McQuay SWT023C User Manual

Catalog 865-5
Modular Self-Contained Air Conditioning Systems
Type SWT 023C—040C 20 to 45 Tons
Engineered for flexibility and performance™
Continued Leadership in Floor-By-Floor,
Self-Contained System Designs . . . . . . . . . . . . . . 3
Agency Listed . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
System Performance Providing Tenant Comfort
and Operating Economy . . . . . . . . . . . . . . . . . . . . 4
McQuay Self-Contained VAV Systems . . . . . . . . . 4
Cabinet, Casing and Frame . . . . . . . . . . . . . . . . . 5
Modular Design . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Condensing Section . . . . . . . . . . . . . . . . . . . . . . . 5
Design Features . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Cooling Coil Section . . . . . . . . . . . . . . . . . . . . . . . 6
Heating Section . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Supply Fan Section . . . . . . . . . . . . . . . . . . . . . . . . 6
Economizer Options . . . . . . . . . . . . . . . . . . . . . . . 7
Filter Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Auxiliary Control Options . . . . . . . . . . . . . . . . . . . 8
Selection/Application Flexibility . . . . . . . . . . . . . . . 9
Modular Construction . . . . . . . . . . . . . . . . . . . . . . 9
System Flexibility . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Ultraviolet Lights . . . . . . . . . . . . . . . . . . . . . . . . . 10
Refrigerant R-407C . . . . . . . . . . . . . . . . . . . . . . . 10
®
MicroTech
III Unit Controller . . . . . . . . . . . . . . . 11
Open Choices Benefits for Easy Integration . . . . 11
Alarm Management and Control . . . . . . . . . . . . . 17
Application Considerations . . . . . . . . . . . . . . . . . 18
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Unit Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Acoustical Considerations . . . . . . . . . . . . . . . . . . 19
Recommended Clearances . . . . . . . . . . . . . . . . 19
Equipment Room . . . . . . . . . . . . . . . . . . . . . . . . 19
Ductwork . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Vibration Isolation . . . . . . . . . . . . . . . . . . . . . . . . 20
Condenser Water Piping . . . . . . . . . . . . . . . . . . . 20
Head Pressure Control . . . . . . . . . . . . . . . . . . . . 20
Variable Air Volume . . . . . . . . . . . . . . . . . . . . . . 20
Variable Frequency Drives . . . . . . . . . . . . . . . . . 20
Duct Static Pressure Sensor Placement . . . . . . . 20
Zone Sensor Placement . . . . . . . . . . . . . . . . . . . 20
Filtration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
System Operating Limits . . . . . . . . . . . . . . . . . . . 21
Coil Freeze Protection . . . . . . . . . . . . . . . . . . . . 22
Air Density Correction . . . . . . . . . . . . . . . . . . . . . 22
Unit Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Application Considerations . . . . . . . . . . . . . . . . . 22
Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . 23
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Unit Efficiency Ratings . . . . . . . . . . . . . . . . . . . . 26
Correction Multipliers . . . . . . . . . . . . . . . . . . . . . 26
DX Cooling Capacity Data . . . . . . . . . . . . . . . . . 26
Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . 26
Waterside Economizer Capacity . . . . . . . . . . . . . 29
Heating Capacity Data . . . . . . . . . . . . . . . . . . . . 31
Component Pressure Drops . . . . . . . . . . . . . . . . 31
Fan Curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . . 37
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Supply Power Wiring . . . . . . . . . . . . . . . . . . . . . . 41
Unit Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Engineering Guide Specifications . . . . . . . . . . . . 43
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Safety Agency Listed . . . . . . . . . . . . . . . . . . . . . 43
Cabinet, Casing and Frame . . . . . . . . . . . . . . . . 43
Filter/Economizer Section . . . . . . . . . . . . . . . . . . 43
Fan Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
MicroTech III Unit Controller . . . . . . . . . . . . . . . . 46
Open Communications Protocol . . . . . . . . . . . . . 48
2 McQuay Catalog 865-5
SWT - 040 - C
Self-contained Water-cooled Top mounted fan
Design vintage
Nominal capacity
Introduction
Continued Leadership in Floor-By-Floor, Self-Contained System Designs
McQuay SWT self-contained air conditioning systems trace their history to the late 1970s and the pioneering concepts of Blazer Industries. Working closely with the consulting engineer to solve special system and space challenges, Blazer Industries developed and provided the first self-contained, variable air volume systems with water side economizer cycle for the prestigious 499 Park Avenue office building. Following the success of this project was more than a decade of innovation and product leadership, with thousands of systems provided for prominent building projects.
In 1991, McQuay acquired Blazer Industries. The result has been a continuation of this tradition of innovation and leadership. The comprehensive, updated modular McQuay SWT system offering is now supplying quiet, efficient and flexible systems to meet today’s diverse and demanding performance needs for new and retrofit, commercial, industrial and institutional buildings world­wide.

Nomenclature

Agency Listed

McQuay and MicroTech are registered trademarks of McQuay International.
DesignFlow, Hi-F, Protocol Selectability, RoofPak, SelectTools, SpeedTrol, SuperMod, UltraSeal, and VaneTrol
Microsoft is a registered trademark of Microsoft Corporation.
Copyright © 2011 McQuay International. All rights reserved throughout the world.
are trademarks of McQuay International.
Windows is a trademark of Microsoft Corporation.
McQuay Catalog 865-5 3
McQuay Self-Contained VAV Systems

System Performance Providing Tenant Comfort and Operating Economy

Since the introduction of self-contained systems in the late 1970s, the industry has seen this concept grow into one of the most widely specified systems for new office buildings, for retrofitting existing structures, and for institutional, industrial, and other spe­cialized applications. The reason is simple: system performance. Designed specifically to satisfy growing system retrofit needs, McQuay SWT self-contained VAV systems provide the total per­formance advantage of:
Modular construction
• Prime candidate for building renovation
• Special 34.5" maximum section width fits through a 3' door frame
• Refrigerant lines always remain intact
• Requires minimum floor area when reassembled
• Retrofit alternative where existing chiller cannot be accessed for replacement
Tenant Comfort
• Tenants enjoy individual control over comfort conditions and off-hour system operation
• Tenants benefit from their individual efforts to control energy costs
• Routine service is located where it minimizes tenant inconvenience
• Individual or dual systems per floor provide system redundancy and standby
First cost economics
• VAV system flexibility uses building diversity to reduce system tonnage and first cost
• Factory packaged concept reduces field labor, installation time and expense
• No expensive chilled water piping or chiller room
• Individually tested, factory designed systems reduce start-up and installation expense
• Reduce penthouse and equipment room requirements
• Centralize condenser water and condensate piping and streamline system layout
Energy-saving VAV system control
• Reduces fan kW and operating costs at part load condi­tions
• Savings maximized through use of variable speed fan control
• Individual zone control without overcooling or use of reheat
Quiet system operation
• Provided by structural quality and specialized design
• Recognized for quiet operation by renowned U.S. acous­tical consultants
Energy saving economizer operation
• Water or air economizer capability for optimized energy savings
• Economizer reduces compressor operating hours and energy costs
• Year-round “free cooling” capability
Energy saving building part load operation
• System energy efficiency comparable to central chilled water systems
• Multiple systems and compressors versus a single, large central plant
• Efficient system for partial occupancy and after hours operation
• Operate only the system(s) on the floor(s) requiring after hours use
Figure 1. McQuay Self-Contained VAV Systems
System savings of advanced MicroTech III™ DDC
control system
• Monitoring and diagnostics reduce the potential for expensive field repairs
• Industry leading Protocol Selectability™ feature provides effective BAS selection flexibility
Reduced system maintenance and service costs
• No complicated central chiller plant to maintain
• Service and maintenance are performed out of the occu­pied space
• Control and product reliability functions designed by the equipment manufacturer for single source responsibility and improved reliability
4 McQuay Catalog 865-5
Fan Section
Filter / Waterside Economizer Section
Main Heating / Cooling Section
Design Features

Cabinet, Casing and Frame

For vibration control and rigging strength, the SWT unit base is constructed of welded structural steel channel and 10- gauge gal­vanized steel panels. Heavy-duty lifting brackets are strategically placed for balanced cable or chain hook lifting.
For long equipment life, unit exterior panels are constructed of heavy gauge, pre-painted, galvanized steel. The complete cabinet, frame and access panels are insulated with 1 inch thick, 1.5 lb. dual density insulation. Double wall construction is available to enhance performance and satisfy IAQ requirements.
For maintenance and service ease, system components are strate­gically located for ease of inspection and maintenance. Refrigera­tion components are positioned out of the airstream so adjustments and readings can be made without disrupting system operation. Service friendly access is made through heavy-duty, conveniently removable panels. Access panels are set on neoprene gaskets to prevent air leakage.

Modular Design

The SWT unit is easily disassembled into three compact sections; main cooling/heating, filter/waterside economizer and fan. See “Modular Construction” under “System Flexibility” on page 9.
Figure 2. SWT Cabinet

Condensing Section

Multiple compressors are featured in all SWT systems for effi­cient system part load control, quiet operation and system redun­dancy. Compressors are quiet, reliable hermetic scroll type complete with sightglass, anti-slug protection, and motor overload protection. Suction and discharge service valves, with gauge ports, are available on each compressor. Individual branch circuit fusing protects each compressor. The unit’s MicroTech III™ con­trol system incorporates timing functions to prevent compressor short cycling. All compressors are resiliently mounted to mini­mize any noise transmission. The condensing section is insulated and segregated from the air handling section of the unit to avoid transmission of noise to the circulated air stream.
Figure 3. Copeland SpecterTM scroll compressor
Each compressor is on an independent refrigerant circuit complete with filter-drier, liquid moisture indicator/sightglass, thermal expansion valve capable of modulation from 100-25% of its rated capacity, liquid line shutoff valve with charging port, high pres­sure relief device and high and low pressure cutouts. If any com­pressor is made inoperable, the remaining compressors are still allowed to operate.
The unit’s MicroTech III controller senses entering condenser water temperature and prevents mechanical cooling when the tem­perature falls below an adjustable setpoint value, minimum 55°F. For systems which will see entering condenser water temperatures below 55°F, a waterside economizer or head pressure activated control valve is available.
SWT water cooled condensers feature a mechanically cleanable, all copper design using the same high performance enhanced tub­ing found in modern centrifugal chillers. Liquid refrigerant sub­cooling is provided as standard. Each condenser is part of an independent refrigerant circuit and comes complete with a spring loaded high pressure relief valve. All condensers are indepen­dently leak tested. All completed units are leak tested, evacuated and shipped with a full operating charge of R-22 and oil. R-407C is also available as an alternate selection.
The condenser assembly and all factory water piping is rated for a waterside working pressure of 400 psig and is factory leak tested before shipment. Condenser water channels are mechanically cleanable by removing brass service plugs that are sealed with
McQuay Catalog 865-5 5
Refrig. Flow Ckt 1 Refrig. Flow Ckt 2
Ckt 2
Ckt 1
Ckt 1
Ckt 1
Ckt 1
Ckt 1
Ckt 1
Ckt 1
Ckt 1
Ckt 2
Ckt 2
Ckt 2
Ckt 2
Ckt 2
Ckt 2
Ckt 2
Airflow
a02
Design Features
reusable o-ring gaskets. Main interconnecting condenser water headers include vent and drain plugs and a large cleanout plug for removing debris dislodged during cleaning. Condensers are fac­tory piped for a single condenser water supply and a single con­denser water return connection.
Both right-hand and left-hand piping locations are available.

