Our commitment is to provide practical solutions for the industries needs and to be both a leader and partner in the
effective use of microprocessor controls.
Heatpump Water-Air/Water-Water Heatpump/Chillers MCS-8 Version 7 Manual Revision 4.0
2
1 Revision Page
Date Author Description of Changes
9/4/97 Kelly Mitchell Draft
5/1/98 Kelly Mitchell Updated manual for release version 1.0
5/12/98 R C Toney Update for Empire State Bldg. changes version1.1
7/15/98 R C Toney Minor corrections to the v1.1, control state summary and flow
diagram of the heat pump was added, changed to version 1.2
10/21/98
J G Walterick V7 update to generic, SI8/16, rearrange setpoints, new setpoints
8/28/00
02/02/01
02/02/01
07/15/02
7/28/03
09/10/04
09/24/04
Brian Walterick Revisions to make manuals for both heatpumps and chillers-
Labeled the manual Revision 2.0
Brian Walterick Updated manual for Modulating Hot Water Valve Heating Control
Brian Walterick Updated manual for Modulating Economizer Valve Control
R C Toney Updated manual reflects the new set points required for control
zone control. Cutin/cutout no longer supported. Software FHP
07.00-S and greater support changes. Manual labeled as Revision
2.2
SAK Updating Manual
RCT Communicating thermostat and all of its functions are now
supported in HPMP 7.00-U and greater software. The reheat
function has been separated from the heat function. PC-Config 32
bit version 1.69 or greater is required to support these new
functions.
RCT Added a modulating reheat function. PC-Config 32 bit version
1.70or greater is required to support these new functions.
Page 3
Heatpump Water-Air/Water-Water Heatpump/Chillers MCS-8 Version 7 Manual Revision 4.0
2 Table of Contents .................................................................................................................................3
3 Introduction to the MCS-8 Heatpump / Chiller Controller..................................................................6
3.1 The MCS-8 Micro Controller:.....................................................................................................6
3.2 The MCS-8 will control the following items:.............................................................................7
3.3 Control will be based upon the following:..................................................................................7
4 Introduction to Control Modes and States............................................................................................8
4.1 CONTROL MODES...................................................................................................................8
4.1.1 FAN/PUMP ONLY MODE..................................................................................................................................8
5.1.1 Wiring from the MCS-8.....................................................................................................................................12
5.1.2 Temperature sensor.........................................................................................................................................12
5.1.6 Fan switch.........................................................................................................................................................14
20 The MCS Trouble Shooting Quick Reference Sheet .........................................................................41
21 Summary of Control States ................................................................................................................43
Page 6
Heatpump Water-Air/Water-Water Heatpump/Chillers MCS-8 Version 7 Manual Revision 4.0
6
3 Introduction to the MCS-8 Heatpump / Chiller Controller
3.1 The MCS-8 Micro Controller:
The MCS-8 micro controller is designed to be the primary controller for a heatpump / chiller package. The MCS-8
control algorithm provides the ultimate in control strategies by enabling:
• The user to custom the controlling sensors in each of the four different modes,
• Establish targets and control zones that can be modified after a package has been commissioned,
• Eliminate service calls by:
• Take corrective action to prevent an alarm condition from occurring, and
• Automatically restarting a package following an alarm condition and not locking the package off
unless the same alarm has occurred twice with in a settable time period.
• Provide an easy to understand man-machine-interface by:
• Indicating the state of the system in English terms and
• Identifying in English terms all alarms and date/time stamping them.
The system design is modular and allows for one, two, three or four compressors. This is accomplished by coupling an
MCS-8 with either MCS I/O, RO-8 or SI-8 or SI-16 boards that provides the additional inputs that is required.
The system provides for:
• Optional economy stage for heating and or cooling,
• Complete dehumidification control and
• Standard heating and cooling control.
The user may select to have a single low pressure and a single high-pressure alarm input or specify individual low
pressure and individual high-pressure alarms by compressor. The user may also have digital low pressure and highpressure inputs or analog inputs. (Analog inputs provide actual suction and discharge pressure.)
The Windows based PC-Config program supports the flexibility of the control algorithm. The following is an example of
a water / air package using return air for the decisions in the fan / pump and dehumidification modes while using the
supply air input for decisions in the cooling and heating modes.
Page 7
Heatpump Water-Air/Water-Water Heatpump/Chillers MCS-8 Version 7 Manual Revision 4.0
7
The following is an example of a package using zone air for all decisions. The zone temperature and humidity input can
be provided by MCS-STAT, communicating thermostat.
For additional flexibility the MCS-STAT is now supported with this software. This enables communication via the MCSSTAT to be provided in the zone area.
3.2 The MCS-8 will control the following items:
• Blower motor(s) or pumps, (on/off plus speed control)
• Ball valve that directs flow through the economizer coil,
• Heatpump / chiller reversing valve(s),
• Compressors (up to 4),
• Hot gas reheat,
• Electric heating,
• Modulating reheat,
• Hot water heating and
• Alarm indicator.
3.3 Control will be based upon the following:
• Internal time clock that is battery backed up;
• Internal set points that can be adjusted with the proper authorization in a commissioned unit;
• Condenser water in & condenser water out;
• Return, Supply, Zone or Ambient air temperature;
• Return, Supply, Zone or Ambient air humidity;
• Run enable switch (digital input from the building management system), Network Run enable, or Run
enable from a MCS-STAT, communicating thermostat;
• System schedule override from the MCS-STAT, this is based upon the time in setpoint #20 when the
override button on the MCS-STAT is pushed and the system is not in an alarm mode.
• A series of safety indicators (some will require manual intervention while others will result in an automatic
restart when the condition is corrected).
Page 8
Heatpump Water-Air/Water-Water Heatpump/Chillers MCS-8 Version 7 Manual Revision 4.0
8
4 Introduction to Control Modes and States
4.1 CONTROL MODES
The Control Mode dictates the general status of the unit and which Control States can be entered. There are four
modes and each mode has a unique control sensor and set points that are associated with that mode.
4.1.1 FAN/PUMP ONLY MODE
The FAN/PUMP ONLY STATE indicates this mode. It is in this mode that the system determines if any of the
other three modes should be entered. The other three modes; cooling, heating or dehumidification; will be
entered based upon set points 1 through 3: COOL ENABLE, HEAT ENABLE AND DEHD ENABLE.
Once the system is in one of the other three modes, its requirements must be satisfied and control returned to
the fan/pump only mode before any of the other modes can be entered.
In the example shown, the Return Air Sensor is the controlling sensor in this mode. If the Return Air is greater
than the cooling set point, the system will enter the Cooling Mode.
4.1.2 COOLING MODE
Once in this mode the system will develop a control-cooling zone based upon set points 4, 5 & 6. The system
will move through the cooling states to maintain the temperature within this control zone. Once the cooling
target has been satisfied, the system will return to the FAN/PUMP ONLY MODE.
In the example shown, the Supply Air Sensor is the controlling sensor in this mode. The system will step up
and down through all of the cooling states based upon the supply air temperature. Once the supply air cool
temperature target has been satisfied, the system will return to the FAN/PUMP ONLY MODE.
•Control
Control Zone +
Ta rget
Control Zone-
Page 9
Heatpump Water-Air/Water-Water Heatpump/Chillers MCS-8 Version 7 Manual Revision 4.0
9
4.1.3 HEATING MODE
Once in this mode the system will develop a control-heating zone based upon set points 10, 11 & 12. The
system will move through the heating states to maintain the temperature within this control zone. Once the
heating target has been satisfied, the system will return to the FAN/PUMP ONLY MODE.
The system will support three different types of heating:
1. Reversing Valve. The reversing valve will be turned on when in the heating mode and the
compressors will be staged on/off to maintain the temperature within the control-heating zone.
2. Hot Water Valve. The hot water valve will be modulated when in the heating mode to maintain the
temperature within the control-heating zone. Set points 46 through 54 will control the modulation of the valve.
3. Electric Heat. The relay output for the electric heat will be turned on when the control temperature is
below the control-heating zone. There can be only one stage of electric heat.
In the example shown, the Supply Air Sensor is the controlling sensor in this mode. The system will step up
and down through all of the heating states based upon the supply air temperature. Once the supply air heat
temperature target has been satisfied, the system will return to the FAN/PUMP ONLY MODE.
4.1.4 DEHUMIDIFICATION MODE
Once in this mode the system will develop a control dehumidification zone based upon set points 16, 17 & 18.
The control air will be cooled and reheated to dry out the air. The system will move through the
dehumidification states to maintain the humidity within this control zone. Once the humidity target has been
satisfied, the system will turn off the reheat and either return to the FAN/PUMP ONLY MODE if the control
temperature does not require cooling or to the first stage of cooling.
The reheat function is now specified independently from the heat options, refer to the section on reheat.
The Heat Type is Electric Heat, its associated RO is EL HEAT and the Reheat Type is Hot Gas its
associated RO is HGreheat.
In this mode the system is also checking to ensure that air temperature remains in the range created by the
values contained in set points #40,ALLOW DEHUMD, and #41, DISALW DHDIFF. If the temperature is not
with in this range, the system will immediately return to the FAN/PUMP ONLY MODE for further action. Note
the temperature sensor that is being checked is specified as the controlling sensor in the FAN/PUMP ONLY
MODE.
