ƤInput 340~550VAC, 3-phase 4 wires
ƤHigh efficiency up to 90%
ƤProtections: Short circuit / Overload /
Over voltage / Over temp.
ƤInstalled on DIN rail TS35/7.5 or 15
ƤEN61000-6-2 industrial immunity level
Ƥ100% full load burn-in test
ƤApprovals: UL / CUL / TUV / CB / CE
ƤCooling by free air convection
Ƥ3 years warranty
AC input voltage range
AC inrush current
DC adjustment range
Overload protection
Over voltage protection
Over temp. protection
Withstand voltage
Working temperature
Safety standards
EMC standards
Connection
Packing
340~550 VAC, 3-phase 4 wires (dual-phase
operation possible)
Cold start, 50A
24V: 24~28V, 48V: 48~55V
105%~150% rated output power;
Constant current limiting, auto recovery
24V: 30~36V, 48V: 59~66V shut off,
AC recycle to re-start
Shut down output voltage, recovers
automatically after temperature goes down
I/P-O/P: 3KVAC, I/P-FG: 1.5KVAC, 1 minute
-20 ~ +70OC (refer to output derating curve)
UL508, UL60950-1, TUV EN60950-1 approved
EN55022 class B, EN61000-3-2,3, ENV50204,
EN61000-4-2,3,4,5,6,8,11, EN61000-6-2 heavy
industry level, EN61204-3
I/P: 4 poles, O/P: 4 poles screw D IN terminal
2.5kg ; 6pcs / 16.0kg / 1.75CUFT
480W Three Phase DIN Rail Power480W Three Phase DIN Rail Power
227x 125.2x 100 m m
CASE : 930A
. . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . . . .
. . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Stock No. Model No. Output Tol. R&N Effi.
10951
10952
DRT-480-24
DRT-480-48
24V, 0~20A
48V, 0~10A
²1%
²1%
80mV
80mV
89%
90%