M&C TechGroup DIL-1-H Operator's manual

Operating Manual
Gas Dilution Unit
Versions DIL-1, DIL-1/H
Gas sampling and gas conditioning technology 2-1.1.7.6-ME
This Operating Manual does not claim completeness and may be sub­ject to technical modifications. © 11/2005 M&C TechGroup Germany GmbH. Reproduction of this document or its content is not allowed without permission from M&C. 1st Edition: 11/2005
Dear customer,
we have made up this operating manual in such a way that all necessary information about the prod­uct can be found and understood quickly and easily. Should you still have any question, please do not hesitate to contact M&C directly or go through your appointed dealer. Respective contact addresses are to be found in the annexe to this operating man­ual. Please also contact our homepage www.mc-techgroup.com for further information about our prod­ucts. There, you can read or download the data sheets and operating manuals of all M&C products as well as further information in German, English and French.
Gas sampling and gas conditioning technology 2-1.1.7.6-ME
3
Contents
1 General information ...................................................................................................................... 5
2 declaration of conformity ............................................................................................................. 5
3 Safety instructions ....................................................................................................................... 6
4 Warranty ........................................................................................................................................ 6
5 Used terms and signal indications ............................................................................................. 7
6 Introduction ................................................................................................................................... 8
7 Application .................................................................................................................................... 8
7.1 Variations .............................................................................................................................. 10
8 Technical Data ............................................................................................................................ 13
9 Dilution principle ........................................................................................................................ 14
10 Dimensions ................................................................................................................................. 15
11 Receipt and storage ................................................................................................................... 18
12 Installation information .............................................................................................................. 18
13 Installation ................................................................................................................................... 18
13.1 Connection of the supply or sample lines .............................................................................. 18
13.2 Connection of sample gas and heated sample lines ............................................................. 19
13.3 Connection of dilution gas or bypass gas .............................................................................. 20
13.4 Connection of calibration gas ................................................................................................ 20
13.5 Electrical connection ............................................................................................................. 20
14 Initial starting .............................................................................................................................. 22
14.1 Calibration ............................................................................................................................. 24
15 Closing down .............................................................................................................................. 24
16 Maintenance ................................................................................................................................ 25
16.1 Disassembly of the crosspiece .............................................................................................. 26
16.2 Cleaning of the critical orifice and check or change of the O-rings ....................................... 27
16.3 Change and cleaning of the injection nozzle ......................................................................... 28
16.4 Removing the bypass T-piece ............................................................................................... 28
16.5 Change and cleaning of the bypass injection nozzle and control or change of the o-ring .... 28
17 Spare parts list ............................................................................................................................ 29
18 Appendix ..................................................................................................................................... 29
Gas sampling and gas conditioning technology 2-1.1.7.6-ME
List of Illustrations
Figure 1 Dilution unit DIL-1 ............................................................................................................... 8
Figure 2 Dilution unit DIL-1/H ............................................................................................................ 9
Figure 3 Gas flow scheme DIL-1 with possible options .................................................................. 11
Figure 4 Gas flow scheme DIL-1/H with possible options ............................................................... 11
Figure 5 Dilution unit DIL-1/H with control panel –S or -S1 ............................................................. 12
Figure 6 Dilution unit DIL-1/H with set -A or -A1 ............................................................................. 12
Figure 7 Dilution principle ............................................................................................................... 14
Figure 8 Dimensions (mm) dilution units DIL–1.. and control panel –S or –S1 ............................... 17
Figure 9 DIL-1 with control panel -S1.............................................................................................. 17
Figure 10 Electrical connection for DIL-1/H.. .................................................................................... 21
Figure 11 Extract from the injector data sheet .................................................................................. 23
Figure 12 Suction flow at 0,9 or 1bar abs. in dependence on the bypass gas pressure .................. 23
Figure 13 Explosion drawing of the dilution crosspiece .................................................................... 26
Figure 14 Crosspiece with critical orifice and O-ring seals ............................................................... 27
Figure 15 Bypass T-piece with injection nozzle and o-ring ............................................................... 28
Gas sampling and gas conditioning technology 2-1.1.7.6-ME
5
Head Office
M&C TechGroup Germany GmbH Rehhecke 79 40885 Ratingen Germany
Telephone: 02102 / 935 - 0 Fax: 02102 / 935 - 111 E - mail: info@mc-techgroup.com
www.mc-techgroup.com
1 GENERAL INFORMATION
The product described in this operating manual has been examined before delivery and left our works in perfect condition related to safety regulations. In order to keep this condition and to guarantee a safe operation, it is important to heed the notes and prescriptions made in this operating manual. Fur­thermore, attention must be paid to appropriate transportation, correct storage, as well as professional installation and maintenance work. All necessary information a skilled staff will need for appropriate use of this product are given in this operating manual.
