Continued Leadership in Floor-By-Floor,
Self-Contained System Designs
McQuay SWT self-contained air conditioning systems trace their
history to the late 1970s and the pioneering concepts of Blazer
Industries. Working closely with the consulting engineer to solve
special system and space challenges, Blazer Industries developed
and provided the first self-contained, variable air volume systems
with water side economizer cycle for the prestigious 499 Park
Avenue office building. Following the success of this project was
more than a decade of innovation and product leadership, with
thousands of systems provided for prominent building projects.
In 1991, McQuay acquired Blazer Industries. The result has been
a continuation of this tradition of innovation and leadership. The
comprehensive, updated modular McQuay SWT system offering
is now supplying quiet, efficient and flexible systems to meet
today’s diverse and demanding performance needs for new and
retrofit, commercial, industrial and institutional buildings worldwide.
Nomenclature
Agency Listed
McQuay and MicroTech are registered trademarks of McQuay International.
System Performance Providing Tenant
Comfort and Operating Economy
Since the introduction of self-contained systems in the late 1970s,
the industry has seen this concept grow into one of the most
widely specified systems for new office buildings, for retrofitting
existing structures, and for institutional, industrial, and other specialized applications. The reason is simple: system performance.
Designed specifically to satisfy growing system retrofit needs,
McQuay SWT self-contained VAV systems provide the total performance advantage of:
• Modular construction
• Prime candidate for building renovation
• Special 34.5" maximum section width fits through a 3'
door frame
• Refrigerant lines always remain intact
• Requires minimum floor area when reassembled
• Retrofit alternative where existing chiller cannot be
accessed for replacement
• Tenant Comfort
• Tenants enjoy individual control over comfort conditions
and off-hour system operation
• Tenants benefit from their individual efforts to control
energy costs
• Routine service is located where it minimizes tenant
inconvenience
• Individual or dual systems per floor provide system
redundancy and standby
• First cost economics
• VAV system flexibility uses building diversity to reduce
system tonnage and first cost
• Factory packaged concept reduces field labor, installation
time and expense
• No expensive chilled water piping or chiller room
• Individually tested, factory designed systems reduce
start-up and installation expense
• Reduce penthouse and equipment room
requirements
• Centralize condenser water and condensate piping and
streamline system layout
• Energy-saving VAV system control
• Reduces fan kW and operating costs at part load conditions
• Savings maximized through use of variable speed fan
control
• Individual zone control without overcooling or use of
reheat
• Quiet system operation
• Provided by structural quality and specialized design
• Recognized for quiet operation by renowned U.S. acoustical consultants
• Energy saving economizer operation
• Water or air economizer capability for optimized energy
savings
• Economizer reduces compressor operating hours and
energy costs
• Year-round “free cooling” capability
• Energy saving building part load operation
• System energy efficiency comparable to central chilled
water systems
• Multiple systems and compressors versus a single, large
central plant
• Efficient system for partial occupancy and after hours
operation
• Operate only the system(s) on the floor(s) requiring after
hours use
Figure 1. McQuay Self-Contained VAV Systems
• System savings of advanced MicroTech III™ DDC
control system
• Monitoring and diagnostics reduce the potential for
expensive field repairs
• Industry leading Protocol Selectability™ feature provides
effective BAS selection flexibility
• Reduced system maintenance and service costs
• No complicated central chiller plant to maintain
• Service and maintenance are performed out of the occupied space
• Control and product reliability functions designed by the
equipment manufacturer for single source responsibility
and improved reliability
4McQuay Catalog 865-5
Fan Section
Filter / Waterside
Economizer Section
Main Heating /
Cooling Section
Design Features
Cabinet, Casing and Frame
For vibration control and rigging strength, the SWT unit base is
constructed of welded structural steel channel and 10- gauge galvanized steel panels. Heavy-duty lifting brackets are strategically
placed for balanced cable or chain hook lifting.
For long equipment life, unit exterior panels are constructed of
heavy gauge, pre-painted, galvanized steel. The complete cabinet,
frame and access panels are insulated with 1 inch thick, 1.5 lb.
dual density insulation. Double wall construction is available to
enhance performance and satisfy IAQ requirements.
For maintenance and service ease, system components are strategically located for ease of inspection and maintenance. Refrigeration components are positioned out of the airstream so
adjustments and readings can be made without disrupting system
operation. Service friendly access is made through heavy-duty,
conveniently removable panels. Access panels are set on neoprene
gaskets to prevent air leakage.
Modular Design
The SWT unit is easily disassembled into three compact sections;
main cooling/heating, filter/waterside economizer and fan. See
“Modular Construction” under “System Flexibility” on page 9.
Figure 2. SWT Cabinet
Condensing Section
Multiple compressors are featured in all SWT systems for efficient system part load control, quiet operation and system redundancy. Compressors are quiet, reliable hermetic scroll type
complete with sightglass, anti-slug protection, and motor overload
protection. Suction and discharge service valves, with gauge
ports, are available on each compressor. Individual branch circuit
fusing protects each compressor. The unit’s MicroTech III™ control system incorporates timing functions to prevent compressor
short cycling. All compressors are resiliently mounted to minimize any noise transmission. The condensing section is insulated
and segregated from the air handling section of the unit to avoid
transmission of noise to the circulated air stream.
Figure 3. Copeland SpecterTM scroll compressor
Each compressor is on an independent refrigerant circuit complete
with filter-drier, liquid moisture indicator/sightglass, thermal
expansion valve capable of modulation from 100-25% of its rated
capacity, liquid line shutoff valve with charging port, high pressure relief device and high and low pressure cutouts. If any compressor is made inoperable, the remaining compressors are still
allowed to operate.
The unit’s MicroTech III controller senses entering condenser
water temperature and prevents mechanical cooling when the temperature falls below an adjustable setpoint value, minimum 55°F.
For systems which will see entering condenser water temperatures
below 55°F, a waterside economizer or head pressure activated
control valve is available.
SWT water cooled condensers feature a mechanically cleanable,
all copper design using the same high performance enhanced tubing found in modern centrifugal chillers. Liquid refrigerant subcooling is provided as standard. Each condenser is part of an
independent refrigerant circuit and comes complete with a spring
loaded high pressure relief valve. All condensers are independently leak tested. All completed units are leak tested, evacuated
and shipped with a full operating charge of R-22 and oil. R-407C
is also available as an alternate selection.
The condenser assembly and all factory water piping is rated for a
waterside working pressure of 400 psig and is factory leak tested
before shipment. Condenser water channels are mechanically
cleanable by removing brass service plugs that are sealed with
McQuay Catalog 865-55
Refrig. Flow Ckt 1
Refrig. Flow Ckt 2
Ckt 2
Ckt 1
Ckt 1
Ckt 1
Ckt 1
Ckt 1
Ckt 1
Ckt 1
Ckt 1
Ckt 2
Ckt 2
Ckt 2
Ckt 2
Ckt 2
Ckt 2
Ckt 2
Airflow
a02
Design Features
reusable o-ring gaskets. Main interconnecting condenser water
headers include vent and drain plugs and a large cleanout plug for
removing debris dislodged during cleaning. Condensers are factory piped for a single condenser water supply and a single condenser water return connection.
Both right-hand and left-hand piping locations are available.
Cooling Coil Section
SWT evaporator coils incorporate a high efficiency ripple corrugated fin design. SWT system design maximizes coil face area
without developing uneven, performance robbing di sr upt ions in
airflow patterns. The result is high coil performance and reduced
static pressure losses. Coils are 4 or 6 row configurations.
The evaporator coil is mounted in a stainless steel double sloped
drain pan. The condensate drain line is trapped internal to the unit,
eliminating the expense and inconsistency of field installed traps.
Figure 4. Evaporator Coil Circuiting
Hot Water Heat
Hot water coils have 1 or 2 rows with high efficiency ripple corrugated fin design and 1/2 inch O.D. seamless copper tubes. Coils
are available complete with a factory mounted, piped and wired 2way or modulating valve controlled by the unit’s MicroTech III
controller. A factory mounted freezestat is provided to help protect against coil freeze-up.
Supply Fan Section
Figure 5. Supply Fan
The supply fan section uses one or two double width, double inlet
medium pressure forward curved fans and housings. Each fan is
statically and dynamically balanced. The fan assembly is constructed of high strength structural steel and welded for maximum
strength. The entire fan assembly is mounted on spring isolators
for excellent isolation effectiveness. Seismic control restrained
spring isolators are available. A vibration dampening flex connection is installed at the fan discharge. The entire fan, motor and
drive assembly is dynamically balanced at the factory for quiet
operation.
All evaporator coils are interlaced circuiting, keeping the full face
of the coil active to eliminate air temperature stratification. For
optimum part load performance, all three and four circuit evaporator coils are circuited for both interlaced and row control. Compressor staging is sequenced to take maximum advantage of
available coil surface.
Each evaporator coil circuit is furnished with a wide range thermostatic expansion valve with an adjustable superheat setting and
external equalizer.
Supply fans are configured with a gradual expansion, aerodynamic duct within the cabinet. This unique gradual expansion feature contributes to the high performance of the SWT by lowering
brake horsepower and sound power levels.
All fans are mounted on solid steel shafts rotating in 200,000 hour
pillow block ball bearings with grease fittings. Multiple belt,
fixed pitch sheaves are matched to the specific cfm, static pressure and horsepower requirements of the system. Drives rated for
a minimum of 150% of fan design are available. Drive components and fan bearings are easily accessed for periodic mainte-
Heating Section
SWT units are available as cooling only systems or with factory
installed electric or hot water heat for morning warm-up, constant
volume and specialty heating requirements.
Electric Heat
nance.
Fan motors are three phase, NEMA design B, rated at 40°C.
Motor availability includes high efficiency open drip-proof and
totally enclosed, EPACT compliant, NEMA T-frame selections
and premium efficiency selections. Motors are 1800 RPM with
grease lubricated ball bearings.
The factory assembled electric heating coils are constructed of
low watt density nickel-chromium elements for long lasting durability. Electric heaters are protected by automatic reset high limit
controls and line break protection. Heater branch circuits are individually protected by branch circuit fusing. The MicroTech III
control system sequences the electric heating elements for operating economy.
6McQuay Catalog 865-5
Design Features
Energy saving advanced technology variable frequency drive
(VFD) fan speed control is available with the convenience and
cost savings of factory mounting and testing. All VFD selections
are plenum rated. A manually activated bypass contactor is available to allow system operation even in the event of drive service.
MicroTech III controls provide advanced duct static pressure control. Static pressure can be controlled by either a single or two
duct static pressure sensors. All VAV systems include an adjustable duct high-limit switch to protect duct work from excessive
pressure.
Economizer Options
Waterside Economizer
An energy saving, waterside economizer package is available on
all units. The complete economizer system is factory mounted
including a 4-row mechanically cleanable coil, control valves and
factory piping complete with cleanouts. The complete economizer
package is rated for up to 400 psig waterside working pressure
and the entire coil and piping assembly is factory leak tested.
Economizer operation is controlled by the SWT’s MicroTech III
controller to maximize free cooling potential. Economizer operation is enabled whenever the available cooling tower water temperature is less than the unit entering air temperature by a field
adjustable value, generally 5-7°F. The economizer control valve
modulates in response to the cooling load. Control valve operation
can be selected to (1) maintain full flow through the unit at all
times or (2) isolate the unit from the condenser water loop when
there is no call for cooling to save energy with a variable pumping
system. (Economizer control valves do not eliminate the need to
provide unit isolation valves.) To extend free cooling savings,
mechanical cooling is enabled during economizer operation. Only
when the economizer valve is driven 90% open and the cooling
load is not satisfied, will compressors be staged to maintain cooling setpoint. Economizer control will maintain full free cooling
capability until disabled by the economizer changeover setpoint.
A factory mounted freezestat is provided to help protect against
coil freeze-up.
Condenser Head Pressure Control
For applications where a waterside economizer package is not
being used and entering condenser water temperatures can be less
than 55°F, condenser head pressure control is required. To satisfy
these applications, a factory installed 2-way, head pressure activated control valve is available to maintain unit operation with
entering condenser water temperatures as low as 40°F.
An airside economizer control package is available for controlling
field installed mixing dampers capable of 100% outside airflow.
Economizer operation will be controlled by the SWT's MicroTech
III controller to maximize free cooling potential. Economizer
operation is enabled whenever an outside air (or comparative)
enthalpy sensor or outside air temperature sensor indicates that
outside air is suitable for free cooling. The economizer damper
control actuator shall modulate in response to the cooling load.
The outside air damper will be positioned to maintain minimum
ventilation requirements when economizer is disabled.
To extend free cooling savings, mechanical cooling is enabled
during economizer operation. Only when the economizer damper
is driven 90% open and the cooling load is not satisfied, will compressors be staged to maintain cooling setpoint. Economizer control will maintain full free cooling capability until disabled by the
economizer changeover setpoint. Factory supplied mixing boxes
are available for airside economizer use using the McQuay
Vision™ air handling unit platform.
McQuay Catalog 865-57
Filter Section
All SWT units are provided, as standard, with 4" deep extended
media 30% efficient filters. For higher filtration requirements,
65% and 85% AmericanAirFilter
with an optional pre-filter rack. Filters are removable from the
rear of the unit or through hinged and latched side access doors on
the filter box.