The set points values that are associated with each mode must be set based upon the control sensor that is used with
each mode.
4.2 CONTROL STATES
The MCS-8 controller is a state computer, that is, decisions are made based upon set points, timers and sensor inputs,
the controller moves from one state to another. The controller will change states to ensure the proper functioning of the
heatpump / chiller package.
Control States perform the following:
Page 10
Heatpump Water-Air/Water-Water Heatpump/Chillers MCS-8 Version 7 Manual Revision 4.0
0
• Provides an easy to understand status of the system. For example, HEATPUMP OFF state indicates that
the system is off or the COOL: 1 COMP states indicates that the system is in the cooling mode and that
compressor 1 is on and providing cooling.
• Dictates, which relays (RO’S) will be on in a given state.
• Indicates how long the system has been in the current state.
• The system moves from one state to another in a fixed sequence with fixed rules.
This strategy is based upon providing target set points for heating, cooling and dehumidification. The system then
controls the heatpump / chiller capacity to maintain the target temperature. Set points that contain differential values are
used to calculate a control zone and the system will determine if more or less cooling, heating or dehumidification
capacity is needed to remain in this control zone.
The control states are divided into the following two groups:
• HEAT PUMP / CHILLER CONTROL STATES, these states deal with the status of the heat pump / chiller
system. They will indicate if the system is running and what action is being taken.
• ECONOMIZER CONTROL STATES, these states deal with the status of the economizer valve.
Control states, on the MCS-8, are displayed on the 2x16 LCD by depressing the SERVICE DIAGNOSTICS entry key
and then selecting the option CONTROL STATUS. (Depress the enter key.) The up and down arrow may then used to
scroll between the information screens. The control states can also be accessed via the PC-Conn program by selecting
‘STATUS’ from the button bar on the ‘SYS INF’ screen.
4.3 CONTROL STATUS DISPLAY (from the MCS-8 keypad)
The following will be displayed:
The FIRST SCREEN will display the HEAT PUMP / CHILLER CONTROL STATE and the time in that state.
Line 1)
Line 2) (time HH:MM:SS)
The SECOND SCREEN will display by selecting with either the INCREASE or DECREASE key. This screen will
display the ECONOMIZER CONTROL STATE and the time in that state.
Line 1)
Line 2) (time HH:MM:SS)
COOL: 2 COMPS
TIMER 1:26:06
ECON COOLING
TIMER 1:28:06
4.4 CONTROL STATUS DISPLAY (from the PC-Conn Program)
The status of both the HEAT PUMP / CHILLER STATES and ECONOMIZER STATES can also be viewed from the
PC-Conn program by accessing the STATUS button; in the lower right section of the status screen. The following will
be displayed:
1
Page 11
Heatpump Water-Air/Water-Water Heatpump/Chillers MCS-8 Version 7 Manual Revision 4.0
11
Page 12
Heatpump Water-Air/Water-Water Heatpump/Chillers MCS-8 Version 7 Manual Revision 4.0
2
5 MCS-STAT Support
One MCS-STAT is support in this software. It must be associated with the zone options.
5.1.1 Wiring from the MCS-8.
Communications between the MCS-8 and the communicating thermostat is provided via a four wire shielded
cable. This will provide the power and the RS485 communications. Two wires provide communications by
connecting the MCS I/O connector to the MCS-STAT. Make sure that the + terminal on the MCS-8 is
connected to the + on the MCS-STAT. The MCS-STAT requires 12 volts, this can be provided by connecting
the other two wires to the +12 volt and ground terminals on the MCS-8 and the MCS-STAT.
5.1.2 Temperature sensor.
• This is a temperature sensor with accuracy of ± 0.1°F between 32°F and 99°F; it will provide the zone
temperature.
• This sensor display type must be STAT1F in the SI Info screen for the PC-Config.
• If used this must be in selected in the HT Pmp Info screen as the zone temperature.
5.1.3 Humidity sensor
• This is a humidity sensor with accuracy of ± 0.2% between 0% and 100%; it will provide the zone humidity.
• This sensor display type must be STAT1% in the SI Info screen for the PC-Config.
• If used this must be in selected in the HT Pmp Info screen as the zone humidity.
5.1.4 LCD Display
• If the indicator is pointing to:
Actual: either the temperature which will be followed by an °F, e.g. 73.4°F, or the humidity, e.g. 45.7, will
be displayed. Either the up or down arrows will toggle between these two values.
Cool: The value of setpoint #4, COOL TARGET, will be displayed. This value can be changed with the up
and down arrows within the minimum and maximum range that is set for this setpoint. When the SET
button is pressed the new value will be transmitted to the MCS-8.
Heat: The value of setpoint #10, HEAT TARGET, will be displayed. This value can be changed with the up
and down arrows within the minimum and maximum range that is set for this setpoint. When the SET
button is pressed the new value will be transmitted to the MCS-8.
• If a alarm is active, an alarm number will be displayed on the MCS-STAT to indicate the alarm reason.
5.1.5 LCD Alarms
ALARM NAME DESCRIPTION # Displayed
INVALID CFG The configuration of the MCS-8 is
INVALID CLOCK The hardware clock on the MCS-
LOST MCS I/O An MCS I/O board is not
MCS I/O OFF LINE An MCS I/O board has gone off
EVAP OVRFLW1 An overflow on evaporator #1
1
invalid or wrong type. The system
will not run.
2
8 has failed. Processing will
continue using the software
clock.
3
communicating.
4
line.
5
has occurred. Refer to setpoint
#30.
1
Page 13
Heatpump Water-Air/Water-Water Heatpump/Chillers MCS-8 Version 7 Manual Revision 4.0
3
EVAP OVRFLW2 An overflow on evaporator #2
6
has occurred. Refer to setpoint
#31.
DIG SAFETY A safety error condition has been
7
indicated. Refer to setpoint #32.
NO FLOW A no flow error condition has
8
been indicated. Refer to setpoint
#33.
COND FREEZE A condenser freeze condition has
9
been indicated. Refer to setpoint
#34.
EVAP FREEZE A evaporator freeze condition has
10
been indicated. Refer to setpoint
#35.
NOT USED 11
DIG LOCKOUT A lockout error condition has
12
been indicated. Refer to setpoint
#37.
NO AIR FLOW Air flow has been lost. Refer to
13
setpoint #38.
HI DISC PSI #1 A high pressure on compressor 1
14
has occurred. Refer to setpoint
#39
HI DISC PSI #2 A high pressure on compressor 2
15
has occurred. Refer to setpoint
#39
HI DISC PSI #3 A high pressure on compressor 3
16
has occurred. Refer to setpoint
#39
HI DISC PSI #4 A high pressure on compressor 4
17
has occurred. Refer to setpoint
#39
LOW SUCT PSI #1 A low pressure on compressor 1
18
has occurred. Refer to setpoint
#36
LOW SUCT PSI #2 A low pressure on compressor 2
19
has occurred. Refer to setpoint
#36
LOW SUCT PSI #3 A low pressure on compressor 3
20
has occurred. Refer to setpoint
#36
LOW SUCT PSI #4 A low pressure on compressor 4
21
has occurred. Refer to setpoint
#36
SENSOR FAILURE RTN TEMP The specified return temperature
22
sensor has failed.
SENSOR FAILURE RTN HUMID The specified return humidity
23
sensor has failed.
SENSOR FAILURE WATER OUT The specified water out sensor
24
has failed.
SENSOR FAILURE WATER IN The specified water in sensor has
25
failed.
SENSOR FAILURE COMP1 Either the high or low pressure
26
sensor for compressor 1 has
failed.
1
Page 14
Heatpump Water-Air/Water-Water Heatpump/Chillers MCS-8 Version 7 Manual Revision 4.0
4
SENSOR FAILURE COMP2 Either the high or low pressure
SENSOR FAILURE COMP3 Either the high or low pressure
SENSOR FAILURE COMP4 Either the high or low pressure
NOT USED 30
NOT USED 31
5.1.6 Fan switch
• The fan switch indicates if the fan is to be on continuously, ON position or AUTO the system will control the
fan status.
• If used this sensor display type must be STAT1FN in the SI Info screen for the PC-Config.
5.1.7 Off/AUTO/SCHEDULED switch
• This switch indicates if the unit is in an off, auto or schedule mode.
OFF: will force the system to be off. This is in affect another run/stop switch to the MCS-8.
AUTO: will override the operating schedule making it always true.
SCHD: will allow the system to follow the operating schedule that is setup in the MCS-8.
• This sensor display type must be STAT1SY in the SI Info screen for the PC-Config.
27
sensor for compressor 2 has
failed.
28
sensor for compressor 3 has
failed.
29
sensor for compressor 4 has
failed.
5.1.8 Override button
• The override button performs the following functions:
If an alarm has occurred, the MCS-STAT horn will be on and the alarm light will be flashing.
- The first time that the button is pushed, the horn will be turned off but the alarm light will remain flashing.
- The second time that the button is pushed, the alarm light go off and a lockout reset message will be
transmitted to the MCS-8. This will perform the same action as if the lockout reset button on the MCS-8
was pushed.
If the system has no active alarms and the override button is pushed and the MCS-8 has the system off
due to the schedule being false; the schedule will be overridden for the time specified in setpoint #20. The
system will be enabled to run for this amount of time.
