Valid Command: !AA(Data)[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax error or communication error may get no re-
sponse.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of response module (00 to FF)
(Data) Name of module
Example:
Command: $01M Receive: !017021
Read address 01 module name, returns name 7021.
Command: $03M Receive: !037021P
Read address 03 module name, returns name 7021P.
Related Command: Sec. 2.6 ~AAO(Data)
CB-7021, CB-7022, CB-7024 User’s Manual
33
2.6 ~AAO(Data)
Description: Set Module Name Syntax: ~AAO(Data)[CHK](cr)
~ Delimiter character
AA Address of setting module (00 to FF)
O Command for setting module name
(Data) New name for module, max 6 characters
Response: Valid Command: !AA[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax error or communication error may get no
response.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of response module (00 to FF)
Example:
Command: ~01O7021 Receive: !01
Set address 01 module name to 7021, returns successfulful.
Command: $01M Receive: !017021
Read address 01 module name, returns 7021.
Related Command: Sec. 2.5 $AAM
34
CB-7021, CB-7022, CB-7024 User’s Manual
2.7 #AA(Data)
Description: Output Analog Value Note: The command is for CB-7021/21P only. Syntax: #AA(Data)[CHK](cr)
# Delimiter character AA Address of output module (00 to FF)
(Data) analog output value, reference Sec. 1.10 for its format. Response: Valid Command: >[CHK](cr)
Out of Range: ?AA[CHK](cr) Ignore Command: ![CHK](cr)
Syntax error or communication error may get no re-
sponse. > Delimiter for valid command
? Delimiter while the (Data) is out of range, and the output
will go to the closest value in the setting of module’s range.
! Delimiter for the module’s host watchdog flag is set, and
the output command will be ignored and the output is set to Safe Value.
AA Address of response module (00 to FF)
Example:
Command: $012 Receive: !01300600
Read Address 01 configuration, returns output type 0 to 20
mA, engineer unit format and output change immediate.
Command: #0105.000 Receive: >
Output address 01 value 5.0 mA, returns successful.
Command: #0125.000 Receive: ?01
Output address 01 value 25.0 mA, returns the value is out of
CB-7021, CB-7022, CB-7024 User’s Manual
35
range, and the output is set to 20.0 mA.
Command: $022 Receive: !02300601
Read address 02 configuration, returns output type 0 to 20
mA, percent of span format, output change immediate.
Command: #02+050.00 Receive: >
Output address 02 value 50% (=10 mA), returns successful.
Command: $032 Receive: !02300602
Read address 03 configuration, returns output type 0 to 20
mA, hexadecimal format, output change immediate.
Command: #03800 Receive: >
Output address 03 value 0x800 (=10 mA), returns successful.
Related Command: Sec. 2.1 %AANNTTCCFF, Sec. 2.2 $AA2 Related Topics: Sec. 1.10 Configuration Tables, Sec. 3.5 Analog Output
36
CB-7021, CB-7022, CB-7024 User’s Manual
2.8 $AA0
Description: Perform 4 mA Calibration Note: The command is for CB-7021/21P only. Syntax: $AA0[CHK](cr)
$ Delimiter character
AA Address of setting module (00 to FF)
0 command for performing 4 mA calibration
Response: Valid Command: !AA[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax error or communication error may get no re-
sponse.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of response module (00 to FF)
Example:
Command: $010 Receive: !01
Perform address 01 4 mA calibration, returns successful.
Related Command: Sec. 2.9 $AA1, Sec. 2.10 $AA3VV Related Topics: Sec. 1.9 Calibration
CB-7021, CB-7022, CB-7024 User’s Manual
37
2.9 $AA1
Description: Perform 20 mA Calibration Note: The command is for CB-7021/21P only. Syntax: $AA1[CHK](cr)
$ Delimiter character
AA Address of setting module (00 to FF)
1 command for performing 20 mA calibration
Response: Valid Command: !AA[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax error or communication error may get no
response.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of response module (00 to FF)
Example:
Command: $011 Receive: !01
Perform address 01 20 mA calibration, returns successful.
Related Command: Sec. 2.8 $AA0, Sec. 2.10 $AA3VV Related Topics: Sec. 1.9 Calibration
38
CB-7021, CB-7022, CB-7024 User’s Manual
2.10 $AA3VV
Description: Trim Calibration Note: The command is for CB-7021/21P only. Syntax: $AA3VV[CHK](cr)
$ Delimiter character
AA Address of setting module (00 to FF)
3 Command for trimming calibration
VV 2’s complement hexadecimal to trim the analog output
value. 00 to 5F to increase 0 to 95 counts, and FF to A1 to
decrease 1 to 95 counts. Each count indicates 4.88µA or
2.44mV.