TM
Varicel® filters are available
Design Features
Electrical
Each unit is completely wired and tested at the factory prior to
shipment. Wiring complies with NEC requirements and conforms
to all applicable UL standards for reliability and safety. All electrical components are labeled according to the electrical diagram
and are UL recognized whenever applicable. Line voltage components and wiring are physically separated from the low voltage
control system.
The supply fan motor, compressor motors and electric heat all
have individual branch circuit fuse protection. Control circuit
power is supplied through a factory installed, low voltage transformer. The supply fan motor circuit includes a three phase contactor and ambient compensated overload protection with manual
reset. Each refrigerant circuit includes both a high and low pressure cutout switch and a coil frost protection thermostat.
A terminal block is provided for the single, main power connection and a terminal board is provided for low voltage control wiring. A factory mounted, non-fused main circuit interrupter is
available for disconnecting the main electrical power to the unit.
The switch is visible, located at the front of the unit, and is accessible without unit penetration. Dual power blocks or disconnect
switches are available to accommodate requirements for standby,
emergency power supplies.
Controls
Phase Failure/Undervoltage Protection – Factory installed
phase failure/under voltage protection is available to protect three
phase motors from damage due to single phasing, phase reversal
and low voltage conditions.
Individual Unit Factory T est – All SWT units are provided completely factory assembled, piped, wired, tested, and shipped in one
piece. Each unit undergoes a factory test that includes:
• Dynamic trim balance of the completed fan assembly
• Run check of all electrical components, alarms and shutdowns,
including proper control sequencing
• Pressure test, at rated pressure, of refrigerant coils, water coils
and condensers prior to assembly
• Final leak check of the completed refrigerant circuits
• Final leak check of the completed water circuit
• Compressor run check
Verification of factory run test is available at time of unit shipment.
Figure 8. Test Stand
MicroTech III Unit Controls
All SWT units feature advanced MicroTech III DDC controls to
provide all temperature and static pressure control, product reliability control functions, system time clock and all monitoring
and diagnostics. Each MicroTech III control system features a
human interface with a 4-line, 20 character English language display for fast system diagnostics and adjustments. The complete
control system is factory installed and commissioned prior to
shipment.
Protocol Selectability™ Feature
All MicroTech III control systems have McQuay's exclusive Protocol Selectability feature. MicroTech III control systems can be
factory configured for standalone operation or for incorporation
into an independent building automation system using either the
BACnet
MS/TP, BACnet/IP or LonTalk protocols.
Auxiliary Control Options
Condenser Water Flow Switch –A factory installed, flow switch
is available to verify water flow status at each unit. Compressor
operation is disabled and an alarm signal provided if condenser
water flow is lost. Unit operation is restored when water flow has
again been sensed. Water flow status is displayed at the MicroTech III control’s plain language screen.
Freezestat – A nonaveraging type freezestat is available factory
installed on the entering face of the economizer coil. Upon sensing a potential freeze condition, the unit supply air fan is shut
down, the economizer (and heating) valve drives to the full open
position and an alarm signal is provided. Unit operation is
restored following the manual reset of the freezestat.
8McQuay Catalog 865-5
Fan Section
Main Heating /
Cooling Section
Optional Hot
Water Coil
Connections
Condensate
Drain
Filter /
Waterside
Economizer
Section
Water In
Water Out
System Flexibility
Along with providing high quality and state-of-the-art innovation,
SWT self-contained systems emphasize system flexibility, flexibility not even considered by the competition. McQuay SWT systems offer customized flexibility to satisfy a wide range of diverse
applications.
Selection/Application Flexibility
Nominal cooling capacities range from 15 to 45 tons and all units
feature a 6 row evaporator coil. In addition, all units offer multiple
compressor selections to meet exacting system requirements.
Many standard compressor/coil capacity selections are available.
The flexibility to optimize the self-contained system to fit the
application is a McQuay SWT advantage. Available system applications include:
• VAV discharge air temperature control with static
pressure control
• Discharge air temperature control with constant air
volume
• Constant volume, zone temperature control
• 100% outside air control
• Dehumidification control, with or without reheat control
In addition to compressor/coil flexibility, SWT systems offer double width, double inlet, forward curved fans with factory mounted
variable frequency drives for maximizing VAV system fan performance. High efficiency fan capability coupled with extensive
compressor flexibility can provide the right system selection for
the application.
pressure, a 20% reduction in supply air CFM can reduce the
fan BHP requirements by 25% or more.
• Reduced supply air CFM provides reduced fan sound power
generation and a quieter room environment.
• Reduced supply air CFM can often reduce the equipment room
size due to the use of a physically smaller unit size.
Figure 9. Modular Construction
Modular Construction
The SWT unit has been designed with the flexibility to be easily
disassembled into three compact sections. The three sections are
the main cooling/heating, filter/waterside economizer and fan sections. Whereas most competitive products require removal of the
door frame, each SWT section has a maximum width of 34.5",
including fastener heads, and can fit through standard 3' steel door
frames.
The system installer is able to break the unit down into its three
main sections without breaking any refrigerant lines. All SWT
refrigerant lines remain intact, contained in the main cooling/heating section. This SWT feature can add up to substantial savings
by avoiding the field expense to braze, evacuate and charge each
refrigerant circuit.
Optimal Discharge Air Temperature:
More and more system engineers are designing optimal discharge
air temperature systems to improve system performance and system first cost, and the McQuay SWT provides the flexibility to do
it successfully. Optimal discharge air temperature systems are
designed to provide unit leaving air temperature selections of 5253°F versus more conventional systems that supply air at temperatures closer to 58°F. This five to six °F reduction in air temperature to the room diffusers can subsequently reduce the required
supply air volume to the room by 20-25%.
The benefits of optimal discharge air temperature systems become
quite apparent with a look at the advantages offered with reduced airflow:
• Reduced supply air CFM reduces first cost and installation
cost by allowing smaller duct sizes and a smaller air distribution system.
• Reduced supply air CFM reduces fan BHP requirements.
Depending on changes in duct size and the resulting total static
Arrangement Flexibility
All SWT systems offer the flexibility of right-hand and left-hand
piping arrangements and front and rear fan discharge orientations.
Piping and fan arrangement flexibility can simplify mechanical
equipment room arrangement, improve installed cost and improve
total system performance.
Filtration Flexibility
SWT systems are offered with 4 inch, 30% efficient pleated filters
as standard. 4 inch, 65% efficient pleated filters and 4 inch, 85%
efficient filters with pre-filters are also available.
Energy Saving Economizer Flexibility
To improve system operating performance, all SWT s ystems of fer
complete factory mounted and controlled waterside economizer
capability. Each waterside economizer system includes a 4 row,
mechanically cleanable coil with dual, two-way control valves to
allow use in either a constant or variable volume pumping system.
In addition, units can be applied with air economizer cycles with
integrated factory control.
Heating Flexibility
A variety of heating media is offered with each SWT system. Hot
water coils with modulating valve and actuator are available along
with staged electric heat to provide heating control in a variety of
applications.
McQuay Catalog 865-59
System Flexibility
Controllers
MicroTech III DDC control systems provide constant volume,
variable air volume, 100% outside air, and/or dehumidification
control flexibility. Each MicroTech III control system comes with
a control screen conveniently mounted on the front of the unit to
allow easy adjustment and monitoring of control functions. And
with its easy to follow and read English language menus and data
displays, it simply encourages and invites the operator to take
advantage of its many capabilities.
Figure 10. MicroTech III Controller
Protocol Selectability Feature
All MicroTech III control systems have McQuay's exclusive Protocol
Selectability feature. MicroTech III control systems can be factory
configured for standalone operation or for incorporation into an independent building automation system using either the BACnet
MS/TP, BACnet/IP or LonTalk protocols.
Summary of Available Options:
• Multiple compressor/coil capacity selections
• Multiple control op ti on s: VAV, C V, 100% OA,
dehumidification
• Non-fused main power disconnect switch
• Dual non-fused main disconnect switches
• Non-averaging freezestat for hot water, or waterside econo-
mizer coil protection
• Unit phase failure/under voltage protection
• Premium efficiency fan motors
• TEFC fan motors
• Condenser water flow switch
• 4-row waterside economizer system
• Air cycle economizer system
• Modulating hot water heat
• Staged electric heat
• Factory mounted and controlled variable
frequency drives
• High efficiency filtration options
• Right- and left-hand piping selections
• Front and back fan discharge arrangements
• Head pressure control valve
• Special coil coatings
• Double wall cabinet construction
• Seismic fan isolation
• R407C refrigerant
• UV lights
Ultraviolet Lights
Factory-installed ultraviolet lights are available on the downstream side of all cooling coils and above the unit drain pan.
All ultraviolet lights are pre-engineered and factory installed for
ease of use and proper placement for maximum effectiveness. The
ultraviolet lamps irradiate the coil and drain pan surfaces with
light in the 245 nanometer wavelength of the light spectrum (UVC). UV-C light has proven effective in killing most bacteria,
molds, and viruses in both laboratory and practical application.
This complete package of equipment and ultraviolet lights
includes Intertek Services Inc. (ETL) safety agency certification.
Figure 11: Ultraviolet light
Features
• High-output, hot cathode lamps produce ultraviolet germicidal
irradiation (UVGI) for 254 nm that constantly irradiates the
coil and drain pan surfaces.
• Fixture design and stainless steel construction make the ultra-
violet light device suitable for saturated air conditions.
• Automatic disconnects are standard on all doors (or panels)
with line-of-sight access to the lamps to help prevent eye contact with the UV-C ultraviolet light.
• Special ultraviolet filtering glass windows block ultraviolet
light, allowing the coil, drain pan, and lights to be inspected
while in use from outside the unit.
Benefits
• For pennies a day, UVGI can improve IAQ by destroying
mold, fungi, and bacteria on coil and drain pan surfaces.
• Clean coil surfaces maintain peak heat tra nsfer for “ near new”
performance and lower energy costs.
• Reduced coil and drain pan maintenance requirements and
costs.
• Satisfies GSA federal facilities standard requirements for
UVGI lights to be incorporated downstream of all cooling
coils and above all drain pans to control airborne and surface
microbial growth and transfer.
Refrigerant R-407C
McQuay SWP units with independent refrigerant circuits are
available with non-ozone depleting R-407C refrigerant.
Features
• HFC-407C refrigerant is environmentally friendly with zero
ozone depleting allowance (ODP).
• ASHRAE Standard 34, Designation and Safety Classification
of Refrigerants, classifies HFC-407C as an A1 (lower toxicity—no flame propagation) refrigerant.
• Units are factory engineered for proper cooling performance
using R-407C.
• Units are factory charged with R-407C and synthetic oil (such
as POE), and they include components and controls specifically tailored to R-407C.
• Units are factory tested prior to shipment.
Benefits
• HFC-407C allows you to provide your tenants with a comfort-
able building environment in an environmentally friendly way.
• With no phase out date for production of HFC-407C, a reliable
supply should be available for the life of your equipment.
10McQuay Catalog 865-5
MicroTech® III Unit Controller
McQuay SWP systems continue to provide industry leading
performance, equipped with a complete MicroTech III
control system. In addition to providing stable, efficient
temperature, and static pressure control, the controller is
capable of providing comprehensive diagnostics, alarm
monitoring, and alarm specific component shutdown if
critical equipment conditions occur. The unit controllers are
factory mounted and configured for stand-alone operation or
integration with a building automation system (BAS)
through an optional communication module with our Open
Choices feature.
Open Choices Benefits for Easy Integration
Easy, low cost integration into most building automation
systems without costly gateway panels.
• Flexibility to select either BACnet® or L
communication. Units are LonMark® 3.4 certified with
the appropriate communications module for L
networks.
• Comprehensive unit control and status information is
available at the BAS regardless of communication
protocol.
• Long-term choices for equipment adds or replacements,
and for service support.
• Flexible alarm notification and prioritization with Intrinsic
Alarm Management (BACnet).
• Simplified BAS integration with the ability to set network
parameters at the unit controller, reducing installation time
and costs.
• Easy monitoring and troubleshooting of communication
status from the unit controller to the BAS.
Components
Each SWP self-contained system is equipped with a
complete MicroTech III unit control system that is preengineered, preprogrammed, and factory tested prior to
shipment. Each of the MicroTech III unit control systems is
composed of several components that are individually
replaceable for ease of service.
ONWORKS®
ONWORKS
These components include:
• Unit controller with user interface display and navigation wheel
• Optional expansion modules
• Communication module (optional)
• Pressure transducers
• Unit-mounted temperature sensors
• Zone temperature sensor packages
• Humidity sensor
Main Control Board (MCB)
The main control board (MCB) contains a microprocessor
that is preprogrammed with the software necessary to
control the unit. This provides that schedules, set points and
parameters are not lost, even during a long-term power
outage. The microprocessor board processes system input
data and then determines and controls output responses. An
RS-232 communication port is provided as standard to allow
for direct or modem access with a PC-based service tool.
Expansion Modules
These boards are used to expand the input and output
capability of the unit controller. Each board communicates
via serial data communications. These microprocessor based
boards provide independent operation and alarm response
even if communication is lost with the unit controller.
