MEANWELL MW LPV-20-15 Datasheet

Page 1
20W Single Output Switching Power Supply
Features :
Constant voltage design
LPV-20 series
Universal AC input / Full rangeWithstand 300VAC surge input for 5 secondsProtections: Short circuit / Over load / Over voltageCooling by free air convectionSmall and compact sizeFully encapsulated with IP67 level (Note.7)Fully isolated plastic case Class power unit, no FGClass 2 power unitass LPSPSuitable for LED lighting and moving sign applications100% full load burn-in testLow cost, high reliability2 years warranty
IP67
SPECIFICATION
MODEL LPV-20-5 LPV-20-12 LPV-20-15 LPV-20-24
DC VO LTAG E
RATED CURRENT
CURRENT RANGE
RATED POWER
OUTPUT
INPUT
PROTECTION
ENVIRONMENT
SAFETY &
EMC
NOTE
RIPPLE & NOISE (max.)
VOLTAGE TOLERANCE Note.3
LINE REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
AC CURRENT (Typ.)
INRUSH CURRENT(Typ.)
MAX. No. of PSUs on 16A CIRCUIT BREAKER
LEAKAGE CURRENT
OVER LOAD
OVER VOLTAGE
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMC EMISSION
EMC IMMUNITY
MTBF
DIMENSIONOTHERS
PACKING
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. Derating may be needed under low input voltage. Please check the static characteristics for more details.
5. The power supply is considered as a component that will be operated in combination with final equipment. Since EMC performance will be affected by the complete installation, the final equipment manufacturers must re-qualify EMC Directive on the complete installation again.
6. Length of set up time is measured at first cold start. Turning ON/OFF the power supply may lead to increase of the set up time.
7. Suitable for indoor use or outdoor use without direct sunlight exposure. Please avoid immerse in the water over 30 minute.
8. The unit might not be suitable for lighting applications in EU countries. Please check with your local authorities for the possible use of the unit.
5V 12V 15V 24V
3A 1.67A 1.33A 0.84A
0 ~ 3A 0 ~ 1.67A 0 ~ 1.33A 0 ~ 0.84A
15W 20W 20W 20.2W
Note.2
80mVp-p 120mVp-p 120mVp-p 150mVp-p
±5.0%
±1.0%
±2.0%
Note.6
500ms, 20ms / 230VAC 500ms, 20ms / 115VAC at full load
50ms/230VAC 16ms/115VAC at full load
Note.4
90 ~ 264VAC 127 ~ 370VDC
47 ~ 63Hz
77% 81% 83% 83%
0.55A/115VAC 0.35A/230VAC
COLD START 70A(twidth=215 s measured at 50% Ipeak) at 230VACμ
8 units (circuit breaker of type B) / 14 units (circuit breaker of type C) at 230VAC
0.25mA / 240VAC
110 ~ 150% rated output power
Protection type : Hiccup mode, recovers automatically after fault condition is removed
5.75 ~ 6.75V 13.8 ~ 16V 17.5 ~ 21V 28 ~ 32V
Protection type : Shut off o/p voltage, clamping by zener diode
-30 ~ +70 (Refer to "Derating Curve")
20 ~ 90% RH non-condensing
-40 ~ +80 , 10 ~ 95% RH
±℃ ℃0.03%/ (0 ~ 50 )
10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes
UL879, UL1310, CSA C22.2 No. 207-M89,CAN/CSAC22.2 No. 223-M91,TUV EN60950-1,IP67 approved
I/P-O/P:3KVAC
I/P-O/P:>100M Ohms / 500VDC / 25 / 70% RH
Compliance to EN55022 (CISPR22) Class B, EN61000-3-2 ClassA, EN61000-3-3
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, light industry level, criteria A
786.5Khrs min. MIL-HDBK-217F (25 )
118*35*26mm (L*W*H)
0.22Kg; 60pcs/14.2Kg/0.62CUFT
LPS
Bauar Sicherheit
www. ID2000000000
tgepruft
egel gema od
os
be
wac g
tuv.com
File Name:LPV-20-SPEC 2015-05-28
Page 2
20W Single Output Switching Power Supply
LPV-20 series
Mechanical Specification
600 30± 118
AC/N(Blue) AC/L(Brown)
UL1015 18AWG
Recommend Mounting Direction
Block Diagram
3.5
2- 3.6ψ
3.5
35
Tcase: Max. CaseTemperature.
Tcase
Case No. 972A Unit:mm
3.5
17
3.5
28
600 30±
UL1015 18AWG
+V(Red)
-V(Black)
26
fosc : 65KHz
I/P
Derating Curve
Derating Curve Static Characteristics
LOAD (%)
LOAD (%)
LOAD (%)
EMI FILTER
&
RECTIFIERS
O.L.P.
100
80
60
40
20
-15 0 15 30
-30 60 70
04050
POWER
SWITCHING
PWM
CONTROL
(HORIZONTAL)
RECTIFIERS
&
FILTER
100
90
80
70
60
50
LOAD (%)
LOAD (%)
40
90 100 125 135 145 155 165 175 180 200 230 264
+V
-V
DETECTION
CIRCUIT
O.V.P.
175
AMBIENT TEMPERATURE ( )
INPUT VOLTAGE (V) 60Hz
File Name:LPV-20-SPEC 2015-05-28
Loading...