1
Page 15
Heatpump Water-Air/Water-Water Heatpump/Chillers MCS-8 Version 7 Manual Revision 4.0
5
6 Heatpump / Chiller Control States:
The MCS-8 control algorithm will move from one state to another based upon set points, timers and sensor inputs. The
states and set points are defined in this document. The sophisticated control algorithm allows the controller to decide on
the number of heating, cooling or dehumidification stages based on one sensor while FAN/PUMP ONLY stage can be
controlled based on the same or a different sensor. (For instance: In the fan/pump mode the decision to cool, heat or
dehumidify could be based on return air while in the control of cooling and or heating modes the decision could be
based on supply air.) Refer to the section on CONTROL MODE. The system will develop cooling, heating and
dehumidification control zones and move through the various states to maintain the control air temperature or humidity
within those control zones.
5.1 BASE STATES
At startup the system will be in off state and when temperature and humidity conditions have been satisfied the system
will be in fan/pump only state.
6.1.1 ‘HEATPUMP OFF’ state-
When the system is powered up it will delay going into the normal operating mode based on the ‘STARTUP DLY’ set
point.
This state will also be entered if the RUN/STOP or NETWORK RUN/STOP switch is set to STOP or the MCS-STAT
system switch is set to OFF. Or if the RUN/STOP or NETWORK RUN/STOP switch is set to RUN and the MCS-STAT
system switch is set to SCHD and the operating schedule is false.
Once the startup delay time has expired the system and the system is enabled to run, the next state, FAN/PUMP
ONLY state, will be entered.
6.1.2 ‘FAN/PUMP ONLY’ state- (FAN/PUMP ONLY Control Mode)
When the system exits the HEATPUMP OFF state it will enter the FAN/PUMP ONLY state if either the operating
schedule is true or the RUN/STOP input is in run mode. (The RUN/STOP input is from a user input, usually the building
management system.) From this state the decision is made to go to heating, cooling, dehumidification or stay in the
‘FAN/PUMP ONLY’ state based on its controlling sensor. Examples of the set points for the ‘FAN/PUMP ONLY’ state
are shown below. These are based on using return air as the controlling sensor.
‘FAN/PUMP ONLY’ state –
Set Point # 1 ‘COOL ENABLE’ 75.0F
Set Point # 2 ‘HEAT ENABLE’ 68.0F
Set Point # 3 ‘DEHD ENABLE’ 55.0%
6.2 COOLING’ states – (COOLING Control Mode)
These states are entered from the ‘FAN/PUMP ONLY’ state. Examples of the set points for the COOLING state are
shown below, based on using supply air as the controlling sensor.
Cooling mode –
Set Point # 4 ‘COOL TARGET’ 50.0F
Set Point # 5 ‘COOL ZONE+’ 5.0F
Set Point # 6 ‘COOL ZONE- ’ - 5.0F
A cooling zone will be developed based upon the COOL TARGET and the COOL ZONE+ and the
COOL ZONE- set points. The system will add or remove cooling stages as needed to maintain the
temperature within the control cooling zone.
1
Page 16
Heatpump Water-Air/Water-Water Heatpump/Chillers MCS-8 Version 7 Manual Revision 4.0
6
6.2.1 ECONO COOLING
This state is the economize mode and it will be entered if the controlling air temperature rises above the COOL
TARGET set point and the water temperature is below the COOL’G WATER set point. The valve that directs the water
flow will remain open in all cooling states as long as the water temperature is below the COOL’G WATER set point. The
ECONOMIZER STATES indicate the status of this valve. In this state:
• The blower motor(s) is on.
• The valve that directs the water flow is open if the entering water is below the cold-water set point.
This state will be exited and the FAN ONLY state will be entered once the controlling air temperature has been
satisfied. If additional cooling is required, the system will move to the COMPRESSOR 1 COOLING stage. The system
will remain in the ECONO COOLING state for a minimum time as specified in the STEP DELAY set point unless the
water temperature is too warm to provide cooling, the system will immediately move to the COMP1 COOLING state.
6.2.2 COOL: 1 COMP
This state is the first stage of mechanical cooling and it will be entered if the controlling air temperature rises above this
stage’s set point. In this state:
• The blower motor(s) is on.
• The valve that directs the water flow is open if the water temperature is below the cool water set point.
• The reversing valve is on (cool state).
• Compressor one is turned on.
Once the controlling air temperature has been satisfied the ECONO COOLING state will be entered. If additional
cooling is required the system will move to COOL: 2 COMP. The system will remain in the COOL: 1 COMP state for a
minimum time as specified in the STEP DELAY set point.
6.2.3 COOL: 2 COMPS
This state is the second stage of mechanical cooling and it will be entered if an additional stage of cooling is needed to
keep the controlling air temperature within the control cool zone. In this state:
• The blower motor(s) is on.
• The valve that directs the water flow is open if the water temperature is below the cool water set point.
• The reversing valve is on (cool state).
• Compressor one is turned on.
• Compressor two is turned on.
Once the controlling air temperature has been satisfied the COOL: 1 COMP state will be entered. If additional cooling is
required the system will move to COOL: 3 COMP. The system will remain in the COOL: 2 COMP state for a minimum
time as specified in the STEP DELAY set point.
6.2.4 COOL: 3 COMPS
This state is the third stage of mechanical cooling and it will be entered if an additional stage of cooling is needed to
keep the controlling air temperature within the control cool zone. In this state:
• The blower motor(s) is on.
• The valve that directs the water flow is open if the water temperature is below the cool water set point.
• The reversing valve is on (cool state).
• Compressor one is turned on.
• Compressor two is turned on.
• Compressor three is turned on.
1
Page 17
Heatpump Water-Air/Water-Water Heatpump/Chillers MCS-8 Version 7 Manual Revision 4.0
7
Once the controlling air temperature has been satisfied the COOL: 2 COMP state will be entered. If additional cooling is
required the system will move to COOL: 4 COMP. The system will remain in the COOL: 3 COMP state for a minimum
time as specified in the STEP DELAY set point.
6.2.5 COOL: 4 COMPS
This state is the fourth stage and final stage of mechanical cooling and it will be entered if an additional stage of cooling
is needed to keep the controlling air temperature within the control cool zone. In this state:
• The blower motor(s) is on.
• The valve that directs the water flow is open if the water temperature is below the cool water set point.
• The reversing valve is on (cool state).
• Compressor one is turned on.
• Compressor two is turned on.
• Compressor three is turned on.
• Compressor four is turned on.
Once the controlling air temperature has been satisfied the COOL: 3 COMP state will be entered. The system will
remain in the COOL: 4 COMP state for a minimum time as specified in the STEP DELAY set point.
6.3 HEATING’ states - (HEATING Control Mode)
These states are entered from the ‘FAN/PUMP ONLY’ state. Examples of the set points for the HEATING state
are shown below based on using supply air as the controlling sensor.
Heating mode –
Set Point # 10 ‘HEAT TARGET’ 70.0F
Set Point # 11 ‘HEAT ZONE+’ 1.0F
Set Point # 12 ‘HEAT ZONE-‘ -1.0F
A heating zone will be developed based upon the HEAT TARGET and the HEAT ZONE+ and
the HEAT ZONE- set points. The system will add or remove heating stages if type of heating is
reversing valve or if hot water the system will modulate the valve as needed to maintain the
temperature within the control heating zone. If the heating type is electric, the system will turn
on the electric heat relay when the temperature is below the control heating zone.
6.3.1 ECON HEATING
This state is the economize heating and it will be entered if the controlling air temperature falls below this stage’s
set point and the water temperature is above the HEAT’G WATER set point. The valve that directs the water
flow will remain open in all heating states as long as the water temperature is above the HEAT’G WATER set
point. The ECONOMIZER STATES indicate the status of this valve. In this state:
• The blower motor(s) is on.
• The valve that directs the water flow is open, if the entering water is above the heating water set
point.
Economize heating is if available will be utilized by all three types of heating.
This state will be exited and the fan/pump only mode will be entered once the air temperature has been
satisfied. The system will remain in the ECONO HEATING state for a minimum time as specified in the STEP
DELAY set point unless the water temperature is too cool to provide heating and the controlling air temperature
is calling for additional heating.
1
Page 18
Heatpump Water-Air/Water-Water Heatpump/Chillers MCS-8 Version 7 Manual Revision 4.0
8
6.4 HEATING’ states - (type of heat is REVERSING VALVE)
When the type of heat utilizes the reversing valve, the system will stage the compressors to maintain the control
temperature with in the control heat zone.
6.4.1 HEAT: 1 COMP (type of heat is REVERSING VALVE)
This state is the first stage of mechanical heating and it will be entered if the controlling air temperature falls
below this stage’s set point. In this state:
• The blower motor(s) is on.
• The valve that directs the water flow is open if the water temperature is above the heating water set
point.
• The reversing valve is off (heat state).
• Compressor one is turned on.
Once the controlling air temperature has been satisfied the system will move to the ECONO HEATING mode. If
additional heating is required, the system will move to the HEAT: 2 COMPS state. The system will remain in the
HEAT: 1 COMP state for a minimum time as specified in the STEP DELAY set point.
6.4.2 HEAT: 2 COMPS (type of heat is REVERSING VALVE)
This state is the second stage of mechanical heating and it will be entered if an additional stage of heating is
needed to keep the controlling air temperature within the control heat zone. In this state:
• The blower motor(s) is on.