Communication Module
An optional communication module provides the means to
factory or field configure MicroTech III unit controls for
interoperability with an independent BAS. Communication
modules are available to support industry recognized
communication protocols including BACnet MS/TP,
BACnet/ IP and L
Keypad/Display
All MicroTech III unit controllers include a push/pull
navigation wheel and display. The display is a supertwist
nematic type with highly visible black characters on a
yellow background. The 5-line by 22-character format
allows for easy to understand plain English display
messages. All operating conditions, system alarms, control
parameters and schedules can be monitored from the
keypad/display. If the correct password has been entered,
any adjustable parameter or schedule can be modified from
the keypad.
ONWORKS.
Figure 12. MicroTech III Keypad/DisplayMicroTech III Unit Controls
McQuay Catalog 865-511
MicroTech® III Unit Controller
Temperature and Humidity Sensors
With the exception of the zone, outside air and return air
sensors, all temperature sensors are factory installed and
tested. Zone sensor packages are available to suit any
application. A humidity sensor is available for field
installation.
Static Pressure Transducers
All pressure transducers are factory installed and tested.
Connection and routing of field-supplied sampling tubes is
done at time of unit installation.
Zone Temperature Sensors
Two optional zone temperature sensors are available:
• Zone sensor with tenant override switch
• Zone sensor with tenant override switch and remote set
point adjustment
Timed tenant override is a standard MicroTech III
control feature.
Zone sensors are required for the controller’s purge cycle,
space reset of supply air set point, and night setback or setup
features. All zone sensors are field installed with field
wiring terminated at a separate, clearly marked terminal
strip.
Stand-alone Controller Features
MicroT ech III applied rooftop unit controls include all of the
essential features required to make them capable of
completely independent, stand-alone operation.
Internal Time Clock
An internal, battery-backed time clock is included in the
MicroTech III unit controller. Current date and time can be
quickly and easily set at the user interface keypad.
Internal Schedule
Seven daily schedules and one holiday schedule can be
entered at the keypad of all unit controllers. For each of
these eight schedules, one start and one stop time can be
entered. Up to 10 holiday periods, of any duration, can be
designated. The unit will automatically run according to the
holiday schedule on the holiday dates. To handle special
occasions, an additional ‘one event’ schedule can also be
used.
In lieu of its internal schedule, the unit can be operated
according to a network schedule from a BAS.
External Time Clock or Tenant Override Input
An input is supplied that can be used to accept a field wired
start/stop signal from a remote source. An external time
clock, a tenant override switch, or both may be connected.
Whenever the external circuit is closed, the controller
overrides the internal schedule (if activated) and places the
unit into the occupied mode.
If the internal schedule or a BAS network schedule is used,
field wiring is not required.
Timed Tenant Override
Off-hour operation flexibility is a must in today’s office
environments and even stand-alone MicroTech III controls
handle it with ease. When unit operation is desired during
unoccupied hours, initiate timed tenant override by pressing
the tenant override button on either of the optional zone
sensor packages. The unit then starts and runs in the
occupied mode for a keypad-adjustable length of time (up to
five hours). If the button is pressed again while the unit is
operating, the timer resets to the full time allowance without
interrupting unit operation. Tenant override operation also
can be initiated by a BAS.
Three Remote Set Point Adjustment Options
1 Remote user interface option (RUI).
2 Building automation system (BAS). See “Open Choices
Benefits for Easy Integration” on page 11.
3 All constant air volume-zone temperature control
(CAV-ZTC) unit controllers include an input that can
be used to remotely adjust the zone cooling and
heating set points. To use this feature, wire the optional
zone sensor package with set point adjustment to the
controller. The remote set point adjustment feature can
be enabled or disabled from the keypad at any time.
When enabled, remote set point adjustment is
available even if the return temperature is selected to
be the Control Temperature.
Auto/Manual Operation Selection
Automatic or manual operation can be controlled either
remotely or at the keypad.
All controllers include three inputs that can be used to
enable or disable cooling, heating, and fan operation from
remote switches. With the “heat enable” and “cool enable”
terminals, the operator can enable cooling, heating, or both
as desired. Using the system “off” terminals, the operator
can disable the fans, and thus the entire unit.
12McQuay Catalog 865-5
MicroTech® III Unit Controller
From the keypad, there are a variety of occupancy and auto!
manual control mode selections available to the operator:
• Control modes
– Off manual
– Auto
– Heat/cool
– Cool only
– Heat only
– Fan only
Compressor Lead-lag Selection
All unit controllers are capable of automatic compressor,
lead-lag control.
Waterside Economizer Changeover
On units equipped with a waterside economizer package, the
MicroTech III unit controller includes an internal
changeover strategy that compares entering cooling tower
water temperature to the unit’s mixed air temperature. If the
entering water temperature is less than the mixed air
temperature by a field-adjustable differential (typically 5°F
to 7ºF), the economizer control valve modulates in response
to the cooling load.
warm-up or cool-down periods or when the outdoor air
temperature is mild.
Night Setback and Setup Control
When one of the zone temperature sensors is connected to
the unit controller, night setback heating and night setup
cooling control are available. Separate, keypad
programmable night heating and cooling set points are used
to start the unit when necessary. After the unit starts, night
setback and setup control is similar to normal occupied
control except that the minimum outside air damper position
is set to zero. If the outside air is suitable for free cooling, it
is used during night setup operation.
Airside Economizer Changeover Selection
On units equipped with an economizer, there are three
methods of determining whether the outdoor air is suitable
for free cooling: two methods sense enthalpy (dry bulb
temperature and humidity) and one senses outdoor air dry
bulb temperature.
The two enthalpy changeover methods use external, factory
installed controls. One compares the outdoor ambient
enthalpy to a set point; the other is a solid state device that
compares the outdoor ambient enthalpy to the return air
enthalpy. This comparative enthalpy control can improve
total economizer performance.
All unit controls include an internal dry bulb changeover
strategy that can be selected at the keypad. When this
method is selected, the controller compares the outdoor air
dry-bulb temperature to a keypad programmable set point.
The external enthalpy control input is then ignored.
Cooling and Heating Lockout Control
All unit controls include separate keypad programmable set
points for locking out mechanical cooling and heating.
Mechanical cooling is locked out when the outdoor
temperature is below the cooling lockout set point; heating is
locked out when the outdoor temperature is above the
heating lockout set point. This feature can save energy cost
by eliminating unnecessary heating and cooling during
McQuay Catalog 865-513
MicroTech® III Unit Controller
Except for 100% outside air applications, night setback
control is available even if the unit is not equipped with any
heating equipment. When the space temperature falls to the
night setback set point, the fans simply start and run until the
temperature rises above the differential. This feature might
be useful for applications that use, for example, ductmounted reheat coils.
Morning Warm-up Control
If the Control Temperature (space or return) is below set
point when the unit enters the occupied mode, the morning
warm-up control function will keep the outside air dampers
closed while heat is supplied to satisfy set point. The outside
air damper will remain closed until either the space
temperature rises to the
heating set point or the keypad adjustable morning warm-up
timer expires (default is 90 minutes). The morning warm-up
timer supplies the minimum required amount of outdoor air
after a certain time regardless of the space temperature.
Morning warm-up control is automatically included on all
except 100% outside air units. It is available even if the unit
is not equipped with any heating equipment, for applications
that utilize, for example, duct-mounted reheat coils.
Condenser Head Pressure Control (units without
waterside economizer only)
Mechanical cooling is allowed whenever the entering
cooling tower water temperature is 55ºF or warmer, without
the use of head pressure control. When the entering water
temperature is below 55ºF, a factory-installed and factorycontrolled two-way modulating head pressure control valve
can be utilized. The regulating valve is controlled by the
MicroTech III controller to maintain refrigerant head
pressure.
During the purge time window, the unit starts and runs
whenever these three requirements are met:
• The space temperature must be warm enough to enable
occupied cooling.
• The outside air enthalpy must be low enough to enable
the economizer.
• The outside air temperature must be at least 3°F less
than the space temperature.
When any one of these conditions is no longer true, the unit
shuts down. As conditions allow, purge cycles the unit in
this manner until it enters the occupied mode.
Proportional Integral (PI) Control
The Proportional Integral (PI) control algorithm controls
modulating actuators to maintain a measured variable
(temperature or pressure) at or near its set point. For
example, it controls economizer dampers to maintain the
discharge cooling set point and it controls the supply fan
variable frequency drives to maintain the duct static pressure
set point. The integral control feature effectively eliminates
“proportional droop” (load dependent offset) resulting in the
tightest possible control.
For each PI loop, four keypad adjustable parameters allow
the control loop to be properly tuned for any application:
•Period
• Dead band
• Proportional band
• Integral time
Appropriate default values for these parameters are loaded
into each controller. These default values will provide proper
control for most applications; therefore, field tuning is
usually not required and thus start-up time is reduced.
Outdoor Air Purge Control (units with airside
economizer only)
Purge control is designed to take advantage of cool early
morning outside air conditions. It starts the fans and
modulates the economizer dampers to maintain occupied
cooling requirements during unoccupied periods, if
conditions are appropriate. This provides the opportunity to
flush the space with fresh outdoor air prior to occupancy.
Purge operation is possible only during a keypad-adjustable
time window prior to occupancy (0 to 240 minutes). When
the purge-cycle is active, mechanical cooling is disabled. To
use the purge feature, connect one of the zone temperature
sensors to the unit controller. Below is a description of purge
control operation.
14McQuay Catalog 865-5
Change Algorithm
The PI function is also used to adjust set points instead of
controlling variable speed drives or actuators directly. For
example, in zone control applications, the PI loop
automatically “changes” the discharge temperature set point
(cooling or heating) as the Control Temperature deviates
from the zone set point. Another PI loop then controls the
economizer actuator or heating valve actuator using the
current discharge temperature set point. Unlike a typical
“mastersubmaster” reset strategy, this “cascade control”
continuously adjusts the discharge set point, even if the
Control Temperature’s deviation from set point remains
constant. This means that the unit’s cooling or heating
output is set according to the actual load, not just the current
zone temperature. The tightest possible zone temperature
control results because “proportional droop” (load
dependent offset) is eliminated.
Calibrat
When initiated at the keypad by an operator, the Calibrate
function automatically calibrates all actuator position
feedback inputs and all pressure transducer inputs. It does
e
MicroTech® III Unit Controller
this by shutting the unit down and then driving all actuators
to the full closed and full open positions. The controller
records the input voltage values that correspond to these
positions. The pressure transducer input voltages, which are
assumed for 0.00-in. W.C., are also recorded. When
Calibrate is finished, enter an operator command at the
keypad to start the unit.
Field Output Signals
All MicroTech III controls include two solid-state relay
outputs that are available for field connection to any
suitable device: the remote alarm output and the occupied
output. These two outputs are used to signal field equipment
of unit status.
Remote Alarm Output: The remote alarm output can
be used to operate a 24 volt relay to provide a remote
alarm signal to a light, audible alarm, or other device
when an alarm condition exists at the unit.
Fan Operation Output: The fan operation output is
used to operate a 24 volt relay to control field equipment that depends on fan operation; for instance, to
open field installed isolation dampers or VAV boxes. T o
allow actuators enough time to stroke, the fan operation
output is energized three minutes before the fans start. It
then remains energized until thirty seconds after the uni t
airflow switch senses no airflow. The fan operation output is on whenever the unit airflow switch senses airflow.
Outside Air Damper output: Use to signal an outside
air damper actuator to open whenever the unit is in an
occupied cooling or heating condition.
Standard Control Options
SWP Self-Contained systems are available for most any
constant or variable air volume application. MicroTech III
controls offer three basic control configurations that use
sophisticated state change control logic to provide stable,
reliable and efficient control:
• Variable air volume with discharge temperature control
(DAC)
• Constant air volume with zone temperature control (S
CC)
• Constant air volume with discharge temperature control (DAC)
When combined with MicroTech III’s many available
control capabilities, both factory-installed and keypadprogrammable, these three basic configurations can be
customized to meet the requirements of the most demanding
applications.
Constant Air Volume with Zone Temperature
Control (SCC)
SCC units are available in either cooling only or cooling
with modulating heat configurations. Either of these
configurations is available for 100% recirculated, mixed, or
100% outdoor air applications.
Constant Air Volume with Discharge Temperature
Control (DTC)
DTC units are available in cooling only, cooling with singlestage “morning warm-up” heat, or cooling with modulating
heat configurations. This unit configuration can be used for
applications that have zone controlled terminal heating coils
or for constant volume, 100% outdoor air applications. The
discharge temperature control strategies used with the hybrid
DTC unit are identical to those used with the DTC unit.
Discharge Temperature Control
MicroTech III VAV-DTC and CAV-DTC controls provide
sophisticated and flexible discharge air temperature control
that is only possible with DDC systems. Separate discharge
air temperature set points are used for cooling and
modulating heating control. At the keypad, the operator can
either enter the desired set points or select separate reset
methods and parameters for each set point.
Control Temperature
The Control Temperature make s the heat/cool changeover
decision. It determines whether cooling or heating is
enabled; the discharge temperature then determines whether
cooling or heating is actually supplied. At the keypad, the
operator can choose the source of the Control Temperature
from among the following selections.
