Mean Well DRT-960 series Test Results / Test Reports

Page 1
960W Three Phase Industrial DIN RAIL Power Supply
DRT-960 series
MODELDRT-960-24
OUTPUT FUNCTION TEST
NO TEST ITEM SPECICATION TEST CONDITION RESULT VERDICT
mVp-p (Max ) I/P: 400VAC
O/P:FULL LOAD Ta:25
V1:
15 mVp-p (Max ))
P
2 OUTPUT VOLTAGE
ADJUST RANGE
3 OUTPUT VOLTAGE
TOLERANCE
4 LINE REGULATION V1: -0.5%~ 0.5 % (Max)
5 LOAD REGULATION V1: -0.5 %~ 0.5 % (Max)
9 OVER/UNDERSHOOT TEST
10 DYNAMIC LOAD V1: 2400 mVp-p I/P: 400 VAC
CH1: 24 V~ 28 V I/P: 400 VAC
O/P:MIN LOAD Ta:25
V1: -1 %~ 1 % (Max)
400VAC: 200 ms (Max) 400VAC/ 122 ms 6 SET UP TIME 500VAC: 200 ms (Max)
400VAC: 60 ms (Max) 400VAC/ 34 ms 7 RISE TIME 500VAC: 60 ms (Max)
400VAC: 10 ms (TYP) 400VAC/ 14 ms 8 HOLD UP TIME 500VAC: 30 ms(TYP)
< +5%
I/P: 340 VAC / 550 VAC O/P:FULL/ MIN LOAD Ta:25
I/P: 340 VAC ~ 550 VAC O/P:FULL LOAD Ta:25
I/P: 400 VAC O/P:FULL ~MIN LOAD Ta:25
I/P: 400 VAC I/P: 500 VAC O/P:FULL LOAD Ta:25
I/P: 400 VAC I/P: 500 VAC O/P:FULL LOAD Ta:25
I/P: 400 VAC I/P: 500 VAC O/P:FULL LOAD Ta:25
I/P: 400 VAC O/P:FULL LOAD Ta:25
O/P:FULL /Min LOAD 90%DUTY/1KHZ Ta:25
21.32
V~
29.42
V/ 400 VAC
21.32
V~
29.42
V/ 500 VAC
V1: 0.2 %~ -0.2 %
V1: 0.05 %~ -0.05 %
V1: 0.15 %~ -0.15 %
500VAC/ 91 ms
500VAC/ 28 ms
500VAC/ 31 ms
TEST: <5
1249 mVp-p
P
P
P
P
P
P
P
%
P
P
Model: DRT-960-24 Test Report 1 / 5
Page 2
960W Three Phase Industrial DIN RAIL Power Supply
DRT-960 series
INPUT FUNCTION TEST
NO TEST ITEM SPECICATION TEST CONDITION RESULT VERDICT
2 INPUT FREQUENCY RANGE 47HZ ~63 HZ
NO DAMAGE OSC
3 EFFICIENCY
5 INRUSH CURRENT
91 % (TYP)
400V/ 2 A (TYP) I = 1.91 A/400 VAC 4 INPUT CURRENT 500V/ 1.6 A (TYP)
400V/ 50 A(TYP) I = 30 A/400AC
COLD START
I/P:TESTING O/P:FULL LOAD Ta:25
I/P: LOW-LINE-3V= 337 V HIGH-LINE+15%= 600 V O/P:FULL/MIN LOAD ON: 30 Sec . OFF: 30 Sec 10MIN ( AC POWER ON/OFF NO DAMAGE )
I/P: 340 VAC ~ 550 VAC O/P:FULL~MIN LOAD Ta:25
I/P: 400 VAC O/P:FULL LOAD Ta:25
I/P: 400 VAC I/P: 500 VAC O/P:FULL LOAD Ta:25
I/P: 400 VAC O/P:FULL LOAD Ta:25
270 V~264V 1 INPUT VOLTAGE RANGE 340VAC~550 VAC)
TEST: OK
TEST: OK
91.2 %
I = 1.54 A/ 500 VAC
P
P
P
P
P
6 LEAKAGE CURRENT < 3.5 mA / 530 VAC I/P: 530 VAC
O/P:Min LOAD Ta:25
L1-FG: L2-FG: L3-FG:
0.7
0.7
0.7
mA mA mA
PROTECTION FUNCTION TEST
NO TEST ITEM SPECICATION TEST CONDITION RESULT VERDICT
1 OVER LOAD PROTECTION 105 %~ 125 % I/P: 400 VAC
I/P: 500 VAC O/P:TESTING Ta:25
2 OVER VOLTAGE PROTECTION CH1: 30 V~ 36 V I/P: 400 VAC
I/P: 500 VAC O/P:MIN LOAD Ta:25
3 OVER TEMPERATURE PROTECTION SPEC:
TSW1: 110+5 O.T.P. TSW2: 85+5 O.T.P. NO DAMAGE
4 SHORT PROTECTION SHORT EVERY OUTPUT
1 HOUR NO DAMAGE
I/P: 400 VAC O/P:FULL LOAD
I/P: 550 VAC O/P: Full LOAD Ta:25
112 %/ 400 VAC 112 %/ 500 VAC Constant Current Limiting
32.7 V/ 400 VAC
32.7 V/ 500 VAC Shunt down Re- power ON
O.T.P. Active Shut down o/p voltage,recovers
automatically after temperature goes down
NO DAMAGE Constant Current Limiting ,unit will Shut down o/p voltage after 3 sec, Re-power on to recover
P
P
P
P
P
Model: DRT-960-24 Test Report 2 / 5
Page 3
960W Three Phase Industrial DIN RAIL Power Supply
DRT-960 series
ENVIRONMENT TEST
NO TEST ITEM SPECICATION TEST CONDITION RESULT VERDICT
1 TEMPERATURE RISE TEST
MODELDRT-960-24
1. ROOM AMBIENT BURN-IN 2 HRS I/P: 400VAC O/P: FULL LOAD Ta= 29
2. HIGH AMBIENT BURN-IN 2 HRS I/P: 400VAC O/P: FULL LOAD Ta= 47.4
NO Position P/N
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15
2 OVER LOAD BURN-IN TEST NO DAMAGE
1 HOUR ( MIN )
3 LOW TEMPERATURE
TURN ON TEST
TURN ON AFTER 2 HOUR
ROOM AMBIENT
LF1 TR-422
C5 LF2 TR-546 Q50 15NK90Z 15A/900V STW Q53 15NK90Z 15A/900V STW L51 TR-533 D50 BYC10-600 10A/600V PH
T1 COIL TF-1175
C116 U102 UCC2895N
TSW2 ST-85
L203 TR-584 C205 L202 TR-528 D202 60CPQ150 60A/150V IR
470U/420V HU 105
470U/35V NCC 105 KY
1500U/35V NCC 105 KY
I/P: 400 VAC O/P: 110 ﹪LOAD Ta:25
I/P: 400 VAC O/P: 100 ﹪LOAD Ta= -20
HIGH AMBIENT
Ta= 29
69.3 79.2
60.6 70.3
85.4 95.1
65.5 76.1
54.1 63.9
73.4 87.4
59.1 68.7
80.1 88.8
51.1 58.0
59.7 67.7
68.9 77.4
103.8 113.9
77.6 86.6
85.3 94.2
85.7 94.3
TESTOK
TESTOK
Ta= 47.4
P
P
P
4 HIGH HUMIDITY
HIGH TEMPERATURE HIGH VOLTAGE TURN ON TEST
5 TEMPERATURE
COEFFICIENT
6 VIBRATION TEST 1 Carton & 1 Set
AFTER 12 HOURS IN CHAMBER ON CONTROL 45 NO DAMAGE
0.03 %(0~50℃)
+
(1) Waveform: Sine Wave (2) Frequency:10~500Hz (3) Sweep Time:10min/sweep cycle (4) Acceleration:2G (5) Test Time:1 hour in each axis (X.Y.Z) (6) T a:25
I/P: 567 VAC O/P:FULL LOAD Ta= 45 HUMIDITY= 95 %R.H I/P: 230 VAC O/P:FULL LOAD
TESTOK
P
+ 0.01 %(0~50)
P
TESTOK
P
Model: DRT-960-24 Test Report 3 / 5
Page 4
960W Three Phase Industrial DIN RAIL Power Supply
DRT-960 series
SAFETY TEST
NO TEST ITEM SPECICATION TEST CONDITION RESULT VERDICT
1 WITHSTAND VOLTAGE I/P-O/P: 3 KVAC/min
I/P-FG: 1.5 KVAC/min O/P-FG: 0.5 KVAC/min
I/P-O/P: 3.6 KVAC/min I/P-FG: 1.8 KVAC/min O/P-FG: 0.6 KVAC/min Ta:25
I/P-O/P: 4.11 mA I/P-FG:
O/P-FG: 5.76 mA NO DAMAGE
2.74
mA
P
2 ISOLATION RESISTANCE I/P-O/P:500VDC>100M
I/P-FG: 500VDC>100M O/P-FG:500VDC>100M
3 GROUNDING CONTINUITY FG(PE) TO CHASSIS
OR TRACE < 100 m
4 APPROVAL
TUV: Certificate NO :R50061104 UL: File NO :E215312/E183223
I/P-O/P: 500 VDC
I/P-FG: 500 VDC
O/P-FG: 500 VDC Ta:25
40 A / 2min Ta:25
I/P-O/P: I/P-FG: 12 G
O/P-FG: NO DAMAGE
30
18
14 m
G
G
E.M.C TEST
NO TEST ITEM SPECICATION TEST CONDITION RESULT VERDICT
1 HARMONIC EN61000-3-2
CLASS A
2 CONDUCTION EN55022 EN55011
CLASS B
3 RADIATION EN55022 EN55011
CLASS B
4 E.S.D EN61000-4-2
INDUSTRY AIR:8KV / Contact:4KV
5 E.F.T EN61000-4-4
INDUSTRY INPUT: 2KV
6 SURGE IEC61000-4-5
INDUSTRY L-N :2KV L,N-PE:4KV
I/P: 400 VAC/50HZ O/P:FULL LOAD Ta:25
I/P: 400 VAC (50HZ) O/P:FULL/50% LOAD Ta:25
I/P: 400 VAC (50HZ) O/P:FULL LOAD Ta:25
I/P: 400 VAC/50HZ O/P:FULL LOAD Ta:25
I/P: 400 VAC/50HZ O/P:FULL LOAD Ta:25
I/P: 400 VAC/50HZ O/P:FULL LOAD Ta:25
PASS
PASS Test by certified Lab P
PASS Test by certified Lab P
CRITERIA A
CRITERIA A
CRITERIA A
P
P
P
P
P
P
P
7
Test by certified Lab Test Report Prepare
Model: DRT-960-24 Test Report 4 / 5
Page 5
960W Three Phase Industrial DIN RAIL Power Supply
DRT-960 series
M.T.B.F & LIFE CYCLE CALCULATION
NO TEST ITEM SPECICATION TEST CONDITION RESULT VERDICT
1 CAPACITOR
LIFE CYCLE
2 MTBF MIL-HDBK-217F NOTICES2 PARTS COUNT
SUPPOSE C 205 IS THE MOST CRITICAL COMPONENT I/P: 400VAC O/P:FULL LOAD Ta= 25 LIFE TIME= 98254 HRS I/P: 400VAC O/P:FULL LOAD Ta= 45 LIFE TIME= 47122 HRS
TOTAL FAILURE RATE: 122.5K HRS
P
P
COMPONENT STRESS TEST
NO TEST ITEM SPECICATION TEST CONDITION RESULT VERDICT
1 Power Transistor
( D to S) or (C to E) Peak Voltage
2 Diode Peak Voltage D201 Rated
3 Input Capacitor Voltage C5 Rated
Q 50 Rated 15NK90Z : 900V 15A
60CPQ150 : 150 V 60A
: 470u / 420V/ 105
I/P:High-Line +3V = 553 V O/P: (1)Full Load Turn on (2) Full Load (3)Output Short Ta:25
I/P:High-Line +3V = 553 V O/P: (1)Full Load Turn on (2) Full Load (3)Output Short Ta:25
I/P:High-Line +3V = 553 V O/P: (1)Full Load Turn on /Off (2) Min load Turn on /Off
(3)Full Load /Min load Change
Ta:25
(1) 788 V (2) 748 V (3) 368 V
(1) 96 V (2) 100 V (3) 100 V
(1) 414 V (2) 388 V
(3) 388 V
P
P
P
4 Control IC Voltage Test U102 Rated
UCC2895N\ : 17 V
I/P:High-Line +3V = 553 V O/P: (1)Full Load Turn on /Off (2) Min load Turn on /Off
(3)Full Load /Min load Change Ta:25
(1) 15.4 V (2) 15.4 V (3) 15.4 V
P
DATE SAMPLE TEST RESULT TESTER APPROVAL
2005/3/2 RD SAMPLE PASS VINCENT TSENG MAX LIN
2005/6/1
PRODUCT SAMPLE
W0504A02
PASS VINCENT TSENG MAX LIN
2003/12/12 A50-F023
Model: DRT-960-24 Test Report 5 / 5
Loading...