Response: Valid Command: !AA[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax error or comm. error may get no response.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of response module (00 to FF)
Example:
Command: $0131F Receive: !01
Trim address 01 output to increase 31 counts, returns
successful.
Related Command: Sec. 2.8 $AA0, Sec. 2.9 $AA1, Sec. 2.13 $AA7 Related Topics: Sec. 1.9 Calibration
CB-7021, CB-7022, CB-7024 User’s Manual
39
2.11 $AA4
Description: Set PowerOn Value Note: The command is for CB-7021/21P only. Syntax: $AA4[CHK](cr)
$ Delimiter character
AA Address of setting module (00 to FF)
4 Command for setting PowerOn Value. Store the current
output value as PowerOn Value.
Response: Valid Command: !AA[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax error or communication error may get no re-
sponse.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of response module (00 to FF)
Example:
Command: #0100.000 Receive: >
Set address 01 output 0.0 mA, returns successful.
Command: $014 Receive: !01
Set address 01 PowerOn V alue, returns successful. The
module 01 will go to 0.0 mA with module power on.
Related Command: Sec. 2.7 #AA(Data) Related Topics: Sec. 3.5 Analog Output
40
CB-7021, CB-7022, CB-7024 User’s Manual
2.12 $AA6
Description: Last Value Readback Note: The command is for CB-7021/21P only. Syntax: $AA6[CHK](cr)
$ Delimiter character
AA Address of reading module (00 to FF)
6 Command for reading last output command value
Response: Valid Command: !AA(Data)[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax error or communication error may get no
response.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of response module (00 to FF)
(Data) The last output command value. If no output applied to
the module, the (Data) is the PowerOn V alue of the
module. Refer to Sec. 1.10 for formatting.
Example:
Command: #0110.000 Receive: !01
Set address 01 output 10.0, returns successful.
Command: $016 Receive: !0110.000
Read address 01 last output command value, returns 10.000.
Related Command: Sec. 2.7 #AA(Data), Sec. 2.14 $AA8 Related Topics: Sec. 3.7, Current Readback
CB-7021, CB-7022, CB-7024 User’s Manual
41
2.13 $AA7
Description: Perform 10V Calibration Note: The command is for CB-7021/21P only. Syntax: $AA7[CHK](cr)
$ Delimiter character
AA Address of setting module (00 to FF)
1 command for performing 10V calibration
Response: Valid Command: !AA[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax error or communication error may get no re-
sponse.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of response module (00 to FF)
Example:
Command: $017 Receive: !01
Perform address 01 10V calibration, returns successful.
Related Command: Sec. 2.10 $AA3VV Related Topics: Sec. 1.9 Calibration
42
CB-7021, CB-7022, CB-7024 User’s Manual
2.14 $AA8
Description: Current Readback Note: The command is for CB-7021/21P only. Syntax: $AA6[CHK](cr)
$ Delimiter character
AA Address of reading module (00 to FF)
8 Command for current readback
Response: Valid Command: !AA(Data)[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax error or communication error may get no re-
sponse.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of response module (00 to FF)
(Data) The current output value. Refer to Sec. 1.9 for format.
Example:
Command: $012 Receive: !01320614
Read address 01 configuration, returns output type 0 to 10V,
9600 bps, eng. unit format and slew rate is 1.0V/Second.
Command: #0110.000 Receive: !01
Set address 01 output 10.0V, returns successful.
Command: $016 Receive: !0110.000
Read address 01 last output command value, returns 10.000.
Command: $018 Receive: !0101.000
Read address 01 current value, returns 1.0V.
Command: $018 Receive: !0101.500
CB-7021, CB-7022, CB-7024 User’s Manual
43
Read address 01 current value, returns 1.5V.
Related Command: Sec. 2.7 #AA(Data), Sec. 2.12 $AA6 Related Topics: Sec. 3.6 Slew Rate Control, Sec. 3.7 Current Readback
44
CB-7021, CB-7022, CB-7024 User’s Manual
2.15 #AAN(Data)
Description: Output Analog Value for Channel N Note: The command is for CB-7022 and CB-7024 only. Syntax: #AAN(Data)[CHK](cr)
# Delimiter character
AA Address of output module (00 to FF)
N Output channel (0 to 1 for CB-7022, 0 to 3 for CB-
7024)
(Data) Analog output value, reference Sec. 1.10 for its format. Response: Valid Command: >[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Ignore Command: ![CHK](cr)
Syntax error or communication error may get no
response.