• Space temperature sensor
• Return temperature sensor
• Outside air temperature sensor (modulating heat only)
• Network communication
The operator enters separate cool and heat enable set points
and deadbands that the Control Temperature is compared
with (see <CrossReference>Figure 13). When the Control
Temperature is greater than or equal to the cooling set point
plus DB/2, cooling is enabled. When the Control
Temperature is less than or equal to the heat set point minus
DB/2, heating is enabled. If desired, these set points and
differentials can be set so that there is a dead band in which
both cooling and heating are disabled. The controller’s
software prevents simultaneous cooling and heating.
Variable Air Volume with Discharge Temperature
Control (DTC)
All VAV units provide true discharge temperature control in
addition to duct static pressure control. Cooling only,
cooling with single-stage “morning warm-up” heat, and
cooling with modulating heat configurations are available.
McQuay Catalog 865-515
MicroTech® III Unit Controller
Figure 13: Control Temperature Logic
Proportional Integral Modulation
When operating in economizer free cooling or unit heating,
the previously described PI algorithm maintains discharge
temperature control. It provides precise control of the
economizer dampers, modulating gas heat, steam or hot
water valves.
Compressor Staging
Two staging algorithms are available to control a unit’s
multiple steps of capacity control, Degree-Time (also known
as “average”) and Nearest. These control algorithms provide
reliable discharge temperature control while managing
compressor cycling rates. Constraints on compressor staging
are essential for preventing short cycling, which can reduce
compressor life by causing improper oil return and excessive
heat buildup in the motor windings.
The Degree-Time Compressor staging algorithm keeps track
of the discharge temperature and stages cooling up or down
to maintain an average temperature that is equal to the
discharge cooling set point. A stage change can occur only
(1) after the keypad adjustable inter-stage timer has expired
(five minute default setting) and (2) if the discharge
temperature is outside a keypad programmed dead band.
After these two conditions have been met, staging occurs as
the controller attempts to equalize two running totals:
degree-time above set point and degree-time below set point.
The result is that the average discharge temperature is
maintained at the cooling set point.
The Nearest Compressor staging algorithm keeps track of
the discharge temperature and stages cooling up or down to
maintain the discharge temperature as close as possible to
set point. A stage change can occur only (1) after the keypad
adjustable inter-stage timer has expired (five minute default
setting) and (2) if the control logic calculates that a stage
change will result in a discharge temperature closer to set
point than the existing condition. The controller logic
continually calculates the expected effect of a stage change
and uses this information before making a change. A change
is made only if it will bring the discharge temperature closer
to set point, resulting in a more consistent discharge
temperature, reduced compressor cycling and more stable
control VA V box control.
Supply Air Reset
By automatically varying the discharge air temperature to
suit a building’s cooling or heating needs, supply air
temperature reset can increase the energy efficiency of VAV
and CAV-DTC systems. MicroTech III controllers offer a
variety of different reset strategies that can be selected at the
keypad. Because they are keypad programmable, reset
strategies can be changed or eliminated as desired. Separate
strategies can be selected for both cooling and modulating
heat. If reset is not desired, a fixed discharge cooling or
heating set point can be entered.
The following reset methods are available:
• Space temperature
• Return temperature
• Outdoor air temperature
• Supply airflow (VAV, cooling set point only)
• External 0–10 VDC or 0–20 mA signal
• Network communication
For all temperature reset methods, the minimum and
maximum cooling and heating set points are keypad
programmable along with the corresponding minimum and
maximum space, return or outdoor air temperature
parameters. For the supply airflow method, the discharge set
point will be reset as the supply fan modulates between 30%
adjustable and 100% adjustable. For the external method,
the discharge set point will be reset as the voltage or current
signal varies over its entire range. For units in a BAS
network, the discharge set points are reset via the
communication signal.
Zone Temperature Control
MicroTech III CAV-ZTC controls provide the sophisticated
and flexible zone temperature control that is only possible
with DDC systems. Zone temperature sensors are available
with or without a remote set point adjustment. With the
remote adjustment model, the space set point can be set at
the keypad or at the zone sensor package. Even if a zone
sensor is connected, remote set point adjustment can be
enabled or disabled as desired at the keypad.
Control Temperature
The Control Temperature is the representative zone
temperature. When compared with the zone set points, the
Control Temperature determines whether the unit supplies
heating, cooling, or neither. It also determines the amount of
cooling or heating required to satisfy the load. Its source can
be selected at the keypad from among the following
selections:
• Zone temperature sensor
• Return temperature sensor
16McQuay Catalog 865-5
MicroTech® III Unit Controller
Because it is the representative zone temperature, the
Control Temperature is the primary input to the MicroTech
III zone temperature control algorithms. Control
Temperature parameters are described below. The
controller’s software will prevent cooling and heating from
being inadvertently enabled at the same time.
Change and Proportional Integral Mo du la tio n
When economizer “free” cooling or unit heating is required,
the two MicroTech III PI loops combine for cascade-type
control, providing the tightest possible zone temperature
control. By controlling the discharge temperature along with
the zone temperature, these functions eliminate temperature
variations near the diffusers that could otherwise occur as a
result of traditional zone control’s inherent lag effect.
Change: If the Control Temperature is above or below
the set point by more than the dead band, the Change PI
loop periodically adjusts the cooling or heating discharge air temperature set point either up or down as
necessary . The amount of this set point change corresponds to the Control Temperature’s position in the
modulation range. The farther the Control Temperature
is from the set point, the greater the discharge set point
change will be. The Change-adjusted discharge cooling
and heating set points are limited to ranges defined by
keypad programmable maximum and minimum values.
PI: Using the Change function’s current discharge set
point, the PI function maintains precise discharge temperature control by modulating the economizer dampers
and gas heat, steam or hot water heating valves.
Compressor Staging
Compressor staging is controlled directly by the Control
T emperature. When the Control Temperature is warmer than
the zone cooling set point, cooling is staged up; when the
Control Temperature is cooler than the zone cooling set
point, cooling is staged down. However, a stage change can
only occur when the Control Temperature is outside the dead
band (see <CrossReference>Figure 14). Staging is
constrained by an inter-stage delay timer (five minute
default setting) and minimum and maximum discharge air
temperature limits (all keypad programmable). These
constraints protect the compressors from short cycling while
eliminating temperature variations near the diffusers.
Figure 14: Compressorized Logic
Project Ahead Algorithm
Because the inherent lag effect in zone temperature control
applications can cause overshoot during warm-up or cooldown periods, MicroTech III features a “Project Ahead”
control algorithm. Project Ahead calculates the rate at which
the Control Temperature is changing and reduces the unit’s
cooling or heating output as the zone temperature nears its
set point, essentially eliminating overshoot.
Duct Static Pressure Control
On all VAV-DTC units, duct static pressure control is
maintained by the PI algorithm, which provides precise
control of the supply fan variable speed drive. The keypad
programmable set point can be set between 0.20-in. W.C.
and 4.00-in. W.C.
On larger buildings with multiple floors, multiple trunk runs
or large shifts in load due to solar effects (east/west building
orientation), an optional second duct static sensor is offered.
The MicroTech III controller automatically selects and uses
the lower of the two sensed pressures to control fan volume
to provide adequate static pressure to the most demanding
space at all times.
Operating States
Operating states define the current overall status of the selfcontained system. At the user interface, the operator can
display the current operating state and thereby quickly
assess the unit’s operating condition.
Alarm Management and Control
MicroTech III unit controllers are capable of sophisticated
alarm management and controlled response functions. Each
alarm is prioritized, indicated, and responded to with the
appropriate action. The active alarm (up to 10 alarms,
arranged by alarm priority) and previous alarm (up to 25
alarms, arrange by date/time cleared), each with a time and
date stamp, can be displayed at the user interface. Generally
speaking, whenever a current alarm is cleared, it is logged as
a previous alarm and the oldest previous alarm is removed.
Alarm Priority
The various alarms that can occur are prioritized according
to the severity of the problem. See
<CrossReference>Table 1. Three alarm categories are used:
faults, problems, and warnings.
1 Faults are the highest priority alarms. If a fault
condition occurs, the complete unit shuts down until
the alarm condition is gone and the fault is manually
cleared at the keypad. A fault example is Fan Fail
alarm.
McQuay Catalog 865-517
MicroTech® III Unit Controller
2 Problems are the next lower priority to alarms. If a
problem occurs, the complete unit does not shut down,
but its operation is modified to compensate for the
alarm condition. A problem automatically clears when
the alarm condition that caused it is gone. Compressor
Fail is an example of a problem where only the
affected compressor is shut down.
3 Warnings are the lowest priority alarms. No control
action is taken when a warning occurs; it is indicated
to alert the operator that the alarm condition needs
attention. T o make su re that they are read, the operator
must manually clear all warnings. Dirty Filter
indication is an example of a warning.
Generally, a specific alarm condition generates an alarm that
falls into only one of these categories. Under different sets
of circumstances, however, the freezestat and most of the
sensor failure alarm conditions can generate alarms that fall
into multiple categories.
Adjustable Alarm Limits
Four alarm indications have adjustable limits that are used to
trigger the alarm. The high return temperature alarm and the
high and low supply temperature alarms are adjusted at the
user interface. The dirty filter alarm(s) is adjusted at the
sensing device.
Table 1: MicroTech III Alarm Summary
Alarm NameFaultProblemWarning
FreezeXX
SmokeX
Temperature Sensor
Failure
Duct High LimitX
High Return TemperatureX
High Discharge
Temperature
Low Discharge
Temperature
Fan FailureX
Fan RetryX
Discharge Air Capacity
Feedback
Economizer StuckXX
Auxillary Control Board
Enabled
Low AirflowX
Circuit 1–8
High Pressure
Circuit 1–8
Low Pressure/Frost
Compressor 1–8 Motor
Protection
Compressor 1–8 FailureX
Airflow Switch
(False Airflow)
Dirty FilterX
XX
X
X
X
X
X
X
X
X
18McQuay Catalog 865-5
Application Considerations
The following section contains basic application and installation
guidelines which must be considered as part of the detailed analysis of any specific project.
General
Units are intended for use in normal heating, ventilating and air
conditioning applications. Consult your local McQuay sales representative for applications involving operation at high entering
condenser water temperatures, high altitudes, non-cataloged voltages and for applications requiring modified or special control
sequences. Consult your local McQuay sales representative for
job specific unit selections that fall outside of the range of the catalog tables, such as 100% outside air applications.
For proper operation, rig units in accordance with instructions
stated in IM 709.
Factory check, test and start procedures must be explicitly followed to achieve satisfactory start-up and operation
(see IM 709).
Many self-contained system applications take advantage of the
significant energy savings provided by the use of economizer
operation. When a water economizer system is used, mechanical
refrigeration is typically not required below an entering condenser
water temperature of 55°F. Standard McQuay self-contained systems are designed to operate with entering water temperatures
down to 50°F when a water economizer is used and 55°F with no
water economizer. For applications where a water economizer
system cannot be used, a modulating head pressure control system
is available to permit operation at entering condenser water temperatures below 55°F.
Unit Location
Make sure that the floor is structurally strong enough to support
the unit with minimum deflection (See “Unit and Component
Weights in lbs.” on page 42). Provide proper structural support to
minimize sound and vibration transmission. A concrete floor
should be considered. Extra caution is required when installing on
a wooden structure. Units must be installed level from front-toback and over their length.
Unit fresh air intakes must be located away from building flue
stacks, exhaust ventilators and areas containing automotive or
other exhaust to prevent the possible introduction of contaminated
air to the system. Consult code requirements for minimum fresh
air volumes.
Allow sufficient space around the unit for service and maintenance clearance. Refer to Figure 15 for recommended service/maintenance clearances. See also “Recommended
Clearances” on page 19“. Locate equipment room access doors in
a manner that can assist in service access if needed (i.e., coil
removal). Contact your local McQuay sales representative if
reduced service/maintenance clearances are required.
Where code considerations, such as the NEC, require extended
clearances, they take precedence over minimum service/maintenance clearances.
Acoustical Considerations
Good acoustical design is a critical part of any successful installation and should start at the earliest stages in the design process.
Each of the four common sound paths must be addressed. These
are: (1) radiated sound through the casing of the unit, (2) structure
borne vibration, (3) airborne sound through the supply air duct
and (4) airborne sound through the return air duct.
Some basic guidelines for good acoustic performance include:
1. Always provide proper structural support under the unit.
2. Provide adequate mass in the floor structure, especially
when located over an occupied space where good acoustics are essential.
3. Seal all supply and return air duct penetrations once the
duct is installed.
4. Don't overlook the return air path. Always include some
duct work (acoustically lined tee) at the return inlet.
5. Minimize system static pressure losses to reduce fan
sound generation.
6. Select the appropriate unit/fan for the application. Fans
should be selected as close as possible to their peak
static efficiency. To assist you, peak static efficiency is
identified by the first system curve to the right of the
shaded "Do not select" region on each fan curve.
7. Design duct systems to minimize turbulence.
8. Account for low frequency duct breakout noise in system design. Route the first 20' of rectangular duct over
non-sensitive areas and avoid large duct aspect ratios.
Consider round or oval duct to reduce breakout.
Recommended Clearances
For good installation, service and maintenance access, follow recommended clearances. Minimum clearances required by local,
state or federal codes, such as the NEC, take precedence over
those listed below. Clearance is required to allow room for side
filter access, mechanical cleaning of condenser tubes and economizer coil access to expansion valves and other control components and to allow for possible fan shaft or compressor removal.