• The valve that directs the water flow is open if the water temperature is above the heating water set
point.
• The reversing valve is off (heat state).
• Compressor one is turned on.
• Compressor two is turned on.
Once the controlling air temperature has been satisfied the system will move to the HEAT: 1 COMP mode. If
additional heating is required, the system will move to the HEAT: 1 COMPS state. The system will remain in the
HEAT: 2 COMPS state for a minimum time as specified in the STEP DELAY set point.
6.4.3 HEAT: 3 COMPS (type of heat is REVERSING VALVE)
This state is the third stage of mechanical heating and it will be entered if an additional stage of heating is
needed to keep the controlling air temperature within the control heat zone. In this state:
• The blower motor(s) is on.
• The valve that directs the water flow is open if the water temperature is above the heating water set
point.
• The reversing valve is off (heat state).
• Compressor one is turned on.
• Compressor two is turned on.
• Compressor three is turned on.
Once the controlling air temperature has been satisfied the system will move to the COMP2 HEATING mode. If
additional heating is required, the system will move to the COMP4 HEATING state. The system will remain in
the COMP3 HEATING state for a minimum time as specified in the STEP DELAY set point.
1
Page 19
Heatpump Water-Air/Water-Water Heatpump/Chillers MCS-8 Version 7 Manual Revision 4.0
9
6.4.4 HEAT: 4 COMPS (type of heat is REVERSING VALVE)
This state is the fourth and final stage of mechanical heating and it will be entered if an additional stage of
heating is needed to keep the controlling air temperature within the control heat zone. In this state:
• The blower motor(s) is on.
• The valve that directs the water flow is open if the water temperature is above the heating water set
point.
• The reversing valve is off (heat state).
• Compressor one is turned on.
• Compressor two is turned on.
• Compressor three is turned on.
• Compressor four is turned on.
Once the controlling air temperature has been satisfied the system will move to the HEAT: 3 COMPS mode.
The system will remain in the HEAT: 4 COMPS state for a minimum time as specified in the STEP DELAY set
point.
6.5 HEATING’ states - (type of heat is HOT WATER VALVE)
When the type of heat utilizes hot water, the system will modulate the hot water valve to maintain the control
temperature with in the control heat zone. The system determines if the control temperature is within, above or
below the control zone and the control temperatures rate of change. Based upon this information the system
determines if the hot water valve should be modulated and by what percentage. Refer to set points 46 through
54.
6.5.1 HEAT-HOLDING (type of heat is HOT WATER VALVE)
No change will be made to the hot water valve opening. The control temperature is being maintained.
6.5.2 HEAT-CLOSING (type of heat is HOT WATER VALVE)
The system will reduce the valve’s opening percentage. The control temperature is above the control zone and
the control temperature is not falling faster than allowed, based upon set point 53, HW MAX ROC-. If the valve
is completely closed, the system will move the to the FAN/PUMP ONLY state.
6.5.3 HEAT-OPENING (type of heat is HOT WATER VALVE)
The system will increase the valve’s opening percentage. The control temperature is below the control zone and
the control temperature is not increasing at a fast enough rate. The amount that the valve will be opened by will
be calculated based upon where the temperature is in relationship to the heat target.
6.5.4 HEAT-SLOPE CL (type of heat is HOT WATER VALVE)
The system will reduce the valve’s opening percentage. The control temperature is moving toward the heat
target too fast. If the control temperature is within the control zone, the valve percentage open will be reduced by
the value in set point 48, HW MIN ADJ%. If the temperature is outside of the control zone, the amount that the
valve will be closed by will be calculated based upon where the temperature is in relationship to the heat target.
6.5.5 HEAT-SLOPE OP (type of heat is HOT WATER VALVE)
The system will increase the valve’s opening percentage. The control temperature is moving is not moving
toward the heat target. If the control temperature is within the control zone, the valve percentage open will be
increased by the value in set point 48, HW MIN ADJ%. If the temperature is outside of the control zone, the
amount that the valve will be opened by will be calculated based upon where the temperature is in relationship
to the heat target.
1
Page 20
Heatpump Water-Air/Water-Water Heatpump/Chillers MCS-8 Version 7 Manual Revision 4.0
0
6.6 HEATING’ states - (type of heat is ELECTRIC HEAT)
If type of heating is electric, this is only one stage of heating. It is either on if heat is required or off.
6.6.1 ELECTRIC HEAT (type of heat is ELECTRIC HEAT)
The system will turn on the electric heat when the control temperature is below the control heat zone. The
electric heat will remain on until the control temperature is above the control heat zone.
6.7 DEHUMID states – (DEHUMIDIFICATION Control Mode)
These states are entered from the ‘FAN/PUMP ONLY’ state. Examples of the set points for the DEHUMID state
are shown below based on using return air as the controlling sensor.
Dehumidification mode –
Set Point # 16 ‘DEHD TARGET’ 55.0%
Set Point # 17 ‘DEHUM ZONE+’ 5.0%
Set Point # 18 ‘DEHUM ZONE- ‘ -5.0%
A dehumidification zone will be developed based upon the DEHD TARGET and the DEHUM
ZONE+ and the DEHUM ZONE- set points. The system will add or remove dehumidification
stages as needed to maintain the humidity within the control dehumidification zone.
REFER TO THE REHEAT OPTIONS SECTION.
Note: The ECONO COOLING is enabled during dehumidification if the water temperature is below the ECON
CL ON set point #28. The valve that directs the water flow will remain open in all dehumidification stages as long
as the water temperature remains below this set point
6.7.1 DEHUM: 1 COMP
This state can only be entered if the system is in the FAN/PUMP ONLY state. This state is entered when the
controlling air humidity (usually return or zone humidity) rises
controlling air temperature is below the allow dehumidification set point. If the controlling air temperature is
above the cooling setpoint the system will enter COOLING. (COOLING has priority since we want to take out moisture but don’t want the reheat on.) In this state:
• The blower motor(s) is on.
• The valve that directs the water flow is open if the water temperature is below the cool water set
point.
• The reversing valve is on (cool state).
• Compressor one is turned on.
• Enable reheat.
above the control dehumidification zone and the
When the controlling air humidity drops below the control dehumidification zone or the controlling air
temperature is above the disallow dehumidification set point calculation, the system will return to the
FAN/PUMP ONLY state. The system will remain in the DEHUM: 1 COMP state for a minimum time as specified
in the STEP DELAY set point unless the controlling air temperature is above the disallow dehumidification set
point calculation.
2
Page 21
Heatpump Water-Air/Water-Water Heatpump/Chillers MCS-8 Version 7 Manual Revision 4.0
6.7.2 DEHUM: 2 COMPS
This state is the second stage of mechanical dehumidification and it will be entered if an additional stage of
dehumidification is needed to keep the controlling air humidity within the control dehumidification zone. In this
state:
• The blower motor(s) is on.
• The valve that directs the water flow is open if the water temperature is below the cool water set
point.
• The reversing valve is on (cool state).
• Compressor one is turned on.
• Enable reheat.
• Compressor two is turned on.
If the controlling air temperature is above the disallowed dehumidification set point calculation, the system will
immediately return to the FAN/PUMP ONLY state. If the system determines that this stage is no longer needed
to keep the humidity within the control dehumidification zone, Compressor two will be turned off and the system
will return to the DEHUM: 1 COMP state. The system will remain in the DEHUM: 2 COMP state for a minimum
time as specified in the STEP DELAY set point unless the controlling air temperature is above the disallow
dehumidification set point calculation.
6.7.3 DEHUM: 3 COMPS
This state is the third stage of mechanical dehumidification and it will be entered if an additional stage of
dehumidification is needed to keep the controlling air humidity within the control dehumidification zone. In this
state:
• The blower motor(s) is on.
• The valve that directs the water flow is open if the water temperature is below the cool water set
point.
• The reversing valve is on (cool state).
• Compressor one is turned on.
• Enable reheat.
• Compressor two is turned on.
• Compressor three is turned on.
If the controlling air temperature is above the disallowed dehumidification set point calculation, the system will
immediately return to the FAN ONLY state. If the system determines that this stage is no longer needed to keep
the humidity within the control dehumidification zone, Compressor three will be turned off and the system will
return to the DEHUM: 2 COMP state. The system will remain in the DEHUM: 3 COMP state for a minimum time
as specified in the STEP DELAY set point unless the controlling air temperature is above the disallow
dehumidification set point calculation.
6.7.4 DEHUM: 4 COMPS
This state is the fourth and last stage of mechanical dehumidification and it will be entered if an additional stage
of dehumidification is needed to keep the controlling air humidity within the control dehumidification zone. In this
state:
• The blower motor(s) is on.
• The valve that directs the water flow is open if the water temperature is below the cool water set
point.
• The reversing valve is on (cool state).
• Compressor one is turned on.
• Enable reheat.
• Compressor two is turned on.
• Compressor three is turned on.
21
Page 22
Heatpump Water-Air/Water-Water Heatpump/Chillers MCS-8 Version 7 Manual Revision 4.0
2
• Compressor four is turned on.
If the system determines that this stage is no longer needed to keep the humidity within the control
dehumidification zone, Compressor four will be turned off and the system will return to the DEHUM: 3 COMP
state. The system will remain in the DEHUM: 4 COMP state for a minimum time as specified in the STEP
DELAY set point unless the controlling air temperature is above the disallow dehumidification set point
calculation.