2 DECLARATION OF CONFORMITY
CE - Certification
The product described in this operating manual complies with the following EC directives:
EMV-Instruction
The requirements of the EC directive 2004/108/EC “Electromagnetic compatibility“ are met.
Low Voltage Directive
The requirement of the EC directive 2006/95/EC “Low Voltage Directive“ are met. The compliance with this EC directive has been examined according to DIN EN 61010.
Declaration of conformity
The EU Declaration of conformity can be downloaded from the M&C homepage or directly requested from M&C.
Gas sampling and gas conditioning technology 2-1.1.7.6-ME
3 SAFETY INSTRUCTIONS
Please take care of the following basic safety procedures when mounting, starting up or operating this equipment:
Read this operating manual before starting up and use of the equipment. The information and warn­ings given in this operating manual must be heeded.
Any work on electrical equipment is only to be carried out by trained specialists as per the regulations currently in force.
Attention must be paid to the requirements of VDE 0100 (IEC 364) when setting high-power electrical units with nominal voltages of up to 1000 V, together with the associated standards and stipulations.
Check the details on the type plate to ensure that the equipment is connected to the correct mains voltage.
Protection against touching dangerously high electrical voltages: Before opening the equipment, it must be switched off and hold no voltages. This also applies to any external control circuits that are connected.
The device is only to be used within the permitted range of temperatures and pressures. Check that the location is weather-protected. It should not be subject to either direct rain or moisture. The device must not be used in hazardous areas. Installation, maintenance, monitoring and any repairs may only be done by authorized personnel with
respect to the relevant stipulations.
4 WARRANTY
If the equipment fails, please contact M&C directly or else go through your M&C authorised dealer. We offer a one year warranty as of the day of delivery as per our normal terms and conditions of sale, and assuming technically correct operation of the unit. Consumables are hereby excluded. The terms of the warranty cover repair at the factory at no cost or the replacement at no cost of the equipment free ex user location. Reshipments must be send in a sufficient and proper protective packaging.
Gas sampling and gas conditioning technology 2-1.1.7.6-ME
7
DANGER!
This means that death, severe physical injuries and/or important ma­terial damages will occur in case the respective safety measures are not fulfilled.
WAR N ING !
This means that death, severe physical injuries and/or important ma­terial damages may occur in case the respective safety measures are not fulfilled.
CARE!
This means that minor physical injuries may occur in case the re­spective safety measures are not fulfilled.
CAR E!
Without the warning triangle means that a material damage may oc­cur in case the respective safety measures are not met.
ATT ENT I ON !
This means that an unintentional situation or an unintentional status may occur in case the respective note is not respected.
NOTE!
These are important information about the product or parts of the operating manual which require user’s attention.
SKILLED STAFF
These are persons with necessary qualification who are familiar with installation, use and maintenance of the product.
5 USED TERMS AND SIGNAL INDICATIONS
Gas sampling and gas conditioning technology 2-1.1.7.6-ME
Depression manometer*
300
280
Sample gas in*
(non diluted)
Test gas* in
Bypass gas
in*
Option I Bypass out*
(diluted)
205
180
Ø6mm
95
Option II Sample gas out*
(diluted)
Sample gas out** (non diluted)
Dilution gas in*
* Tube connection 6mm ( 1/4“ on request) ** Tube connection 8mm ( 3/8“ on request)
6 INTRODUCTION
The non-heated or electrically heated M&C dilution unit DIL-1 /(H) is used in the analysis technique whereever the measuring method or the handling of the process gas requires a dilution of the sample gas or the components to be measured. Examples are the measurement of extremely toxic gases, the determination of the gas moisture or emission measurement.
The M&C dilution unit is based on the functional dilution technique which is proved since years in the M&C gas sample probe SP2000-H/DIL.
For further information or personal advice, we have pleasure to be at your disposal. Further you may contact our internet pages with our complete product catalogue under:
www.mc-techgroup.com
7 APPLICATION
The following illustrations show versions DIL-1 and DIL-1/H.
Figure 1 Dilution unit DIL-1
Gas sampling and gas conditioning technology 2-1.1.7.6-ME
450
430
300
280
** Connection tube 8x1mm
* Connection tube 6x1mm
Bypass-
gas in*
Sample in*
(non diluted)
Ø 6
Sample out**
(non diluted)
Dilution gas in*
Testgas
in*
Depression-
manometer*
Option I Bypass out*
(undiluted)
Alarm-Kontakt
230V,50Hz
(115V,60Hz)
Temp.-min
Netz
Tsoll
Tu<-30°C
0-180°C
To>+30°C
Reset
PG 13,5
104
Option II Sample out*
(undiluted)
Figure 2 Dilution unit DIL-1/H
9
The M&C dilution units DIL-... are mounted on a plate for wall mounting. The operating temperature of the non heated version DIL-1 is the ambient temperature. Version DIL-1/H is heated up to 180 °C and is equipped with a heat insulated cover (Version for 320 °C on request).