Unit Front42 inch
Unit Rear24 inch
Motor Location Side36 inch
Piping Location Side36 inch
Side Without Motor or Piping24 inch
Clearance at Face of VFD42 inch
For clearance requirements less than those indicated, consult
your local McQuay sales
representative.
A lined section of supply air duct should extend at least 15 feet
from the equipment room. The use of round duct should be
reviewed as it will significantly reduce low frequency sound near
the equipment room. If rectangular duct is used, the aspect ratio of
the duct should be kept as small as possible. The large flat surfaces associated with large aspect ratios will transmit sound to the
space and the potential for duct generated noise, such as oil canning, is increased. The maximum recommended supply air duct
velocity is 2000 feet per minute.
When direct ducting to the fan outlet, a minimum of two fan
diameters from the fan outlet is recommended and the elbow
should turn in the direction of fan rotation. Abrupt turns, takeoffs,
etc., will generate air turbulence and resulting unwanted sound
and should be avoided.
Duct Protection
An adjustable duct high limit switch is standard equipment on all
SWT system's with VAV controls. This is of particular importance
Note: 36 inches are required if water and condensate drain
connections are left-hand, or fan discharge arrange-
when fast acting, normally closed boxes are used. The switch is
field adjustable and must be set to meet the specific rating of the
system ductwork.
ment is back.
Vibration Isolation
Equipment Room
Locate the equipment room away from sound sensitive areas.
Whenever possible, isolate the equipment room from these areas
by locating rest rooms, utility rooms, stairwells, hallways, elevators, etc., around its perimeter. This allows not only isolation from
radiated sound but provides the capability to route ductwork over
less sensitive areas.
Acoustically seal the equipment room. All equipment room penetrations should be sealed with a high quality, flexible material to
prevent air and noise from escaping. Even a small leak will compromise the acoustic performance of the installation. The equipment room door should seal tightly on a perimeter gasket.
Equipment room wall construction should be concrete block or
offset, double stud. The decision will depend on the critical nature
of the application. If offset, double stud construction is used the
cavity should be lined with glass fiber insulation and a double
layer of sheetrock used on each side of the wall.
Ductwork
Fan noise can be carried through the ductwork to occupied spaces
and likely will be the most challenging to control. Careful duct
design and routing practice is required. The ASHRAE Applications Handbook discusses sound attenuation relevant to self-contained system applications. Contact your local McQuay sales
representative for sound power data for designing the appropriate
sound levels for your specific application.
Return Duct
The return duct is the most often over looked. Return air can be
ducted directly to the unit or ducted into the equipment room. If
ducted to the equipment room, an elbow should be installed
within the equipment room. Running a return air drop to near the
floor of the room will provide added attenuation. A length of lined
ductwork should extend from the equipment room to a l ength of
15 feet. The maximum recommended return air duct velocity is
1000 feet per minute.
Duct connections to the unit or to the acoustic discharge plenum
should be made with a flexible connection. Flexible piping and
electrical connections should not be required, but attention should
be paid to these areas to avoid vibration transmission from outside
sources to the SWT unit.
Condenser Water Piping
Always follow good industry practice in the design of the water
piping system. Attention to water treatment and proper strainer
application are always necessary. All SWT systems feature
mechanically cleanable condensers and optional waterside economizer coils. In addition to mechanically cleanable heat exchangers, cleanouts are provided in the interconnecting piping and in
the internal condensate drain trap. Costly field traps are not
required. To allow periodic cleaning of the condensers and economizer coils, isolation valves should be provided. Condensers,
economizer coils and hot water coils are provided with vent and
drain connections.
Always review for possible requirements for condenser piping
insulation, especially if cold entering condenser water conditions
(<55°F) will be experienced.
Head Pressure Control
If cold entering condenser water conditions (<55°F) will be experienced, a waterside economizer or a condenser head pressure
control valve is required. A 2-way, head pressure activated control
valve is available factory installed for these applications. A head
pressure control valve is not required when the SWT unit is
applied with factory waterside economizer package.
Variable Air Volume
Variable frequency drives offer reliable speed control over a wide
range of airflow, with advantages in sound and energy performance. In addition, McQuay offers the ability to sense duct static
pressure in multiple locations, enhancing control accuracy and
helping minimize energy use.
20McQuay Catalog 865-5
hp2hp
1
density
2
density
1
---------------------
rpm
2
rpm
1
------------
3
=
Application Considerations
Variable Frequency Drives
Variable frequency drives provide the most efficient means of
variable volume control by taking advantage of the fan law relation between fan speed (rpm) and fan brake horsepower (bhp).
Also, since airflow reduction is accomplished by changing fan
speed, the noise penalties often associated with mechanical control devices, e.g. inlet vanes, are not introduced. The following
equation illustrates how fan bhp varies as the cube of the change
in fan speed:
In an ideal system, at 50% fan speed, brake horsepower would be
reduced to 12.5% of that at full speed.
Variable frequency control varies the speed of the fan by adjusting
the frequency and voltage to the motor. Keeping a constant
volts/frequency ratio (constant magnetic flux) to the motor allows
the motor to run at its peak efficiency over a wide range of speeds
and resulting fan airflow volumes.
Duct Static Pressure Sensor Placement
The static pressure should be sensed near the end of the main duct
trunk(s). The MicroTech III static pressure control should be
adjusted so that at full airflow all of the terminals receive the minimum static pressure required plus any downstream resistance.
Control is to the lowest static pressure set point that will satisfy
airflow requirements. Lower static pressure setpoints will reduce
fan brake horsepower requirements and fan sound generation.
The static pressure sensor tap should be located in the ductwork in
an area free from turbulence effects and at least 10 duct diameters
downstream and several duct diameters upstream from any major
interference, including branch takeoffs. The SWT MicroTech III
control system can receive a second duct static pressure sensor in
installations having multiple duct trunks or significantly varying
zones. The control logic will maintain static pressure at both sensors.
Zone Sensor Placement
Placement of the zone temperature sensor is extremely important
to provide proper and economical operation of the heating and
cooling system. It is generally recommended that the space sensor
be located on an inside wall (3 to 5 feet from an outside wall) in a
space having a floor area of at least 400 square feet. The sensor
should not be located below the outlet of a supply air diffuser, in
the direct rays of the sun, on a wall adjacent to an unheated or
abnormally warm room (boiler or incinerator room), or near any
heat producing equipment. Where zone sensor placement is a
problem, all SWT zone control systems have, as standard, the
capability to use the return air sensor for heating & cooling control.
Filtration
Filters should be routinely replaced to minimize filter loading. As
filters get dirty, the filter pressure drop increases, affecting system
airflow and energy requirements. Depending on fan type, forward
curved or airfoil, this airflow change can be significant. The effect
of filter loading is the most critical when using high efficiency filters.
When making a fan selection, a pressure drop component for filters as they get dirty should be included in the system total static
pressure. A value midway between clean and dirty filter ratings is
recommended. If a minimum airflow is critical, the fan selection
should be made using the higher, dirty filter pressure drop value.
For VAV systems, consider setting the fan control device such that
part of its modulation range can be used to maintain airflow as filters become dirty. Following these recommendations should limit
airflow fluctuation as the filters load.
System Operating Limits
SWT units can be applied in a wide range of system needs. High
cfm/ton or high/low discharge temperature applications are available. However, for proper system operation, some application limits do apply.
Airflow
Maximum cfm limits, based on coil face velocity, are
givenTable 4 on page 25.
Separate minimum design cfm limits, by unit size, are given in the
physical data table for constant and variable air volume applications. Fan modulation should be limited to 40% of the minimum
design cfm limit. Minimum airflow conditions are also dependent
on fan selection criteria. Contact your McQuay sales re prese nta tive to answer any questions on minimum airflow capability or for
conditions not shown in the catalog.
VAV box minimum airflow settings should correspond with the
minimum VAV fan operating point. All units are provided with
multi-groove, fixed pitch sheaves. During system air balance,
alternate fixed pitch sheaves may be needed to match final system
requirements. Alternate sheaves are available from McQuay.
Fan Heat
Sensible heat gain from the fan, fan motor and drives occurs in all
fan systems and its effect must be considered during equipment
selection. It is an added load in cooling and an added source when
in heating. The majority of the heat gain occurs through the fan
itself, as the air is elevated from the low-pressure side to the highpressure side of the fan. Moving the motor out of the air stream
has a negligible effect on overall fan heat gain. A unit with higher
fan power requirements/higher fan heat will have less net cooling
capability and may not have enough left to satisfy system loads.
As a "rule of thumb," a typical supply fan heat gain is 3°F. However, fan heat gain can be quickly calculated once the fan has been
selected and the fan brake horsepower has been determined.
Using Figure 16, "Fan & Motor Heat Gain", select your fan brake
horsepower on the horizontal axis, move up vertically until you
intersect with the heat gain curve and then move horizontally to
find the fan heat gain in Mbh.
McQuay Catalog 865-521
Application Considerations
Figure 16. Fan and Motor Heat Gain
(Fan Heat (Mbh)
Fan T emperature rise =
(1.085 x Fan cfm)
A draw through unit has the fan located after the DX cooling coil.
In this arrangement, fan heat is applied as reheat to the cold, conditioned air coming off of the coil. This arrangement will have a
lower sensible heat ratio and higher dehumidification capability
than a blow through coil arrangement. The discharge temperature
available to the supply duct is always the sum of the coil leaving
air temperature plus the fan temperature rise. This must be considered when selecting the supply air volume required to satisfy
space requirements.
Example:
52°F leaving coil temp.
+ 3°F fan temp. rise = 55°F discharge air temp.
Condenser Water Flow
System capacity tables provide selections for a condenser flow
rate of 3 gpm/ton. For a given entering condenser water temperature, 3 gpm/ton will provide maximum unit performance. Reducing condenser water flow rates to 2.5 or 2 gpm/ton can
significantly reduce pumping energy costs and reduce piping
costs. The reduction in pumping energy can be compared to the
change in unit performance and an evaluation made. The SWT
capacity tables can be used for condenser flow rates from 2 to 3
gpm/ton by using the appropriate leaving condenser water temperature column (interpolation is allowed). Minimum condenser
flow rate is 2 gpm/ton.
Coil Freeze Protection
Consideration must always be made for coil freeze protection
when applying units in geographic areas which see subfreezing
temperatures. Careful design of outside air/return air mixing systems is critical to minimizing freeze potential. Some applications
may require the use of glycol and/or preheat coils. No control
sequence can prevent coil freezing in the event of power failure.
A nonaveraging type freezestat is factory installed on all units
with hot water heat or waterside economizer. If a potential freeze
condition is sensed, unit water valves will be driven to the full
open position, the supply fan de-energized and an alarm signal
sounded.
In nonducted return applications where the equipment room is the
mixing plenum, some form of heat within the equipment room
should be considered.
Air Density Correction
Fan performance data is based on standard 70°F air temperature
and zero feet altitude (sea level). For applications other than standard, a density ratio must be multiplied to actual static pressure
values. Density correction factors are expressed as a function of
temperature and altitude in Table 2.
Table 2. Temperature and altitude conversion factors
All units require 3-phase, 60 Hz, 208, 230, 460 or 575 volt power
or 3-phase, 50 Hz, 400 volt power. Units will operate satisfactorily at ±10% of rated voltage at the power connection terminals of
the unit. All units include individual branch circuit fusing of all
motor loads and have a single-point power connection. A factory
mounted, nonfused disconnect switch is an available option.
All wiring must be installed in accordance with the NEC and local
codes.
22McQuay Catalog 865-5
Selection Procedure
Achieving the optimal performance of any system requires both
accurate system design and proper equipment selection. Factors
which control unit selection include applicable codes, ventilation
and filtration requirements, heating and cooling loads, acceptable
temperature differentials and installation limitations. McQuay
SWT units offer a wide selection of component options providing
the capability to meet diverse application needs.
The McQuay SelectTools™ software selection program allows
your local McQuay sales representative to provide you with fast,
accurate and complete selection of McQuay SWT units. Unit
selection can also be accomplished through reference to physical,
performance, dimensional and unit weight data included in this
catalog. Due to the variety of cooling system options available,
only a sampling of cooling capacity data has been presented in
this catalog
Proper equipment selection can be accomplished by following
these three simple steps:
1. Select unit size and compressor combination.
2. Selecting heating system.
3. Select fan and motor.
The following example is provided to illustrate the catalog selec-
tion procedure
Selection Example:
Scheduled Design Requirements:
Supply air volume12,000 cfm
Maximum face velocity550 fpm
Supply fan external SP2.00" w.g.
Altitudesea level
Variable air volume system with fan speed control
Hot water heat
Water economizer system
30% pleated filters
460V/60Hz/3Ph
Double wall construction
Stainless steel drain pan
Premium efficiency motor
Summer Design:
DX coil mixed air dry bulb80F
DX coil mixed air wet bulb67F
Sensible load345,000 Btu/hr
Total load450,000 BTU/hr
Supply fan sensible heat
rise
Entering condenser water 85F
Leaving condenser water 95F
Minimum condenser water 55F
3F
Winter Design:
Return air temperature60°F
Space heating load450 mbh
Entering hot water temperature 180°F
Step 1 - Unit Size Selection
Unit size is based on coil face area and cooling capacity requirements. Supply air capacity and maximum face velocity constraints
should serve as a guide for selecting coil dimensions and cabinet
size.