Cooling Coil Section

SWT evaporator coils incorporate a high efficiency ripple corru­gated fin design. SWT system design maximizes coil face area without developing uneven, performance robbing di sr upt ions in airflow patterns. The result is high coil performance and reduced static pressure losses. Coils are 4 or 6 row configurations.
The evaporator coil is mounted in a stainless steel double sloped drain pan. The condensate drain line is trapped internal to the unit, eliminating the expense and inconsistency of field installed traps.
Figure 4. Evaporator Coil Circuiting
Hot Water Heat
Hot water coils have 1 or 2 rows with high efficiency ripple corru­gated fin design and 1/2 inch O.D. seamless copper tubes. Coils are available complete with a factory mounted, piped and wired 2­way or modulating valve controlled by the unit’s MicroTech III controller. A factory mounted freezestat is provided to help pro­tect against coil freeze-up.

Supply Fan Section

Figure 5. Supply Fan
The supply fan section uses one or two double width, double inlet medium pressure forward curved fans and housings. Each fan is statically and dynamically balanced. The fan assembly is con­structed of high strength structural steel and welded for maximum strength. The entire fan assembly is mounted on spring isolators for excellent isolation effectiveness. Seismic control restrained spring isolators are available. A vibration dampening flex connec­tion is installed at the fan discharge. The entire fan, motor and drive assembly is dynamically balanced at the factory for quiet operation.
All evaporator coils are interlaced circuiting, keeping the full face of the coil active to eliminate air temperature stratification. For optimum part load performance, all three and four circuit evapora­tor coils are circuited for both interlaced and row control. Com­pressor staging is sequenced to take maximum advantage of available coil surface.
Each evaporator coil circuit is furnished with a wide range ther­mostatic expansion valve with an adjustable superheat setting and external equalizer.
Supply fans are configured with a gradual expansion, aerody­namic duct within the cabinet. This unique gradual expansion fea­ture contributes to the high performance of the SWT by lowering brake horsepower and sound power levels.
All fans are mounted on solid steel shafts rotating in 200,000 hour pillow block ball bearings with grease fittings. Multiple belt, fixed pitch sheaves are matched to the specific cfm, static pres­sure and horsepower requirements of the system. Drives rated for a minimum of 150% of fan design are available. Drive compo­nents and fan bearings are easily accessed for periodic mainte-

Heating Section

SWT units are available as cooling only systems or with factory installed electric or hot water heat for morning warm-up, constant volume and specialty heating requirements.
Electric Heat
nance. Fan motors are three phase, NEMA design B, rated at 40°C.
Motor availability includes high efficiency open drip-proof and totally enclosed, EPACT compliant, NEMA T-frame selections and premium efficiency selections. Motors are 1800 RPM with grease lubricated ball bearings.
The factory assembled electric heating coils are constructed of low watt density nickel-chromium elements for long lasting dura­bility. Electric heaters are protected by automatic reset high limit controls and line break protection. Heater branch circuits are indi­vidually protected by branch circuit fusing. The MicroTech III control system sequences the electric heating elements for operat­ing economy.
6 McQuay Catalog 865-5
Design Features
Energy saving advanced technology variable frequency drive (VFD) fan speed control is available with the convenience and cost savings of factory mounting and testing. All VFD selections are plenum rated. A manually activated bypass contactor is avail­able to allow system operation even in the event of drive service.
MicroTech III controls provide advanced duct static pressure con­trol. Static pressure can be controlled by either a single or two duct static pressure sensors. All VAV systems include an adjust­able duct high-limit switch to protect duct work from excessive pressure.

Economizer Options

Waterside Economizer
An energy saving, waterside economizer package is available on all units. The complete economizer system is factory mounted including a 4-row mechanically cleanable coil, control valves and factory piping complete with cleanouts. The complete economizer package is rated for up to 400 psig waterside working pressure and the entire coil and piping assembly is factory leak tested.
Economizer operation is controlled by the SWT’s MicroTech III controller to maximize free cooling potential. Economizer opera­tion is enabled whenever the available cooling tower water tem­perature is less than the unit entering air temperature by a field adjustable value, generally 5-7°F. The economizer control valve modulates in response to the cooling load. Control valve operation can be selected to (1) maintain full flow through the unit at all times or (2) isolate the unit from the condenser water loop when there is no call for cooling to save energy with a variable pumping system. (Economizer control valves do not eliminate the need to provide unit isolation valves.) To extend free cooling savings, mechanical cooling is enabled during economizer operation. Only when the economizer valve is driven 90% open and the cooling load is not satisfied, will compressors be staged to maintain cool­ing setpoint. Economizer control will maintain full free cooling capability until disabled by the economizer changeover setpoint. A factory mounted freezestat is provided to help protect against coil freeze-up.
Condenser Head Pressure Control
For applications where a waterside economizer package is not being used and entering condenser water temperatures can be less than 55°F, condenser head pressure control is required. To satisfy these applications, a factory installed 2-way, head pressure acti­vated control valve is available to maintain unit operation with entering condenser water temperatures as low as 40°F.
Figure 6. Mechanically Cleanable Waterside Economizer Coil
Figure 7. Economizer Piping
Airside Economizer
An airside economizer control package is available for controlling field installed mixing dampers capable of 100% outside airflow. Economizer operation will be controlled by the SWT's MicroTech III controller to maximize free cooling potential. Economizer operation is enabled whenever an outside air (or comparative) enthalpy sensor or outside air temperature sensor indicates that outside air is suitable for free cooling. The economizer damper control actuator shall modulate in response to the cooling load. The outside air damper will be positioned to maintain minimum ventilation requirements when economizer is disabled.
To extend free cooling savings, mechanical cooling is enabled during economizer operation. Only when the economizer damper is driven 90% open and the cooling load is not satisfied, will com­pressors be staged to maintain cooling setpoint. Economizer con­trol will maintain full free cooling capability until disabled by the economizer changeover setpoint. Factory supplied mixing boxes are available for airside economizer use using the McQuay Vision™ air handling unit platform.
McQuay Catalog 865-5 7

Filter Section

All SWT units are provided, as standard, with 4" deep extended media 30% efficient filters. For higher filtration requirements, 65% and 85% AmericanAirFilter with an optional pre-filter rack. Filters are removable from the rear of the unit or through hinged and latched side access doors on the filter box.
TM
Varicel® filters are available
Design Features

Electrical

Each unit is completely wired and tested at the factory prior to shipment. Wiring complies with NEC requirements and conforms to all applicable UL standards for reliability and safety. All elec­trical components are labeled according to the electrical diagram and are UL recognized whenever applicable. Line voltage compo­nents and wiring are physically separated from the low voltage control system.
The supply fan motor, compressor motors and electric heat all have individual branch circuit fuse protection. Control circuit power is supplied through a factory installed, low voltage trans­former. The supply fan motor circuit includes a three phase con­tactor and ambient compensated overload protection with manual reset. Each refrigerant circuit includes both a high and low pres­sure cutout switch and a coil frost protection thermostat.
A terminal block is provided for the single, main power connec­tion and a terminal board is provided for low voltage control wir­ing. A factory mounted, non-fused main circuit interrupter is available for disconnecting the main electrical power to the unit. The switch is visible, located at the front of the unit, and is acces­sible without unit penetration. Dual power blocks or disconnect switches are available to accommodate requirements for standby, emergency power supplies.

Controls

Phase Failure/Undervoltage Protection – Factory installed phase failure/under voltage protection is available to protect three phase motors from damage due to single phasing, phase reversal and low voltage conditions.
Individual Unit Factory T est – All SWT units are provided com­pletely factory assembled, piped, wired, tested, and shipped in one piece. Each unit undergoes a factory test that includes:
Dynamic trim balance of the completed fan assembly
Run check of all electrical components, alarms and shutdowns,
including proper control sequencing
Pressure test, at rated pressure, of refrigerant coils, water coils
and condensers prior to assembly
Final leak check of the completed refrigerant circuits
Final leak check of the completed water circuit
Compressor run check
Verification of factory run test is available at time of unit ship­ment.
Figure 8. Test Stand
MicroTech III Unit Controls
All SWT units feature advanced MicroTech III DDC controls to provide all temperature and static pressure control, product reli­ability control functions, system time clock and all monitoring and diagnostics. Each MicroTech III control system features a human interface with a 4-line, 20 character English language dis­play for fast system diagnostics and adjustments. The complete control system is factory installed and commissioned prior to shipment.
Protocol Selectability™ Feature
All MicroTech III control systems have McQuay's exclusive Pro­tocol Selectability feature. MicroTech III control systems can be factory configured for standalone operation or for incorporation into an independent building automation system using either the
BACnet
MS/TP, BACnet/IP or LonTalk protocols.

Auxiliary Control Options

Condenser Water Flow Switch –A factory installed, flow switch is available to verify water flow status at each unit. Compressor operation is disabled and an alarm signal provided if condenser water flow is lost. Unit operation is restored when water flow has again been sensed. Water flow status is displayed at the Micro­Tech III control’s plain language screen.
Freezestat – A nonaveraging type freezestat is available factory installed on the entering face of the economizer coil. Upon sens­ing a potential freeze condition, the unit supply air fan is shut down, the economizer (and heating) valve drives to the full open position and an alarm signal is provided. Unit operation is restored following the manual reset of the freezestat.
8 McQuay Catalog 865-5
Fan Section
Main Heating / Cooling Section
Optional Hot Water Coil Connections
Condensate Drain
Filter / Waterside
Economizer Section
Water In
Water Out
System Flexibility
Along with providing high quality and state-of-the-art innovation, SWT self-contained systems emphasize system flexibility, flexi­bility not even considered by the competition. McQuay SWT sys­tems offer customized flexibility to satisfy a wide range of diverse applications.

Selection/Application Flexibility

Nominal cooling capacities range from 15 to 45 tons and all units feature a 6 row evaporator coil. In addition, all units offer multiple compressor selections to meet exacting system requirements. Many standard compressor/coil capacity selections are available. The flexibility to optimize the self-contained system to fit the application is a McQuay SWT advantage. Available system appli­cations include:
VAV discharge air temperature control with static
pressure control
Discharge air temperature control with constant air
volume
Constant volume, zone temperature control
100% outside air control
Dehumidification control, with or without reheat control
In addition to compressor/coil flexibility, SWT systems offer dou­ble width, double inlet, forward curved fans with factory mounted variable frequency drives for maximizing VAV system fan perfor­mance. High efficiency fan capability coupled with extensive compressor flexibility can provide the right system selection for the application.
pressure, a 20% reduction in supply air CFM can reduce the fan BHP requirements by 25% or more.
Reduced supply air CFM provides reduced fan sound power
generation and a quieter room environment.
Reduced supply air CFM can often reduce the equipment room
size due to the use of a physically smaller unit size.
Figure 9. Modular Construction