The temperature is regulated by an integrated capillary thermostat, adjustable from 0-180 °C, includ­ing an excess temperature limiter and a low temperature alarm. (Optional: Temperature sensor PT100 or thermocouple “”K” for external temperature controller on request)
The connection of the heated lines is made without cold bridges into the heated part. Before the dilu­tion gas enters the dilution unit, it is heated up to the operating temperature via a gas pre-heater. In order to protect the dilution part against contaminations, internal protective filters are installed for the sample gas and the dilution gas stream.
For calibration of the analyser, test gas can be feeded via the integrated test gas connection. A preci­sion pressure controller with manometer is used for adjustment of the necessary dilution gas admis­sion pressure. Via a vacuum pressure gauge, the function of the dilution injector is controlled. Both, pressure controller and pressure gauge have to be ordered separately. Two versions are available: Set -A (-A1) for direct mounting on the mounting plate and control panel type -S (-S1) for external 19" rack mounting. A shut-off valve and a flowmeter for adjustment of the calibration gas are included in the version –S (-S1).
The dilution unit can realize dilution ratios of 10:1 to 500:1. In case of high dilution ratios, a respective small quantity of gas is sampled from the process. Optionally, a bypass injector –B (Option I) is avail­able in order to shorten the response time in case of operation with atmospheric pressure. The bypass injector is integrated right in front of the dilution unit.
The pressure regulator versions –A / -S include a pressure regulator with manometer for the dilution gas as well as a manometer for control of the depression on the critical orifice. In case of option I, an additional pressure controller with manometer is included in both mounting versions -A1 / -S1. The construction of the dilution unit guarantees easy operation and maintenance being independent from process temperature.
Gas sampling and gas conditioning technology 2-1.1.7.6-ME
7.1 VARIATIONS
The two basic versions DIL-1 and DIL-1/H can be extended by several options. Option I
Includes a bypass for dilution gas with bypass injector for a fast suction of sample gas in order to shorten for example the response time in case of high dilution ratios.
Option II
Includes an additional sample gas outlet „non-diluted“.
Option –A
Includes a pressure regulator with manometer and a manometer for control of the low pressure on the critical orifice. These are mounted directly onto the dilution unit. (see figure 6).
Option –A1
Includes in addition to option -A a pressure regulator with manometer for operating the bypass of op­tion I. This option is also mounted directly onto the dilution unit (see figure 6).
Option –S
Includes the necessary pressure regulator with manometer, shut-off valves and flowmeter, incorpo-
rated externally in a 19“ control panel (see figure 5). The connection of the sampling or the supply
lines to the downstream analysis system have to be executed by the client. Connections which are marked accordingly are available on the back side of the 19“ unit.
Option –S1
Includes in addition to option -S the pressure regulator with manometer for operating the bypass of op­tion I, mounted externally into the 19“ control panel (see figure 5). The connection of the sampling or supply lines to the downstream analyse system has be made by the client. Connections which are marked accordingly are available on the back side of the 19” unit.
The following illustrations show the gas flow of the dilution units DIL-1 and DIL-1/H with all possible options.
Gas sampling and gas conditioning technology 2-1.1.7.6-ME
11
Bypass-out
Test gas
Sample
in
Sample out
Sample out
Undiluted (Option II )
diluted
Dilution gas
-1-0bar
0-6bar
Option I
Bypass
0-6bar
*
**
**
*
**
** Components for version/control panel -A or -S * Additional components for -A or -S for version/control panel -A1 or -S1
Bypass out
180°C
Sample
in
Test gas
Sample out
undiluted (Option II )
Sample out
undiluted
Dilution gas
0-6bar
**
-1-0bar
0-6bar
*
Bypass
**
Option I
**
*
** Components for version/control panel -A or -S * Additional components for -A or -S for version/control panel -A1 or -S1
Figure 3 Gas flow scheme DIL-1 with possible options
Figure 4 Gas flow scheme DIL-1/H with possible options