Based on the given data, the appropriate coil face area may be
determined as follows:
Minimum face area = supply air volume/maximum face velocity
=12,000 cfm/550 fpm
= 21.8 square feet
Note: Unit data is based on standard air conditions of
70°F at sea level. See “Application Considerations”
on page 20 for temperature/altitude conversion factors for non-standard conditions.
Referring to Table 4 on page 25 under the Physical Data section,
the 23.3 square foot coil of the SWT040C satisfies the requirements.
Step 2 - Unit DX Cooling Selection
Since the design cfm is less than the nominal value in the DX
Cooling Capacity Data table, the capacities must be adjusted.
See Table 5. DX Cooling Capacity Correction Multipliers on
page 26 .
Using the "DX Cooling Capacity Data" tables provided, the unit
selection is a SWT040C with (1) 6hp and (3) 10hp compressors.
Unit performance from the table equals 512.8 TMBH/375.9
SMBH at 123gpm. Adjusting for the lower cfm yields:
Total capacity = 512.8 MBH x .973 = 499.0 MBH
Sensible capacity = 375.9 MBH x .929 = 349.2 MBH
Coil LAT = 80º F - 349.2 MBH / (1.085 x 12,000 cfm) = 53.2°F.
Condenser flow rate = 123 gpm x .973 = 120 gpm
Step 3 - Economizer Capacity Selection
Determine the Waterside Economizer Capacity by referring to
Table 18 on page 30. Use entering air of 80/67°F and entering
water of 55°F at 120 gpm. Interpolating for the required gpm,
economizer performance equals 276.3 TMBH / 261.9 SMBH at
the unit's nominal cfm. Using the Waterside Economizer Capacity
Correction Factors (Table 6 on page 26), performance at the specified cfm can be found.
Total capacity = 276.3 MBH x 0.943 = 260.6 MBH
Sensible capacity = 261.9 MBH x 0.904 = 236.8 MBH
McQuay Catalog 865-523
Selection Procedure
Step 4 - Heating Selection
Determine hot water capacity from Table 19 on page 31. After
interpolating for the specified cfm, Table 19 indicates a total of
457mbh.
Step 5 - Fan/Motor Selection
Fan/motor selection is based on unit total static pressure and
design airflow. Total static pressure includes the internal air pressure drops of unit components and external air pressure drops of
supply and return air duct systems. See “” on page 31 for internal
pressure drops of unit components. Values in the table may be
interpolated for the specified cfm.
Internal pressure drops:
DX coil (wet surface)0.68" w.g.
Economizer coil (dry surface)0.38" w.g.
Hot water coil0.11" w.g.
4", 30% efficient filters0.19" w.g.
Total internal pressure drop1.36" w.g.
Entering the fan curve for the SWT040C at 12,000cfm and 3.75"
w.g., yields 13.0 required fan brake horsepower . A 15 horsepower
motor can be selected.
Step 6 - Calculating Unit Weight
Referring to Table 29 on page 42, for a SWT040C:
Unit weight = SWT basic unit + 6 row evaporator coil
+ economizer coil + water (econ. coil)
+ hot water coil + water (HW coil) + [(1) 6 hp,
(3)10 hp] compressor / condenser
+ water (condenser) SAF + SAF motor + VFD
= 1473 + 450 + 410 + 11 1 + 152 + 32 + 1233 + 74 + 1 120 + 185 + 50
= 5,290 Lbs.
Step 7 - Supply Power Wiring
Sizing supply power wire for a unit is based on the circuit with the
highest amperage draw. All electrical equipment is wired to a central control panel for either single or optional dual power connections. See “” on page 40 for FLA and RLA ratings. Determine
Minimum Circuit Ampacity (MCA) as follows:
MCA = [1.25 x RLA or FLA of largest motor] + [1.00 x RLA or
FLA of all other loads] + [2 amps (controls)]
RLA/FLA
(1) 6 horsepower compressors8.1 amps each
(3) 10 horsepower compressors14.1 amps each
15 horsepower premium efficiency
Note: If a unit has been selected with non-concurrent electric
heat, MCA must be calculated for both the heating mode and the
cooling mode and the larger value used.
18.9 amps
Step 8 - R-407C Performance
The cooling tables (starting on page 26) document the old R-22
cooling capacity and compressor kW. The R-407C performance
correction factors vary slightly with the unit size and operating
conditions but can be estimated as shown in the table below. Use
the McQuay SelectTools™ computer selection program to obtain
the exact R-407C performance.
Table 3. R-407C correction facto r
Compressor capacity
0.96 to .98
24McQuay Catalog 865-5
Table 4. SWT 018C Through SWT 040C
Physical Data
Data
018C023C028C035C040C
SWT Model Size
Compressor
Quantity44444
SizeSee DX Cooling Capacity Tables
Evaporator Coil
Face Area (Ft.
2
)
11.815.318.923.326.3
Rows4, 64, 64, 64, 64, 6
Fpi1212121212
Performance
a
EER / IPLV13.33
13.9514.713.4713.27
Waterside Economizer Coil
Face Area (Ft.
2
)
11.815.318.923.326.3
Rows44444
FPI1212121212
Maximum Working Pressure (psig)400400400400400
Hot Water Heating Coil
Face Area (Ft.2)
9.312.816.320.223.8
Rows1, 21, 21, 21, 21, 2
Fpi1212121212
Electric Heat
Kw3434343434
Filters
(Qty) size (in)
4” depth
Evaporator Fan
b
(3) 20 x 20(3) 20 x 20(3) 20 x 20(5) 20 x 20(5) 20 x 20
(2) 25 x 20(2) 25 x 20(2) 25 x 20(5) 25 x 20(5) 25 x 20
(4) 16 x 25(4) 16 x 25(4) 16 x 25
Quantity11122
Size1518181515
Minimum Horsepower57.5101015
Maximum Horsepower1015202025
Minimum Design cfm, CV29503825472558256575
Minimum Design cfm, VAV472061207560932010520
Maximum Design cfm70809180113401398015780
Condensers
Waterside Working Pressure (psig)400400400400400
Minimum Entering Temperature (°F)
Mechanical Cooling
5555555555
Minimum GPM 2541536669
Maximum GPM88108125159166
a. Based on ARI 340/360-93 standard rating conditions, 80/67°F to the coil, 85-95° condenser water.
b. Standard fan TSP limit is 5.5 inches of water. Consult your local McQuay sales representative for applications beyond this range.
For 50 Hz applications, the total capacity must be derated by 0.89 and the sensible capacity must be derated by 0.94. The 50 Hz supply
fan motor horsepower selections must be based on fan brake horsepower (from Fig ure 21th rough Figur e 29 ) divided by 0.8.
DX Cooling Capacity Data
SWT023C - 8000 CFM
Table 7. SWT023C - 8000 CFM (4 Compressors)
CompressorsEDB(°F)EWB(°F)EWT(°F)TMBHSMBHLDBLWBGPM
75298.6230.448.648.471
7562
(4)6HP
Note: See T able5 DX Cooling Capacity Correction Factors on page26 for determining unit capacity at other than nominal cfm. For a comp uter genera ted job specific selection, con tact you r
local McQuay sales representative. For 50 Hz applications, the tot al cap ac ity must be dera ted by 0.89 and the sensible cap acity must be derate d by 0.94. All cap acit ies ar e gross an d
do not account for fan motor heat.
Altitude and/or Glycol selections also available.
Note: See Table5 DX Cooling Capacity Correction Factors on page 26 for de termining unit capacity at other than nom inal cfm.
For a computer generated job specific selection, contact your local McQuay sales representative.
For 50 Hz applications, the total capacity must be derated by 0.89 and the sensible capacity must be derated by 0.94.
All capacities are gross and do not account for fan motor heat.
Altitude and/or Glycol selections also available.
Note: Fan TSP limit is 5.5" of water. Consult your local McQuay sales representative for applications beyond this range.
36McQuay Catalog 865-5
3.25
23.58
19.33
9.58
18.25
33.75
L
G x H
Return air
FILTER SECTION
ECONOMIZER
EVAPORATOR
HEATER
ELECTRICAL PANEL
A
Sloped S. S.
drain pans
Condenser
Compressor
Sloped S. S.
drain pans
3.25
23.58
19.33
9.58
18.25
33.75
L
G x H
Return air
FILTER SECTION
ECONOMIZER
EVAPORATOR
HEATER
ELECTRICAL PANEL
Condenser
Compressor
A
Dimensional Data
Figure 26. Left Side, Front (CW) DischargeFigure 27. Left Side, Back (CCW) Discharge
Note: Select unit arrangement on the unit selection.
Table 22. SWT018C - 040C Dimensions
BASIC UNIT018C023C028C035C040C
A
B
C
DFan Discharge18.6221.8821.8818.6218.62
EFan Discharge15.8818.8818.8815.8815.88
FUnit Side to Fan32.6931.0631.0623.8823.88
GReturn Duct Height45.9445.9445.9445.9445.94
HReturn Duct Length80.0080.0080.0096.0096.00
JWater Out/In (ODS)2-1/82-1/82-1/82-5/82-5/8
KHot Water Out/In (ODS)1-5/81-5/81-5/81-5/81-5/8
LTo Fan Discharge2.02.02.06.466.46
a. Dimensions do not include lifting lugs, handle, latch, or fastener extensions.
b. For shipping dimensions add 4" (102mm) to depth, 8" (204mm) to length, and 4" (102mm) to height.
Depth
Length
Height
a b
a b
52.0052.0052.0052.0052.00
a b
84.0084.0084.00100.00100.00
112.75112.75112.75112.75112.75
McQuay Catalog 865-537
FFDD
15.0
(381)
E
34.0
(864)
78.5
(199.4)
B
72.0
(182.8)
Mechanical
Access
Power entry
7/8" (2.2) KO
Electrical
Access
MicroTech II
System
Indicator
Panel
Fan
Outlets
1.0 (25)Neoprene
Isolation Pads
shipped separately
Connection
Plate
Return Air
Unit Front Plan
Left side piping
connections
Right side piping
connections
(optional)
Supply fan motor
Front Elevation
(For dimentions B, D, E and F see Table 5)
AFD
(Optional)
L
3.125 (79)
Power Entry
Dimensional Data
Figure 28. Unit Front Plan and Front Elevation
Note: 1. See Table 25 for dimensions B, D, E, F and L.
2. Service connections determined when facing the front of the unit. Left-hand standard, right-hand optional. Please indicate on the unit submittal.
3. Unit sizes 018C, 023C, and 028C have single fan.
4. Unit sizes 018C, 023C, and 028C have single mechanical access panel in bottom front and bottom back.
38McQuay Catalog 865-5
Figure 29. Back Elevation and Left Side (typical SWT018C - 040C)
Mechanical access
Connection
plate
2.0 TYP
G x H
Return air opening
Mechanical acces s (3 ) (4 )
26.63
1.0 Neoprene
Isolation pads
shipped separately
C
B(2)
Back Elevation
23.81
(K) Hot Water Out
(K) Hot Water In
10.38
A
A
36.5
Main
Lifting rod
(by others)
Place through
base channel
Filter/water
economizer
1.12 ODS drain
(J) Water out
(J) Water in
G x H
Retun air
Left Elevation
Main and filter/waterside
economizer connection
Section A-A
Dimensional Data
Note: 1. Filters are removable from the rear of the unit or through a side filter access door, located on piping connection side.
2. Length will be increased by approximately 3-1/2”, for piping connections when water economizer option is ordered
3. Mechanical access panels(s) in the back of the unit start 2” below return duct opening. Do not obstruct the access panel(s).
4. There are two access doors on 018C, 023C, and 028C instead of three as shown.
5. All dimensions are given in inches.
6. All dimensions are ±0.25”.
Note: Note:
McQuay Catalog 865-539
Electrical Data
Table 23. SAF Motor Nameplate Amp Table
HorsepowerTYPE
3
5
7.5
10
15
20
25
a. 460/60/3 motors are used. Derate nameplate horsepower to 0.83 to obtain actual horsepower.
i.Nam eplate 208V: Min. 187V, Max. 229V
ii.Nameplate 230V: Min. 207V, Max. 253V
iii. Nameplate 460V: Min. 414V, Max. 506V
iv. Nameplate 575V: Min. 518V, Max. 632
b. 50 Hertz
i.Nam eplate 400V: Min. 342V, Max. 418V
3. Power lead wire sizing:
a. For units with cooling capability (all concurrent
loads) with or without hot water heating and circuits with motor loads only:
MCA = 1.25 (largest motor RLA or FLA) + other
loads + 2 amps
b. For units with cooling capability and non concur-
rent electric heat capability:
In the cooling mode, the loads will be composed of
supply fan motor and compressors. In heating
mode, the loads will be compose of supply fan
motor and electric heater. The MCA is calculated
for unit running in either mode; the highest value
obtained is used for the MCA.
i.Fo r unit in cooling mode:
MCA = 1.25 (largest RLA or FLA) + other
loads + 2 amps
ii.For unit in heating mode:
MCA = 1.25 (electric heat FLA + supply fan
motor FLA) + 2 amps
Note: Use copper wire only.
4. Size wires in accordance with T able 310-16 or 310-19 of
the National Electrical Code.