Modular Construction

The SWT unit has been designed with the flexibility to be easily disassembled into three compact sections. The three sections are the main cooling/heating, filter/waterside economizer and fan sec­tions. Whereas most competitive products require removal of the door frame, each SWT section has a maximum width of 34.5", including fastener heads, and can fit through standard 3' steel door frames.
The system installer is able to break the unit down into its three main sections without breaking any refrigerant lines. All SWT refrigerant lines remain intact, contained in the main cooling/heat­ing section. This SWT feature can add up to substantial savings by avoiding the field expense to braze, evacuate and charge each refrigerant circuit.
Optimal Discharge Air Temperature:
More and more system engineers are designing optimal discharge air temperature systems to improve system performance and sys­tem first cost, and the McQuay SWT provides the flexibility to do it successfully. Optimal discharge air temperature systems are designed to provide unit leaving air temperature selections of 52­53°F versus more conventional systems that supply air at temper­atures closer to 58°F. This five to six °F reduction in air tempera­ture to the room diffusers can subsequently reduce the required supply air volume to the room by 20-25%.
The benefits of optimal discharge air temperature systems become quite apparent with a look at the advantages offered with reduced air­flow:
Reduced supply air CFM reduces first cost and installation
cost by allowing smaller duct sizes and a smaller air distribu­tion system.
Reduced supply air CFM reduces fan BHP requirements.
Depending on changes in duct size and the resulting total static
Arrangement Flexibility
All SWT systems offer the flexibility of right-hand and left-hand piping arrangements and front and rear fan discharge orientations. Piping and fan arrangement flexibility can simplify mechanical equipment room arrangement, improve installed cost and improve total system performance.
Filtration Flexibility
SWT systems are offered with 4 inch, 30% efficient pleated filters as standard. 4 inch, 65% efficient pleated filters and 4 inch, 85% efficient filters with pre-filters are also available.
Energy Saving Economizer Flexibility
To improve system operating performance, all SWT s ystems of fer complete factory mounted and controlled waterside economizer capability. Each waterside economizer system includes a 4 row, mechanically cleanable coil with dual, two-way control valves to allow use in either a constant or variable volume pumping system. In addition, units can be applied with air economizer cycles with integrated factory control.
Heating Flexibility
A variety of heating media is offered with each SWT system. Hot water coils with modulating valve and actuator are available along with staged electric heat to provide heating control in a variety of applications.
McQuay Catalog 865-5 9
System Flexibility

Controllers

MicroTech III DDC control systems provide constant volume, variable air volume, 100% outside air, and/or dehumidification control flexibility. Each MicroTech III control system comes with a control screen conveniently mounted on the front of the unit to allow easy adjustment and monitoring of control functions. And with its easy to follow and read English language menus and data displays, it simply encourages and invites the operator to take advantage of its many capabilities.
Figure 10. MicroTech III Controller
Protocol Selectability Feature
All MicroTech III control systems have McQuay's exclusive Protocol Selectability feature. MicroTech III control systems can be factory configured for standalone operation or for incorporation into an inde­pendent building automation system using either the BACnet MS/TP, BACnet/IP or LonTalk protocols.
Summary of Available Options:
Multiple compressor/coil capacity selections
Multiple control op ti on s: VAV, C V, 100% OA,
dehumidification
Non-fused main power disconnect switch
Dual non-fused main disconnect switches
Non-averaging freezestat for hot water, or waterside econo-
mizer coil protection
Unit phase failure/under voltage protection
Premium efficiency fan motors
TEFC fan motors
Condenser water flow switch
4-row waterside economizer system
Air cycle economizer system
Modulating hot water heat
Staged electric heat
Factory mounted and controlled variable
frequency drives
High efficiency filtration options
Right- and left-hand piping selections
Front and back fan discharge arrangements
Head pressure control valve
Special coil coatings
Double wall cabinet construction
Seismic fan isolation
R407C refrigerant
UV lights

Ultraviolet Lights

Factory-installed ultraviolet lights are available on the down­stream side of all cooling coils and above the unit drain pan.
All ultraviolet lights are pre-engineered and factory installed for ease of use and proper placement for maximum effectiveness. The ultraviolet lamps irradiate the coil and drain pan surfaces with light in the 245 nanometer wavelength of the light spectrum (UV­C). UV-C light has proven effective in killing most bacteria, molds, and viruses in both laboratory and practical application. This complete package of equipment and ultraviolet lights includes Intertek Services Inc. (ETL) safety agency certification.
Figure 11: Ultraviolet light
Features
High-output, hot cathode lamps produce ultraviolet germicidal
irradiation (UVGI) for 254 nm that constantly irradiates the coil and drain pan surfaces.
Fixture design and stainless steel construction make the ultra-
violet light device suitable for saturated air conditions.
Automatic disconnects are standard on all doors (or panels)
with line-of-sight access to the lamps to help prevent eye con­tact with the UV-C ultraviolet light.
Special ultraviolet filtering glass windows block ultraviolet
light, allowing the coil, drain pan, and lights to be inspected while in use from outside the unit.
Benefits
For pennies a day, UVGI can improve IAQ by destroying
mold, fungi, and bacteria on coil and drain pan surfaces.
Clean coil surfaces maintain peak heat tra nsfer for “ near new”
performance and lower energy costs.
Reduced coil and drain pan maintenance requirements and
costs.
Satisfies GSA federal facilities standard requirements for
UVGI lights to be incorporated downstream of all cooling coils and above all drain pans to control airborne and surface microbial growth and transfer.

