MEANWELL PSC-100A Datasheet

Page 1
100W Single Output with Battery Charger(UPS Function)
SPECIFICATION
PSC-100A -C =Blank,-C ; Blank=PCB only, -C=Enclosed type=Blank,-C ; Blank=PCB only, -C=Enclosed type
PSC-100 series
Universal AC input / Full range5"x3" compact sizeModels with L-Bracket and cover available (PSC-100x-C, x=A,B)Protections: Short circuit / Overload / Over voltageBattery low protection / Battery reverse polarity protection by fuseRelay contact signal output for AC OK and Battery LowCooling by free air convection100% full load burn-in test 2 years warranty
..
MODEL
OUTPUT NUMBER
DC VO LTAG E
RATED CURRENT
CURRENT RANGE
RATED POWER
OUTPUT
INPUT
PROTECTION
ALARM FUNCTION
ENVIRONMENT
SAFETY &
EMC
(Note 4)
NOTE
RIPPLE & NOISE (max.)
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE Note.3
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
AC CURRENT (Typ.) INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
OVERLOAD
OVER VOLTAGE
BATTERY CUT OFF
AC OK
BATTERY LOW
WORKING TEMP.
WORKING HUMIDITY STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMC EMISSION
EMC IMMUNITY
MTBF
DIMENSIONOTHERS
PACKING
PSC-100A
CH1
13.8V
4.75A
0 ~ 7A
100.05W
Note.2
100mVp-p
CH1: 12 ~ 15V
±1.0% ±0.5% ±0.5%
2400ms, 30ms/230VAC 2400ms, 30ms/115VAC at full load
Note.4
40ms/230VAC 16ms/115VAC at full load
90 ~ 264VAC 127 ~ 370VDC
47 ~ 63Hz
86%
2A/115VAC 1.2A/230VAC COLD START 35A/115VAC 70A/230VAC
<1mA / 240VAC
105 ~ 150% rated output power
Protection type : Hiccup mode, recovers automatically after fault condition is removed CH1:14.49 ~ 18.63V
Protection type : Shut down o/p voltage, re-power on to recover 10 0.5V±
Relay contact output, ON : AC OK ; OFF : AC Fail ; Max. rating : 30V / 1A
Note.6
Relay contact output, OFF : Battery OK ; ON : Battery Low ; Max. rating : 30V / 1A
Battery low voltage : < 11V Battery low voltage : < 22V
-20 ~ +70 (Refer to "Derating Curve")
20 ~ 90% RH non-condensing
-20 ~ +85 , 10 ~ 95% RH
±℃℃0.03%/ (0~50 ) on CH1 output 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
UL60950-1, TUV EN60950-1 approved
I/P-O/P:3KVAC I/P-FG:2.0KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
Compliance to EN55022 (CISPR22) Class B, EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, light industry level, criteria A
417.6K hrs min. MIL-HDBK-217F (25 )
PCB:127*76.2*31mm (L*W*H) ; Enclosed type:130*85*37mm (L*W*H) PCB:0.23Kg; 63pcs/15.5Kg/1.35CUFT ; Enclosed type:0.44Kg;32pcs/15Kg/0.64CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.¢
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. Length of set up time is measured at first cold start. Turning ON/OFF the power supply may lead to increase of the set up time.
5. Heat sink HS2,HS3 can not be shorted.
6. Heat sink HS2,HS3 must have safety isolation distance from system case.
7. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to EMI testing of component power supplies. (as available on http://www.meanwell.com)
8. Please refer to suggest application (2) (4) in page 3.
CH2
13.8V
2.5A
--------
--------
--------
--------
--------
PSC-100B
CH1
27.6V
2.4A
0 ~ 3.5A
100.74W
100mVp-p
CH1: 24 ~ 29V
±1.0% ±0.5% ±0.5%
88%
CH1:28.98 ~ 37.26V
20 1V±
CH2
27.6V
1.25A
--------
--------
--------
--------
--------
File Name:PSC-100-SPEC 2015-07-17
Page 2
100W Single Output with Battery Charger(UPS Function)
PSC-100 series
Mechanical SpecificationMechanical Specification
M2
AC FUSE
T3.15A/250V
FS1
3 2 1
CN1
M1
5.6
31max.