Gas sampling and gas conditioning technology 2-1.1.7.6-ME
450
430
300
** Connection tube 8x1mm
* Connection tube 6x1mm
Bypass
gas IN*
Sample IN* (undiluted)
Ø
Sample OUT** (undiluted)
Dilution gas IN*
Testgas IN*
Depression manometer*
Option II
Sample out*
(undiluted)
(undiluted)
Bypass out*
Option I
104
Alarm-Kontakt
230V,50Hz
(115V,60Hz)
Temp.-min
3
2
1
L
N
8
6
7
4 5 L
Netz
Tsoll
Tu<-30°C
0-180°C
To>+30°C
Reset
PG 13,5
open
482
132 (3HE)
Option: Bypass
1,0
0,0
6,0
5,0
Bypass-Injector
3,0
2,0
4,0
Steuer panel
Dilution gas
1,0
0,0
6,0
5,0
3,0
2,0
4,0
open
-0,4
0,0
Injector
Depression
-1,0
-0,8
Test gas
-0,6
-0,2
Option
500
480
370
350
Ø 6
Sample in*
(undiluted)
Test gas in*
Sample out**
(diluted)
Option I Bypass out*
(undiluted)
Dilution gas
in*
104
PG 13,5
0-180°C
Tu<-20°C
To>+20°C
Tsoll
Reset
Power 230V 50Hz
115V 60Hz
Alarm contact
Temp.-min
Option II Sample out*
(undiluted)
* Tube connection 6 x 1mm ** Tube connection 8 x 1mm
Figure 5 Dilution unit DIL-1/H with control panel –S or -S1
Figure 6 Dilution unit DIL-1/H with set -A or -A1
Gas sampling and gas conditioning technology 2-1.1.7.6-ME
8 TECHNICAL DATA
Dilution ratios of the critical orifices „a“ to „g“
a b c d e f g
500
200
100
50
30*
20
10:1
Sample flow rate with critical orifices „a“ to „g“
1,4
2,7
5,5
11
19*
28
55l/h1)
Possibility to adapt the dilution factor
With dilution gas pressure adjustment -5% to +30%2)
Dilution gas flow rate with injector version I or II
I: 480 - 600 Nl/h, optional II: 1800 – 3000 Nl/h
Dilution gas pressure on inlet of pressure controller
Min. 4,5 bar, max. 16 bar
Bypass injector /B: pressure / Gas consumption / flow rate
approx. 2 bar : injector gas approx. 300 l/h : sample gas approx. 150 l/h
Process pressure
0,9 to 2 bar abs. at constant pressure
Fault caused by process temperature variations
No fault, operation independent of process tempera­ture
Fault caused by process low or over pressure
Influence negligible at pressure changes 200mbar and if test gas is given to the probe under process conditions. Otherwise proportional to pressure changes.
Fault caused by atmospheric pressure variations
< 1% with a variation of 50 mbar
Material in contact with the sample gas
Stainl. Steel 316Ti, quartz glass, FPM, graphite
Power supply for DIL-1/H
230V 50Hz, (optional 115V 60Hz), 800W
Temperature controller for DIL-1/H
Capillary thermostat adjustable 0-180 °C, with ex­cess temperature limiter and low temperature alarm as changeover contact, potentialfree alarm point T30 °C to T
Set
,
contact rating max. 250V 3A~ 0,25A =
Weight
approx. 8 kg
Type
M&C Dilution unit DIL-1/(H) with orifice „e“, dilution ratio 30:1, Standard
DIL-1
Dilution unit non heated
DIL-1/H(a)
Dilution unit electrically heated to 180°C, (a) = voltage 115V 60Hz
Option I
Bypass injector –B
Option II
Additional sample gas outlet undiluted
DIL-1/..-A
Option: mounting set for dilution unit, 1 pressure controller and 2 manometers
DIL-1/..-A1
Option: mounting set for dilution unit/Bypass injector, 2 pressure controllers and 3 manometers
DIL-1/..-S
Option: control panel with 1 pressure controller, 2 manometers, flowmeter, 2 shut-off valves
DIL-1/..-S1
Option: control panel with 2 pressure controller, 3 manometers, flowmeter, 2 shut-off valves
13
* Standard, others to be indicated along with order, intermediate values possible.
1)
approx at 3 bar dilution gas.
2)
-5%, however not possible with orifice „g“.
Gas sampling and gas conditioning technology 2-1.1.7.6-ME
Orifice type
a b c d e f g
Dilution ratio*
500:1
200:1
100:1
50:1
30:1
20:1
10:1
Volume flow through the orifice [Nl/h]
1,4
2,7
5,5
11
19
28
55
9 DILUTION PRINCIPLE
The functional principle of the dilution unit is based on ultrasonic flow through a critical orifice (see Fig.
4). The flow through the orifice is constant when the differential pressure via the orifice is higher than 500 mbar. For the atmospheric inlet pressure (Pin = 1020 mbar), this means a pressure at the orifice outlet (Pout) of less than 520 mbar absolute. The necessary vacuum at the orifice outlet is produced by an injector operated with dilution gas.
Depending on the critical orifice selected, dilution rates can be between 10:1 and 500:1. The table be­low gives an overview of the dilution factor and sample gas volume using the injector I (480 – 600 Nl/h):
* with Injector II 50:1 to 2000:1
Figure 7 Dilution principle
How to check the dilution ratios and the exact adjustment of the pressure conditions are described in chapter 14.1.