> Delimiter for valid command
? Delimiter for invalid command. When the (Data) is out
of range, and the output will go to the closest value in the
module’s range.
! Delimiter for the module’s host watchdog status is set,
and the output command will be ignored.
AA Address of response module (00 to FF)
Example for CB-7022:
Command: $012 Receive: !013F0600
Read address 01 configuration, returns multichannel output,
9600 bps and engineering unit format.
Command: $0190 Receive: !0110
CB-7021, CB-7022, CB-7024 User’s Manual
45
Read address 01, channel 0 DA config., returns 4 to 20 mA.
output and change immediate.
Command: #01005.000 Receive: >
Output address 01 channel 0 value 5.0 mA, returns success-
ful.
Command: #01025.000 Receive: ?01
Output address 01 channel 0 value 25 mA, returns out of range,
and the output of channel 0 is set to the 20.0 mA
Example for CB-7024:
Command: $012 Receive: !01300600
Read address 01 configuration, returns type 0 to 20mA, 9600
bps and engineer unit format, output change immediate.
Command: #010+05.000 Receive: >
Output address 01 channel 0 value 5.0 mA, returns success-
ful.
Command: #010+25.000 Receive: ?01
Output address 01 channel 0 value 25.0 mA, returns the value
is out of range, and the output of channel 0 is set to the 20.0
mA.
Related Command: Sec. 2.1 %AANNTTCCFF, Sec. 2.2 $AA2 Related Topics: Sec. 1.10 Configuration Tables, Sec. 3.5 Analog Output
46
CB-7021, CB-7022, CB-7024 User’s Manual
2.16 $AA0N
Description:
CB-7022: Perform 4 mA Calibration for Channel N
CB-7024: Perform 0 mA/-10V Calibration for Channel N
Note: The command is for CB-7022 and CB-7024 only. Syntax: $AA0N[CHK](cr)
$ Delimiter character
AA Address of setting module (00 to FF)
0 command for doing 4 mA (or 0 mA/-10V) calibration
N channel to calibrate (0 to 1 for CB-7022, 0 to 3 for CB-
7024)
Response: Valid Command: !AA[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax error or communication error may get no
response.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of response module (00 to FF)
Example:
Command: $0101 Receive: !01
Perform Address 01 channel 1 calibration (4 mA for CB-7022,
0 mA or -10.0V for CB-7024), returns successful.
Related Command: Sec. 2.17 $AA1N, Sec. 2.18 $AA3NVV Related Topics: Sec. 1.9 Calibration
CB-7021, CB-7022, CB-7024 User’s Manual
47
2.17 $AA1N
Description:
CB-7022: Perform 20 mA Calibration for Channel N
CB-7024: Perform 20 mA/+10V Calibration for Channel N
Note: The command is for CB-7022 and CB-7024 only. Syntax: $AA1N[CHK](cr)
$ Delimiter character
AA Address of setting module (00 to FF)
1 Command for perform 20 mA (or +10V) calibration
N Channel to calibrate (0 to 1 for CB-7022, 0 to 3 for
CB-7024)
Response: Valid Command: !AA[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax error or communication error may get no
response.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of response module (00 to FF)
Example:
Command: $0112 Receive: !01
Perform address 01 channel 1 calibration (20 mA for
CB-7022, 20 mA or 10.0V for CB-7024), returns successful.
Related Command: Sec. 2.16 $AA0N, Sec. 2.18 $AA3NVV Related Topics: Sec. 1.9 Calibration
48
CB-7021, CB-7022, CB-7024 User’s Manual
2.18 $AA3NVV
Description: Trim Calibration for Channel N Note: The command is for CB-7022 and CB-7024 only Syntax: $AA3NVV[CHK](cr)
$ Delimiter character
AA Address of setting module (00 to FF)
3 Command for trimming calibration
N Channel to trim (0 to 1 for CB-7022, 0 to 3 for
CB-7024)
VV 2’s complement hex to trim output value. 00 to 5F to
increase 0 to 95 counts, and FF to A1 to decrease 1 to 95
counts. A count = 4.88µA/2.44mV for CB-7022 and
2.44µA or 1.22mV for CB-7024.
