Nexus 110 AC Sounder & Sounder-Beacon
Installation Instructions
Tone Tone Type Tone Description / Application Dip Switch 3rd Stage Peak Sound
(
S1/S2) Tone Level (dBA@1m)
1
. 970Hz (BS5839-1:2002) O-O-O-O-O-O 18 110
2
. 800Hz/970Hz @ 2Hz (BS5839-1:2002) O-O -O -O- O- I 1 110
3
. 800Hz – 970Hz @ 1Hz (BS5839-1:2002) O-O -O -O- I- O 1 110
4
. 970Hz 1s OFF/1s ON (Apollo Fire Systems Alert Tone, BS5839-1:2002) O- O - O -O - I - I 1 110
5
. 970Hz, 0.5s/ 630Hz, 0.5s (Apollo Fire Systems Evacuate Tone, BS5839-1:2002) O-O -O -I- O- O 1 110
6. 554Hz, 0.1s/ 440Hz, 0.4s (France – AFNOR NF S 32 001 ) O- O - O -I - O - I 1 107
7. 500 – 1200Hz, 3.5s/ 0.5s OFF (Netherlands – NEN 2575:2000) Dutch Slow Whoop O- O - O -I - I - O 1 110
8. 420Hz 0.625s ON/0.625s OFF (Australia AS1670 Alert tone) O - O - O -I - I - I 1 105
9
. 500 – 1200Hz, 0.5s/ 0.5s OFF x 3/1.5s OFF (Australia AS1670 Evacuation tone) O-O-I -O-O- O 1 110
1
0. 550Hz/440Hz @ 0.5Hz O- O - I -O - O - I 19 107
1
1. 970Hz, 0.5s ON/0.5s OFF x 3/ 1.5s OFF (ISO 8201 Low tone) O- O - I -O - I - O 1 110
1
2. 2850Hz, 0.5s ON/0.5s OFF x 3/1.5s OFF (ISO 8201 High tone) O - O - I -O - I - I 1 112
13. 1200Hz – 500Hz @ 1Hz (DIN 33 404) O- O - I -I - O - O 1 110
14. 400Hz O - O - I -I - O - I 18 105
15. 550Hz, 0.7s/1000Hz, 0.33s O - O - I -I - I - O 1 111
16. 1500Hz – 2700Hz @ 3Hz (Vandal Alarm) O - O - I - I - I - I 1 116
17. Simulated Bell O-I -O -O- O- O 1 112
18. 2130Hz O- I - O -O - O - I 1 113
1
9. 660Hz O- I - O -O - I - O 10 109
2
0. 660Hz 1.8s ON/1.8s OFF O - I - O -O - I - I 19 108
2
1. 660Hz 0.15s ON/0.15s OFF O- I - O -I - O - O 19 107
2
2. 510Hz, 0.25s/ 610Hz, 0.25s O - I - O -I - O - I 1 107
2
3. 800/1000Hz 0.5s each (1Hz) O- I -O - I - I -O 1 111
2
4. 250Hz – 1200Hz @ 12Hz O - I - O - I - I - I 1 105
2
5. 500Hz – 1200Hz @ 0.33Hz. O- I- I - O -O - O 1 110
26. 2400Hz – 2900Hz @ 9Hz O- I -I -O - O - I 1 116
27. 2400Hz – 2900Hz @ 3Hz O - I - I -O - I - O 1 116
28. 800Hz – 970Hz @ 100Hz O - I - I - O - I - I 1 110
29. 800Hz – 970Hz @ 9Hz O -I - I - I -O -O 1 110
30. 800Hz – 970Hz @ 3Hz O - I - I - I - O - I 1 110
31. 800Hz, 0.25s ON/1s OFF O - I - I - I - I - O 1 108
32. 500Hz – 1200Hz, 3.75s/0.25s OFF (AS2220) O - I - I - I - I - I 1 110
33. 340Hz I-O -O -O- O- O 1 106
34. 1000Hz I- O - O -O - O - I 18 111
35. 1400Hz – 1600Hz, 1s/1600Hz – 1400Hz, 0.5s (NF 48-265) I- O - O -O - I - O 1 110
36. 660Hz 6.5s ON/13s OFF I -O - O - O -I -I 19 108
37. 1000Hz/2000Hz, 1s each I- O - O- I - O-O 1 113
38. 720Hz, 0.7s ON/0.3s OFF I - O - O -I - O - I 1 106
39. 970Hz, 0.25s ON/OFF I - O - O -I - I - O 1 110
40. 2800Hz, 1s ON/OFF I - O - O - I - I - I 1 113
41. 2800Hz 0.25s ON/OFF I- O - I -O - O - O 1 113
42. 2400/2900 @ 2Hz I - O - I -O - O - I 1 115
43. Chime, 554Hz/440Hz Single shot ‘ding dong’ I - O - I -O - I - O1 104
44. Chime, 554Hz/440Hz Repeating ‘ding dong’ I - O - I - O - I - I 1 107
45. Chime, 970Hz/800Hz Single shot ‘ding dong’ I- O - I - I- O - O 1 106
46. Chime, 970Hz/800Hz Repeating ‘ding dong’ I - O - I - I - O - I1 106
47. Hooter, Repeating I - O - I - I - I - O 1 107
48. Gentle alarm - Tone 2, rises slowly to full volume over 30s I - O - I - I - I - I 1 109
49. Time-Out Alarm – As Tone 2, cuts off after 10 mins I- I - O -O - O - O 1 109
50. Time-Out Alarm – As Tone 2, cuts off after 2 mins I - I - O -O - O - I 1 109
51. 750Hz 0.33s ON/0.51s OFF I - I -O -O - I - O 1 106
52. 750Hz 0.51s ON/0.33s OFF I - I - O - O - I - I 1 107
53. 550Hz, 0.33s/1000Hz, 0.7s I - I - O -I - O - O 1 111
54. 600Hz – 900Hz/ 0.9s I - I - O - I - O - I 1 109
55. 660Hz – 680Hz/ 0.9s I - I - O - I - I - O 1 105
56. 670Hz – 725Hz/ 0.9s I - I - O - I - I - I 1 107
57. 920Hz – 750Hz/ 0.9s I - I - I -O - O - O 1 110
58. 700Hz - 900Hz, 0.3s/0.6s OFF I - I - I - O - O - I 1 109
59. 900Hz - 760Hz, 0.6s/0.3s OFF I - I - I - O - I - O 1 110
60. 750Hz I - I - I - O - I - I 18 107
61. Power Only – Use with Stage 3 control for manual/intermittent chime triggering I - I - I - I - O - O 43
62. Power Only – Use with Stage 3 control for manual/intermittent chime triggering I - I - I - I - O - I 43
63. Power Only – Use with Stage 3 control for manual/intermittent horn triggering I - I - I - I - I - O 47
64. Reserved for future use I - I - I - I - I - I
FR
NL
EN
DE
ES
PT
IT
PL
SE
DK