Refrigerant R-407C

McQuay SWP units with independent refrigerant circuits are available with non-ozone depleting R-407C refrigerant.
Features
HFC-407C refrigerant is environmentally friendly with zero
ozone depleting allowance (ODP).
ASHRAE Standard 34, Designation and Safety Classification
of Refrigerants, classifies HFC-407C as an A1 (lower toxic­ity—no flame propagation) refrigerant.
Units are factory engineered for proper cooling performance
using R-407C.
Units are factory charged with R-407C and synthetic oil (such
as POE), and they include components and controls specifi­cally tailored to R-407C.
Units are factory tested prior to shipment.
Benefits
HFC-407C allows you to provide your tenants with a comfort-
able building environment in an environmentally friendly way.
With no phase out date for production of HFC-407C, a reliable
supply should be available for the life of your equipment.
10 McQuay Catalog 865-5
MicroTech® III Unit Controller
McQuay SWP systems continue to provide industry leading performance, equipped with a complete MicroTech III control system. In addition to providing stable, efficient temperature, and static pressure control, the controller is capable of providing comprehensive diagnostics, alarm monitoring, and alarm specific component shutdown if critical equipment conditions occur. The unit controllers are factory mounted and configured for stand-alone operation or integration with a building automation system (BAS) through an optional communication module with our Open Choices feature.
Open Choices Benefits for Easy Integra­tion
Easy, low cost integration into most building automation systems without costly gateway panels.
Flexibility to select either BACnet® or L
communication. Units are LonMark® 3.4 certified with the appropriate communications module for L networks.
Comprehensive unit control and status information is
available at the BAS regardless of communication protocol.
Long-term choices for equipment adds or replacements,
and for service support.
Flexible alarm notification and prioritization with Intrinsic
Alarm Management (BACnet).
Simplified BAS integration with the ability to set network
parameters at the unit controller, reducing installation time and costs.
Easy monitoring and troubleshooting of communication
status from the unit controller to the BAS.
Components
Each SWP self-contained system is equipped with a complete MicroTech III unit control system that is pre­engineered, preprogrammed, and factory tested prior to shipment. Each of the MicroTech III unit control systems is composed of several components that are individually replaceable for ease of service.
ONWORKS®
ONWORKS
These components include:
• Unit controller with user interface display and naviga­tion wheel
• Optional expansion modules
• Communication module (optional)
• Pressure transducers
• Unit-mounted temperature sensors
• Zone temperature sensor packages
• Humidity sensor
Main Control Board (MCB)
The main control board (MCB) contains a microprocessor that is preprogrammed with the software necessary to control the unit. This provides that schedules, set points and parameters are not lost, even during a long-term power outage. The microprocessor board processes system input data and then determines and controls output responses. An RS-232 communication port is provided as standard to allow for direct or modem access with a PC-based service tool.
Expansion Modules
These boards are used to expand the input and output capability of the unit controller. Each board communicates via serial data communications. These microprocessor based boards provide independent operation and alarm response even if communication is lost with the unit controller.
Communication Module
An optional communication module provides the means to factory or field configure MicroTech III unit controls for interoperability with an independent BAS. Communication modules are available to support industry recognized communication protocols including BACnet MS/TP, BACnet/ IP and L
Keypad/Display
All MicroTech III unit controllers include a push/pull navigation wheel and display. The display is a supertwist nematic type with highly visible black characters on a yellow background. The 5-line by 22-character format allows for easy to understand plain English display messages. All operating conditions, system alarms, control parameters and schedules can be monitored from the keypad/display. If the correct password has been entered, any adjustable parameter or schedule can be modified from the keypad.
ONWORKS.
Figure 12. MicroTech III Keypad/DisplayMicroTech III Unit Controls
McQuay Catalog 865-5 11
MicroTech® III Unit Controller
Temperature and Humidity Sensors
With the exception of the zone, outside air and return air sensors, all temperature sensors are factory installed and tested. Zone sensor packages are available to suit any application. A humidity sensor is available for field installation.
Static Pressure Transducers
All pressure transducers are factory installed and tested. Connection and routing of field-supplied sampling tubes is done at time of unit installation.
Zone Temperature Sensors
Two optional zone temperature sensors are available:
• Zone sensor with tenant override switch
• Zone sensor with tenant override switch and remote set point adjustment
Timed tenant override is a standard MicroTech III control feature.
Zone sensors are required for the controller’s purge cycle, space reset of supply air set point, and night setback or setup features. All zone sensors are field installed with field wiring terminated at a separate, clearly marked terminal strip.
Stand-alone Controller Features
MicroT ech III applied rooftop unit controls include all of the essential features required to make them capable of completely independent, stand-alone operation.
Internal Time Clock
An internal, battery-backed time clock is included in the MicroTech III unit controller. Current date and time can be quickly and easily set at the user interface keypad.
Internal Schedule
Seven daily schedules and one holiday schedule can be entered at the keypad of all unit controllers. For each of these eight schedules, one start and one stop time can be entered. Up to 10 holiday periods, of any duration, can be designated. The unit will automatically run according to the holiday schedule on the holiday dates. To handle special occasions, an additional ‘one event’ schedule can also be used.
In lieu of its internal schedule, the unit can be operated according to a network schedule from a BAS.
External Time Clock or Tenant Override Input
An input is supplied that can be used to accept a field wired start/stop signal from a remote source. An external time clock, a tenant override switch, or both may be connected. Whenever the external circuit is closed, the controller overrides the internal schedule (if activated) and places the unit into the occupied mode.
If the internal schedule or a BAS network schedule is used, field wiring is not required.
Timed Tenant Override
Off-hour operation flexibility is a must in today’s office environments and even stand-alone MicroTech III controls handle it with ease. When unit operation is desired during unoccupied hours, initiate timed tenant override by pressing the tenant override button on either of the optional zone sensor packages. The unit then starts and runs in the occupied mode for a keypad-adjustable length of time (up to five hours). If the button is pressed again while the unit is operating, the timer resets to the full time allowance without interrupting unit operation. Tenant override operation also can be initiated by a BAS.
Three Remote Set Point Adjustment Options
1 Remote user interface option (RUI).
2 Building automation system (BAS). See “Open Choices
Benefits for Easy Integration” on page 11.
3 All constant air volume-zone temperature control
(CAV-ZTC) unit controllers include an input that can be used to remotely adjust the zone cooling and heating set points. To use this feature, wire the optional zone sensor package with set point adjustment to the controller. The remote set point adjustment feature can be enabled or disabled from the keypad at any time. When enabled, remote set point adjustment is available even if the return temperature is selected to be the Control Temperature.
Auto/Manual Operation Selection
Automatic or manual operation can be controlled either remotely or at the keypad.
All controllers include three inputs that can be used to enable or disable cooling, heating, and fan operation from remote switches. With the “heat enable” and “cool enable” terminals, the operator can enable cooling, heating, or both as desired. Using the system “off” terminals, the operator can disable the fans, and thus the entire unit.
12 McQuay Catalog 865-5
MicroTech® III Unit Controller
From the keypad, there are a variety of occupancy and auto! manual control mode selections available to the operator:
• Occupancy modes – Auto – Occupied – Unoccupied – Bypass (tenant override)
• Control modes – Off manual – Auto – Heat/cool – Cool only – Heat only – Fan only
Compressor Lead-lag Selection
All unit controllers are capable of automatic compressor, lead-lag control.
Waterside Economizer Changeover
On units equipped with a waterside economizer package, the MicroTech III unit controller includes an internal changeover strategy that compares entering cooling tower water temperature to the unit’s mixed air temperature. If the entering water temperature is less than the mixed air temperature by a field-adjustable differential (typically 5°F to 7ºF), the economizer control valve modulates in response to the cooling load.
warm-up or cool-down periods or when the outdoor air temperature is mild.
Night Setback and Setup Control
When one of the zone temperature sensors is connected to the unit controller, night setback heating and night setup cooling control are available. Separate, keypad programmable night heating and cooling set points are used to start the unit when necessary. After the unit starts, night setback and setup control is similar to normal occupied control except that the minimum outside air damper position is set to zero. If the outside air is suitable for free cooling, it is used during night setup operation.
Airside Economizer Changeover Selection
On units equipped with an economizer, there are three methods of determining whether the outdoor air is suitable for free cooling: two methods sense enthalpy (dry bulb temperature and humidity) and one senses outdoor air dry bulb temperature.
The two enthalpy changeover methods use external, factory installed controls. One compares the outdoor ambient enthalpy to a set point; the other is a solid state device that compares the outdoor ambient enthalpy to the return air enthalpy. This comparative enthalpy control can improve total economizer performance.
All unit controls include an internal dry bulb changeover strategy that can be selected at the keypad. When this method is selected, the controller compares the outdoor air dry-bulb temperature to a keypad programmable set point. The external enthalpy control input is then ignored.
Cooling and Heating Lockout Control
All unit controls include separate keypad programmable set points for locking out mechanical cooling and heating. Mechanical cooling is locked out when the outdoor temperature is below the cooling lockout set point; heating is locked out when the outdoor temperature is above the heating lockout set point. This feature can save energy cost by eliminating unnecessary heating and cooling during
McQuay Catalog 865-5 13
MicroTech® III Unit Controller
Except for 100% outside air applications, night setback control is available even if the unit is not equipped with any heating equipment. When the space temperature falls to the night setback set point, the fans simply start and run until the temperature rises above the differential. This feature might be useful for applications that use, for example, duct­mounted reheat coils.
Morning Warm-up Control
If the Control Temperature (space or return) is below set point when the unit enters the occupied mode, the morning warm-up control function will keep the outside air dampers closed while heat is supplied to satisfy set point. The outside air damper will remain closed until either the space temperature rises to the
heating set point or the keypad adjustable morning warm-up timer expires (default is 90 minutes). The morning warm-up timer supplies the minimum required amount of outdoor air after a certain time regardless of the space temperature.
Morning warm-up control is automatically included on all except 100% outside air units. It is available even if the unit is not equipped with any heating equipment, for applications that utilize, for example, duct-mounted reheat coils.
Condenser Head Pressure Control (units without waterside economizer only)
Mechanical cooling is allowed whenever the entering cooling tower water temperature is 55ºF or warmer, without the use of head pressure control. When the entering water temperature is below 55ºF, a factory-installed and factory­controlled two-way modulating head pressure control valve can be utilized. The regulating valve is controlled by the MicroTech III controller to maintain refrigerant head pressure.
During the purge time window, the unit starts and runs whenever these three requirements are met:
• The space temperature must be warm enough to enable occupied cooling.
• The outside air enthalpy must be low enough to enable the economizer.
• The outside air temperature must be at least 3°F less than the space temperature.
When any one of these conditions is no longer true, the unit shuts down. As conditions allow, purge cycles the unit in this manner until it enters the occupied mode.
Proportional Integral (PI) Control
The Proportional Integral (PI) control algorithm controls modulating actuators to maintain a measured variable (temperature or pressure) at or near its set point. For example, it controls economizer dampers to maintain the discharge cooling set point and it controls the supply fan variable frequency drives to maintain the duct static pressure set point. The integral control feature effectively eliminates “proportional droop” (load dependent offset) resulting in the tightest possible control.
For each PI loop, four keypad adjustable parameters allow the control loop to be properly tuned for any application:
•Period
• Dead band
• Proportional band
• Integral time
Appropriate default values for these parameters are loaded into each controller. These default values will provide proper control for most applications; therefore, field tuning is usually not required and thus start-up time is reduced.
Outdoor Air Purge Control (units with airside economizer only)
Purge control is designed to take advantage of cool early morning outside air conditions. It starts the fans and modulates the economizer dampers to maintain occupied cooling requirements during unoccupied periods, if conditions are appropriate. This provides the opportunity to flush the space with fresh outdoor air prior to occupancy. Purge operation is possible only during a keypad-adjustable time window prior to occupancy (0 to 240 minutes). When the purge-cycle is active, mechanical cooling is disabled. To use the purge feature, connect one of the zone temperature sensors to the unit controller. Below is a description of purge control operation.
14 McQuay Catalog 865-5
Change Algorithm
The PI function is also used to adjust set points instead of controlling variable speed drives or actuators directly. For example, in zone control applications, the PI loop automatically “changes” the discharge temperature set point (cooling or heating) as the Control Temperature deviates from the zone set point. Another PI loop then controls the economizer actuator or heating valve actuator using the current discharge temperature set point. Unlike a typical “mastersubmaster” reset strategy, this “cascade control” continuously adjusts the discharge set point, even if the Control Temperature’s deviation from set point remains constant. This means that the unit’s cooling or heating output is set according to the actual load, not just the current zone temperature. The tightest possible zone temperature control results because “proportional droop” (load dependent offset) is eliminated.
Calibrat
When initiated at the keypad by an operator, the Calibrate function automatically calibrates all actuator position feedback inputs and all pressure transducer inputs. It does
e
MicroTech® III Unit Controller
this by shutting the unit down and then driving all actuators to the full closed and full open positions. The controller records the input voltage values that correspond to these positions. The pressure transducer input voltages, which are assumed for 0.00-in. W.C., are also recorded. When Calibrate is finished, enter an operator command at the keypad to start the unit.
Field Output Signals
All MicroTech III controls include two solid-state relay outputs that are available for field connection to any
suitable device: the remote alarm output and the occupied output. These two outputs are used to signal field equipment of unit status.
Remote Alarm Output: The remote alarm output can be used to operate a 24 volt relay to provide a remote alarm signal to a light, audible alarm, or other device when an alarm condition exists at the unit. Fan Operation Output: The fan operation output is used to operate a 24 volt relay to control field equip­ment that depends on fan operation; for instance, to open field installed isolation dampers or VAV boxes. T o allow actuators enough time to stroke, the fan operation output is energized three minutes before the fans start. It then remains energized until thirty seconds after the uni t airflow switch senses no airflow. The fan operation out­put is on whenever the unit airflow switch senses air­flow. Outside Air Damper output: Use to signal an outside air damper actuator to open whenever the unit is in an occupied cooling or heating condition.
Standard Control Options
SWP Self-Contained systems are available for most any constant or variable air volume application. MicroTech III controls offer three basic control configurations that use sophisticated state change control logic to provide stable, reliable and efficient control:
• Variable air volume with discharge temperature control (DAC)
• Constant air volume with zone temperature control (S CC)
• Constant air volume with discharge temperature con­trol (DAC)
When combined with MicroTech III’s many available control capabilities, both factory-installed and keypad­programmable, these three basic configurations can be customized to meet the requirements of the most demanding applications.
Constant Air Volume with Zone Temperature Control (SCC)
SCC units are available in either cooling only or cooling with modulating heat configurations. Either of these configurations is available for 100% recirculated, mixed, or 100% outdoor air applications.
Constant Air Volume with Discharge Temperature Control (DTC)
DTC units are available in cooling only, cooling with single­stage “morning warm-up” heat, or cooling with modulating heat configurations. This unit configuration can be used for applications that have zone controlled terminal heating coils or for constant volume, 100% outdoor air applications. The discharge temperature control strategies used with the hybrid DTC unit are identical to those used with the DTC unit.
Discharge Temperature Control
MicroTech III VAV-DTC and CAV-DTC controls provide sophisticated and flexible discharge air temperature control that is only possible with DDC systems. Separate discharge air temperature set points are used for cooling and modulating heating control. At the keypad, the operator can either enter the desired set points or select separate reset methods and parameters for each set point.
Control Temperature
The Control Temperature make s the heat/cool changeover decision. It determines whether cooling or heating is enabled; the discharge temperature then determines whether cooling or heating is actually supplied. At the keypad, the operator can choose the source of the Control Temperature from among the following selections.
• Space temperature sensor
• Return temperature sensor
• Outside air temperature sensor (modulating heat only)
• Network communication
The operator enters separate cool and heat enable set points and deadbands that the Control Temperature is compared with (see <CrossReference>Figure 13). When the Control Temperature is greater than or equal to the cooling set point plus DB/2, cooling is enabled. When the Control Temperature is less than or equal to the heat set point minus DB/2, heating is enabled. If desired, these set points and differentials can be set so that there is a dead band in which both cooling and heating are disabled. The controller’s software prevents simultaneous cooling and heating.
Variable Air Volume with Discharge Temperature Control (DTC)
All VAV units provide true discharge temperature control in addition to duct static pressure control. Cooling only, cooling with single-stage “morning warm-up” heat, and cooling with modulating heat configurations are available.
McQuay Catalog 865-5 15
MicroTech® III Unit Controller
Figure 13: Control Temperature Logic
Proportional Integral Modulation
When operating in economizer free cooling or unit heating, the previously described PI algorithm maintains discharge temperature control. It provides precise control of the economizer dampers, modulating gas heat, steam or hot water valves.
Compressor Staging
Two staging algorithms are available to control a unit’s multiple steps of capacity control, Degree-Time (also known as “average”) and Nearest. These control algorithms provide reliable discharge temperature control while managing compressor cycling rates. Constraints on compressor staging are essential for preventing short cycling, which can reduce compressor life by causing improper oil return and excessive heat buildup in the motor windings.
The Degree-Time Compressor staging algorithm keeps track of the discharge temperature and stages cooling up or down to maintain an average temperature that is equal to the discharge cooling set point. A stage change can occur only (1) after the keypad adjustable inter-stage timer has expired (five minute default setting) and (2) if the discharge temperature is outside a keypad programmed dead band. After these two conditions have been met, staging occurs as the controller attempts to equalize two running totals: degree-time above set point and degree-time below set point. The result is that the average discharge temperature is maintained at the cooling set point.
The Nearest Compressor staging algorithm keeps track of the discharge temperature and stages cooling up or down to maintain the discharge temperature as close as possible to set point. A stage change can occur only (1) after the keypad adjustable inter-stage timer has expired (five minute default setting) and (2) if the control logic calculates that a stage change will result in a discharge temperature closer to set point than the existing condition. The controller logic continually calculates the expected effect of a stage change and uses this information before making a change. A change is made only if it will bring the discharge temperature closer to set point, resulting in a more consistent discharge temperature, reduced compressor cycling and more stable control VA V box control.
Supply Air Reset
By automatically varying the discharge air temperature to suit a building’s cooling or heating needs, supply air temperature reset can increase the energy efficiency of VAV and CAV-DTC systems. MicroTech III controllers offer a variety of different reset strategies that can be selected at the keypad. Because they are keypad programmable, reset strategies can be changed or eliminated as desired. Separate strategies can be selected for both cooling and modulating heat. If reset is not desired, a fixed discharge cooling or heating set point can be entered.
The following reset methods are available:
• Space temperature
• Return temperature
• Outdoor air temperature
• Supply airflow (VAV, cooling set point only)
• External 0–10 VDC or 0–20 mA signal
• Network communication
For all temperature reset methods, the minimum and maximum cooling and heating set points are keypad programmable along with the corresponding minimum and maximum space, return or outdoor air temperature parameters. For the supply airflow method, the discharge set point will be reset as the supply fan modulates between 30% adjustable and 100% adjustable. For the external method, the discharge set point will be reset as the voltage or current signal varies over its entire range. For units in a BAS network, the discharge set points are reset via the communication signal.
Zone Temperature Control
MicroTech III CAV-ZTC controls provide the sophisticated and flexible zone temperature control that is only possible with DDC systems. Zone temperature sensors are available with or without a remote set point adjustment. With the remote adjustment model, the space set point can be set at the keypad or at the zone sensor package. Even if a zone sensor is connected, remote set point adjustment can be enabled or disabled as desired at the keypad.
Control Temperature
The Control Temperature is the representative zone temperature. When compared with the zone set points, the Control Temperature determines whether the unit supplies heating, cooling, or neither. It also determines the amount of cooling or heating required to satisfy the load. Its source can be selected at the keypad from among the following selections:
• Zone temperature sensor
• Return temperature sensor
16 McQuay Catalog 865-5
MicroTech® III Unit Controller
Because it is the representative zone temperature, the Control Temperature is the primary input to the MicroTech III zone temperature control algorithms. Control Temperature parameters are described below. The controller’s software will prevent cooling and heating from being inadvertently enabled at the same time.
Change and Proportional Integral Mo du la tio n
When economizer “free” cooling or unit heating is required, the two MicroTech III PI loops combine for cascade-type control, providing the tightest possible zone temperature control. By controlling the discharge temperature along with the zone temperature, these functions eliminate temperature variations near the diffusers that could otherwise occur as a result of traditional zone control’s inherent lag effect.
Change: If the Control Temperature is above or below the set point by more than the dead band, the Change PI loop periodically adjusts the cooling or heating dis­charge air temperature set point either up or down as necessary . The amount of this set point change corre­sponds to the Control Temperature’s position in the modulation range. The farther the Control Temperature is from the set point, the greater the discharge set point change will be. The Change-adjusted discharge cooling and heating set points are limited to ranges defined by keypad programmable maximum and minimum values. PI: Using the Change function’s current discharge set point, the PI function maintains precise discharge tem­perature control by modulating the economizer dampers and gas heat, steam or hot water heating valves.
Compressor Staging
Compressor staging is controlled directly by the Control T emperature. When the Control Temperature is warmer than the zone cooling set point, cooling is staged up; when the Control Temperature is cooler than the zone cooling set point, cooling is staged down. However, a stage change can only occur when the Control Temperature is outside the dead band (see <CrossReference>Figure 14). Staging is constrained by an inter-stage delay timer (five minute default setting) and minimum and maximum discharge air temperature limits (all keypad programmable). These constraints protect the compressors from short cycling while eliminating temperature variations near the diffusers.
Figure 14: Compressorized Logic
Project Ahead Algorithm
Because the inherent lag effect in zone temperature control applications can cause overshoot during warm-up or cool­down periods, MicroTech III features a “Project Ahead” control algorithm. Project Ahead calculates the rate at which the Control Temperature is changing and reduces the unit’s cooling or heating output as the zone temperature nears its set point, essentially eliminating overshoot.
Duct Static Pressure Control
On all VAV-DTC units, duct static pressure control is maintained by the PI algorithm, which provides precise control of the supply fan variable speed drive. The keypad programmable set point can be set between 0.20-in. W.C. and 4.00-in. W.C.
On larger buildings with multiple floors, multiple trunk runs or large shifts in load due to solar effects (east/west building orientation), an optional second duct static sensor is offered. The MicroTech III controller automatically selects and uses the lower of the two sensed pressures to control fan volume to provide adequate static pressure to the most demanding space at all times.
Operating States
Operating states define the current overall status of the self­contained system. At the user interface, the operator can display the current operating state and thereby quickly assess the unit’s operating condition.