Gas sampling and gas conditioning technology 2-1.1.7.6-ME
15
300
280
205
180
95
Ø 6
450
430
250
230
Ø6
155
95
10 DIMENSIONS
The following illustration shows the dimensions of the dilution units DIL-1 and DIL-1/H. DIL-1:
DIL-1 with /A or /A1:
Gas sampling and gas conditioning technology 2-1.1.7.6-ME
DIL-1/H:
450
430
300
280
Ø 6
Tsoll
Tu<-30°C
0-180°C
To>+30°C
Reset
PG 13,5
104
500
480
350
Ø 6
104
PG 13,5
0-180?C
Tu<-30°C
To>+30°C
Tsoll
Reset
DIL-1/H with /A or /A1 :
Gas sampling and gas conditioning technology 2-1.1.7.6-ME
Option control panel –S or -S1:
Auf
Open
482 (84TE)
132 (3HE)
Option: Bypass
1,0
0,0
6,0
5,0
Bypass-Injector Beipass-Injektor
3,0
2,0
4,0
Steuerpanel
Dilution gas
Verdünnungsgas
1,0
0,0
6,0
5,0
3,0
2,0
4,0
Auf
Open
-0,4
0,0
Injektor-Unterdruck
Injector-vacuum
-1,0
-0,8
Test gas
Prüfgas
-0,6
-0,2
Back pressure max. 1,2 bar abs.
Sample gas IN
17
Figure 8 Dimensions (mm) dilution units DIL–1.. and control panel –S or –S1
Figure 9 DIL-1 with control panel -S1
Gas sampling and gas conditioning technology 2-1.1.7.6-ME
NOTE!
The dilution unit should be stored in a protected, frost-free room!
NOTE!
The dilution unit must be checked for its suitability for use with the available operating parameters prior to installation (see type plate).
NOTE!
Increases of pressure due to use of long sample gas lines at the outlet may have a great influence on the measuring result. For this reason, we recom­mend the following nominal widths and lengths for the sample lines in de­pendence on the type of injector: Injector type I:
i
6mm max. 50m
i
8mm max. 150m
Injector type II:
i
8mm max. 15m
i
10mm max. 40m
i
12mm max. 80m
11 RECEIPT AND STORAGE
Carefully remove the dilution unit and any accessories from the transport packaging immediately af-
ter receipt and check the completeness of the delivery against the packing list.
Check the goods for possible transport damages and, if necessary, notify immediately your trans-
port insurer of any damage.
12 INSTALLATION INFORMATION
The safety rules and regulations for the prevention of accidents must be observed during installation and also subsequent operation. The information in chapter 3 “Important Safety Information“ must be observed.
The following also applies: Select the optimal sampling point according to the generally applicable directives or coordinate
with the responsible departments.
13 INSTALLATION
The M&C dilution units DIL-1... are designed for stationary use. With correct selection of the sample point and proper installation, they will work for many years with a minimum of maintenance required.
13.1 CONNECTION OF THE SUPPLY OR SAMPLE LINES
Gas sampling and gas conditioning technology 2-1.1.7.6-ME
19
Connection
Dimension
Sample In (undiluted)
Tube 6 x 1mm
Testgas in
Tube 6 x 1mm
Dilution gas In
Tube 6 x 1mm
Low pressure manometer
Tube 6 x 1mm
Sample gas Out (diluted)
Tube 8 x 1mm
Option I:
Bypass gas In
Tube 6 x 1mm
Bypass gas Out (diluted)
Tube 6 x 1mm
Option II:
Sample gas Out (undiluted)
Tube 6 x 1mm
NOTE!
When connecting hose pipes to stainl. Steel fittings, a supporting sleeve must always be used.
The connection must be checked for tightness.
The connections for the supply and sample lines are as follows:
13.2 CONNECTION OF SAMPLE GAS AND HEATED SAMPLE LINES
All connections for the sample gas or heated sample lines are tube connectors out of stainl. steel suit­able for connection of stainl. steel tubes or hose pipes with dimension 6x1mm. Only the outlet of the diluted sample gas is dimensioned for stainl. steel tube or flexible tube of 8x1mm.
The connection to the non heated versions DIL-1 is made directly to the respective fittings (see figure
1). The connection of the heated sample lines to the heated versions DIL-1/H is shown in figure 2.
Remove the protective cover  Open the fastening clamp  Mount the hose pipe or tube to the respective fittings  Shut the fastening clamp again  Install the protective cover again.
Gas sampling and gas conditioning technology 2-1.1.7.6-ME
WAR N ING !
The incorrect mains voltage can destroy the unit. Check the type plate for the correct voltage prior to connection!