Response: Valid Command: !AA[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax or comm. error may not get response.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of response module (00 to FF)
Example:
Command: $01321F Receive: !01
Trim address 01 channel 2 output 31 counts, returns OK
Related Command: Sec. 2.16 $AA0N, Sec. 2.17 $AA1N Related Topics: Sec. 1.9 Calibration
CB-7021, CB-7022, CB-7024 User’s Manual
49
2.19 $AA4N
Description: Set PowerOn Value for Channel N Note: The command is for CB-7022 and CB-7024 only. Syntax: $AA4N[CHK](cr)
$ Delimiter character
AA Address of setting module (00 to FF)
4 Command for setting PowerOn Value, store the current
output value as PowerOn Value.
N Channel to set (0 to 1 for CB-7022, 0 to 3 for CB-7024)
Response: Valid Command: !AA[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax error or communication error may not get
response.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of response module (00 to FF)
Example for CB-7024:
Command: #012+00.000 Receive: >
Set address 01 channel 2 output 0.0, returns successful.
Command: $0142 Receive: !01
Set address 01 channel 2 PowerOn Value, returns successful.
The Power-On Value of channel 2 is set to 0.0 now.
Related Command: Sec. 2.15 #AAN(Data), Sec. 2.21 $AA7N Related Topics: Sec. 1.10, Configuration Tables; Sec. 3.5, Analog Output
50
CB-7021, CB-7022, CB-7024 User’s Manual
2.20 $AA6N
Description: Last Value of Channel N Readback Note: The command is for CB-7022 and CB-7024 only. Syntax: $AA6N[CHK](cr)
$ Delimiter character
AA Address of reading module (00 to FF)
6 Command for reading last output command value
N Channel to readback (0 to 1 for CB-7022, 0 to 3 for CB-
7024)
Response: Valid Command: !AA(Data)[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax or comm. error may not get response.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of response module (00 to FF)
(Data) Last output command value. See Sec. 1.9 for format.
Example for CB-7024:
Command: #013+10.000 Receive: !01
Set address 01 channel 3 output 10.0, returns successful.
Command: $0163 Receive: !01+10.000
Read address 01 channel 3 last output command value, re-
turns 10.000.
Related Command: Sec. 2.15, #AAN (Data); Sec. 2.22, $AA8N Related Topics: Sec. 3.7, Current Readback
CB-7021, CB-7022, CB-7024 User’s Manual
51
2.21.1 $AA7N
Description: Perform 10V Calibration for Channel N Note: The command is for CB-7022 only. Syntax: $AA7N[CHK](cr)
$ Delimiter character
AA Address of reading module (00 to FF)
7 command for performing 10V calibration
N channel to calibrate (0 to 1)
Response: Valid Command: !AA[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax error or communication error may get no re-
sponse.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of response module (00 to FF)
Example:
Command: $0170 Receive: !01
Perform address 01 channel 0 10V calibration, returns
successful.
Related Command: Sec. 2.16, $AA0N, Sec. 2.17, $AA1N Related Topics: Sec. 1.9, Calibration
52
CB-7021, CB-7022, CB-7024 User’s Manual
2.21.2 $AA7N
Description: Read PowerOn Value of Channel N Note: The command is for CB-7024 only. Syntax: $AA7N[CHK](cr)
$ Delimiter character
AA Address of reading module (00 to FF)
7 Command for reading PowerOn Value
N Channel to readback (0 to 3)
Response: Valid Command: !AA(Data)[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax error or communication error may not get
response.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of response module (00 to FF)
(Data) Last output command value. See Sec. 1.9 for the
format.
Example:
Command: $0170 Receive: !01+00.000
Read address 01 channel 0 PowerOn Value, returns +10.0.
Related Command: Sec. 2.19, $AA4N
CB-7021, CB-7022, CB-7024 User’s Manual
53
2.22 $AA8N
Description: Current Value of Channel N Readback Note: The command is for CB-7022 and CB-7024 only. Syntax: $AA8N[CHK](cr)
$ Delimiter character
AA Address of reading module (00 to FF)
8 Command for read current output value
N Channel to readback (0 to 1 for CB-7022, 0 to 3 for CB-
7024)
Response: Valid Command: !AA(Data)[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax error or communication error may not get
response.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of response module (00 to FF)
(Data) Last output command value. See Sec. 1.9 for format.
Example for CB-7024:
Command: $012 Receive: !01320614
Read address 01 configuration, returns output type 0 to 10V,
9600 bps, engineer unit format and slew rate is 1.0V/Second.