Alarm Management and Control

MicroTech III unit controllers are capable of sophisticated alarm management and controlled response functions. Each alarm is prioritized, indicated, and responded to with the appropriate action. The active alarm (up to 10 alarms, arranged by alarm priority) and previous alarm (up to 25 alarms, arrange by date/time cleared), each with a time and date stamp, can be displayed at the user interface. Generally speaking, whenever a current alarm is cleared, it is logged as a previous alarm and the oldest previous alarm is removed.
Alarm Priority
The various alarms that can occur are prioritized according to the severity of the problem. See <CrossReference>Table 1. Three alarm categories are used: faults, problems, and warnings.
1 Faults are the highest priority alarms. If a fault
condition occurs, the complete unit shuts down until the alarm condition is gone and the fault is manually cleared at the keypad. A fault example is Fan Fail alarm.
McQuay Catalog 865-5 17
MicroTech® III Unit Controller
2 Problems are the next lower priority to alarms. If a
problem occurs, the complete unit does not shut down, but its operation is modified to compensate for the alarm condition. A problem automatically clears when the alarm condition that caused it is gone. Compressor Fail is an example of a problem where only the affected compressor is shut down.
3 Warnings are the lowest priority alarms. No control
action is taken when a warning occurs; it is indicated to alert the operator that the alarm condition needs attention. T o make su re that they are read, the operator must manually clear all warnings. Dirty Filter indication is an example of a warning.
Generally, a specific alarm condition generates an alarm that falls into only one of these categories. Under different sets of circumstances, however, the freezestat and most of the sensor failure alarm conditions can generate alarms that fall into multiple categories.
Adjustable Alarm Limits
Four alarm indications have adjustable limits that are used to trigger the alarm. The high return temperature alarm and the high and low supply temperature alarms are adjusted at the user interface. The dirty filter alarm(s) is adjusted at the sensing device.
Table 1: MicroTech III Alarm Summary
Alarm Name Fault Problem Warning
Freeze X X Smoke X
Temperature Sensor
Failure
Duct High Limit X
High Return Temperature X
High Discharge
Temperature
Low Discharge
Temperature
Fan Failure X
Fan Retry X
Discharge Air Capacity
Feedback
Economizer Stuck X X
Auxillary Control Board
Enabled
Low Airflow X
Circuit 1–8
High Pressure
Circuit 1–8
Low Pressure/Frost
Compressor 1–8 Motor
Protection
Compressor 1–8 Failure X
Airflow Switch (False Airflow)
Dirty Filter X
XX
X
X
X
X
X
X
X
X
18 McQuay Catalog 865-5
Application Considerations
The following section contains basic application and installation guidelines which must be considered as part of the detailed analy­sis of any specific project.

General

Units are intended for use in normal heating, ventilating and air conditioning applications. Consult your local McQuay sales rep­resentative for applications involving operation at high entering condenser water temperatures, high altitudes, non-cataloged volt­ages and for applications requiring modified or special control sequences. Consult your local McQuay sales representative for job specific unit selections that fall outside of the range of the cat­alog tables, such as 100% outside air applications.
For proper operation, rig units in accordance with instructions stated in IM 709.
Factory check, test and start procedures must be explicitly fol­lowed to achieve satisfactory start-up and operation (see IM 709).
Many self-contained system applications take advantage of the significant energy savings provided by the use of economizer operation. When a water economizer system is used, mechanical refrigeration is typically not required below an entering condenser water temperature of 55°F. Standard McQuay self-contained sys­tems are designed to operate with entering water temperatures down to 50°F when a water economizer is used and 55°F with no water economizer. For applications where a water economizer system cannot be used, a modulating head pressure control system is available to permit operation at entering condenser water tem­peratures below 55°F.

Unit Location

Make sure that the floor is structurally strong enough to support the unit with minimum deflection (See “Unit and Component Weights in lbs.” on page 42). Provide proper structural support to minimize sound and vibration transmission. A concrete floor should be considered. Extra caution is required when installing on a wooden structure. Units must be installed level from front-to­back and over their length.
Unit fresh air intakes must be located away from building flue stacks, exhaust ventilators and areas containing automotive or other exhaust to prevent the possible introduction of contaminated air to the system. Consult code requirements for minimum fresh air volumes.
Allow sufficient space around the unit for service and mainte­nance clearance. Refer to Figure 15 for recommended ser­vice/maintenance clearances. See also “Recommended Clearances” on page 19“. Locate equipment room access doors in a manner that can assist in service access if needed (i.e., coil removal). Contact your local McQuay sales representative if reduced service/maintenance clearances are required.
Where code considerations, such as the NEC, require extended clearances, they take precedence over minimum service/mainte­nance clearances.

Acoustical Considerations

Good acoustical design is a critical part of any successful installa­tion and should start at the earliest stages in the design process. Each of the four common sound paths must be addressed. These are: (1) radiated sound through the casing of the unit, (2) structure borne vibration, (3) airborne sound through the supply air duct and (4) airborne sound through the return air duct.
Some basic guidelines for good acoustic performance include:
1. Always provide proper structural support under the unit.
2. Provide adequate mass in the floor structure, especially when located over an occupied space where good acous­tics are essential.
3. Seal all supply and return air duct penetrations once the duct is installed.
4. Don't overlook the return air path. Always include some duct work (acoustically lined tee) at the return inlet.
5. Minimize system static pressure losses to reduce fan sound generation.
6. Select the appropriate unit/fan for the application. Fans should be selected as close as possible to their peak static efficiency. To assist you, peak static efficiency is identified by the first system curve to the right of the shaded "Do not select" region on each fan curve.
7. Design duct systems to minimize turbulence.
8. Account for low frequency duct breakout noise in sys­tem design. Route the first 20' of rectangular duct over non-sensitive areas and avoid large duct aspect ratios. Consider round or oval duct to reduce breakout.

Recommended Clearances

For good installation, service and maintenance access, follow rec­ommended clearances. Minimum clearances required by local, state or federal codes, such as the NEC, take precedence over those listed below. Clearance is required to allow room for side filter access, mechanical cleaning of condenser tubes and econo­mizer coil access to expansion valves and other control compo­nents and to allow for possible fan shaft or compressor removal.
Unit Front 42 inch Unit Rear 24 inch Motor Location Side 36 inch Piping Location Side 36 inch Side Without Motor or Piping 24 inch Clearance at Face of VFD 42 inch
For clearance requirements less than those indicated, consult your local McQuay sales representative.
McQuay Catalog 865-5 19
Airflow
24"
42"
Evaporator Coil
Compressors
36"
24"
or
36"
1111342
AFD
Front
Right Side
Condenser Cleanout
Electrical Panel
Left Side
Back
(See Note )
Motor
(See Note)
Motor
(See Note)
Application Considerations
Figure 15. Recommended Service/Maintenance Clearances
Supply Duct
A lined section of supply air duct should extend at least 15 feet from the equipment room. The use of round duct should be reviewed as it will significantly reduce low frequency sound near the equipment room. If rectangular duct is used, the aspect ratio of the duct should be kept as small as possible. The large flat sur­faces associated with large aspect ratios will transmit sound to the space and the potential for duct generated noise, such as oil can­ning, is increased. The maximum recommended supply air duct velocity is 2000 feet per minute.
When direct ducting to the fan outlet, a minimum of two fan diameters from the fan outlet is recommended and the elbow should turn in the direction of fan rotation. Abrupt turns, takeoffs, etc., will generate air turbulence and resulting unwanted sound and should be avoided.
Duct Protection
An adjustable duct high limit switch is standard equipment on all SWT system's with VAV controls. This is of particular importance
Note: 36 inches are required if water and condensate drain
connections are left-hand, or fan discharge arrange-
when fast acting, normally closed boxes are used. The switch is field adjustable and must be set to meet the specific rating of the system ductwork.
ment is back.

