M&C TechGroup LA-1.4 Datasheet

Page 1
LA-1.1, L A-1.4
Embracing Challenge
Electronic controllers series LA®
Version LA-1.1, LA-1.4
Special Features
2 mounting types
Line break supervision
2 potential free change-over contacts
LED’s for displaying operational and
fault status
For max. 100m sensor cable as standard
Switching point adjustable
Application
The LA-1.. electronic controllers serve to feed and distribute the signals of the liquid alarm sensors LA1S and LA25S.
Description
Two mounting types are available, wall­mounting LA1.1 and rail-mounting LA1.4.
A line break supervision is integrated for sure operation.
There are two LEDs for displaying opera­tional and fault status as well as two potential­free changeover contacts with «safety-first» switching action for sure alarm signalling. The electronic controllers are equipped with an alarm reset that may be activated or desacti­vated. During delivery, it is not activated.
By using one of the contacts, a pump or a solenoid valve in the gas conditioning system can be switched directly and the second con­tact can be used as a status alarm.
The switching point of the electronic control­ler LA-1.. is adjustable via a potentiometer. At works, a standard alignment is made.
The special electronic controller ER142 Exi (Part no.: 03E2009/a) without line break super­vision is for the intrinsically safe feeding of the LA 1 and LA 25 sensor (old series!) located in a hazardous area.
Technical specications and illustrations are without obligation, subject to modications. 09.96/11.06
M&C TechGroup Germany GmbH • Rehhecke 79 • 40885 Ratingen • Germany info@mc-techgroup.com • www.mc-techgroup.com • Fon +49 2102 935-0 • Fax +49 2102 935-111
8.2
Page 2
Dimensions
50
80
160
148
Sensor
Ø 4,3
230
115
LNPE
56
12
3
22 21 24 14 11 12
rt
gn
78
P1
210
LA 1.1 in wall mounting housing
LA 1.4 in rail mounting housing
22.8
21 24
22
NC
5 6
7 8
bn. wh.
wh.
bn.
adj.
Sensitivity
Al. Reset
Alarm
OK.
Flüssigkeitsalarm LA1.4
Liquidalarm
1211 14 NC
L/+ N/- PE PE
2 3
1
4
111
Dimensions in mm
Technichal Data
Electronic controllers type LA-1.1 LA-1.4
Part Number 230V 50/60Hz 115V 50/60Hz 24V DC 24V AC
Mounting Wall mounting housing Rail mounting housing EN 50022
Sensor inlets 1
Power consumption 2 VA 1VA
Alarm-relay (2x MC/NC/NO) 250V DC/AC 250V AC/DC
contact rating DC=50W, AC=500VA, 3A DC=45W, AC=500VA, 2A
Cable inlet 1x terminals 3mm - 6,5mm
Electrical connection terminals max. 2,5 mm2
Adjustment of switching point via potentiometer after opening of housing via potentiometer in the housing front
Distance between sensor and electronic LA-1.. max. 100m
Line break supervision yes
Alarm reset** yes
Protection type IP65 EN60529 IP20 EN60529
Housing material Polycarbonate Polyamide PA 6.6 combustibility class VO (UL94)
Ambient temperature -25 °C to +60 °C
Dimensions B 80xL 160xH 55 mm B 22,8 x L 100 x H 111 mm
Weight 0,31 kg 0,23 kg
* Reversible distribution voltage 230V 50Hz / 115V 60Hz, at works adjusted to 230V 50Hz. ** at works desactivated
03 E 2001* 03 E 2001* 03 E 2001 d 03 E 2001 b
2x terminals 5mm - 10mm
03 E 2006 03 E 2006 a 03 E 2006 d 03 E 2006 d
8.2
M&C TechGroup Germany GmbH • Rehhecke 79 • 40885 Ratingen • Germany info@mc-techgroup.com • www.mc-techgroup.com • Fon +49 2102 935-0 • Fax +49 2102 935-111
Technical specications and illustrations are without obligation, subject to modications. 09.96/11.06