Command: #010+10.000 Receive: !01
Set address 01 channel 0 output 10.0V, returns successful.
Command: $0160 Receive: !01+10.000
Read address 01 channel 0 last output command value, re-
turns 10.000.
54
CB-7021, CB-7022, CB-7024 User’s Manual
Command: $0180 Receive: !01+01.000
Read address 01 channel 0 current value, returns 1.0V.
Command: $0180 Receive: !01+01.500
Read address 01 channel 0 current value, returns 1.5V.
Related Command: Sec. 2.15, #AAN(Data); Sec. 2.20, $AA6N Related Topics: Sec. 3.7, Current Readback
CB-7021, CB-7022, CB-7024 User’s Manual
55
2.23 $AA9N
Description: Read DA Configuration of Channel N Note: The command is for CB-7022 only. Syntax: $AA9N[CHK](cr)
$ Delimiter character
AA Address of reading module (00 to FF)
9 Command for reading DA configuration
N Channel to read DA configuration (0 to 1)
Response: Valid Command: !AA TS[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax error or communication error may not get
a response.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of response module (00 to FF)
T Analog output type. See Sec. 1.10 for format. S Analog output slew rate. See Sec. 1.10 for format.
Example:
Command: $0190 Receive: !0110
Read address 01 channel 0 DA configuration, returns 4 to 20
mA output and change immediate.
Related Command: Sec. 2.24, $AA9NTS
56
CB-7021, CB-7022, CB-7024 User’s Manual
2.24 $AA9NTS
Description: Set DA Configuration of Channel N Note: The command is for CB-7022 only. Syntax: $AA9NTS[CHK](cr)
$ Delimiter character
AA Address of reading module (00 to FF)
9 Command for setting DA configuration
N Channel to set DA configuration (0 to 1)
T Analog output type. Refer Sec. 1.10 for type select S Analog output slew rate. Refer Sec. 1.10 for slew rate
select
Response: Valid Command: !AA[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax error or communication error may not get
a response.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of response module (00 to FF)
Example:
Command: $019121 Receive: !01
Set address 01 channel 1 DA configuration: 0 to 10V output
and slew rate 0.625V/Second, returns successful.
Related Command: Sec. 2.23 $AA9N
CB-7021, CB-7022, CB-7024 User’s Manual
57
2.25 ~**
Description: Host OK.
Host sends this command to all modules broadcasting that the host
is OK.
Command: ~**[CHK](cr)
~ Delimiter character
** command for all modules
Response: No response. Example:
Command: ~** No response
Send Host OK to all modules.
Related Command: Sec. 2.26, ~AA0; Sec. 2.27, ~AA1; Sec. 2.28, ~AA2; Sec. 2.29, ~AA3EVV; Sec. 2.30, ~AA4; Sec. 2.31, ~AA4N; Sec. 2.32, ~AA5; Sec. 2.33, ~AA5N Related Topic: Sec. 3.2, Module Status; Sec. 3.3, Dual Watchdog Operation
58
CB-7021, CB-7022, CB-7024 User’s Manual
2.26 ~AA0
Description: Read Module Status Syntax: ~AA0[CHK](cr)
~ Delimiter character AA Address of reading module (00 to FF) 0 Command for reading module status
Response: Valid Command: !AASS[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax error or communication error may not get
response. ! Delimiter for valid command ? Delimiter for invalid command AA Address of response module (00 to FF) SS Module Status. The status will store into EEPROM and
only may reset by the command ~AA1.
76543210
1*devreseR2*devreseR
*1: Host watchdog enable flag, 0=Disable, 1=Enable *2: Host watchdog timeout flag, 0=Clear, 1=Set
Example:
Command: ~010 Receive: !0104
Read address 01 module status, returns 04, host watchdog
timeout flag is set.
Related Command: Sec. 2.27, ~AA1; Sec2.29, ~AA3EVV Related Topic: Sec. 3.2, Module Status; Sec. 3.3, Dual Watchdog Operation
CB-7021, CB-7022, CB-7024 User’s Manual
59
2.27 ~AA1
Description: Reset Module Status Command: ~AA1[CHK](cr)
~ Delimiter character
AA Address of setting module (00 to FF)
1 Command for reset module status
Response: Valid Command: !AA[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax or communication error may not get a
response.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of response module (00 to FF)
Example:
Command: ~010 Receive: !0104
Read address 01 module status, returns 04, host watchdog
timeout flag is set.
Command: ~011 Receive: !01
Reset address 01 module status, returns successful.