Vibration Isolation

Equipment Room

Locate the equipment room away from sound sensitive areas. Whenever possible, isolate the equipment room from these areas by locating rest rooms, utility rooms, stairwells, hallways, eleva­tors, etc., around its perimeter. This allows not only isolation from radiated sound but provides the capability to route ductwork over less sensitive areas.
Acoustically seal the equipment room. All equipment room pene­trations should be sealed with a high quality, flexible material to prevent air and noise from escaping. Even a small leak will com­promise the acoustic performance of the installation. The equip­ment room door should seal tightly on a perimeter gasket.
Equipment room wall construction should be concrete block or offset, double stud. The decision will depend on the critical nature of the application. If offset, double stud construction is used the cavity should be lined with glass fiber insulation and a double layer of sheetrock used on each side of the wall.

Ductwork

Fan noise can be carried through the ductwork to occupied spaces and likely will be the most challenging to control. Careful duct design and routing practice is required. The ASHRAE Applica­tions Handbook discusses sound attenuation relevant to self-con­tained system applications. Contact your local McQuay sales representative for sound power data for designing the appropriate sound levels for your specific application.
Return Duct
The return duct is the most often over looked. Return air can be ducted directly to the unit or ducted into the equipment room. If ducted to the equipment room, an elbow should be installed within the equipment room. Running a return air drop to near the floor of the room will provide added attenuation. A length of lined ductwork should extend from the equipment room to a l ength of 15 feet. The maximum recommended return air duct velocity is 1000 feet per minute.
Duct connections to the unit or to the acoustic discharge plenum should be made with a flexible connection. Flexible piping and electrical connections should not be required, but attention should be paid to these areas to avoid vibration transmission from outside sources to the SWT unit.

Condenser Water Piping

Always follow good industry practice in the design of the water piping system. Attention to water treatment and proper strainer application are always necessary. All SWT systems feature mechanically cleanable condensers and optional waterside econo­mizer coils. In addition to mechanically cleanable heat exchang­ers, cleanouts are provided in the interconnecting piping and in the internal condensate drain trap. Costly field traps are not required. To allow periodic cleaning of the condensers and econo­mizer coils, isolation valves should be provided. Condensers, economizer coils and hot water coils are provided with vent and drain connections.
Always review for possible requirements for condenser piping insulation, especially if cold entering condenser water conditions (<55°F) will be experienced.

Head Pressure Control

If cold entering condenser water conditions (<55°F) will be expe­rienced, a waterside economizer or a condenser head pressure control valve is required. A 2-way, head pressure activated control valve is available factory installed for these applications. A head pressure control valve is not required when the SWT unit is applied with factory waterside economizer package.

Variable Air Volume

Variable frequency drives offer reliable speed control over a wide range of airflow, with advantages in sound and energy perfor­mance. In addition, McQuay offers the ability to sense duct static pressure in multiple locations, enhancing control accuracy and helping minimize energy use.
20 McQuay Catalog 865-5
hp2hp
1
density
2
density
1
---------------------


rpm
2
rpm
1
------------


3
=
Application Considerations

Variable Frequency Drives

Variable frequency drives provide the most efficient means of variable volume control by taking advantage of the fan law rela­tion between fan speed (rpm) and fan brake horsepower (bhp). Also, since airflow reduction is accomplished by changing fan speed, the noise penalties often associated with mechanical con­trol devices, e.g. inlet vanes, are not introduced. The following equation illustrates how fan bhp varies as the cube of the change in fan speed:
In an ideal system, at 50% fan speed, brake horsepower would be reduced to 12.5% of that at full speed.
Variable frequency control varies the speed of the fan by adjusting the frequency and voltage to the motor. Keeping a constant volts/frequency ratio (constant magnetic flux) to the motor allows the motor to run at its peak efficiency over a wide range of speeds and resulting fan airflow volumes.

Duct Static Pressure Sensor Placement

The static pressure should be sensed near the end of the main duct trunk(s). The MicroTech III static pressure control should be adjusted so that at full airflow all of the terminals receive the min­imum static pressure required plus any downstream resistance. Control is to the lowest static pressure set point that will satisfy airflow requirements. Lower static pressure setpoints will reduce fan brake horsepower requirements and fan sound generation.
The static pressure sensor tap should be located in the ductwork in an area free from turbulence effects and at least 10 duct diameters downstream and several duct diameters upstream from any major interference, including branch takeoffs. The SWT MicroTech III control system can receive a second duct static pressure sensor in installations having multiple duct trunks or significantly varying zones. The control logic will maintain static pressure at both sen­sors.

Zone Sensor Placement

Placement of the zone temperature sensor is extremely important to provide proper and economical operation of the heating and cooling system. It is generally recommended that the space sensor be located on an inside wall (3 to 5 feet from an outside wall) in a space having a floor area of at least 400 square feet. The sensor should not be located below the outlet of a supply air diffuser, in the direct rays of the sun, on a wall adjacent to an unheated or abnormally warm room (boiler or incinerator room), or near any heat producing equipment. Where zone sensor placement is a problem, all SWT zone control systems have, as standard, the capability to use the return air sensor for heating & cooling con­trol.

Filtration

Filters should be routinely replaced to minimize filter loading. As filters get dirty, the filter pressure drop increases, affecting system airflow and energy requirements. Depending on fan type, forward curved or airfoil, this airflow change can be significant. The effect of filter loading is the most critical when using high efficiency fil­ters.
When making a fan selection, a pressure drop component for fil­ters as they get dirty should be included in the system total static pressure. A value midway between clean and dirty filter ratings is recommended. If a minimum airflow is critical, the fan selection should be made using the higher, dirty filter pressure drop value. For VAV systems, consider setting the fan control device such that part of its modulation range can be used to maintain airflow as fil­ters become dirty. Following these recommendations should limit airflow fluctuation as the filters load.

System Operating Limits

SWT units can be applied in a wide range of system needs. High cfm/ton or high/low discharge temperature applications are avail­able. However, for proper system operation, some application lim­its do apply.
Airflow
Maximum cfm limits, based on coil face velocity, are givenTable 4 on page 25.
Separate minimum design cfm limits, by unit size, are given in the physical data table for constant and variable air volume applica­tions. Fan modulation should be limited to 40% of the minimum design cfm limit. Minimum airflow conditions are also dependent on fan selection criteria. Contact your McQuay sales re prese nta ­tive to answer any questions on minimum airflow capability or for conditions not shown in the catalog.
VAV box minimum airflow settings should correspond with the minimum VAV fan operating point. All units are provided with multi-groove, fixed pitch sheaves. During system air balance, alternate fixed pitch sheaves may be needed to match final system requirements. Alternate sheaves are available from McQuay.
Fan Heat
Sensible heat gain from the fan, fan motor and drives occurs in all fan systems and its effect must be considered during equipment selection. It is an added load in cooling and an added source when in heating. The majority of the heat gain occurs through the fan itself, as the air is elevated from the low-pressure side to the high­pressure side of the fan. Moving the motor out of the air stream has a negligible effect on overall fan heat gain. A unit with higher fan power requirements/higher fan heat will have less net cooling capability and may not have enough left to satisfy system loads.
As a "rule of thumb," a typical supply fan heat gain is 3°F. How­ever, fan heat gain can be quickly calculated once the fan has been selected and the fan brake horsepower has been determined. Using Figure 16, "Fan & Motor Heat Gain", select your fan brake horsepower on the horizontal axis, move up vertically until you intersect with the heat gain curve and then move horizontally to find the fan heat gain in Mbh.
McQuay Catalog 865-5 21
Application Considerations
Figure 16. Fan and Motor Heat Gain
(Fan Heat (Mbh)
Fan T emperature rise =
(1.085 x Fan cfm)
A draw through unit has the fan located after the DX cooling coil. In this arrangement, fan heat is applied as reheat to the cold, con­ditioned air coming off of the coil. This arrangement will have a lower sensible heat ratio and higher dehumidification capability than a blow through coil arrangement. The discharge temperature available to the supply duct is always the sum of the coil leaving air temperature plus the fan temperature rise. This must be consid­ered when selecting the supply air volume required to satisfy space requirements.
Example: 52°F leaving coil temp. + 3°F fan temp. rise = 55°F discharge air temp.
Condenser Water Flow
System capacity tables provide selections for a condenser flow rate of 3 gpm/ton. For a given entering condenser water tempera­ture, 3 gpm/ton will provide maximum unit performance. Reduc­ing condenser water flow rates to 2.5 or 2 gpm/ton can significantly reduce pumping energy costs and reduce piping costs. The reduction in pumping energy can be compared to the change in unit performance and an evaluation made. The SWT capacity tables can be used for condenser flow rates from 2 to 3 gpm/ton by using the appropriate leaving condenser water tem­perature column (interpolation is allowed). Minimum condenser flow rate is 2 gpm/ton.

Coil Freeze Protection

Consideration must always be made for coil freeze protection when applying units in geographic areas which see subfreezing temperatures. Careful design of outside air/return air mixing sys­tems is critical to minimizing freeze potential. Some applications may require the use of glycol and/or preheat coils. No control sequence can prevent coil freezing in the event of power failure.
A nonaveraging type freezestat is factory installed on all units with hot water heat or waterside economizer. If a potential freeze condition is sensed, unit water valves will be driven to the full open position, the supply fan de-energized and an alarm signal sounded.
In nonducted return applications where the equipment room is the mixing plenum, some form of heat within the equipment room should be considered.

