200W Single Out p u t w ith PFC Functi on
SPECIFICATION
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED PO WER
RIPPLE & NOISE (max.)
OUTPUT VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE
LINE REGUL ATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME ( Typ.)
VOLTAGE RANGE
FREQUENCY RANGE
POWER FACTOR (Typ.)
INPUT
PROTECTION
FUNCTION
ENVI RONMENT
SAFETY &
EMC
(Note 4)
NOTE
EFFICIENCY (Typ.)
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
LEAK AGE CURRENT
OVERLOAD
OVER VOLTAGE
OVER TEMPERATURE
5V STANDBY
REMO TE CONTRO L
WORKING TE MP.
WORKING HU MIDITY
STORAGE TEMP., HUMI DITY
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
WITHSTAND VOLTAGE
ISOL ATION RESISTANCE
EMC EMISSION
EMC IMMUNITY
MTBF
DIMENSIONOTHERS
PACKING
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.℃
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives. For guidance on how to perform these EMC tests, please refer to EMI testing of component power supplies.
(as available on http://www.meanwell.com)
5. Derating may be needed under low input voltages. Please check the derating curve for more details.
6. No load power consumption<0.5W when RC+ & RC- (CN100 pin1,2) 0 ~ 0.8V or short.
H RPG-200
■
Features :
Universal AC input / Full range
‧
Built-in active PFC function, PF>0.95
‧
High efficiency up to 89%
‧
Withstand 300VAC surge input for 5 seconds
‧
Protections: Short circuit / Overload / Over voltage / Over temperature
‧
Cooling by free air convection
‧
Built-in constant current limiting circuit
‧
1U low profile 38mm
‧
Built-in remote ON-OFF control
‧
Standby 5V@0.3A
‧
Built-in remote sense function
‧
No load power consumption<0.5W (Note.6)
•
5 years warranty
•
HRPG-200-3.3 HRPG-200-5 HRPG-200-7.5 HRPG-200-12 HRPG-200-15 HRPG-200-24 HRPG-200-36 HRPG-200-48MODE L
3.3V 5V 7.5V 12V 15V 24V 36V 48V
40A 35A 26.7A 16.7A 13.4A 8.4A 5.7A 4.3A
0 ~ 40A 0 ~ 35A 0 ~ 26.7A 0 ~ 16.7A 0 ~ 13.4A 0 ~ 8.4A 0 ~ 5.7A 0 ~ 4.3A
132W 175W 200.3W 200.4W 201W 201.6W 205.2W 206.4W
80mVp-p 90mVp-p 100mVp-p 120mVp-p 150mVp-p 150mVp-p 250mVp-p 250mVp-p
Note.2
2.8 ~ 3.8V 4.3 ~ 5.8V 6.8 ~ 9V 10.2 ~ 13.8V 13.5 ~ 18V 21.6 ~ 28.8V 28.8 ~ 39.6V 40.8 ~ 55.2V
Note .3
±2.0% ±2.0% ±2.0% ±1.0% ±1.0% ±1.0% ±1.0% ±1.0%
±0.5% ±0.5% ±0.5% ±0.3% ±0.3% ±0.2% ±0.2% ±0.2%
±1.5% ±1.0% ±1.0% ±0.5% ±0.5% ±0.5% ±0.5% ±0.5%
100 0ms, 5 0m s/ 230VAC 2500ms, 50ms/115 VAC at fu ll l oad
16m s/230VAC 16 ms/115VAC at fu ll load
Note.5
85 ~ 264VAC 1 20 ~ 3 70 VDC
47 ~ 63Hz
PF>0.95/2 30VAC P F>0.99/115VAC a t full loa d
80% 84%
2.2A/ 115VAC 1.1A/230VAC
35A /115VAC 70 A/230VAC
<1.2m A / 240 VAC
105 ~ 135% r ated output p ower
Pro tection type : Con sta nt cur re nt l imiting, recovers a utom at ically after faul t cond ition is re move d
3.96 ~ 4.62V
Pro tection type : Shut down o/p voltage, re- po wer on to recover
Shut down o/p vol ta ge, recovers auto matically a fter t empe rature goes down
5VSB : 5V@0.3A ; tolerance 5%, ripple : 50mVp-p(max.)±
RC+/RC- : 4 ~10V or open = power on ; 0 ~ 0.8V o r sh ort = po we r off
-40 ~ +70 ( Refe r to "Derating Curv e" )℃
20 ~ 90% RH non-condensing
-40 ~ +85 , 1 0 ~ 95% RH ℃
± ℃ ℃0.03%/ (0 ~ 50 )
10 ~ 500Hz, 5G 10min./1 cycle, 60min. eac h alon g X, Y, Z ax es
UL60950 -1, TUV EN609 50-1 app roved
I/P-O/P :3KVA C I/ P- FG:2KVAC O/P-F G:0. 5KVAC
I/P-O/P, I/P- FG, O/P-FG:10 0M Ohm s / 500V DC / 2 5 / 70% R H℃
Complia nce to E N550 22 ( CISPR22) Class B, EN610 00-3 -2 ,-3
Complia nce to E N610 00-4-2, 3,4,5,6 ,8,11, EN55024, he avy in du st ry level, criteri a A
189 .1K hr s mi n. M IL-HDB K-21 7F (25 )℃
199 *98*38mm ( L* W*H)
0.77Kg; 18pcs/14.9Kg/0.9CUFT
6 ~ 7V 9.4 ~ 10.9V 14.4 ~ 16.8V 18.8 ~ 21.8V 30 ~ 34.8V 41.4 ~ 48. 6V 57.6 ~ 67.2V
86% 88% 88% 88% 89% 89%
Fil e Name: HRPG- 200-SP EC 201 4-02- 12
s er ies

200W Single Out p u t w ith PFC Function
H RP G - 2 0 0
s e r i e s
Mechanical Specification
Terminal Pin N o. Assignmen t
Pin No. Pin No.