The dilution units must be mounted in such a way that touching the live parts is excluded!
In any case, we recommend the use of temperature resistant ca­bles!
The alarm contact for low temperature must be controlled! In case of a low temperature alarm (failure of heating or sensor) the
dilution gas or bypass gas supply must be interrupted to avoid se­rious damage of the dilution unit. We recommend to switch the low temperature alarm onto external solenoid valves that provide the above mentioned function!
13.3 CONNECTION OF DILUTION GAS OR BYPASS GAS
For connection of the supply lines, tube connectors with dimension 6 x 1mm are available. mm zur Verfügung. The connection fittings of the heated dilution units are located outside the cover and can be connected without disassembly. Only when using the heated versions and option I, a heated “undluted” sample line is connected to the bypass outlet. Please act as follows:
Remove protective cover  Open the fastening clamp  Mount the hose pipe or tube to the respective fitting  Shut the fastening clamp again  Install the protective cover again.
When using option –A (only dilution gas) or –A1 (dilution and bypass gas), the supply lines are con­nected to the connection fittings of the precision pressure regulator.
When using the 19“ control panels –S or S1, corresponding connectors for the supply gases are pro- vided at the rear of the unit.
13.4 CONNECTION OF CALIBRATION GAS
For all versions of DIL-1 and DIL-1/H, a tube connector 6 x 1 mm is available for connection of the calibration gas (see figure 4).
13.5 ELECTRICAL CONNECTION
The temperature setting on the dilution unit DIL-1/H is made on the internal capillary thermostate.
Gas sampling and gas conditioning technology 2-1.1.7.6-ME
21
NOTE!
For the erection of power installations with nominal voltages of up to 1000V, the requirements of VDE 0100 and its associated stan­dards and specifications must be observed. A main switch must be provided externally.
The supply circuit of the unit must be equipped with a fuse with the correct rating (over current protection); the electrical details see technical data.
Mains 230V 50Hz or 115V 60Hz
Alarm outlet
1
2
1
2
+30
-30
800 W
WAR N ING !
We recommend the use of temperature resistent cables!
Remove cover of the connection box.  Insert the mains cable (min. 3 x 1,5 mm2) through the cable gland and connect to the appropriate
terminals.
Insert the signal cable (low temperature alarm) through the cable gland and connect to the appro-
priate terminals (contact position Tu shows alarm event).
Screw cover back in place.
Figure 10 Electrical connection for DIL-1/H..
Gas sampling and gas conditioning technology 2-1.1.7.6-ME
WAR N ING !
The supply of gas to the injectors is only allowed when the heated dilution unit has reached its operating temperature (see technical data).
Prior to initial use, make sure that the mains voltage corresponds to the voltage indicated on the type plate!
Do not touch the surface of the heated dilution unit during opera­tion. Due tp its high surface temperatures, it may cause burns. Pro­tective gloves must be worn and the dilution unit must be protected against unauthorised access!
NOTE!
If the set temperature on the capillary controller should be reduced by more than 30°C in one step, the excess temperature cut-off on the thermostat is activated (for re-starting press the reset button).
NOTE!
The total heating time is about 2 hours. After about 1 hour, the lower threshold value ( 30°C below set value) is exceeded.
NOTE!
For safety reasons, the low pressure gauge must show a low pres­sure of >-0,6 bar. With a low pressure of < -0, 6 bar, the critical ori­fice will not function properly. If the necessary low pressure will not be reached, the dilution gas supply pressure must be in­creased.
14 INITIAL STARTING
Prior to initial use, system and process-specific safety measures must be observed. The relevant safety requirements and procedures for the medium to be sampled must be heeded.
The following step-by-step procedure is recommended:
If possible, separate the dilution unit from the sample point, eg. above the ball valve.  In case of heated versions, check the set temperature on the installed thermostat.
For heated versions, switch on the mains voltage.
Open the valve for the dilution gas (for heated version: wait until the complete dilution unit is
heated, approx. 2 h). Set the precision pressure reducer to the pressure specified on the enclosed injector data sheet (see figure 9).
The following table shows an extract from the injector data sheet.
Gas sampling and gas conditioning technology 2-1.1.7.6-ME
23
Injektortyp
I
Injektor-Nr.
689
Für Verdünnungs­system-Nr.
8652/222835
Typ
DIL-1/H-A1
Injector type
Injector No.
For dilution system No.