Air Density Correction

Fan performance data is based on standard 70°F air temperature and zero feet altitude (sea level). For applications other than stan­dard, a density ratio must be multiplied to actual static pressure values. Density correction factors are expressed as a function of temperature and altitude in Table 2.
Table 2. Temperature and altitude conversion factors
AIR
TEMP
0 1000 2000 3000 4000 5000 6000 7000 8000
-20°F 1.20 1.16 1.1 2 1.08 1.04 1.00 0. 97 0.93 0. 89 0°F 1.15 1.10 1.0 8 1.02 0.9 9 0.95 0. 92 0.88 0. 85
20°F 1.11 1.06 1.02 .09 8 0.95 0. 92 0.88 0.85 0.82 40°F 1.0 6 1.02 0.9 8 0.94 0.9 1 0.88 0.84 0.81 0.78 60°F 1.0 2 0.98 0.9 4 0.91 0.8 8 0.85 0.81 0.79 0.76 70°F 1.0 0 0.96 0.9 3 0.89 0.8 6 0.83 0.80 0.77 0.74
80°F 0.9 8 0.94 0.9 1 0.88 0.8 4 0.81 0.78 0.75 0.72 100°F 0.94 0.91 0.88 0.84 0.81 0.78 0.75 0.72 0.70 120°F 0.92 0.88 0.85 0.81 0.78 0.76 0.72 0.70 0.67 140°F 0.89 0.85 0.82 0.79 0.76 0.73 0.70 0.78 0.65
ALTITUDE (FEET)

Unit Wiring

All units require 3-phase, 60 Hz, 208, 230, 460 or 575 volt power or 3-phase, 50 Hz, 400 volt power. Units will operate satisfacto­rily at ±10% of rated voltage at the power connection terminals of the unit. All units include individual branch circuit fusing of all motor loads and have a single-point power connection. A factory mounted, nonfused disconnect switch is an available option.
All wiring must be installed in accordance with the NEC and local codes.
22 McQuay Catalog 865-5
Selection Procedure
Achieving the optimal performance of any system requires both accurate system design and proper equipment selection. Factors which control unit selection include applicable codes, ventilation and filtration requirements, heating and cooling loads, acceptable temperature differentials and installation limitations. McQuay SWT units offer a wide selection of component options providing the capability to meet diverse application needs.
The McQuay SelectTools™ software selection program allows your local McQuay sales representative to provide you with fast, accurate and complete selection of McQuay SWT units. Unit selection can also be accomplished through reference to physical, performance, dimensional and unit weight data included in this catalog. Due to the variety of cooling system options available, only a sampling of cooling capacity data has been presented in this catalog
Proper equipment selection can be accomplished by following these three simple steps:
1. Select unit size and compressor combination.
2. Selecting heating system.
3. Select fan and motor. The following example is provided to illustrate the catalog selec-
tion procedure
Selection Example:
Scheduled Design Requirements:
Supply air volume 12,000 cfm Maximum face velocity 550 fpm Supply fan external SP 2.00" w.g. Altitude sea level Variable air volume system with fan speed control Hot water heat Water economizer system 30% pleated filters 460V/60Hz/3Ph Double wall construction Stainless steel drain pan Premium efficiency motor
Summer Design:
DX coil mixed air dry bulb 80F DX coil mixed air wet bulb 67F Sensible load 345,000 Btu/hr Total load 450,000 BTU/hr Supply fan sensible heat
rise Entering condenser water 85F Leaving condenser water 95F Minimum condenser water 55F
3F
Winter Design:
Return air temperature 60°F Space heating load 450 mbh Entering hot water temperature 180°F
Step 1 - Unit Size Selection
Unit size is based on coil face area and cooling capacity require­ments. Supply air capacity and maximum face velocity constraints should serve as a guide for selecting coil dimensions and cabinet size.
Based on the given data, the appropriate coil face area may be determined as follows:
Minimum face area = supply air volume/maximum face velocity
=12,000 cfm/550 fpm = 21.8 square feet
Note: Unit data is based on standard air conditions of
70°F at sea level. See “Application Considerations” on page 20 for temperature/altitude conversion fac­tors for non-standard conditions.
Referring to Table 4 on page 25 under the Physical Data section, the 23.3 square foot coil of the SWT040C satisfies the require­ments.
Step 2 - Unit DX Cooling Selection
Since the design cfm is less than the nominal value in the DX Cooling Capacity Data table, the capacities must be adjusted. See Table 5. DX Cooling Capacity Correction Multipliers on page 26 .
CFM correction factor = design cfm / nominal cfm = 12,000 / 14,000 = .857
Total heat correction multiplier = .973 Capacity required from table = 450mbh /.973 = 462.5 mbh
Sensible heat correction multiplier =.929 Capacity required from table = 345 mbh /.929 = 371.4 mbh
Using the "DX Cooling Capacity Data" tables provided, the unit selection is a SWT040C with (1) 6hp and (3) 10hp compressors. Unit performance from the table equals 512.8 TMBH/375.9 SMBH at 123gpm. Adjusting for the lower cfm yields:
Total capacity = 512.8 MBH x .973 = 499.0 MBH Sensible capacity = 375.9 MBH x .929 = 349.2 MBH Coil LAT = 80º F - 349.2 MBH / (1.085 x 12,000 cfm) = 53.2°F. Condenser flow rate = 123 gpm x .973 = 120 gpm
Step 3 - Economizer Capacity Selection
Determine the Waterside Economizer Capacity by referring to Table 18 on page 30. Use entering air of 80/67°F and entering water of 55°F at 120 gpm. Interpolating for the required gpm, economizer performance equals 276.3 TMBH / 261.9 SMBH at the unit's nominal cfm. Using the Waterside Economizer Capacity Correction Factors (Table 6 on page 26), performance at the spec­ified cfm can be found.
Total capacity = 276.3 MBH x 0.943 = 260.6 MBH Sensible capacity = 261.9 MBH x 0.904 = 236.8 MBH
McQuay Catalog 865-5 23
Selection Procedure
Step 4 - Heating Selection
Determine hot water capacity from Table 19 on page 31. After interpolating for the specified cfm, Table 19 indicates a total of 457mbh.
Step 5 - Fan/Motor Selection
Fan/motor selection is based on unit total static pressure and design airflow. Total static pressure includes the internal air pres­sure drops of unit components and external air pressure drops of supply and return air duct systems. See “” on page 31 for internal pressure drops of unit components. Values in the table may be interpolated for the specified cfm.
Internal pressure drops:
DX coil (wet surface) 0.68" w.g. Economizer coil (dry surface) 0.38" w.g. Hot water coil 0.11" w.g. 4", 30% efficient filters 0.19" w.g. Total internal pressure drop 1.36" w.g.
External pressure drop:
Supply + return duct 2.00" w.g.
Total static pressure = internal drops + external drops = 1.34" + 2.00" = 3.36" w.g.
Entering the fan curve for the SWT040C at 12,000cfm and 3.75" w.g., yields 13.0 required fan brake horsepower . A 15 horsepower motor can be selected.
Step 6 - Calculating Unit Weight
Referring to Table 29 on page 42, for a SWT040C:
Unit weight = SWT basic unit + 6 row evaporator coil + economizer coil + water (econ. coil)
+ hot water coil + water (HW coil) + [(1) 6 hp, (3)10 hp] compressor / condenser
+ water (condenser) SAF + SAF motor + VFD = 1473 + 450 + 410 + 11 1 + 152 + 32 + 1233 + 74 + 1 120 + 185 + 50 = 5,290 Lbs.
Step 7 - Supply Power Wiring
Sizing supply power wire for a unit is based on the circuit with the highest amperage draw. All electrical equipment is wired to a cen­tral control panel for either single or optional dual power connec­tions. See “” on page 40 for FLA and RLA ratings. Determine Minimum Circuit Ampacity (MCA) as follows:
MCA = [1.25 x RLA or FLA of largest motor] + [1.00 x RLA or FLA of all other loads] + [2 amps (controls)]
RLA/FLA (1) 6 horsepower compressors 8.1 amps each (3) 10 horsepower compressors 14.1 amps each 15 horsepower premium efficiency
supply fan motor
MCA = [1.25 x 18.9] + [(8.1 + 14.1 + 14.1 + 14.1)] + [2] = 76.0 amps
Note: If a unit has been selected with non-concurrent electric heat, MCA must be calculated for both the heating mode and the cooling mode and the larger value used.
18.9 amps
Step 8 - R-407C Performance
The cooling tables (starting on page 26) document the old R-22 cooling capacity and compressor kW. The R-407C performance correction factors vary slightly with the unit size and operating conditions but can be estimated as shown in the table below. Use the McQuay SelectTools™ computer selection program to obtain the exact R-407C performance.
Table 3. R-407C correction facto r
Compressor capacity
0.96 to .98
24 McQuay Catalog 865-5
Table 4. SWT 018C Through SWT 040C
Physical Data
Data
018C 023C 028C 035C 040C
SWT Model Size
Compressor
Quantity 44444
Size See DX Cooling Capacity Tables
Evaporator Coil
Face Area (Ft.
2
)
11.8 15.3 18.9 23.3 26.3
Rows 4, 6 4, 6 4, 6 4, 6 4, 6
Fpi 1212121212
Performance
a
EER / IPLV 13.33
13.95 14.7 13.47 13.27
Waterside Economizer Coil
Face Area (Ft.
2
)
11.8 15.3 18.9 23.3 26.3
Rows 44444
FPI 1212121212
Maximum Working Pressure (psig) 400 400 400 400 400
Hot Water Heating Coil
Face Area (Ft.2)
9.3 12.8 16.3 20.2 23.8
Rows 1, 2 1, 2 1, 2 1, 2 1, 2
Fpi 1212121212
Electric Heat
Kw 34 34 34 34 34
Filters
(Qty) size (in)
4” depth
Evaporator Fan
b
(3) 20 x 20 (3) 20 x 20 (3) 20 x 20 (5) 20 x 20 (5) 20 x 20 (2) 25 x 20 (2) 25 x 20 (2) 25 x 20 (5) 25 x 20 (5) 25 x 20 (4) 16 x 25 (4) 16 x 25 (4) 16 x 25
Quantity 11122
Size 15 18 18 15 15
Minimum Horsepower 5 7.5 10 10 15
Maximum Horsepower 10 15 20 20 25
Minimum Design cfm, CV 2950 3825 4725 5825 6575
Minimum Design cfm, VAV 4720 6120 7560 9320 10520
Maximum Design cfm 7080 9180 11340 13980 15780
Condensers
Waterside Working Pressure (psig) 400 400 400 400 400
Minimum Entering Temperature (°F)
Mechanical Cooling
55 55 55 55 55
Minimum GPM 2541536669
Maximum GPM 88 108 125 159 166
a. Based on ARI 340/360-93 standard rating conditions, 80/67°F to the coil, 85-95° condenser water. b. Standard fan TSP limit is 5.5 inches of water. Consult your local McQuay sales representative for applications beyond this range.
McQuay Catalog 865-5 25
Performance Data
Unit Efficiency Ratings Correction Multipliers
DX Cooling Capacity Correction Multipliers
Table 5. DX Cooling Capacity Correction Multipliers
Description
Total Heat 0.968 0.971 0.985 0.991 1.000 1.006 1.012 1.019 1.025
Sensible Heat 0.900 0.925 0.952 0.974 1.000 1.024 1.048 1.070 1.093
Compressor Motor Kw 0.980 0.985 0.989 0.995 1.000 1.004 1.006 1.011 1.017
-20% -15% -10% -5% Std. +5% +10% +15% +20%
Waterside Economizer Capacity Correction Factors
Table 6. Waterside Economizer Capacity Correction Factors
Cfm Compared To Rated Quantity Total Cooling Capacity Multiplier Sensible Cooling Capacity Multiplier
-20% 0.920 0.870
-10% 0.960 0.930
Waterside Economizer
STD. 1.000 1.000 +10% 1.04 1.06 +20% 1.08 1.12
Percent Standard Cfm
50 Hertz
For 50 Hz applications, the total capacity must be derated by 0.89 and the sensible capacity must be derated by 0.94. The 50 Hz supply fan motor horsepower selections must be based on fan brake horsepower (from Fig ure 21th rough Figur e 29 ) divided by 0.8.