Command: ~010 Receive: !0100
Read address 01 module status, returns 00, Module Status is
clear.
Related Command: Sec. 2.25, ~**; Sec. 2.26, ~AA0 Related Topic: Sec. 3.2, Module Status; Sec. 3.3, Dual Watchdog Operation
60
CB-7021, CB-7022, CB-7024 User’s Manual
2.28 ~AA2
Description: Read Host Watchdog Timeout Interval Command: ~AA2[CHK](cr)
~ Delimiter character
AA Address of reading module (00 to FF)
2 Command for reading host watchdog timeout interval
Response: Valid Command: !AAEVV[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax or communication error may not get a
response.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of response module (00 to FF)
E 1=Enable/0=Disable host watchdog
VV Timeout interval in hexadecimal format, count for 0.1
second, 01 = 0.1 second and FF = 25.5 seconds
Example:
Command: ~012 Receive: !010FF
Read address 01 host watchdog timeout interval, returns host
watchdog disable, and time interval is 25.5 seconds.
Related Command: Sec. 2.25, ~**; Sec. 2.26, ~AA0; Sec. 2.27, ~AA1; Sec. 2.29, ~AA3EVV; Sec. 2.30, ~AA4; Sec. 2.31, ~AA4N; Sec. 2.32, ~AA5; Sec. 2.33, ~AA5N Related Topic: Sec. 3.2, Module Status; Sec. 3.3, Dual Watchdog Operation
CB-7021, CB-7022, CB-7024 User’s Manual
61
2.29 ~AA3EVV
Description: Set Host Watchdog Timeout Interval Command: ~AA3EVV[CHK](cr)
~ Delimiter character
AA Address of setting module (00 to FF)
3 Command for setting host watchdog timeout value
E 1=Enable/0=Disable host watchdog
VV Timeout interval, from 01 to FF, each for 0.1 second
Response: Valid Command: !AA[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax error or communication error may get no re-
sponse.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of response module (00 to FF)
Example:
Command: ~010 Receive: !0100
Read address 01 module status, returns host watchdog
timeout flag is clear and host watchdog is disabled.
Command: ~013164 Receive: !01
Set address 01 host watchdog timeout interval 10.0
seconds and enable host watchdog, returns successful.
Command: ~012 Receive: !0164
Read address 01 host watchdog timeout interval, returns
10.0 seconds.
Command: ~** Receive: no response
62
CB-7021, CB-7022, CB-7024 User’s Manual
Reset the host watchdog timer.
Wait for about 10 seconds and don’t send command ~**, the LED
of module will go to flash.
Command: ~010 Receive: !0104
Read address 01 module status, returns host watchdog
timeout flag is set and host watchdog is disabled.
Command: ~011 Receive: !01
Reset address 01 module status, returns successful.
Related Command:
Sec. 2.25 ~**, Sec. 2.26 ~AA0, Sec. 2.27 ~AA1, Sec. 2.28 ~AA2, Sec. 2.30 ~AA4, Sec. 2.31 ~AA4N, Sec. 2.32 ~AA5, Sec. 2.33
~AA5N
Related Topic: Sec. 3.2 Module Status, Sec. 3.3 Dual Watchdog Operation
CB-7021, CB-7022, CB-7024 User’s Manual
63
2.30 ~AA4
Description: Read Safe Value. Note: The command is for CB-7021/21P only. Command: ~AA4[CHK](cr)
~ Delimiter character
AA Address of reading module (00 to FF)
4 Command for read Safe Value
Response: Valid Command: !AA(Data)[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax error or communication error may not get a
response.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of response module (00 to FF)
(Data) Safe Value of module. Refer Sec. 1.10 for data format
Example:
Command: ~014 Receive: !0105.000
Read address 01 Safe Value, returns 5.0.
Related Command:
Sec. 2.25, ~**; Sec. 2.26, ~AA0; Sec. 2.27, ~AA1; Sec. 2.28, ~AA2; Sec. 2.29, ~AA3EVV; Sec. 2.32, ~AA5
Related Topic:
Sec. 3.2, Module Status; Sec. 3.3, Dual Watchdog Operation
64
CB-7021, CB-7022, CB-7024 User’s Manual
2.31 ~AA4N
Description: Read Safe Value of Channel N Note: The command is for CB-7022 and CB-7024 only. Command: ~AA4N[CHK](cr)
~ Delimiter character
AA Address of reading module (00 to FF)
4 Command for reading Safe Value
N Channel to read (0 to 1 for CB-7022, 0 to 3 for CB-
7024)
Response: Valid Command: !AA(Data)[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax error or communication error may not get a
response.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of response module (00 to FF)
(Data) Safe Value of module. Refer Sec. 1.10 for data format.
