MDT Dimming Actuator
MDT Dimming Actuator 2/4-fold, MDRC
Version
AKD-0201.02 Dimming Actuator 2-fold 3TE MDRC, 230VAC, 2 x 250W or 1 x 500W
AKD-0401.02 Dimming Actuator 4-fold 6TE MDRC, 230VAC, 4 x 250W, 1 x 500W + 2 x 250W or 2 x 500W
The MDT Dimming Actuator receives KNX/EIB telegrams and dimms/switches up to 4 independent electrical loads.
Each output can be operated manually via a push button.
The dimming actuator supports the usual loads and is optimized for dimmable LED lamps from 2W. In trailing edge phase
operation mode, universal or ECO lamps up to 200W are supported. Older lamps which can not be operated in trailing
edge operation mode are supported in leading edge operation mode up to 50W.
The connected lamps can be dimmed depending on the time of day. By the automatic dimming the evening operation
with high brightness lightning can be avoided. The brighness can be adjusted individually depending on the time of day
or the position of the sun.
The integrated active power meter records the current consumption per channel and sends the value to the bus.
The diagnostics function calculates the utilization of the channel and sends it in plain text as a 14-byte telegram.
Additionally the dimmer has overload/short circuit and temperature protection with alarm message.
The parallel operation of two channels allows dimming of loads up to 500W (LED lights up to 400W).
The MDT Dimming Actuator is a modular installation device for xed installation in dry rooms. It ts on DIN 35mm rails in
power distribution boards or closed compact boxes.
For project design and commissioning of the MDT Dimming Actuator it is recommended to use the ETS.
Please download the application software at www.mdt.de/Downloads.html
AKD-0401.02AKD-0201.02
• Production in Germany, certied according to ISO 9001
• Comprehensive application
• Optimized for dimmable LED lights > 2W
• For HV- Halogen lights and NV- Halogen lights with transformer/EVG
• Operation in leading-edge or trailing-edge selectable
• Active power measurement
• Integrated diagnostic function with plain text message
• Overload-/short circuit- and temperature protection with message
• Time functions (switch-on/switch-off delay, staircase light function)
• Automatic time dependent dimming
• Softstart, global and individual dimming speed
• Day/Night function
• Parallel operation of 2 channels with 500W total power output
• Push Button for manual operation and indicator for each channel
• Separate L-/N connections for each channel
(different phases possible L1, L2, L3)
• 3 years warranty
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1
Tel.: + 49 - 2263 - 880
Stand: 0319
•
Fax: + 49 - 2263 - 4588 • knx@mdt.de
•
www.mdt.de
DIN EN ISO 9001
TAW Cert
Zert.Nr.1905606

MDT Dimming Actuator
Technical Data AKD-0201.02 AKD-0401.02
Number of outputs 2 4
Supply voltage outputs 230VAC/50Hz 230VAC/50Hz
Max. fuse per channel 10A 10A
Possible load distribution 2 x 250W or 1 x 500W
1 x 500W + 2 x 250W or 2 x 500W
Max. load for each channel
HV halogen lamps 250W 250W
Universal/ECO lamps in
trailing edge phase operation mode*
Old LED lamps in
leading edge phase operation mode*
200W 200W
50W 50W
Wound transformators 200W 200W
Minimum lamp load per channel**
Specication KNX interface
Available application software
2W 2W
TP-256 TP-256
ETS 4/5 ETS 4/5
Permitted wire gauge
Screw terminal
KNX busconnection terminal
1 x (0,5 - 4,0mm²)
2 x (0,5 - 2,5mm²)
0,8mm Ø, solid core 0,8mm Ø, solid core
4 x 250W or
1 x (0,5 - 4,0mm²)
2 x (0,5 - 2,5mm²)
Power supply KNX bus KNX bus
Power consumption KNX bus typ.*** < 0,3W < 0,3W
Power dissipation no load**** < 0,5W < 0,5W
Power dissipation nominal load**** < 4W < 4W
Operation temperature range
Enclosure
Dimensions MDRC (Space Units)
The maximum load and the maximum number of lamps depends on the used lamps. The built-in diagnostics gives an indication of the percentage utilization of the channel.
*
For trailing edge phase operation mode, usually up to 20 LED lamps can be connected.
Minimum load for dimmable LED lamps is 2W, depending on the LED lamp manufacturer. Correct function of the LED lamps has to be checked before installation.
**
Power consumption from KNX Bus **** Power dissipation for each channel
***
Examplary circuit diagram AKD-0401.02 (Operation with 2 different phases)
0 to + 45°C 0 to + 45°C
IP 20 IP 20
3SU 6SU
Important assembly notes:
- Conventionel transformers must be fused on primary
side with adequate fuse according to the size of the
transformator.
- The AC power line has to be connected separately to
each Dimming Actuator. Connecting of several devices
is not allowed.
- The neutral line has to be connected separately to each
channel. Do not bypass directly on the screw terminals.
- Separate L-/N connections for each channel
(different phases possible L1, L2, L3)
Examplary circuit diagram AKD-0401.02 (Parallel operation of 2 channels)