Type
Betriebsdruck
Operating pres-
sure [bar]
Durchfluss
Flow
[l/h]
Unterdruck ohne kritische Düse
Vacuum without critical orifice
[bar]
Unterdruck mit kritischer Düse Vacuum with critical orifice 5,1l/h [bar]
2,4
415
-0,62
-0,61
2,6
435
-0,65
-0,64
2,8
460
-0,68
-0,67
3,0
490
-0,80
-0,77
3,2
510
-0,79
-0,77
3,4
535
-0,79
-0,77
3,6
560
-0,78
-0,76
3,8
585
-0,77
-0,76
4,0
605
-0,77
-0,75
Überprüfung des Verdünnungsfaktors Check of the dilution ratio
Messgasdruck atmosphärisch Sample gas pressure atmospheric
Kritische Düse Critical nozzle
Verd.gas Dilution gas
Verdünnungsgasdruck Dilution gas pressure
Messgas Sample
Verdünnung Dilution
Messwert d. verd. Gases Meas. value of the dil. gas
5,1 l/h
100% N2
3,2 bar
100% O2
100:1
1,0 % O2
NOTE!
The attached bypass injector table shows the suction flows at cor­responding bypass gas pressures for two different process pres­sures, 1 bar and 0,9 bar absolute (see figure 12).
Bypassgas / Bypass gas
Prozessgas / Sample gas
Betriebsdruck
Operating pressure
[bar]
Durchfluss
Flow
[l/h]
Ansaugvolumenstrom bei 1bar abs.
Suction flow at 1bar abs.
[l/h]
Ansaugvolumenstrom bei 0,9bar
abs.
Suction flow at 0,9bar abs. [l/h]
0,5
110
45
-
1,0
155
115
-
1,5
190
200
65
2,0
235
250
135
2,5
270
300
200
3,0
310
350
250
3,5
355
370
270
4,0
395
390
305
4,5
430
425
350
WAR N ING !
In the event of low temperature (failure of the heating) the supply of dilution gas must be interrupted!
Figure 11 Extract from the injector data sheet
For the operation of an installed bypass injector, the necessary pressure must be set on the pres-
sure regulator (see figure 12).
Figure 12 Suction flow at 0,9 or 1bar abs. in dependence on the bypass gas pressure
Gas sampling and gas conditioning technology 2-1.1.7.6-ME
WAR N ING !
The gas pressure must be above 0,7 bar, because the pressure control valve installed has an opening pressure of 0, 7 bar. When using the control panel, the respective ball valve for the test gas supply must be opened and the flow rate be set on the flow-
meter.
14.1 CALIBRATION
A calibration of the downstream analyser system or checking the dilution factor must always be ef­fected under operation conditions.
Above the test gas valve, an appropriate test gas can be feeded.
The procedure for calibration or checking the dilution ratio is as follows:
Supply test gas of a concentration you know.  Check the dilution ratio on the downstream analyser and, if necessary, correct the pressure on the
pressure regulator of the dilution gas.
Test gas feeding without bypass injector
In order to assure that sufficient test gas is available, the test gas quantity should be at least threefold of the flow quantity passing through the critical orifice (see injector data sheet).
Test gas feeding with bypass injector
The test gas quantity must be approximately 10% above the quantity of the volume flow passing though the bypass (see figure 12) and the critical orifice (see figure 11).
15 CLOSING DOWN
Prior to closing down, the heated dilution unit should be purged with inert gas or air to prevent the condensation of agressive components from the process gas.
Gas sampling and gas conditioning technology 2-1.1.7.6-ME
25
WAR N ING !
Agressive condensate possible. Wear safety glasses and appropri­ate protective clothing!
Do not touch the surface of the dilution unit during operation as this can cause burns due to the high surface temperatures. Wear protective gloves. The dilution unit must be protected against un­authorized access!
Before carrying out maintenance work on electrical components, the mains voltage must be disconnected in all poles. This also ap­plies to any connected alarm and control circuits !
NOTE!
The dilution unit does not need to be removed for repair or mainte­nance.
16 MAINTENANCE
Prior to any maintenance of repairing works, system and process specific safety measures must be observed.
No recommendation for maintenance intervals can be given. Maintenance intervals must be deter­mined depending on the particular process conditions and specific application.
The maintenance of the dilution unit is limited mainly to the cleaning of the filter elements, inspection of the seals and maintenance of the dilution systems.
Gas sampling and gas conditioning technology 2-1.1.7.6-ME
WAR N ING !
Nut 2 must only be removed after having disassembled the dilution cross. Disregard may lead to destruction of the critical orifice!
16.1 DISASSEMBLY OF THE CROSSPIECE
For disassembling of the crosspiece, the heating of the heated dilution unit should be switched off so that the unit can cool down.
Figure 13 shows the explosion drawing of the dilution crosspiece.
Figure 13 Explosion drawing of the dilution crosspiece
We recommend to proceed according to the following steps:
Remove the insulation cover of the dilution unit, if applicable;  Remove all tube connectors on the dilution crosspiece. These are:  - Depression manometer nut 6  - Dilution gas inlet nut 4  - Sample gas outlet nut 5  - Removal of nut 1.