Example for CB-7024:
Command: ~0140 Receive: !01+00.000
Read address 01 channel 0 Safe Value, returns +0.0.
Related Command:
Sec. 2.25, ~**; Sec. 2.26, ~AA0; Sec. 2.27, ~AA1; Sec. 2.28, ~AA2; Sec. 2.29, ~AA3EVV; Sec. 2.33, ~AA5N
Related Topic:
Sec. 3.2, Module Status; Sec. 3.3, Dual Watchdog Operation
CB-7021, CB-7022, CB-7024 User’s Manual
65
2.32 ~AA5
Description: Set Safe Value. Note: The command is for CB-7021/21P only. Command: ~AA5[CHK](cr)
~ Delimiter character
AA Address of setting module (00 to FF)
5 Command to store current output as Safe Value
Response: Valid Command: !AA[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax or communication error may not get a response.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of response module (00 to FF)
Example:
Command: #0100.000 Receive: !01
Output address 01 value 0.0, returns successful.
Command: ~015 Receive: !01
Set address 01 Safe Value, returns successful.
Related Command:
Sec. 2.25, ~**; Sec. 2.26, ~AA0; Sec. 2.27, ~AA1; Sec. 2.28, ~AA2; Sec. 2.29, ~AA3EVV; Sec. 2.30, ~AA4
Related Topic:
Sec. 3.2, Module Status; Sec. 3.3, Dual Watchdog Operation
66
CB-7021, CB-7022, CB-7024 User’s Manual
2.33 ~AA5N
Description: Set Safe Value of Channel N Note: The command is for CB-7022 and CB-7024 only. Command: ~AA5N[CHK](cr)
~ Delimiter character
AA Address of setting module (00 to FF)
5 Command to store current output as Safe Value
N Channel to set (0 to 1 for CB-7022, 0 to 3 for CB-7024)
Response: Valid Command: !AA[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax or communication error may not get a response.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of response module (00 to FF)
Example for CB-7024:
Command: #010+05.000 Receive: !01
Output address 01 channel 0 value +5.0, returns successful.
Command: ~0150 Receive: !01
Set address 01 channel 0 Safe Value, returns successful.
Related Command:
Sec. 2.25, ~**; Sec. 2.26, ~AA0; Sec. 2.27, ~AA1; Sec. 2.28, ~AA2; Sec. 2.29, ~AA3EVV; Sec. 2.31, ~AA4N
Related Topic:
Sec. 3.2, Module Status; Sec. 3.3, Dual Watchdog Operation
CB-7021, CB-7022, CB-7024 User’s Manual
67
3. Application Note
3.1 INIT* pin Operation
Each CB-7000 module has a build-in EEPROM to store
configuration information such as address, type, baud rate and other
information. Sometimes, a user may forget the configuration of the
module. Therefore, the CB-7000 have a special mode named “INIT mode”, to help user to resolve this problem. The “INIT mode” is setting as Address=00, baud rate=9600bps, no checksum.
To enable INIT mode, please follow these steps:
Step 1. Power-down the module.
Step 2. Connect the INIT* pin with the GND pin.
Step 3. Power-up the module.
Step 4. Send command $002(cr) in 9600 bps to read the con-
figuration stored in the module’s EEPROM.
Refer to “7000 Bus Converter User Manual” Sec. 5.1
and “Getting Started” for more information.
3.2 Module Status
Power-On Reset or Module W atchdog Reset will put all
outputs to the PowerOn V alue. The module can accept the host’s
command to change the output value.
Host W atchdog Timeout puts all outputs to the Safe V alue.
The host watchdog timeout flag is set, and
be ignored. The module’s LED will flash. The user must reset the
Module Status via command to go to normal operation.
68
CB-7021, CB-7022, CB-7024 User’s Manual
an output command will
3.3 Dual Watchdog Operation
Dual W atchdog = Module W atchdog + Host W atchdog
The Module Watchdog is a hardware reset circuit used to
monitor the module’s operating status. While working in harsh or
noisy environment, the module may go down caused by a noise
signal. The outputs go to the PowerOn Value. The module can
accept the host’s command to change the output value.