Assig nment Assig nment
1
2
3
AC/L
AC/N
FG
Connector Pin No . Assig nment (CN 100) :
HRS DF 11-6D P-2D S or equivalent
Pin No.
Assig nment
1
RC +
2
RC -
3
AUX
4
AUXG
5
6
+S
-S
4,5
DC OU TPUT -V
6,7
DC OU TPUT +V
Matin g Housing
HRS DF11 -6 DS H RS D F11- **SC
or equi valent
or equi valent
Term inal
4.5
13m ax.
1
2
3
4
5
6
7
LE D
CN100
SVR1
57. 5
6.5
28 151
Case N o.90 2E Unit :mm
197
120
199
190
Block Diagram
RECTI FIERS
&
FILTER
RECTI FIERS
&
FILTER
DET ECTION
CIR CUIT
REMOT E
CONTR OL
O.V.P.
FG
AUX
POW ER
I/P
EMI
FILTER
ACTIV E
INR USH
CUR RENT
LIMITING
RECTI FIERS
&
PFC
O.T.P.
POW ER
SWI TCHING
O.L.P.
PWMPFC
CONTR OLCONTR OL
Derating Curve Output Derating VS Input Voltage
125
100
80
60
40
20
-40 0 10 20 30 4 0 50 60 70
(HORI ZONTAL)
(HORI ZONTAL)
100
90
80
70
60
50
40
85 100 125 135 15 5 264
fosc : 70KH z
AUX
AUXG
+S
+V
-V
-S
RC+
RC-
AMBIENT TEMPERATURE ( )℃
INPUT VOLTAGE (V) 60Hz
Fil e Name: HRPG- 200-SP EC 201 4-02- 12

200W Single Out p u t w ith PFC Function
Function Description of CN100
H RP G - 2 0 0
s e r i e s
Pin No. Function
1
2
3
4
5
6 -S
Description
RC+
Turns the output on and off by electric al or dry contact between pin 2 (RC- ). Short: Power OFF, Open: Power ON.
RC-
Remote control ground.
Auxiliary voltage output, 4.75~5.25V, reference to pin 4(AUXG). The maxi mum l oad current is 0.3A. This output is not controlled by the
AUX
"remote ON/OFF control".
Auxiliary voltage output ground. The signal return is isolated from the output terminals (+V & -V).
AUXG
Positive sensing. The +S signal should be connected to the positive terminal of the load. The +S and -S leads should be twisted in pair to
+S
minimize noise pick-up effect. Th e maximum line drop compensation is 0.5V.
Negative s ensi ng. The -S signal should b e connected to the negative terminal of the load. The -S and +S leads should be twisted in pair to
minimize noise pick-up effect. Th e maximum line drop compensation is 0.5V.
Function Manual
1.Remote C on trol
The PSU can be t urned ON/ OF F by using t he "Remote
ON/OFF " fu nction
Bet ween RC-( pin2) a nd RC+ (pi n1)
SW ON (Short )
SW OFF (Open)
Out pu t Statu s
OFF
ON
CN100
RC+
AUX
AUX G
+S
5
SW
6
-S
1
2
+V+V-V- V
CN100
1 3 5
2 4 6
RC-
2.Remote S en se
The remote s en sing c ompensates volt age drop o n the
load w iring up t o 0.5V.
-S
(Pin6)
LO AD
-
Fig 1. 1
LOAD
-
Fig 2. 1
+
+V+V-V- V
CN100
1 3 5
2 4 6
Sense lin es shou ld
be twi sted in pairs
+S
(Pin5)
+
CN100
RC+
AUX
AUX G
+S
5
6
-S
1
2
RC-
Fil e Name: HRPG- 200-SP EC 201 4-02- 12