Now, the dilution crosspiece is accessible for further maintenance and repair work.
Gas sampling and gas conditioning technology 2-1.1.7.6-ME
27
WAR N ING !
Do not clean the critical orifice mechanically. Cleaning should be effected in an ultrasonic bath !
WAR N ING !
The Swagelok® fittings must be carefully tightened to avoid damage of the internal components. Do not tighten the fittings too fast. If a fitting is believed to be leaking, do not tighten further. Disas­semble the fitting completely and tighten it again.
8
16.2 CLEANING OF THE CRITICAL ORIFICE AND CHECK OR CHANGE OF THE O­RINGS
Figure 13 shows the position of the orifice in the crosspiece and the O-ring seals.
Figure 14 Crosspiece with critical orifice and O-ring seals
Please proceed as follows:  Loosen union nut 3 and remove the jet pipe;  Loosen nut 2 and remove the pipe piece with both nuts;  Push the injection nozzle out of the jet pipe side by using the mounting tools (item 8, figure 14);  Push the critical orifice with its nozzle seat and o-ring carefully from the back side of the cross-
piece by using the mounting tool (item 8, figure 14);
Check the o-rings and change them if necessary;  Push the new orifice or the cleaned old one into the o-rings until block.  Now, the dilution unit can be reassembled in reverse order.
Gas sampling and gas conditioning technology 2-1.1.7.6-ME
NOTE!
For cleaning the injector, it is not necessary to remove the nozzle out of the crosspiece. The nozzle can be cleaned together with the complete cross­piece in an ultrasonic bath.
Injection nozzle
O-ring
Bypass T-piece
Jet pipe
Nut 2
Nut 1
Nut 3
Sample gas
Dilution gas
16.3 CHANGE AND CLEANING OF THE INJECTION NOZZLE
For changing the injector nozzle, see figure 14:
Loosen nut 3 and remove jet pipe;  Push the injection nozzle out of the jet pipe side by using the mounting tools (item 8, figure 14);  Check the o-ring and change it if necessary;  Push the new nozzle with o-ring until blocking.
16.4 REMOVING THE BYPASS T-PIECE
For cleaning or changing the bypass injector, the bypass T-piece can be completely disassembled. The following figure shows the bypass T-piece.
Figure 15 Bypass T-piece with injection nozzle and o-ring
Dismantle the T-piece as follows:
Romove insulation cover if applicable;  Remove all tube connectors on the bypass-T. These are: (see figure 15):  - Bypass inlet union nut 1  - Union nut 2 (jet pipe side)  - Union nut 3 (sample inlet).  The bypass-T is now ready for further maintenance and repair.
16.5 CHANGE AND CLEANING OF THE BYPASS INJECTION NOZZLE AND CON­TROL OR CHANGE OF THE O-RING
Push the injection nozzle out of the jet pipe side by using the mounting tools (item 8, figure 14);  Check the o-ring and change if necessary;  Push in the new or cleaned old nozzle with o-ring until blocking.
Gas sampling and gas conditioning technology 2-1.1.7.6-ME
29
NOTE!
For cleaning the injection nozzle, you need not necessarily pull the nozzle out of the T-piece. The nozzle can be cleaned together with the complete T­piece in an ultrasonic bath.
If you blow through the nozzle, this must be done from the jet pipe side.
Recommended spare parts
Part No.
Description
20 S 4300
Complete set critical orifice incl. 2x o-rings. Material: glass # Please specify dilution ra­tio along with order. #
93 S 4000
Injection nozzle incl. o-ring (crosspiece)
93 S 4006
Dilution crosspiece empty, without any inserts, material: SS316
93 S 4016
Bypass T-piece empty, without any inserts, material: SS316
93 S 4020
Crosspiece complete. # Please specify dilution ration along with order #
93 S 4025
Bypass T-piece complete
90 S 4035
Suction tube for DIL 6x1mm with integrated filter sieve incl. Swagelok® nuts, silver­plate cutting ring for dilution crosspiece, material SS316
93 S 0010
Spare thermostate 0-180°C
93 S 0015
Spare heating cartridge HLP, 230V 800W
93 S 0017
Spare heating cartridge HLP, 115V 800W
93 S 0018
Heat conductivity paste for insertion of heating cartridge
93 S 4015
Eductor incl. O-ring for bypass-T-piece
17 SPARE PARTS LIST
The wear, tear and spare part requirements depend on the specific operating conditions. The following table shows an extract of the recommended spare parts for the diluiton units DIL-1 and
DIL-1/H :
18 APPENDIX
Further documentation of our products can be seen in our internet catalogue:
www.mc-techgroup.com
Gas sampling and gas conditioning technology 2-1.1.7.6-ME
Loading...