3.8 Linear Mapping........................................69
HM CB COM 7012 & 17.p65
4
CB-7012, CB-7014, CB-7017 User’s Manual
1. Introduction
CB-7000 is a family of network data acquisition and control
modules. They provide analog-to-digital, digital-to-analog, digital
input/output, timer/counter and other functions. These modules can
be controlled remotely by a set of commands. Common features of
analog input modules are as follows:
l3000VDC isolated analog input.
l24-bit sigma-delta ADC to provide excellent accuracy .
lSoftware calibration
The CB-7012 is a single channel analog input module with
high/low alarm function. The CB-7012D is the CB-7012 with a 4½
digit LED display. The CB-7012F/12FD is a CB-7012/12D with
high speed analog input function. The CB-7014D is CB-7012D
with Linear Mapping function and supports +15V loop power for a
transmitter . The CB-7017 is an eight-channel analog input module.
The CB-7017F is a CB-7017 with high speed analog inputs.
1.1 More Information
Refer to “CB-7000 Bus Converter User Manual”
Chapter 1 for more information as following:
Same as CB-7017
Input Impedance: 20M Ohms
Overvoltage Protection: ±35V
Isolation: 3000VDC
Power Supply
Input: +10 to +30VDC
Consumption: 1.3 W
CB-7012, CB-7014, CB-7017 User’s Manual
11
1.4 Functional Block Diagrams
12
CB-7012, CB-7014, CB-7017 User’s Manual
CB-7012, CB-7014, CB-7017 User’s Manual
13
1.5 Connections
CB-7012/12D/12F/12FD
Analog Input W ire Connection
CB-7014D Analog Input Wire
Connection
CB-7012/12D/12F/12FD/14D
Digital Input W ire Connection
CB-7012/12D/12F/12FD/14D
Digital Output Wire Connection
14
CB-7012, CB-7014, CB-7017 User’s Manual
CB-7017/17F Analog Input
CB-7017/17F Analog Input
Channel 0 to 5 Wire Connection
CB-7017/17F Analog Input
Channel 6 and 7 Wire Connection, when the jumper JP1 set-
Channel 6 and 7 Wire Connection, when the jumper JP1 setting is INIT* mode. (Remove
cover to gain access to jumper
JP1.)
ting is 8 differential mode.
CB-7012, CB-7014, CB-7017 User’s Manual
15
1.6 Quick Start
Refer to “CB-7000 Bus Converter User Manual” and
“Getting Started” for more details.
1.7 Default Setting
Default setting for CB-7012/12D/12F/12FD/14D/17/17F:
lAddress: 01
lAnalog Input Type: Type 08, −10 to +10 V
lBaud rate: 9600 bps
l60 Hz filter rejection, Checksum disable, eng. unit format
lCB-7017/17F set as 6 differential and 2 single-ended modes
lCB-7012F and CB-7017F set as Fast Mode
1.8 Jumper Setting
CB-7017/17F: Jumper JP1 for select the pin INIT*/Vin 7Select 8 differential mode, the pin I INIT*/Vin7- is set to V in7-
Select INIT* mode, the pint INIT*/Vin7- is set to INIT*
16
CB-7012, CB-7014, CB-7017 User’s Manual
1.9 Calibration
Don’t Perform Calibration Until You Understand Procedure.
Calibration requirements for CB-7012/12D/12F/12FD/14D/17/17F:
When calibrating type 0D for CB-7012/12D/12F/12FD/17/17F,
connect external shunt resistor , 125 ohms, 0.1% (Ref. Sec. 1.5).
edoCepyT8090A0B0C0D0
tupnIoreZV0V0V0Vm0Vm0Am0
tupnInapSV01+V5+V1+Vm005+Vm051+Am02+
Calibration Sequence:
1. Connect calibration voltage/current to module’s input. For
CB-7017/17F, connect to channel 0.
(To connect, see Sec. 1.5)
2.Warm-Up for 30 minutes.
3.Set Type to 08.-> See Sec. 2.1.
4.Enable Calibration.-> See Sec. 2.18.
5.Apply Zero Calibration Voltage.
6.Perform Zero Calibration Command.See Sec. 2.6.
7.Apply “Span Input” Calibration Voltage.
8.Perform Span Calibration Command. See Sec. 2.5.
9.Repeat step 4 to step 8 three times.
CB-7012, CB-7014, CB-7017 User’s Manual
17
1.10 Configuration Tables
Configuration T able for CB-7012/12F/12D/12FD/14D/17/17F: