Mean Well DRT-240 series Test Results / Test Reports

Page 1
240W Three Phase Industrial DIN RAIL Power Supply
DRT-240 series
MODELDRT-240-48
OUTPUT FUNCTION TEST
1 RIPPLE & NOISE V1: 80 mVp-p (Max )
I/P: 400 VAC O/P:FULL LOAD Ta:25
V1: 20 mVp-p (Max )
p
2 OUTPUT VOLTAGE
ADJUST RANGE
3 OUTPUT VOLTAGE
TOLERANCE
4 LINE REGULATION V1:-0.5 %~ 0.5 % (Max)
5 LOAD REGULATION V1: -0.5 %~ 0.5 % (Max)
6 SET UP TIME
7 RISE TIME 400 VAC/ 40 ms (Max)
8 HOLD UP TIME 400 VAC/ 20 ms (TYP)
9 OVER/UNDERSHOOT TEST
10 DYNAMIC LOAD V1: 4800 mVp-p I/P: 400 VAC
CH1: 48 V~ 55 V I/P: 400 VAC
O/P:MIN LOAD Ta:25
V1: -1 %~ 1 % (Max)
400 VAC/ 1200 ms (Max) 500 VAC/ 800 ms (Max)
500 VAC/ 40 ms (Max)
500 VAC/ 40 ms (TYP)
< +5%
I/P: 340 VAC / 550 VAC O/P:FULL/ MIN % LOAD Ta:25
I/P: 340 VAC ~ 550 VAC O/P:FULL LOAD Ta:25
I/P: 400 VAC O/P:FULL ~MIN LOAD Ta:25
I/P: 400 VAC I/P: 500 VAC O/P:FULL LOAD Ta:25
I/P: 400 VAC I/P: 500 VAC O/P:FULL LOAD Ta:25
I/P: 400 VAC I/P: 500 VAC O/P:FULL LOAD Ta:25
I/P: 400 VAC O/P:FULL LOAD Ta:25
O/P:FULL /Min LOAD 90%DUTY/1KHZ Ta:25
40.49V~ 56.11V/ 400VAC P
V1: 0.1 %~ -0.1 %
V1: 0.1 %~ -0.1 %
V1: 0.1%~ -0.1 %
400 VAC/ 704 ms 500 VAC/ 316 ms
400 VAC/ 17 ms 500 VAC/ 17 ms
400 VAC/ 49 ms 500 VAC/ 49 ms
TEST: 5 %
654 mVp-p
P
P
P
P
P
P
P
P
Model: DRT-240-48 Test Report 1 / 5
Page 2
240W Three Phase Industrial DIN RAIL Power Supply
DRT-240 series
INPUT FUNCTION TEST
I/P:TESTING O/P:FULL LOAD Ta:25
I/P: LOW-LINE-3V= 337 V HIGH-LINE+15%= 600 V O/P:FULL/MIN LOAD ON: 30 Sec . OFF: 30 Sec 10MIN ( AC POWER ON/OFF NO DAMAGE )
270 V~ 550 V 1 INPUT VOLTAGE RANGE 340VAC~ 550 VAC
TEST: OK
p
2 EFFICIENCY
3 INPUT CURRENT 400 V/ 0.95 A(TYP)
4 INRUSH CURRENT 400 V/ 50 A(TYP)
5 LEAKAGE CURRENT < 3.5 mA / 530 VAC I/P: 562 VAC
89 % (TYP)
500 V/ 0.75 A(TYP)
COLD START
I/P: 400 VAC O/P:FULL LOAD Ta:25
I/P: 400 VAC I/P: 500 VAC O/P:FULL LOAD Ta:25
I/P: 400 VAC O/P:FULL LOAD Ta:25
O/P:Min LOAD Ta:25
89.5 %
I = 0.75 A/ 400 VAC I = 0.55 A/ 500 VAC
I = 14 A/ 400 VAC
P
L1-FG: 0.8 mA L2-FG: 0.8 mA L3-FG: 0.8 mA
PROTECTION FUNCTION TEST
1 OVER LOAD PROTECTION 105 %~ 150 % I/P: 400 VAC
I/P: 500 VAC O/P:TESTING Ta:25
2 OVER VOLTAGE PROTECTION CH1: 59 V~ 66 V I/P: 400 VAC
I/P: 500 VAC O/P:MIN LOAD Ta:25
119 %/ 400 VAC
125 %/ 500 VAC
Constant Current Limiting
64.4 V/ 400 VAC
64.4 V/ 500 VAC
Shunt down Re- power ON
P
P
P
P
P
3 OVER TEMPERATURE PROTECTION SPEC:
100+5 O.T.P. NO DAMAGE
4 SHORT PROTECTION SHORT EVERY OUTPUT
1 HOUR NO DAMAGE
I/P: 400 VAC O/P:FULL LOAD
I/P: 550 VAC O/P: Full LOAD Ta:25
O.T.P. Active
Shut down o/p voltage,recovers automatically after temperature goes down
NO DAMAGE
Constant Current Limiting
Model: DRT-240-48 Test Report 2 / 5
P
p
Page 3
240W Three Phase Industrial DIN RAIL Power Supply
DRT-240 series
ENVIRONMENT TEST
NO TEST ITEM SPECICATION TEST CONDITION RESULT VERDICT
1 TEMPERATURE RISE TEST
MODEL DRT-240-24
1. ROOM AMBIENT BURN-IN: 1 HRS I/P: 400 VAC O/P: FULL LOAD Ta=32.4
2. HIGH AMBIENT BURN-IN: 1.5 HRS I/P: 400 VAC O/P: FULL LOAD Ta= 51.1
NO Position P/N
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15
2 OVER LOAD BURN-IN TEST NO DAMAGE
1 HOUR ( MIN )
3 LOW TEMPERATURE
TURN ON TEST
TURN ON AFTER 2 HOUR
D5 BY228GP 1.5KV/5A PH L1 TR-427 L5 TR-428 Q1 2SK2850 6A/900V FUJI Q2 2SK2850 6A/900V FUJI
TSW1
LF2 TR-423 C34
U1 2842 ON ZD2 BZY97C100 100V/1.5W D13 SF5408 3A/1KV TL
T3 TR-426 C17
T1 COIL TF-1069 LS
C53
220U/35V NCC 105 KY
220U/50V NCC KY 105
1500U/35V NIPP 105℃ KY
ST-95
I/P: 400 VAC O/P: 118 ﹪LOAD Ta:25
I/P: 400 VAC O/P: 100 ﹪LOAD Ta= -30
ROOM AMBIENT
Ta= 32.4
63.9 82.2
52.6 71.5
43.2 62.4
62.5 83.3
66.8 88.3
64.2 85.2
54.5 73.8
49.9 68.6
71.2 90.6
45.3 64.4
62.3 81.6
64.0 83.9
58.1 77.4
60.3℃ 79.0℃
48.4
TEST OK
TEST OK
HIGH AMBIENT
Ta= 51.1
P
66.8℃
P
P
4 HIGH HUMIDITY
HIGH TEMPERATURE HIGH VOLTAGE TURN ON TEST
5 TEMPERATURE
COEFFICIENT
6 VIBRATION TEST 1 Carton & 1 Set Operating at I/P: 400 VAC NO LOAD
AFTER 12 HOURS IN CHAMBER ON CONTROL 50 NO DAMAGE
0.03 %(0~50℃)
+
(1) Waveform: Sine Wave (2) Frequency:10~500Hz (3) Sweep Time:10min/sweep cycle (4) Acceleration:2G (5) Test Time:1 hour in each axis (X.Y.Z) (6) T a:25
I/P: 567 VAC O/P:FULL LOAD Ta= 50 HUMIDITY= 95 %R.H I/P: 400 VAC O/P:FULL LOAD
TEST OK
P
+ 0.01 %(0~50)
TEST OK
Model: DRT-240-48 Test Report 3 / 5
P
P
Page 4
240W Three Phase Industrial DIN RAIL Power Supply
DRT-240 series
SAFETY TEST
1 WITHSTAND VOLTAGE I/P-O/P: 3 KVAC/min
I/P-FG: 1.5 KVAC/min O/P-FG: 5 KVAC/min
2 ISOLATION RESISTANCE I/P-O/P:500VDC>100M
I/P-FG: 500VDC>100M O/P-FG:500VDC>100M
3 GROUNDING CONTINUITY FG(PE) TO CHASSIS
OR TRACE < 100 m
4 APPROVAL
TUV: Certificate NO :R50046131 UL: File NO :E183223
E.M.C TEST
1 HARMONIC EN61000-3-2
CLASS A
2 CONDUCTION EN55011
CLASS B
3 RADIATION EN55011
CLASS B
4 E.S.D EN61000-4-2
INDUSTRY AIR:8KV / Contact:4KV
5 E.F.T EN61000-4-4
INDUSTRY INPUT: 2KV
6 SURGE IEC61000-4-5
INDUSTRY L-N :2KV L,N-PE:4KV
I/P-O/P: 3.6 KVAC/min I/P-FG: 1.8 KVAC/min O/P-FG: 0.6 KVAC/min Ta:25
I/P-O/P: 500 VDC
I/P-FG: 500 VDC
O/P-FG: 500 VDC Ta:25
40 A / 2min Ta:25
I/P: 400 VAC/50HZ O/P:FULL LOAD Ta:25
I/P: 400 VAC (50HZ) O/P:FULL/50% LOAD Ta:25
I/P: 400 VAC (50HZ) O/P:FULL LOAD Ta:25
I/P: 400 VAC/50HZ O/P:FULL LOAD Ta:25
I/P: 400 VAC/50HZ O/P:FULL LOAD Ta:25
I/P: 400 VAC/50HZ O/P:FULL LOAD Ta:25
I/P-O/P: 4.13 mA I/P-FG: 2.98 mA O/P-FG: 6.35 mA NO DAMAGE
I/P-O/P: 5 G I/P-FG: 5 G O/P-FG: 4 G NO DAMAGE 16 m
PASS
PASS Test by certified Lab P
PASS Test by certified Lab P
CRITERIA A
CRITERIA A
CRITERIA A
P
P
P
P
P
P
P
P
7
Test by certified Lab Test Report Prepare
Model: DRT-240-48 Test Report 4 / 5
Page 5
240W Three Phase Industrial DIN RAIL Power Supply
DRT-240 series
M.T.B.F & LIFE CYCLE CALCULATION
1 CAPACITOR
LIFE CYCLE
2 MTBF MIL-HDBK-217F NOTICES2 PARTS COUNT
COMPONENT STRESS TEST
1 Power Transistor
( D to S) or (C to E) Peak Voltage
2 Diode Peak Voltage D 54 Rated
3 Input Capacitor Voltage C 5 Rated
4 Control IC Voltage Test U 1 Rated
SUPPOSE C 53 IS THE MOST CRITICAL COMPONENT I/P: 400 VAC O/P:FULL LOAD Ta= 25 LIFE TIME= 1032823 HRS I/P: 400 VAC O/P:FULL LOAD Ta= 50 LIFE TIME= 186385 HRS
TOTAL FAILURE RATE: 114.6K HRS
Q 1 Rated 2SK2850 : 900 V 6 A
PA905C6: 600 V 20 A
HITACH: 150 u / 400 V 105
2842 : 30V
I/P:High-Line +3V = 553 V O/P: (1)Full Load Turn on (2) Full Load (3)Output Short Ta:25
I/P:High-Line +3V = 553 V O/P: (1)Full Load Turn on (2) Full Load (3)Output Short Ta:25
I/P:High-Line +3V = 553 V O/P: (1)Full Load Turn on /Off (2) Min load Turn on /Off
(3)Full Load /Min load Change (4)Burn-IN Hour
Ta:25 I/P:High-Line +3V = 553 V
O/P: (1)Full Load Turn on /Off (2) Min load Turn on /Off
(3)Full Load /Min load Change (4) Output Short
Ta:25
(1) 288 V (2) 800 V (3) 816 V P
(1) 284 V (2) 420 V (3) 464 V
(1) 414 V (2) 412V (3) 392V (4) 392V
(1) 18.9 V (2) 18.9 V (3) 18.9 V (4) 16.5 V
P
P
P
P
P
DATE SAMPLE TEST RESULT TESTER APPROVAL
2004/2/11 RD SAMPLE PASS VINCENT TSENG MAX LIN
2004/5/5
2004/8/30
PRODUCT SAMPLE
A403A03
PRODUCT SAMPLE
A408A02
PASS VINCENT TSENG MAX LIN
PASS VINCENT TSENG MAX LIN
2003/12/12 A50-F023
Model: DRT-240-48 Test Report 5 / 5