2
Page 23
Heatpump Water-Air/Water-Water Heatpump/Chillers MCS-8 Version 7 Manual Revision 4.0
3
7 Reheat Options
The system will support the following types of reheat. They are specified in the PC-Config program
when the configuration file is built.
7.1 None
No reheat is available.
7.2 Hot Gas Reheat
If the system is in one of the dehumidification states, and the hot gas reheat option has been selected; the relay
that is specified in Reheat Valve cell in the Compressor Information section of PC-Config will be turned on.
7.3 Modulating Reheat only in dehumidification states
If the system is in one of the dehumidification states, and the modulating reheat option has been selected the
system will perform the following function.
The analog output that has been specified will be set to its minimum value, setpoint #13.
A control reheat temperature zone will be developed based upon the reheat target, setpoint #7, and a high and
low limit, setpoints #8 and #9.
Based upon the reheat control sensor as specified, the analog output will be modulated to open, temperature is
below the zone, or close, temperature is above the zone, the valve to maintain the temperature within this zone.
If the temperature is below this zone, the valve will be opened based upon the difference between the target
and the actual temperature. Multiplying the difference by setpoint #15 and dividing by setpoint #19 will adjust
this difference. Thus a difference of 4.0F will be adjusted to a 2.0% increase in the valve opening if setpoint #15
equals 1 and #19 equals 2. If no adjustment is to be made; setpoints #15 and #19 must be set to 1. The
minimum that the valve can be changed is limited by setpoint #57, maximum change and setpoint #58.
If the control temperature is within the reheat temperature zone no change to the valve setting will be made.
The time delay between making decisions to change the valve setting is the value in setpoint #59.
7.4 Electric Reheat
If the system is in one of the dehumidification states, and the electric reheat option has been selected; the relay
that is specified in Reheat Valve cell in the Compressor Information section of PC-Config will be turned on.
7.5 Modulating Reheat in all states except HEATPUMP OFF or lock off states
If the system is not in an off or lockout state, the fan will be on, and this modulating reheat option has been
selected the system will perform the following function.
The analog output that has been specified will be set to its minimum value, setpoint #13.
A control reheat temperature zone will be developed based upon the reheat target, setpoint #7, and a high and
low limit, setpoints #8 and #9.
2
Page 24
Heatpump Water-Air/Water-Water Heatpump/Chillers MCS-8 Version 7 Manual Revision 4.0
4
Based upon the reheat control sensor as specified, the analog output will be modulated to open, temperature is
below the zone, or close, temperature is above the zone, the valve to maintain the temperature within this zone.
If the temperature is below this zone, the valve will be opened based upon the difference between the target
and the actual temperature. Multiplying the difference by setpoint #15 and dividing by setpoint #19 will adjust
this difference. Thus a difference of 4.0F will be adjusted to a 2.0% increase in the valve opening if setpoint #15
equals 1 and #19 equals 2. If no adjustment is to be made; setpoints #15 and #19 must be set to 1. The
minimum that the valve can be changed is limited by setpoint #57, maximum change and setpoint #58.
If the control temperature is within the reheat temperature zone no change to the valve setting will be made.
The time delay between making decisions to change the valve setting is the value in setpoint #59.
This option allows additional heating in any of the active states of the unit.
2
Page 25
Heatpump Water-Air/Water-Water Heatpump/Chillers MCS-8 Version 7 Manual Revision 4.0
5
8 MCS-8 States for Hea tpump / Chiller Faults
8.1 LOCKOUT FAULT
This state is entered whenever a critical situation is encountered that could cause harm to the heat pump /
chiller system. Items such as high or low pressure on any compressor, no airflow, high or low entering or leaving
water, etc will force the system into this state. Lockouts can be reset without authorization from the keypad.
They can also be reset via the PC-connection program, but the user must be authorized. However if the lockout
condition has not been corrected, the system will again be forced into the LOCKOUT state. In this state, all
RO’s except the ALARM RO are set to LOCKOFF, and an alarm message is generated.
LOCKOUT Reset, is required for the system to leave this state. When a LOCKOUT Reset has been initialized,
the system will move to the HEATPUMP OFF state unless there is another lockout condition. There is no
minimum time for this state.
8.2 SAFETY FAULT
This state is entered whenever a critical situation is encountered that could cause harm to the heat pump /
chiller system. Items such as low or high pressure cause a safety fault on the first occurrence. If the same fault
occurs on the same compressor within one hour that compressor is placed in the LOCKOFF state. Other items
such as no water flow, a sensor input SAFETY being on, or a freeze condition will force the system into this
state. In this state, all RO’s except the ALARM RO are turned OFF and an alarm message is generated. The
system will remain in this state for time specified in STEP DELAY set point. After this time, if the condition that
causes the safety fault to occur is no longer present, the system will automatically move to the HEATPUMP
OFF state.
specified in the STEP DELAY set point. Note, if the safety set point is a LOCKOUT type, the system will lock
out.
Note, no manual intervention is required. The system will remain in this state for a minimum time as
Manual intervention,
8.3 SENSOR FAULT
This state will be entered if one of the sensor inputs that are critical to the control algorithms fails.
The following sensors will be checked:
• ENT WTR sensor, temperatures of the input water.
• RETURN T sensor, temperature of the return air. This is checked only if the control algorithm is
based upon the return air.
• RETURN H sensor, humidity of the return air. This is checked only if the control algorithm is using
the humidity control option.
• SUPPLY T sensor, temperature of the supply air. This is checked only if the control algorithm is
based upon the supply air.
In this state an alarm message will be generated indicating which sensor failed and the alarm point will be
turned on and all other points will be turned off.
Manual intervention, LOCKOUT Reset, is required for the system to leave this state. When a LOCKOUT Reset
has been initialized, the system will move to the HEATPUMP OFF state unless there is another lockout
condition. There is no minimum time for this state.
2
Page 26
Heatpump Water-Air/Water-Water Heatpump/Chillers MCS-8 Version 7 Manual Revision 4.0
6
9 ECONOMIZER STATES
The economizer states indicate the status of the economizer. The economizer can be active in various states.
9.1 BYPASSED-COOL
The economizer valve is off because the water temperature is above the value in set point COOL’G WATER.
The heat pump / chiller state is either ECONO COOLING, COOL: 1 COMP, COOL: 2 COMPS, COOL: 3
COMPS, COOL: 4 COMP, DEHUM: 1 COMP, DEHUM: 2 COMPS, DEHUM: 3 COMPS OR DEHUM: 4
COMPS.
7.2 BYPASSED-HEAT
The economizer valve is off because the water temperature is below the value in set point HEAT’G WATER.
The heatpump / chiller state is ECONO HEATING, HEAT: 1 COMP, HEAT: 2 COMPS, HEAT: 3 COMPS or
HEAT: 4 COMPS.
7.3 ECONO OFF
The economizer valve is off. The heatpump / chiller state is either HEATPUMP OFF, FAN ONLY or a fault state.
9.4 ECONO COOL ON
The economizer valve is on because the water temperature is below the value in set point COOL’G WATER.
The heatpump / chiller state is either ECON COOLING, COOL: 1 COMP, COOL: 2 COMPS, COOL: 3 COMPS,
COOL: 4 COMP, DEHUM: 1 COMP, DEHUM: 2 COMPS, DEHUM: 3 COMPS OR DEHUM: 4 COMPS.
9.5 ECONO HEAT ON
The economizer valve is on because the water temperature is above the value in set point HEAT’G WATER.
The heatpump / chiller state is either ECON HEATING, HEAT: 1 COMP, HEAT: 2 COMPS, HEAT: 3 COMPS
or HEAT: 4 COMPS.
9.6 NOT USED
This indicates that economizer is not available on this unit.
2
Page 27
Heatpump Water-Air/Water-Water Heatpump/Chillers MCS-8 Version 7 Manual Revision 4.0
7
10 SET POINTS AND DEFINITIONS:
# Name Description
****
1 COOL ENABLE This set point contains an actual temperature value. Then the system is in the
2 HEAT ENABLE This set point contains an actual temperature value. Then the system is in the
3 DEHD ENABLE This set point contains an actual humidity value. Then the system is in the
****
4 COOL TARGET This set point is used as the base for developing the cooling control zone. Set
5 COOL ZONE+ This set point contains a differential value. It is added to set point #4 to create
6 COOL ZONE- This set point contains a differential value. It is added to set point #4 to create
****
SET POINTS USED TO CONTROL WHEN THE VARIOUS
MODES CAN BE ENTERED FROM THE FAN/PUMP ONLY
STATE.
FAN/PUMP ONLY state, the system will enter the cooling mode if the
controlling air temperature is greater than this value.
FAN/PUMP ONLY state, the system will enter the heating mode if the
controlling air temperature is less than this value.
FAN/PUMP ONLY state, the system will enter the dehumidification mode if the
controlling air humidity is greater than this value. Note cooling takes priority over dehumidification.
SET POINTS USED TO CREATE THE CONTROL COOLING
ZONE.
point #5 is added to the value of this set point to create the upper limit of the
control zone and set point #6 is added from the value of this set point to create
the lower limit of the control zone.
the upper limit of the cooling control zone.
the lower limit of the cooling control zone. This value must be negative.