HS2 HS3
115.8
127
AC Input Connector (CN1) : JST B3P-VH or equivalent
Pin N o.
1 2 3
Assignment
AC/N
No Pin
AC/L
Mating Housing
JST V HR JST SVH-21T-P1.1
or equivalent or equivalent
DC Output Connector (CN2) : JST B8P-VH or equivalent
Pin N o.
Assignment 1,2 3,4 5,6 7,8
-V
+V Bat+ Bat-
: Grounding Required
Mating Housing
JST VHR
or equivalent
76.2
5.7
64.75
3max.
Terminal
Terminal
JST SVH-21T-P1.1
or equivalent
Unit:mm
Cover: No. 946B-T
CN2
1 2 3 4 5 6 7 8 1
2
CN3
3 4
SVR1
4- 3.8£
M3
Mylar film
18
L-Bracket: No. 946A-D
7.1
2-M3
6-M3 L=4
78
130
62
115.8
26
17
68.6
2-M3 L=4
41.7
85
37
8.2
Alarm Output Connector(CN3) : JSTB4B-XH or equivalent
Pin N o.
Assignment
132
AC OK
4
Bat. Low
1.HS2,HS3 cannot be shorted.
2.HS2,HS3 must have safety isolation distance from system case.
3.-V and Bat- can not be shorted.
4.M1 is safety ground. For better EMC performance,Please secure
an electrical connection between M1,M2,M3,and chassis grounding.
Mating Housing
JST XHP
or equivalent
Terminal
JST SXH-001T-P0.6
or equivalent
Block Diagram
I/P
FG
EMI FILTER
&
RECTIFIER
O.L.P.
POWER
SWITCHING
PWM
CONTROL
ALARM
CIRCUIT
RECTIFIERS
&
FILTER
DETECTION
RL1
RL2
CIRCUIT
O.V.P.
Battery Charger
&
Back up Control
AC OK
Bat. Low
+V
-V
Bat. +
Bat. -
File Name:PSC-100-SPEC 2015-07-17
Page 3
100W Single Output with Battery Charger(UPS Function)
PSC-100 series
Output Derating
100
80
60
50
40
LOAD (%)
20
-20 0 2010 30 40
Enclosed tpye
PCB only
6050 70
(HORIZONTAL)
Output Derating VS Input Voltage
100
90
80
70
60
50
LOAD (%)
40
90 10095 120115 160140 200180 240220 264
AMBIENT TEMPERATURE ( )¢
Suggested Application
1.Backup connection for AC interruption
(1) Please refer to the Fig1.1 for suggested connection.
The power supply charges the battery and provides energy to the load at the same time when theAC main is OK.
The battery starts to supply power to the load when the AC mains fails.
-V
+V
Bat+
Bat-
­+
+
-
Load
A : 12V B : 24V
Battery
PCB only Enclosed type
INPUT VOLTAGE (VAC) 60Hz
Fig 1.1 Suggested system connection
2.Alarm signal for AC OK and Battery Low
(1) Alarm signal is sent out through " AC OK " & " Battery Low " pins.(relay contact type)
(2) An external voltage source is required for this function.The maximum applied voltage is 30V and the maximum sink current is 1A.
(3) Table2.1 explains the alarm function built in the power supply
Function
AC OK
Battery Low
Description
The signal is "Low" when the power supply
turns on
The signal turns to be "High" when the power
supply turns OFF
The signal is "Low" when the voltage of
battery is under A:11V, B:22V
The signal is "High" when the voltage of
battery is above A:11V, B:22V
Table 2.1 Explanation of Alarm Signal
Output ofAlarm
Low or short
High or open(External applied voltage 30V max.)
Low or short
High or open(External applied voltage 30V max.)
(4) RL1 (AC OK)signal will go into hiccup mode when the overload protection is activating.
AC OK (Battery low)
CN3 Pin1(Pin3)
CN3 Pin2(Pin4)
Fig 2.2 Internal circuit ofAC OK (Battery Low)
R
V
External voltage source (V) and resistor (R) (The max. Sink is 1Aand 30V)
File Name:PSC-100-SPEC 2015-07-17