5. Wires should be sized for a maximum of 3% voltage
drop. See Table 27 and Table 28 for Single Disconnect
or Power Block lug sizes.
2. Hot water coil weight includes valves and piping.
3. Supply fan weight does not includ e motor or VFD.
018C023C028C035C040C
Unit Size
42McQuay Catalog 865-5
Engineering Guide Specifications
General
Furnish and install, as shown on plans, McQuay model SWT selfcontained packaged air conditioning system(s). Unit performance, electrical characteristics and unit arrangement shall be per
the job schedule.
[Each unit shall be completely factory assembled and shipped in
one piece.] [Each unit shall be shipped in two pieces, a base unit
section and the unit fan section.] All units shall be shipped with a
full charge of Refrigerant 22 or 407C and oil. Unit ratings shall be
in accordance with the latest update of ARI Standard 360.
All units shall have decals and tags to indicate caution areas and
to aid in unit service. A unit nameplate shall be fixed to a permanent panel next to the main control panel access. Electrical wiring
diagrams shall be supplied with each unit. Installation, operating
and maintenance bulletins and start-up forms shall be supplied
with each unit.
Factory Run Test
Each unit shall undergo a rigorous factory run test prior to shipment and factory test sheets shall be available upon request. The
factory test shall include dynamic trim balancing of the completed
fan assembly, a compressor run check, a complete run test of all
electrical components and safeties, including proper control
sequencing, a leak check of all refrigerant circuits, a leak check of
all water circuits and a final unit inspection.
Safety Agency Listed
The complete unit(s) shall be ETL-US and ETL-Canada listed by
Intertek Testing Services, Inc. Units shall conform to bi-national
standard ANSI/UL Standard 1995/CSA Standard C22.2 No. 236.
Unit(s) shall be accepted for use in the City of New York by the
Department of Building, MEA #368-93-E Vol. II.
Cabinet, Casing and Frame
Each unit shall have a welded 3/16" structural steel base integrated with formed members of 10, 12 and 14 gauge continuous
galvanized steel. Exterior frame and panels shall be constructed of
pre-painted galvanized steel for aesthetics and long term durability. Paint finish to include a base primer with a high quality, polyester resin topcoat of a neutral beige color. Finished surface to
withstand a minimum 750-hour salt spray test in accordance with
ASTM B117 standard for salt spray resistance. Lifting brackets
capable of handling the unit shipping weight shall be welded to
the unit base with holes to accept cable or chain hooks.
Each unit shall be compartmentalized for ease of service and shall
be designed to permit adjustment of system electrical and refrigeration components while the unit is in operation. The unit shall
incorporate removable access panels tightly set on neoprene gaskets. Access panels shall be a minimum of 18-gauge galvanized
steel and shall be located on all sides of the unit for complete
accessibility. The airside cabinet shall be insulated with 1", 1.5
pound density coated glass fiber insulation. [Solid galvanized
steel liners shall be provided, allowing no exposed insulation
within the air stream.]
The unit shall be comprised of three distinct sections: 1) Main
cooling/heating, 2) Filter/waterside economizer and 3) Fan section. Each unit shall be designed for disassembly into the three
distinct sections for access to the mechanical equipment room.
Disassembly of the unit shall not require the breaking of any
refrigeration lines. Separation of water piping shall be through the
use of factory installed grooved couplings. The maximum allowable section width, including fastener heads, shall not exceed 34.5
inches.
Filter/Economizer Section:
Filters
Each unit shall be provided with an integral filter section complete with 4" panel filters. The filters shall be removable from the
rear of the unit and shall have side access capability through
[access panels] [hinged and latched access doors] on each end of
the unit. The use of 2" filters is not acceptable.
[4" thick, 30% efficient, UL Std. 900, Class II, AmericanAirFilter
filters shall be provided. Filters shall be frame mounted and shall
slide into galvanized steel tracks contained within the unit.]
[4" thick, 60-65% efficient, UL Std. 900, Class II, AmericanAirFilter Varicel filters shall be provided. Filters shall be frame
mounted and shall slide into galvanized steel tracks contained
within the unit.] [An auxiliary pre-filter rack, with 2" thick 30%
efficient filters, shall be provided to upstream of the high efficiency filters.]
[4" thick, 80-85% efficient, UL Std. 900, Class II, AmericanAirFilter Varicel filters shall be provided. Filters shall be frame
mounted and shall slide into galvanized steel tracks contained
within the unit.] [An auxiliary pre-filter rack, with 2" thick 30%
efficient filters, shall be provided to upstream of the high efficiency filters.]
Waterside Economizer
A complete waterside economizer package shall be provided
including a mechanically cleanable [chemically cleanable] coil,
control valves and factory piping complete with cleanouts. Coils
shall be fabricated of seamless 1/2" diameter copper tubing that is
mechanically expanded into high efficiency aluminum plate fins.
Coils shall be a minimum 4-row, staggered tube design with 12
fins per inch. The complete economizer package shall be rated for
400psig waterside working pressure.
The economizer section shall be complete with an insulated stainless steel drain pan. The drain pan shall be sloped in two directions to provide positive drainage. Access panels on both sides of
the unit shall provide convenient access to the coil, valves and
drain pan for inspection and cleaning. A factory installed drain
line, with trap and cleanout, shall be provided for convenient connection at the unit exterior.
Economizer operation shall be controlled to maximize free cooling. Economizer operation shall be enabled whenever the entering
water temperature is less than the entering air temperature by a
field adjustable value. The economizer control valve shall modulate in response to the cooling load. Control valve operation shall
[maintain full flow through the unit at all times.] [isolate the unit
from the condenser water loop when there is no call for cooling,
allowing for the use of an energy saving, variable pumping system.]
Mechanical cooling shall be enabled during economizer operation. If the economizer control valve is driven 90% open and the
cooling load is not satisfied, compressors will stage on to maintain set point. To maximize energy savings, economizer control
will maintain full water flow until the differential between entering water and entering air temperatures falls below set point.
A factory installed, non-averaging type freezestat shall provide
some protection against coil freeze-up.
McQuay Catalog 865-543
Engineering Guide Specifications
The completed economizer assembly shall be factory leak tested.
Airside Economizer Control
(External Mixing Box)
Integrated airside economizer control capability of a separate unit
or remote mounted mixing box shall be provided. Economizer
operation shall be controlled to maximize free cooling operation.
Economizer shall be enabled whenever the remote [outside air
enthalpy sensor] [comparative enthalpy sensors] [outside air temperature sensor] indicates that outside air is suitable for free cooling. The remote economizer damper actuator shall modulate in
response to the cooling load.
Mechanical cooling shall be enabled during economizer operation. If the outside air damper is driven to 90% open and the cooling load is not satisfied, compressors will stage on to maintain set
point. To maximize energy savings, the economizer control will
maintain 100% outdoor airflow until disabled by the enthalpy or
temperature cutout. Outside air will reset to minimum position at
that time.
Fan Section
Fan Assembly
All fan assemblies shall be statically and dynamically balanced at
the factory, including a final trim balance, prior to shipment. All
fan assemblies shall employ solid steel fan shafts. Heavy-duty pillow block type, self-aligning, grease lubricated ball bearings shall
be used. Bearings shall be sized to provide an L-50 life at 200,000
hours and shall be no smaller than the main shaft diameter. The
entire fan, drive and motor assembly shall be mounted on a
welded, heavy-gauge tubular steel frame and shall be mounted on
[spring isolators] [spring isolators with seismic restraints]. The
fan assembly shall further be isolated from the unit with a flexible
connection at the fan discharge. Fixed pitch V-belt drives with
matching belts shall be provided. V-belt drives shall be selected at
[the manufacturer's standard service factor] [1.5 times fan brake
horsepower].
The fan assembly shall feature a gradual expansion, aerodynamic
duct outlet to reduce system sound generation.
Fan (SWT018C-028C)
The supply air fan shall be a double width, double inlet (DWDI)
forward curved centrifugal fan, with hub and shaft secured with
mating keyways. The fan wheel and housing shall be constructed
from painted steel and shall be Class II construction to satisfy the
specified application.
Fan (SWT035C & 040C)
The supply air fan system shall be dual, double width, double inlet
(DWDI) forward curved centrifugal fans, with hubs and shaft
secured with mating keyways. The fan wheels and housings shall
be constructed from painted steel and shall be Class II construction to satisfy the specified application.
Fan Motor
Fan motors shall be heavy-duty 1800 rpm [open drip-proof
(ODP)] [totally enclosed fan cooled (TEFC)] type with grease
lubricated ball bearings. [Motors shall be high efficiency and meet
applicable EPACT requirements.] [Motors shall be premium efficiency.] Motors shall be NEMA, T-frame, Class B. Motors shall
be mounted on an adjustable base that provides for proper alignment and belt tension adjustment.
Variable Frequency Drives (SWT18C-040C)
An electronic variable frequency drive shall be provided for the
supply air fan. Variable frequency drives shall be latest generation
pulse width modulation type utilizing IGBT technology. The
drive shall be factory installed in a designated location that provides ready access to the drive and does not void unit accessibility. Drives shall meet UL Standard 95-5V and the variable
frequency drive manufacturer shall have specifically approved
them for plenum duty application. The completed unit assembly
shall be listed by a recognized safety agency, such as ETL.
The unit manufacturer shall install all power and control wiring.
A manually activated bypass contactor arrangement shall be provided. The bypass arrangement will allow fan operation at full
design CFM, even if the drive has been removed for service.
The supply air fan drive output shall be controlled by the factory
installed main unit control system and drive status and operating
speed shall be monitored and displayed at the main unit control
panel. A factory mounted, field adjustable duct high-limit control
shall be provided to protect ductwork from excessive duct pressure. The installer shall provide and install sensor tubing from [a
single unit mounted pressure sensor] [two unit mounted pressure
sensors] to the duct location(s).
All drives shall be factory run tested prior to unit shipment.
Coils
Drain Pan
The main coil section shall be complete with an insulated stainless
steel drain pan. The drain pan shall be sloped in two directions to
provide positive drainage. Access panels on both sides of the unit
shall provide convenient access to the coil and drain pan for
inspection and cleaning. A factory installed drain line, with trap
and cleanout, shall be provided for convenient connection at the
unit exterior.
Cooling Coil
Direct expansion (DX) cooling coils shall be fabricated of seamless 1/2" diameter high efficiency copper tubing that is mechanically expanded into high efficiency aluminum plate fins. Coils
shall be a 6-row, staggered tube design with 12 fins per inch. All
units shall have an independent refrigerant circuit per compressor
and shall use a combination row/interlaced circuiting for efficient
part load operation and to prevent air temperature stratification at
partial load conditions. Each circuit shall be fed by an adjustable
thermal expansion valve, with external equalizer, sized to provide
efficient operation at full and at part load operating points. Plastic
sleeves shall protect all distributor tubes.
All coils shall be factory leak tested with high pressure air under
water.
Hot Water Coil
A 1 row hot water heating coil shall be factory installed. Coils
shall be fabricated of seamless 1/2" diameter copper tubing that is
mechanically expanded into high efficiency aluminum plate fins.
All coil vents and drains shall be factory installed. Access panels
shall provide convenient access to the coil and valve for inspection and cleaning.
A factory installed two-way [modulating] [on/off] control valve
and actuator shall provide control of the hot water coil. The valve
actuator shall be controlled by the factory installed main unit control system.
44McQuay Catalog 865-5
Engineering Guide Specifications
[Propylene glycol shall be added to the hot water circuit to protect
against coil freeze-up.]
[A factory installed, non-averaging type freezestat shall provide
some protection against coil freeze-up.]
Coils shall be factory leak tested with high pressure air under
water.
Electric Heat
Staged electric heating coils shall be factory installed in the unit heat
section. Heating coils shall be visible and easily accessed for inspection and service. Heating coils shall be constructed of low watt density, nickel-chromium elements. Equipment protection controls shall
include automatic reset high limit control for each heater element
with manual reset backup line break protection in each heater element branch circuit. Heating element branch circuits shall be individually fused to a maximum of 48 Amps per NEC requirements.
Multiple full magnetic line break contactors shall be controlled by the
factory installed main unit control system to provide multiple stages
of control.
Condensers
Condensers shall be a counter flow, tube and tube design with all
nonferrous water channels. Each condenser shall be on an independent refrigerant circuit and shall provide liquid sub-cooling for
optimum system performance. Condensers shall be rated for
400psig refrigerant working pressure. Each condenser shall be
suitable for 400psig waterside working pressure and shall be
mechanically cleanable. All factory piping shall be capable of a
waterside working pressure of 400 psig. Condensers shall be factory piped to provide for single field condenser water supp ly and
return connections.
Units provided with condensers that are not mechanically cleanable will not be acceptable.
Condensers shall be factory leak tested with high pressure air
under water. The completed condenser and interconnecting piping assembly shall be factory leak tested.
Condenser head pressure control
(Not available with Water Economizer)
Mechanical cooling shall be available whenever entering condenser water temperatures are 55ºF or warmer, without the use of
head pressure control. For entering condenser water temperatures
below 55ºF, a factory installed and controlled 2-way modulating
head pressure control valve shall be provided. The valve actuator
shall be controlled through the factory installed main unit control
system to maintain refrigerant head pressure at entering condenser
water temperatures as low as 40°F.