SET POINTS REQUIRED WITH MODULATING REHEAT.
7 REHT TARGET This set point is used as the base for developing the reheating control zone;
this is used if the modulating reheat option has been selected. Set point #8 is
added to the value of this set point to create the upper limit of the control zone
and set point #9 is added to the value of this set point to create the lower limit
of the control zone.
8 REHT ZONE+ This set point contains a differential value; this is used if the modulating reheat
option has been selected. It is added to set point #4 to create the upper limit of
the cooling control zone.
9 REHT ZONE- This set point contains a differential value; this is used if the modulating reheat
option has been selected. It is added to set point #4 to create the upper limit of
the cooling control zone. This value must be negative.
****
SET POINTS USED TO CREATE THE CONTROL HEATING
ZONE.
10 HEAT TARGET This set point is used as the base for developing the cooling control zone. Set
point #11 is added to the value of this set point to create the upper limit of the
control zone and set point #12 is added from the value of this set point to
create the lower limit of the control zone.
11 HEAT ZONE+ This set point contains a differential value. It is added to set point #10 to create
the upper limit of the heating control zone.
12 HEAT ZONE- This set point contains a differential value. It is added to set point #10 to create
the lower limit of the heating control zone. This value must be negative.
****
SET POINTS REQUIRED WITH MODULATING REHEAT.
2
Page 28
Heatpump Water-Air/Water-Water Heatpump/Chillers MCS-8 Version 7 Manual Revision 4.0
8
# Name Description
13 REHT MINopen This set point is required if the modulating reheat option has been selected. It
contains minimum percentage that the reheat valve will be opened. Normally
set to 0.
14 REHT MINopen This set point is required if the modulating reheat option has been selected. It
contains maximum percentage that the reheat valve will be opened. Normally
set to 100.0.
15 REHT ADJ MUL This set point is required if the modulating reheat option has been selected.
This set point contains a value that is used to adjust the changes to the reheat
valve. The adjustment is first calculated by taking the absolute value of the
difference between the control temperature and the reheat target. This
adjustment is then fine tuned by multiplying by this set point and then dividing
by set point 19.
****
SETPOINTS USED TO CREATE THE CONTROL
DEHUMIDICATION ZONE.
16 DEHD TARGET This set point is used as the base for developing the dehumidification control
zone. Set point #17 is added to the value of this set point to create the upper
limit of the control zone and set point #18 is subtracted from the value of this
set point to create the lower limit of the control zone.
17 DEHUM ZONE+ This set point contains a differential value. It is added to set point #16 to create
the upper limit of the dehumidification control zone.
18 DEHUM ZONE- This set point contains a differential value. It is subtracted from set point #16 to
create the lower limit of the dehumidification control zone.
19 REHT ADJ DIV Refer to set point 15.
****
TIMING SET POINTS.
20 OverrideTime Time expressed in minutes that when the MCS-STAT over ride button is
depressed that the system’s schedule will be active.
21 STARTUP DLY Upon a computer reset or power return, the system will remain in the
STARTUP DELAY state for this period of time.
22 FAN DELAY The minimum time that the system will be in the FAN ONLY STATE.
23 STEP DELAY This is the minimum time that the system will remain in each state unless
otherwise noted.
****
24 STATIC TRG
25 STATIC DBAND
26 FANSP INTVAL The fan speed interval is the time, in seconds, between fan speed changes.
27 FAN MIN STRT The fan speed minimum start is the starting speed of the fan when it has been
****
28 ECON CL ON If the entering water temperature is less than this value minus a dead band of
29 ECON HT OFF If the entering water temperature is greater than this value plus a dead band of
****
SETPOINTS FOR STATIC PSI & FAN CONTROL
The static pressure target. If the static psi value is within ± the STATIC DEAD
BAND of the target no change is made to the current fan speed. If the current
static psi is > ± 0.5 of the target the fan speed is changed by 5 %; otherwise the
fan speed is changed by 1%.
The static dead band is the ± value to the static target, which is allowed with no
change to the fan speed.
off.
SETPOINTS USED FOR CONTROL OF ECONOMIZER.
0.5F, the cooling economizer will be used.
0.5F, the heating economizer will be used.
SETPOINTS THAT ARE TESTED FOR SAFETY CONDITIONS.
30 EVAP OVRFLW1 If the evaporator overflow1 digital input is turned on the system locks off all
relay output points except the alarm.
2
Page 29
Heatpump Water-Air/Water-Water Heatpump/Chillers MCS-8 Version 7 Manual Revision 4.0
9
# Name Description
31 EVAP OVRFLW2 If the evaporator overflow2 digital input is turned on the system locks off all
relay output points except the alarm.
32 DIGITAL SAFETY If the set point is set to ‘ACTIVE’ in the PC-Config program it will cause the
system to test the digital input that indicates that a safety has occurred. When
active and the digital input is on, the system will enter a SAFETY FAULT state.
If this set point has been set up as an ‘ALARM only type, no manual
intervention will be required to restart the system if the safety condition
becomes false. If in the PC-Config program it is setup as a ‘LOCKOUT’ manual
intervention will be required.
33 NO FLOW This set point indicates there is no water flow to the system. If the system is
running everything is shut down except the fan. A safety alarm is generated. If
the system is off it is not allowed to start until flow is detected.
34 COND FREEZEIf leaving water temperature to the condenser drops below this set point value,
the system will enter the SAFETY FAULT OR LOCKOUT state and the COND
FREEZE alarm message will be generated. Purpose is to prevent freeze up.
35 EVAP FREEZEIf entering water temperature to the evaporator drops below this set point
value, the system will enter the SAFETY FAULT OR LOCKOUT state and the
EVAP FREEZE alarm message will be generated. Purpose is to prevent freeze
up.
36 LOW SUCT PSI This may be a digital input or an analog input, by compressor. When the
condition occurs an alarm is generated identifying the compressor with low
suction and the compressor is placed in LOCKOUT. After the delay time the
compressor will be automatically placed back into service. If the condition, to
the same compressor, occurs a second time within an hour, the compressor is
placed into lockout and requires a manual reset.
37 DIGITAL LOCKOUT This set point, when active will cause the system to test the digital input that
indicates that a lockout condition has occurred. When active and the digital
input is on, the system will enter a LOCKOUT FAULT state. If this set point is
set up as a lockout type, manual intervention, lockout reset, will be required to
restart the system.
38 NO AIR FLOW This set point indicates there is no airflow to the system. If the system is
running everything is shut down except the fan. A safety alarm is generated. If
the system is off it is not allowed to start until flow is detected.
39 HI DISC PSI This may be a digital input or an analog input, by compressor. When the
condition occurs an alarm is generated identifying the compressor with high
discharge and the compressor is placed in LOCKOUT. After the delay time the
compressor will be automatically placed back into service. If the condition, to
the same compressor, occurs a second time within an hour, the compressor is
locked out and requires a manual reset.
****
SETPOINTS USED TO ALLOW OR DISALLOW
DEHUMIDICATION.
40 ALLOW DEHUMD This set point contains a temperature value. If the return air temperature is less
41 DISALW DHDIF This set point contains a temperature differential. If the system is in a
****
than the value of this set point, the dehumidification function will be enabled.
dehumidification state and the controlling air temperature is greater than the
ALLOW DEHUMD value plus the value of this set point, the dehumidification
function will be terminated immediately and the system will return to the FAN
ONLY.
SETPOINTS USED TO ADJUST THE COOL ENABLE SET
POINT.
2
Page 30
Heatpump Water-Air/Water-Water Heatpump/Chillers MCS-8 Version 7 Manual Revision 4.0
0
# Name Description
42 RETURN RESET This set point is used to calculate a reset to the COOL ENABLE set point. This
set point contains a temperature value that represents the upper limit of the
COOL ENABLE temperature range. If the COOL ENABLE temperature is
above this value no reset will be made. If the COOL ENABLE temperature is
below this value, a proportional reset will be made as described in set point
MAX RESET.
43 RETURN DIFF This set point is used to calculate a dynamic reset to the COOL ENABLE set
point, set point #1. This set point contains a temperature differential value that
is subtracted for set point #42 to provide the lower limit of the COOL ENABLE
temperature range. If the COOL ENABLE temperature is below this value the
maximum reset allowed will be made. If the COOL ENABLE temperature is
between the value of this set point and set point #42, a proportional reset will
be made as described in set point #44.
44 MAX RESET This set point contains the maximum temperature reset that can be made to
the COOL ENABLE set point, set point #1. If the COOL ENABLE temperature
is in the range developed with the values of set points #42 and #43, a
proportional reset is calculated based on the COOL ENABLE temperatures
position within the range times the value of this set point. This value is added to
the COOL TARGET set point. (If the COOL ENABLE temperature is in the
middle of the range, a reset of 50% of this value would be added to the COOL
ENABLE.
45 RESET DELAY This set point contains a time, in seconds, that controls the delay between
reset calculations. This is intended to dampen the changing of the COOL
TARGET temperature target.
****
SETPOINTS USED TO MODULATE THE HOT WATER
VALVE.
46 HW VLV MIN% This set point contains minimum percentage that the valve will be opened.
Normally set to 2.0.
47 HW VLV MAX% This set point contains maximum percentage that the valve will be opened.
Normally set to 100.0.