The Host Watchdog is a software function to monitor the
host’s operating status. Its purpose is to detect a network/
communication problem or a halted host. If a timeout occurs, the
module will place all outputs to their Safe Value to prevent any
problem in the controlled unit/process.
The CB-7000 module with Dual W atchdog makes the
control system more reliable and safer.
3.4 Reset Status
The Reset Status is set when the module is powered-on or
is reset by the Module Watchdog. It is cleared when the command
Read Reset Status ($AA5) sent. This is useful for user to determine
the module’s working status. When Reset Status is set (the module
is reset) the output is changed to the PowerOn V alue. When the
Reset Status is clear (the module is not reset) the output is not
changed.
3.5 Analog Output
The module’s output have three different condition:
<1> Safe V alue. If the host watchdog times-out, the output
CB-7021, CB-7022, CB-7024 User’s Manual
69
is set to Safe V alue. When the module receives the output command,
such as #AA(Data) or #AAN(Data), the module will returns ignore
(receive:!) and will not change the output to the output command
value. The host watchdog timeout status is set and stored in
EEPROM while the host watchdog timeout interval expired, and can only be cleared by command ~AA1. If the user wants to
change the output, he must first clear the host watchdog timeout
status, then send an output command to change the output to the
desired value.
<2> PowerOn Value. When the module is reset, and/or
when the host watchdog timeout status is clear, the module’s output
is set to predefined PowerOn Value.
<3> Output Command Value. When the host watchdog
timeout status is clear , the user sends command #AA(Data) or
#AAN(Data), to the module to change the output value. The module
will returns successful (receive >). If user sets the output value over
the maximum value of output range, the output will go to maximum
value and returns an out-of-range (receive ?AA) reply. If the output
value is under the minimum value of output range, the output will
go to minimum value and returns out-of-range
(receive ?AA).
3.6 Slew Rate Control
Slew rate control is used to adjust the output rate-of-change.
Most analog output changes are step-changes. In many
applications, this characteristic is undesirable. A gradual output
change under slew rate control is more appropriate.
70
CB-7021, CB-7022, CB-7024 User’s Manual
The CB-7021/21P/22/24 provides programmable slew rate
control. When an output command is sent to CB-7021/21P/22/24
to change the analog value, the output automatically drives to the
new value at the specified slew rate. The CB-7021/21P/22/24
updates the analog output value at 100 conversions per second.
The programmed slew rate sets the value of each 10 ms step change.
Thus, the output is smoothly stepped until the final output value is
reached. Refer to the specifications for the minimum and maxi-
mum slew rates.
3.7 Current Readback
The CB-7021/21P/22 have an analog-to-digit converter to
monitor the current output signal. The current readback will
indicate an open wiring or load when the readback value is far from
the transmitted output value.
The CB-7024 does not have the analog-to-digit converter
to monitor the current output signal. But, the CB-7024 can returns
the current digital value transferred to the DAC.
NOTE: The CB-7024 can’ t read the actual DAC output
current value , thus can’t detect faulty wiring or loads.
CB-7021, CB-7022, CB-7024 User’s Manual
71
For your notes.
72
CB-7021, CB-7022, CB-7024 User’s Manual
For your notes.
CB-7021, CB-7022, CB-7024 User’s Manual
73
For Your Notes.
74
CB-7021, CB-7022, CB-7024 User’s Manual
EC Declaration of Conformity
We, Measurement Computing Corp., declare under sole responsi­bility that the product:
CB-7021/22/24 Digital Output Modules
Part Number Description
to which this declaration relates, meets the essential requirements, is in conformity with, and CE marking has been applied accord­ing to the relevant EC Directives listed below using the relevant section of the following EC standards and other normative docu­ments:
EU EMC Directive 89/336/EEC: Essential requirements relat-
ing to electromagnetic compatibility.
EU 55022 Class B: Limits and methods of measurements of
radio interference characteristics of information technology equipment.
EN 50082-1: EC generic immunity requirements. IEC 801-2: Electrostatic discharge requirements for industrial
process measurement and control equipment.
IEC 801-3: Radiated electromagnetic field requirements for in-
dustrial process measurements and control equipment.
IEC 801-4: Electrically fast transients for industrial process mea-
surement and control equipment.
Carl Haapaoja, Director of Quality Assurance
CB-7021, CB-7022, CB-7024 User’s Manual
75
Measurement Computing Corporation
10 Commerce Way
Suite 1008
Norton, Massachusetts 02766
(508) 946-5100
Fax: (508) 946-9500
E-mail: info@mccdaq.com
www.mccdaq.com