Compressors
Each unit shall have multiple, heavy-duty scroll compressors.
Each compressor shall be on an independent refrigerant circuit
and include [suction and discharge service valves with gauge
ports], sight-glass, anti-slug protection, motor overload protection
and a time delay to prevent short cycling and simultaneous starting of compressors following a power failure. Compressors shall
be isolated on resilient rubber isolators to decrease noise transmission. The number of compressors shall be as shown on the unit
schedule.
Refrigeration Controls
Each unit shall have multiple independent refrigeration circuits.
Each circuit shall include a filter-drier, liquid moisture indicator/sight-glass, thermal expansion valve, liquid line shutoff valve
with charging port and high pressure relief device. The thermal
expansion valve shall be capable of modulation from 100% to
25% of its rated capacity. [Shutoff valves shall isolate each filterdrier and sight-glass. (Units with compressor service valves
only.)] Sight-glasses shall be accessible for viewing without disrupting unit operation. Each circuit shall be dehydrated and factory charged with Refrigerant 407C and oil.
Each refrigerant circuit shall have a high and low-pressure cutout
switch and a coil frost protection thermostat. The high pressure
cutout shall be a manual reset control. Each low pressure control
(loss of charge) and frost protection thermostat shall require a
manual reset if the alarm condition occurs three times within any
24 hour period.
Refrigeration Capacity Control
Refrigeration capacity control shall be accomplished by staging of
the unit's multiple compressors. To maintain desired temperature
control, the unit shall have a minimum of [two] [three] [four]
steps of capacity control.
All compressor capacity control staging shall be controlled by the
factory installed main unit control system.
Electrical
Unit wiring shall comply with NEC requirements and with all
applicable UL standards. All electrical components shall be UL
recognized, where applicable. To provide for easy identification,
all wiring and electrical components shall be numbered, colorcoded and labeled according to the electrical diagrams provided
with each unit. The main unit control panel shall be completely
factory wired and contained in an accessible enclosure. The main
control panel shall be provided with dead front covers over all line
voltage components. A terminal board shall be provided for low
voltage control wiring. Branch circuit fusing, 115V control circuit transformer with fuse, system switches and high temperature
sensor shall also be provided.
Pilot knockouts shall be provided at the main control panel for
field wiring entrance. The unit shall have a [single] [dual] [terminal block] [non-fused disconnect] for main unit power connection.
Each compressor shall be controlled by its own dedicated contactor, shall be individually fused and shall have thermal overload
protection. The supply fan motor circuit shall include a dedicated
contactor, external line break overload protection and dedicated
fuse protection. Group fusing of components in lieu of individual
fuse protection for each component is not acceptable.
The unit control system shall permit starting and stopping of the
unit locally or remotely . The keypad/display and monitoring panel
shall include a three position "on", "off", "auto" switch, an Alarm
indication light and a Power indication light. The Alarm light
shall provide a visual indication whenever a malfunction occurs
and it shall remain until the malfunction is corrected. The control
system shall be capable of providing a remote alarm indication.
The unit control system shall provide for pump start, outside air
damper actuation, smoke shutdown, emergency shutdown, remote
heat enable/disable, remote cool enable/disable, heat indication,
cool indication, fan interlock and fan operation.
McQuay Catalog 865-545
Engineering Guide Specifications
Non-fused Disconnect Switch
[A single non-fused disconnect switch shall be provided for disconnecting electrical power at the unit. The switch handle shall be
visible, located at the front of the unit, and shall be accessible
without unit entrance.]
[Dual non-fused disconnect switches shall be provided for disconnecting electrical power at the unit. One switch will service the
supply fan plus the unit control system. The second switch will
service the condensing unit section. Disconnect switch handles
shall be visible, located at the front of the unit, and shall be accessible without unit entrance.]
Phase Failure/Under Voltage Protection
A phase failure/under voltage protection device shall be provided
to protect three-phase motors from damage due to single phasing,
phase reversal and low voltage conditions.
Water Flow Switch
A water flow switch shall be provided, factory installed, to verify
water flow status at the unit. Compressor operation shall be disabled and an alarm signal provided if condenser water flow is lost.
Unit operation will be restored when water flow has again been
sensed. Water flow status shall be displayed at the unit's main
controller.
Freezestat
(Units with Waterside Economizer)
A non-averaging type freezestat shall be factory installed on the
entering face of the economizer coil. Upon sensing a freeze condition, the unit supply air fan will be shut down, the [economizer]
[heating] [economizer and heating] valve will be driven to the full
open position and an alarm signal will be provided. Unit operation
will be restored following the manual reset of the freezestat.
Freezestat
(Units without Waterside Economizer)
A non-averaging type freezestat shall be factory installed on the
leaving face of the hot water heating coil. Upon sensing a freeze
condition, the unit supply air fan will be shut down, the heating
valve will be driven to the full open position and an alarm signal
will be provided. Unit operation will be restored following the
manual reset of the freezestat.
Battery Pack
The unit shall be provided with a factory mounted and wired
rechargeable battery pack. The battery pack shall be available to
provide control power to unit actuators in the event of a power
failure.
UV Lights
Unit to have factory-mounted UV lights located on the leaving air
side of the cooling coil. Unit to have view port to allow for visual
indication of operation through UV resistant glass. Unit to have
door interlocks on each removable panel accessing UV light.
Interlock to kill power to UV light when panel is removed.
Lamp and fixture to consist of a housing, power source, lamp
sockets, and lamp. All components are to be constructed to withstand typical HVAC environmen ts and are UL/C-UL listed. Housings are to be constructed of type 304 stainless steel and are to be
equipped with both male and female power plugs with one type at
each end to facilitate simple fixture-to-fixture plug-in for AC
power.
Power source shall be an electric, rapid-type with overload protections and is to be designed to maximize radiance and reliability
at UL/C-UL listed temperatures of 55°F–135°F. Power source
will include RF and EMI suppression.
Sockets shall be medium bi-pin, single click safety, twist lock
type and are to constructed of a UVC-resistant polycarbonate.
Lamp shall be a high output, hot cathode, T8 diameter, medium
bi-pin that produces UVGI of 254 nm. Each tube produces the
specified output at 500 fpm and air temperatures of 55°F–135°F.
MicroTech III Unit Controller
Each unit shall be equipped with a complete MicroTech III microprocessor based control system. The unit control system shall
include all required temperature and pressure sensors, compressor
control boards, heating control board, main microprocessor control board and opera-tor interface. The unit control system shall
perform all unit control functions including scheduling, [constant
air volume, zone temperature control (SCC)] [constant air volume, discharge temperature control (DAC)] [variable air volume,
cooling only discharge temperature control [with single-stage
morning warm-up heat] (DAC)] [variable air volume, cooling/modulating heating discharge temperature control (DAC)]
[duct static pressure control], [building static pressure control],
unit diagnostics and safe-ties. All boards shall be individually
replaceable for ease of service. All microprocessors, boards, and
sensors shall be factory mounted, wired and tested.
The microprocessor shall be a stand-alone DDC controller not
dependent on communications with any on-site or remote PC or
master control panel. The microprocessor shall maintain existing
set points and operate stand alone if the unit loses either direct
connect or network communications. The micro-processor memory shall be protected from voltage fluctuations as well as any
extended power failures. All factory and user set schedules and
control points shall be maintained in nonvolatile memory. No settings shall be lost, even during extended power shutdowns.
The main microprocessor shall support an RS-232 direct connection to a product service tool or a modem. A [BACnet
[BACnet
vided for direct connection into the BAS network.
All digital inputs and outputs shall be protected against damage
from transients or wrong voltages. Each digital input and digital
output on the main microprocessor shall be equipped with an LED
for ease of service. An alarm LED on the user interface shall provide quick visual identification that an alarm condition exists. All
field wiring shall be terminated at a separate, clearly marked terminal strip.
The microprocessor shall have a built-in time schedule. The
schedule shall be programmable from the unit keypad interface.
The schedule shall be maintained in nonvolatile memory to insure
that it is not lost during a power failure. There shall be one
start/stop per day and a separate holiday schedule. The controller
shall accept up to sixteen holidays each with up to a 5-day duration. Each unit shall also have the ability to accept a time schedule
via BAS network communications.
If the unit is to be programmed with a night setback or setup function, an optional space sensor shall be provided. Space sensors
shall be available to support field selectable features. Sensor
options shall include:
1. Zone sensor with tenant override switch.
MS/TP] [LonTalk] communications port shall be pro-
/IP]
46McQuay Catalog 865-5
Engineering Guide Specifications
2. #1 plus a heating and cooling set point adjustment. (CAV-ZTC
only)
The unit keypad/display character format shall be 20 characters x
4 lines. The character font shall be 5 x 8 dot matrix. The display
shall be a supertwist nematic (STN) LCD display with black characters on yellow background for high visibility. For ease of service, the display format shall be English language readout. Coded
formats with look-up tables shall not be acceptable.
The keypad interface shall be equipped with eight individual
touch-sensitive membrane key switches that allow convenient
navigation and access to all control functions. All control settings
shall be password protected against unauthorized changes.
The user interaction with the display shall provide the following
information:
32. System operating hours
a. Fan
b. Cooling
c. Individual compressor
d. Heating
e. Economizer
f. Tenant override
g. Dehumidification
The user interaction with the keypad shall provide the following
set points as a minimum:
1. Control modes
a. Off manual
b. Auto
c. Heat/cool
d. Cool only
e. Heat only
f. Fan only
2. Occupancy mode
a. Auto
b. Occupied
c. Unoccupied
d. Tenant override
3. Control temperature (changeover)
a. Return air temperature
b. Space temperature
c. Network signal
d. Outdoor air temp. (VAV w/ mo d. heat )
4. Cooling with deadband
5. Heating with deadband
6. Cooling and heating supply
7. Cooling & heating supply reset options
a. Return air temperature
b. Outdoor air temperature
c. Space temperature
d. Airflow (VAV)
e. No reset
f. Network signal
g. External (1-5 VDC)
8. Temperature alarm limits
a. High supply air temperature
b. Low supply air temperature
c. High return air temperature
9. Lockout control
a. Compressor lockout
b. Heat lockout
10. Lead-lag on compressors
a. Auto
b. Disabled
11. Compressor Inter-stage timers
12. Night setback and setup space temp.
13. Duct static pressure reset options
a. No reset
b. Network
14. Building static pressure (opt.)
15. Minimum outdoor airflow reset
a. Percent of CFM capacity
b. External reset (1-5 VDC)
c. Fixed outdoor damper position
16. Economizer changeover
a. Enthalpy
b. Dry bulb
17. Current time and date
18. Tenant override time
19. Occupied/unoccupied time schedules
20. One event schedule
McQuay Catalog 865-547
Engineering Guide Specifications
21. Holiday dates and duration
22. Service mode
a. Timers normal (all time delays normal)
b. Timers fast (all time delays 20 sec.)
c. Mode normal (unit on)
Open Communications Protocol
The unit control system shall have the ability to communicate to
an independent Building Automation System (BAS) through a
direct [BACnet
tions connection.
[BACnet
col (ANSI/ASHRAE135-2001). A protocol implementation conformance statement (PICS) shall be provided. Multiple units may
be connected in a common communications network.]
[Communications shall conform to LonMark
Guidelines and shall be certified. Controls shall conform to the
[Discharge Air Controller (DAC)] [Space Comfort Controller
(SCC)] profile.]
Through communications, the BAS System Integration (SI) contractor shall be capable of interacting with the individual self-contained unit controllers in the following ways:
/IP] [BACnet MS/TP] [LonTalk] communica-
Communications shall conform to the BACnet proto-
®
Interoperability
1. Access to [quantity and description from specification] “read
only” variables and [quantity and description from specification] “read & and write” variables.
2. Set the un it's operati ng mode.
3. Monitor controller in puts, outputs, setpoints, parameters and
alarms.
4. Chan ge contro ller setpoin ts and confi guration
parameters.
5. Clear alarms.
6. Reset the cooling discharge air temperature setpoint (DAC
units).
7. Reset the heating discharge air temperature setpoint (DAC
units with modulating heat).
8. Reset the duct static pressure setpoint (DAC units).
9. Set the heat/cool changeove r temperature (DAC units).
10.Set the representative zone temperature (DAC units).
It will be the responsibility of the SI Contractor to integrate the
self-contained unit data into the BAS to affect the integrated
building control logic and centralized system workstation interface.
48McQuay Catalog 865-5
McQuay Training and Development
Now that you have made an investment in modern, efficient McQuay equipment, its care should be a high priority. For
training information on all McQuay HVAC product s, please visit us at www.mcquay.com and click on training, or call
540-248-9646 and ask for the Training Department.
Warranty
All McQuay equipment is sold pursuant to its standard terms and conditions of sale, including Limited Product
Warranty. Consult your local McQuay Representative for warranty details. Refer to Form 933-430285Y. To find your
local McQuay Representative, go to www.mcquay.com.
Aftermarket Services
To find your local parts office, visit www.mcquay.com or call 800-37PARTS (800-377-2787). To find your local service
office, visit www.mcquay.com or call 800-432-1342.
This document contains the most current product information as of this printing. For the most up-to-date product
information, please go to www.mcquay.com.
Products manufactured in an ISO certified facility.