48 HW MIN ADJ% This set point contains the minimum adjustment that can be made to the valve
at one time.
49 HW MAX ADJ% This set point contains the maximum adjustment that can be made to the valve
at one time.
50 HW VLV DELAY This set point contains the time expressed in seconds between modulating the
valve.
51 HW VLV MULT This set point contains a value that is used to adjust the changes to the valve.
The adjustment is first calculated by taking the absolute value of the difference
between the control temperature and the heat target. This adjustment is then
fine tuned by multiplying by this set point and then dividing by set point 52.
52 HW VLV DIV Refer to set point 51.
53 HW MAX ROC- This set point contains the rate of change that the system uses to determine if
the control temperature is changing too fast or too slow.
54 HW ROC DELAY This set point contains the time expressed in seconds between calculating the
rate of change of the control temperature.
****
SETPOINTS USED TO MODULATE THE ECONOMIZER and
the REHEAT VALVES.
55 ECON VLV MIN This set point contains the minimum valve opening. If the unit has a valve that
can be modulated, its percent of opening will be modulated between this set
point and set point 54 based upon the control temperature. In this way the
system maximizes the econo cooling or heating capability.
56 ECON VLV MAX This set point contains the maximum valve opening. Refer to set point 54.
3
Page 31
Heatpump Water-Air/Water-Water Heatpump/Chillers MCS-8 Version 7 Manual Revision 4.0
# Name Description
57 REHT MINadj This set point is required if the modulating reheat option has been selected.
This set point contains the minimum adjustment that can be made to the reheat
valve at one time.
58 REHT MAXadj This set point is required if the modulating reheat option has been selected.
This set point contains the maximum adjustment that can be made to the
reheat valve at one time.
59 REHT DELAY This set point is required if the modulating reheat option has been selected.
This set point contains the time expressed in seconds between modulating the
reheat valve.
60 TEST CFG I/O If this setpoint is active and set to 0, the system will not lock out due to lost
I/O’s. This is used only for testing a system. Note the alarm and message will
be generated.
31
Page 32
Heatpump Water-Air/Water-Water Heatpump/Chillers MCS-8 Version 7 Manual Revision 4.0
2
11 Return Air Ta rget Reset Logic
#42 RETURN RESET = 70.0F – Temperature at which target reset starts
#43 RETURN DIFF = 10.0F – Temperature offset from starting return temperature
#44 MAX RESET = 10.0F – Maximum reset adjustment allowed
#45 RESET DELAY = 600s – Time delay between making adjustments
Cool Target Reset
10
9
8
7
6
5
4
Target Reset
3
2
1
0
6061626364656667686970
Return Temperature
3
Page 33
Heatpump Water-Air/Water-Water Heatpump/Chillers MCS-8 Version 7 Manual Revision 4.0
3
12 AUTHORIZATION FUNCTION
The authorization code is a special four-character code that enables access in to the MCS-8 system. The code
must be numeric, with values between 1 and 8, if it is to be entered from the Keypad/Display. If the system is
being accessed via PC-Connection program, the code may consist of any valid alpha/numeric characters. Each
system can have up to 15 different authorization codes. This provides the capability of issuing different codes to
different people if desired. There are four levels of authorization, which provide different capabilities with in the
system. The authorization code and the associated level cannot be displayed or viewed in an MCS-8 system.
These are established when building the configuration file in the PC-Configuration program. The authorization
codes must be protected and remain confidential, if they are compromised unauthorized personnel can gain
access to the system.
From the Keypad/Display the following changes can be made based upon the authorization level:
FUNCTION VIEW SERVICE SUPERVI-
SORY
SENSOR OFFSETS NO YES YES YES
SENSOR DIAGNOSTIC NO YES YES YES
CLEAR ALARM HISTORY NO NO NO YES
CLEAR POINT INFORMATION NO NO NO YES
UNIT INFORMATION / NETWORK ADDRESS NO YES YES YES
DATE & TIME SET YES YES YES YES
DAY OF WEEK SET YES YES YES YES
CHANGE OPERATING SCHEDULES NO YES YES YES
CHANGE MANUAL/AUTO SETTINGS NO NO YES YES
CHANGE SET POINT VALUES* NO YES YES YES
LOCK OUT RESET YES YES YES YES
ACTIVATE / INACTIVATE AUTO ROTATION NO NO NO YES
CHANGE UNIT ADDRESS NO YES YES YES
CHANGE HARDWARE VERSION NUMBER NO NO NO YES
FACTORY
3
Page 34
Heatpump Water-Air/Water-Water Heatpump/Chillers MCS-8 Version 7 Manual Revision 4.0
S
7
8
6
5
2
3
4
A
A
13 The Micro Control Center Keypad Display Quick Ref erence
• No authorization is required in the DISPLAY STATUS section for
viewing information.
• Pressing a key selects the 1st two lines of data. Repressing the
same key selects the next two lines, etc.
• The ALARM STATUS displays all alarms and lockouts while
LOCKOUT STATUS displays only active lockouts.
• The “+” and “-“ keys may be used with alarm & lockout status to
allow scrolling.
• If one or more Micro Control Expansion units are connected to a
Micro Control Center the data will be presented in a continuous
sequence.
FAN ON
END /SELECT NEXT
COMP1
ON
COMP2
REV VALV
ECON H/C
REHEAT
END /SELECT NEXT
ON
ON
ON
OFF
• ADDITIONAL STATUS information shows names, total, run hours
and starts for all RO’s.
• SYSTEM PRESSURE displays information by circuit, SP suction
pressure, DP discharge pressure, OPD oil pump differential, AMP or
motor fault.
• LOCKOUT STATUS for lockouts caused by either suction
discharge oil or amps, the actual value at the time of the lockout of
the associated sensor is displayed.
ENT WTR+ 43.4F
LEV WTR + 88.1F
RETURN T+ 43.3%
RETURN H+ 77.6F
SUPPLY T+ 2.3”
STATIC P RUN
END /SELECT NEXT
RUN/STOP
WTR FLOW
SAFETIES
END /SELECT NEXT
OFF
OFF
OFF
REHEAT ON
END /SELECT NEXT
#1 WATER FREEZE
AUG 26 0:28:37
#2 POWER RETURNED
APR 22 8:15:01
#3 POWER FAILED
APR 22 8:10:15
DISPLAY STATU
COMPRESSOR
STATUS
CONDENSOR
STATUS
EVAPORATOR
STATUS
LARM
STATUS
1
HP Configuration
Single board heat pump
•
Two compressors
•
One valve to control
•
One reversing
•
One reheat point that control
•
compressors reheat
Safety & lockout digital
•
Measure static duct pressure
•
Control is on return air
•
SYSTEM
PRESSURE
SYSTEM
SENSORS
DDITIONTAL
STATUS INFO.
LOCKOUT
STATUS
FAN =1015H
STARTS=0000210
ECON VLV=1002H
STARTS =000201
REV VLV=10020H
STARTS = 00201
OPTION
ST
NEWEST LKOUT 1
ENTR NEW/OPTION
WATER FREEZE
AUG 26 0:28:37
END OF LOCKOUTS
ENTR VIEW
34
Page 35
Heatpump Water-Air/Water-Water Heatpump/Chillers MCS-8 Version 7 Manual Revision 4.0
E
(
)
14 The Micro Control Center Keypad Display Quick Ref erence-
ENTRY KEYS
• The ENTRY keys (SERVICE, SETPOINT, MANUAL and
PROGRAM) provide menu items, some of which when selected will
present sub menus.
• When making value changes the INCREASE (+) & DECREASE
(-) keys may be held for continuous updating.
• Enter authorization code at the authorization function within the
SERVICE DIAGNOSTIC key menu.
#1 COOL ENABLE
ENTR CHG +70.0F
#4 COOL TARGET
ENTR CHG +50.0F
#5 COOL ZONE+
ENTR CHG +5.0F
#6 COOL ZONEENTR CHG –5.0F
#21 STARTUP DLY
ENTR CHG +25
#22 FAN DELAY
ENTR CHG +60
#23 STEP DELAY
ENTR CHG +300
#24 STATIC TRG
ENTR CHG +1.5
CONTROL STATUS
ENTR CHG OPTION
AUTHORIZATION
ENTR CHG OPTION
SENSOR OFFSETS
ENTR CHG OPTION
SENSOR DIAGOSTIC
ENTR CHG OPTION
CLEAR ALRM HSTRY
ENTR CHG OPTION
CLEAR PT INFO
ENTR CHG OPTION
UNIT INFORMATION
ENTR CHG OPTION
• Different items will appear depending on the package
configuration and options selected.
• Units may be English or Metric.
• The clock is factory set at EST or EDST based on time of year.
DATE DISPLAY
ENTR CHG OPTION
TIME DISPLAY
ENTR CHG OPTION
DATE & TIME SET
ENTR CHG OPTION
DAY OF WEEK SET
ENTR CHG OPTION
OPERATING SCHEDS
ENTR CHG OPTION
RELAY OUTS MANAL
ENTR CHG OPTION
ANALG OUTS MANAL
ENTR CHG OPTION
SENSOR INS MANAL
ENTR CHG OPTION
SERVICE
DIAGNOSTI
SETPOINTS
(SAFETIES)
MANUAL
AUTO
LOCKOUT
RESET
RESET LOCKTS?
ENTER KEY=YES
NTRY
PROGRAM
OPTIONS
INCREASE
DECREASE
ENTER
Selects options or enters
changes after adjustments
(+)
(-)
ENTER KEY
have been made.
INCREASE (+)
KEY &
DECRE A S E (-)
Used To adjust
values or change
options selected.
SETPOINTS,
PROGRA M keys.)
KEY
(SERVICE,
MANUAL, &
35
Page 36
Heatpump Water-Air/Water-Water Heatpump/Chillers MCS-8 Version 7 Manual Revision 4.0
p
p
15 The Micro Control Center MCS-8 Quick Reference Sheet
Wiring Guide Notes
• Relay Outputs (RO) 120 VAC 10 amps on the MCS-8.
• SI factory settings for analog inputs. (0 to 5 volts dc)
• All analog inputs must have shield tied to GND.
• MCS-8 factory set address to MCS-8.
• MCS-I/O factory set address to MCSIO#1.
• Details of theMCS-8 items are on the next page.
• Details of the MCS-SI8/16 items are following the MCS-8 page.
High Voltage Wireway Relay Ouptus & 120 VAC 50/60 hertz Input
1. Digital inputs for use on sensor inputs (S I 1-8/16)
2. Wire between +5 & SI
3. Dry Contact MCS-8 jumper setting
4. Shielded cable GND drain must be connected to SI “GND”
(SI 1 through 8 Revision 1.5 & H ig her)
MCS Sensor Input Ter minal Stri ps
Sensor (x)
+5
GND
Shielded cable - min. 24 awg
S1
MCS DRY CO NTACT DI ( SI 1- 8/ 1 6)
Digital
Analo g
:
40
Page 41
Heatpump Water-Air/Water-Water Heatpump/Chillers MCS-8 Version 7 Manual Revision 4.0
20 The MCS Trouble Shooting Quick R efe rence Sheet
PROBLEM POTENTIAL SOLUTION
A sensor input reads -99.9 1) This indicates an open sensor input signal or 5 VDC problem.
a) Check sensor wiring for missing wire or poor connection.
b) Check sensor for bad sensor.
2) If less than 5 VDC on sensor inputs problem with board.
a) Remove all sensor input terminals.
b) Wait about 1 min. or until 5 VDC restored at sensor input.
c) Connect terminals 1 at time until short reappears.
A sensor input reads +999.9 3) This indicates a shorted sensor input signal.
a) Check sensor wiring for +5VDC shorted to signal etc.
b) Check sensor for bad sensor.
A sensor is reading less then 3%
off
‘MCS CONTROLLER
INITIALIZATION’ on LCD display.
Top row of LCD display all bars &
2nd row blank.
LCD blank. 7) Indicates bad connection.
Lost I/O 8) Indicates communications problem.
Invalid reading on one sensor
input.
Changes to MCS not being made. 10) This indicates inability to write to chip U10.
Invalid authorization 11) This indicates an invalid authorization #.
4) This indicates the sensor needs to be calibrated. (You need to have a
valid Authorization code to change sensor offsets)
a) Press Service Diagnostics, press until LCD displays the sensor
offset option
b) Press enter, 1
st
SI# & offset appears (i.e. Suct 1 = 0.0)
c) Scroll using “increase (+)/decrease (-)” keys to find sensor to be
calibrated
d) Press enter, use the “increase (+)/decrease (-)” keys to change
the calibration value. When value is correct, press enter.
5) Indicates Micro in constant reset.
a) Check incoming power > 105 VAC or 22 VAC
6) Indicates software chip problem possible.
a) Possible U11 software version incorrect or chip is bad.
b) Possible U13 GAL chip is incorrect or chip bad.
c) Possible bad connection or cable between LCD and MCS8
a) Connector J2 on MCS not on or offset on connector.
b) Resistor adjustment VR1 out of adjustment.
a) Verify RS485 LED blinking.
b) Verify termination jumper J6 only on at MCS-8 & last I/O.
c) Verify MCS-8 & I/O address’s set correctly.
d) Verify wiring from MCS-8 to each I/O correct.
e) Check fuses/120 VAC on I/O units
9) This indicates an input problem with 1 sensor.
a) Verify jumper settings correct for that SI.
a) Verify ‘EEP WRITE ENABLE’ jumper W6 is on.
b) Not authorized
a) Follow steps below for proper authorization
b) Press SERVICE DIAGNOSTICS key; the authorization option
appears
c) Press the ENTER key
d) From the “Display Status” press keys corresponding to your
authorization #
e) Press ENTER
41
Page 42
Heatpump Water-Air/Water-Water Heatpump/Chillers MCS-8 Version 7 Manual Revision 4.0
PROBLEM POTENTIAL SOLUTION
SI from AMPS board 10 A low. 12) This indicates a problem with this SI only.
a) Jumper setting on this SI in wrong position.
INVALID CONFIG VER 13) Indicates layout of CFG wrong.
a) CFG layout for different version than software chip U11.
INVALID CONFIG TYPE 14) Indicates U10 CFG incompatible with U11 software.
a) Example U10 CFG for home while U11 for chiller.
INVALID CONFIG 15) Indicates Checksum invalid
a) Reload CFG
Sensor input believed invalid
(Under Sensor Diagnostic Sub
Menu)
16) Version 1.5 & higher
a) All jumpers set for ‘DIGITAL’ or ‘ANALOG correctly.
b) Sensor input test (Remove terminal block for sensor testing and
get display to the sensor you are testing by going to ‘SENSOR
DIAGNOSTICS’ under SERVICE DIAGNOSTICS key)
i) If Jumper is set to ‘DIGITAL’ (Display count = 1 or 2)
ii) If Jumper is set to ‘ANALOG’ (Display count = 5, 6 or 7)
c) Check wiring of sensor
42
Page 43
Heatpump Water-Air/Water-Water Heatpump/Chillers MCS-8 Version 7 Manual Revision 4.0
21 Summary of Control States
The following table contains HEAT PUMP / CHILLER CONTROL STATES. The HEAT PUMP control states can be
viewed form the keypad by depressing the SERVICE DIAGNOSTICS key and selecting the CONTROL STATUS
function. The first screen contains the state and the time in that state. The + or – keys will move to the
ECONOMIZER CONTROL STATES.
The following table contains HEATPUMP / CHILLER CONTROL STATES.
LOST I/O The system has detected a failure to communicate to an input or output unit.
LOCKOUT FAULT Lock out input is on. Manual intervention is required-LOCKOUT RESET.
SAFETY FAULT Safety input is on. System will restart when is input is off if the set point is not a lock
SENSOR FAULT One of the sensors has failed either open or closed (999.9 or –99.9). LOCKOUT
HEATPUMP OFF RUN/STOP switch is off (STOP).
FAN/PUMP ONLY FAN or PUMP is ON, no cooling or heating required.
ECONO COOLING Cooling is being provided by the economizer function.
COOL: 1 COMP Compressor 1 is providing cooling.
COOL: 2 COMPS Compressors 1& 2 are providing cooling.
COOL: 3 COMPS Compressors 1, 2 & 3 are providing cooling.
COOL: 4 COMPS Compressors 1,2, 3 & 4 are providing cooling.
DEHUM: 1 COMP Compressor 1 is providing dehumidification.
DEHUM: 2 COMPS Compressors 1& 2 are providing dehumidification.
DEHUM: 3 COMPS Compressors 1, 2 & 3 are providing dehumidification.
DEHUM: 4 COMPS Compressors 1,2, 3&4 are providing dehumidification.
ECONO HEATING Heating is being provided by the economizer function.
HEAT: 1 COMP Compressor 1 is providing heating.
HEAT-HOLDING Heating is being provided by hot water and the valve is not being modulated.
HEAT-CLOSING Heating is being provided by hot water and the valve is being modulated closed.
HEAT-OPENING Heating is being provided by hot water and the valve is being modulated open. The
HEAT-SLOPE CL Heating is being provided by hot water and the valve is being modulated closed.
HEAT-SLOPE OP Heating is being provided by hot water and the valve is being modulated open. The
ELECTRIC HEAT Heating is being provided electric heat.
NAME DESCRIPTION
out type. If it is a LOCKOUT RESET is required.
RESET is required.
The control temperature is with in the control heat zone.
control temperature is with in the control heat zone.
The control temperature is not with in the control heat zone. Percentage of closing
is calculated based on current control temperature and heat target.
control temperature is not with in the control heat zone. Percentage of opening is
calculated based on current control temperature and heat target.
43
Page 44
Heatpump Water-Air/Water-Water Heatpump/Chillers MCS-8 Version 7 Manual Revision 4.0
The following table contains ECONOMIZER CONTROL STATES.
NAME DESCRIPTION
BYPASSED-COOL Economizer valve is off because the water temperature is not cold enough to
provide cooling.
BYPASSED-HEAT Economizer valve is off because the water temperature is not hot enough to
provide heating.
ECONO OFF Economizer valve is off because the heat pump / chiller is either off; fan/pump only
is running or in a fault state.
ECONO COOL ON The heat pump / chiller is in a cooling state. Economizer valve is open and the
water temperature is cold enough to provide cooling
ECONO HEAT ON The heat pump / chiller is in a heating state. Economizer valve is open and the
water temperature is hot enough to provide heating
44