DX Cooling Capacity Data

SWT023C - 8000 CFM
Table 7. SWT023C - 8000 CFM (4 Compressors)
Compressors EDB(°F) EWB(°F) EWT(°F) TMBH SMBH LDB LWB GPM
75 298.6 230.4 48.6 48.4 71
75 62
(4)6HP
Note: See T able5 DX Cooling Capacity Correction Factors on page26 for determining unit capacity at other than nominal cfm. For a comp uter genera ted job specific selection, con tact you r
local McQuay sales representative. For 50 Hz applications, the tot al cap ac ity must be dera ted by 0.89 and the sensible cap acity must be derate d by 0.94. All cap acit ies ar e gross an d do not account for fan motor heat. Altitude and/or Glycol selections also available.
80 67
85 72
85 289.3 226.1 49.1 48.9 70 95 279.3 221.7 49.6 49.4 70 75 323.3 227.1 54.0 53.8 76 85 313.0 223.0 54.4 54.3 75 95 302.3 218.7 54.9 54.8 75 75 349.9 223.3 59.4 59.2 82 85 339.0 219.4 59.9 59.7 81 95 327.5 215.3 60.3 60.2 80
26 McQuay Catalog 865-5
SWT028C - 10,000 CFM
Table 8. SWT028C - 10,000 CFM (4 Compressors)
Compressors EDB(°F) EWB(°F) EWT(°F) TMBH SMBH LDB LWB GPM
75 62
(4) 6HP
80 67
85 72
Table 9. SWT028C - 10,000 CFM (3/1 Compressors)
Compressors EDB(°F) EWB(°F) EWT(°F) TMBH SMBH LDB LWB GPM
75 62
(3) 6HP, (1) 10HP
80 67
85 72
Performance Data
75 314.6 261.7 51.0 50.8 74 85 304.2 257.1 51.4 51.2 73 95 293.7 252.5 51.8 51.6 73 75 339.2 258.0 56.3 56.2 79 85 328.3 253.8 56.7 56.6 79 95 317.0 249.4 57.1 57.0 78 75 366.3 253.9 61.7 61.6 85 85 354.4 249.8 62.1 61.9 84 95 342.4 245.6 62.5 62.3 83
75 364.2 283.6 49.0 48.8 87 85 352.7 278.4 49.5 49.3 86 95 340.5 272.9 50.0 49.8 85 75 394.7 280.0 54.3 54.2 93 85 382.1 274.9 54.8 54.7 92 95 368.9 269.5 55.3 55.1 91 75 427.8 275.5 59.7 59.6 100 85 414.1 270.6 60.2 60.1 99 95 399.8 265.5 60.6 60.5 97
SWT035C - 12,000 CFM
Table 10. SWT035C - 12,000 CFM (2/2 Compressors)
Compressors EDB(°F) EWB(°F) EWT(°F) TMBH SMBH LDB LWB GPM
75 62
(2) 6HP, (2) 10HP
80 67
85 72
Table 11. SWT035C - 12,000 (1/3 Compressors)
Compressors EDB(°F) EWB(°F) EWT(°F) TMBH SMBH LDB LWB GPM
75 62
(1) 6HP, (3) 10HP
80 67
85 72
75 422.1 333.7 49.5 49.3 100 85 408.7 327.6 50.0 49.8 100 95 394.7 321.4 50.4 50.3 99 75 457.8 329.6 54.8 54.7 108 85 443.3 323.8 55.3 55.1 107 95 428.0 317.7 55.7 55.6 105 75 496.5 324.6 60.2 60.1 116 85 481.0 319.1 60.6 60.5 114 95 464.3 313.2 61.1 60.9 113
75 468.6 354.8 47.9 47.8 112 85 454.0 348.0 48.4 48.3 111 95 438.6 341.0 48.9 48.8 110 75 509.4 350.7 53.2 53.1 120 85 493.5 344.1 53.7 53.6 119 95 476.6 337.2 54.2 54.1 118 75 553.9 345.6 58.6 58.5 130 85 536.7 339.2 59.1 59.0 128 95 518.3 332.5 59.6 59.5 127
Note: See Table5 DX Cooling Capacity Correction Factors on page 26 for de termining unit capacity at other than nom inal cfm.
For a computer generated job specific selection, contact your local McQuay sales representative. For 50 Hz applications, the total capacity must be derated by 0.89 and the sensible capacity must be derated by 0.94. All capacities are gross and do not account for fan motor heat. Altitude and/or Glycol selections also available.
McQuay Catalog 865-5 27
Performance Data
SWT040C - 14,000 CFM
Table 12. SWT040C - 14,000 CFM 2/2 Compressors)
Compressors EDB(°F) EWB(°F) EWT(°F) TMBH SMBH LDB LWB GPM
75 62
(2)6HP, (2)10HP
Table 13. SWT040C - 14,000 CFM 1/3 Compressors)
Compressors EDB EWB EWT TM BH SMBH LDB LWB GPM
(1)6HP, (3)10HP
80 67
85 72
75 62
80 67
85 72
75 436.1 364.0 51.2 50.9 103 85 422.2 357.8 51.6 51.3 102 95 407.6 351.3 52.0 51.7 101 75 471.8 359.6 56.4 56.3 110 85 456.9 353.8 56.8 56.6 109 95 440.8 347.5 57.2 57.0 108 75 511.4 354.6 61.8 61.6 119 85 495.0 348.9 62.1 62.0 117 95 477.2 342.8 62.5 62.4 116
75 487.9 387.0 49.6 49.5 116 85 472.2 379.9 50.1 50.0 114 95 456.0 372.5 50.6 50.4 113 75 530.1 382.9 54.9 54.8 124 85 512.8 375.9 55.4 55.3 123 95 494.6 368.6 55.8 55.7 121 75 576.9 377.8 60.2 60.2 134 85 557.8 371.0 60.7 60.6 132 95 537.7 363.9 61.2 61.1 130
28 McQuay Catalog 865-5

Waterside Economizer Capacity

SWT018D - 6000 CFM
Table 14. SWT018D - 6000 CFM
EWT GPM EDB EWB TMBH SMBH LDB LWB LWT
33 43 136.0 128.6 55.4 54.2 51.4
45
55
Note: See Table 6. Waterside Economizer Capacity Correction Factors on page 26 for determining capacity at other than nominal cfm.
72 163.5 142.7 53.3 52.5 49.5 39 51 187.4 145.3 57.8 57.1 52.4 85 225.2 160.8 55.5 54.9 50.3 20 26 74.2 74.2 63.7 57.8 60.7 46 92.7 92.7 60.9 56.8 59.0 26 34 106.0 105.9 63.9 61.6 61.2 59 126.2 120.0 61.7 60.5 59.3
75 62
80 67
75 62
80 67
SWT023D - 8000 CFM
Table 15. SWT023D - 8000 CFM
EWT GPM EDB EWB TMBH SMBH LDB LWB LWT
44 57 180.9 171.1 55.4 54.2 51.4
45
55
Note: See Table 6. Waterside Economizer Capacity Correction Factors on page 26 for determining capacity at other than nominal cfm.
96 216.9 189.6 53.3 52.5 49.5 52 68 249.1 193.3 57.9 57.2 52.4
113 298.6 213.5 55.6 55.0 50.3
26 35 99.1 99.1 63.7 57.8 60.7 61 123.2 123.2 60.9 56.8 59.0 35 46 141.0 141.0 63.9 61.6 61.2 79 167.5 159.5 61.8 60.6 59.3
75 62
80 67
75 62
80 67
SWT028D - 10,000 CFM
Table 16. SWT028D - 10,000 CFM
EWT GPM EDB EWB TMBH SMBH LDB LWB LWT
55 71 224.4 212.3 55.6 54.3 51.3
45
55
Note: See Table 6. Waterside Economizer Capacity Correction Factors on page 26 for determining capacity at other than nominal cfm.
120 266.5 234.2 53.6 52.7 49.4
65 85 307.9 239.6 58.1 57.3 52.3
142 366.1 263.5 55.9 55.2 50.2
33 44 123.9 123.9 63.7 57.8 60.7 76 152.3 152.3 61.1 56.8 59.0 44 57 175.1 175.1 64.0 61.7 61.1 98 206.1 197.1 62.0 60.7 59.2
75 62
80 67
75 62
80 67
120.1 118.4 57.0 55.1 52.3
164.7 135.9 59.3 58.4 53.4
61.1 61.1 65.7 58.6 61.2
93.2 93.2 65.8 62.3 62.1
160.2 157.8 57.0 55.1 52.3
219.3 180.9 59.3 58.4 53.4
81.9 81.9 65.6 58.6 61.3
124.3 124.3 65.8 62.3 62.1
199.9 196.6 57.0 55.2 52.3
272.7 224.9 59.4 58.5 53.3
103.5 103.5 65.5 58.5 61.3
155.4 155.4 65.8 62.3 62.1
Performance Data
McQuay Catalog 865-5 29
Performance Data
SWT035D - 12,000 CFM
Table 17. SWT035D - 12,000 CFM
EWT GPM EDB EWB TMBH SMBH LDB LWB LWT
65 85 289.9 266.5 54.7 53.6 51.8
45
55
Note: See Table 6. Waterside Economizer Capacity Correction Factors on page 26 for determining capacity at other than nominal cfm.
144 338.3 290.5 52.9 52.1 49.7
79 101 399.8 300.7 57.1 56.4 52.9 170 466.0 327.9 55.0 54.4 50.5
39
52 160.6 160.6 62.8 57.5 61.1
92 192.2 192.2 60.4 56.6 59.2
52
69 223.9 221.9 63.1 61.3 61.5 118 261.2 244.9 61.4 60.3 59.4
75 62
80 67
75 62
80 67
SWT040D - 14,000 CFM
Table 18. SWT040D - 14,000 CFM
EWT GPM EDB EWB TMBH SMBH LDB LWB LWT
76
99 339.0 311.5 54.7 53.6 51.8
45
55
Note: See Table 6. Waterside Economizer Capacity Correction Factors on page 26 for determining capacity at other than nominal cfm.
168 396.3 339.9 52.8 52.1 49.7
92 118 467.6 351.4 57.0 56.4 52.9 198 545.9 383.6 54.9 54.4 50.5
46
61 187.4 187.4 62.8 57.5 61.1 107 224.9 224.9 60.3 56.6 59.2
61
80 261.7 259.3 63.1 61.3 61.5 137 305.9 285.7 61.3 60.3 59.5
75 62
80 67
75 62
80 67
259.8 249.5 56.0 54.6 52.9
357.0 283.0 58.4 57.7 54.1
137.0 137.0 64.6 58.2 62.0
201.8 201.9 64.6 61.9 62.7
303.4 291.4 56.0 54.6 53.0
417.3 330.7 58.4 57.6 54.1
159.6 159.6 64.6 58.2 62.0
235.6 235.6 64.6 61.9 62.7
30 McQuay Catalog 865-5
Performance Data

Heating Capacity Data

Hot Water Coil Capacity (1 Row) Table 19. Entering Water 180°F and Entering Air 60°F
UNIT CFM TMBH LWT LDB GPM
018C
023C
028C
035C
040C
Note: For complete one-row capacity and extended two-row capacity, please contact your McQuay sales representative.
Selections based on water, for glycol/water solutions, please contact your McQuay sales representative.
Electric Heat
Table 20. SWT018D - 040D
SWT 208V/60HZ/3PH 230V/60HZ/3PH 400V/50HZ/3PH 460V/60HZ/3PH 575V/60HZ/3PH
Unit Size kW MBH FLA kW MBH FLA kW MBH FLA kW MBH FLA kW MBH FLA
018D - 040D 27.8 94 77.2 34 116 85.6 25.7 88 37.2 34 116 42.8 34 116 34.2
4000 191.6 158.1 103.8 18 7000 241.7 152.4 91.6 18 6000 277.9 158.8 102.4 25 9000 329.7 154.9 93.5 25 8000 353.3 159.8 100.4 35
10500 397.1 157.5 94.6 35
9000 430.2 158.1 103.7 40 13500 512.3 154.0 94.7 40 11000 524.5 158.2 103.6 50 16000 621.0 155.2 95.5 50

Component Pressure Drops

Table 21. Unit Air Pressure Drops (inches w.g.)
Unit CFM 4", 30% Filter 4", 65% Filter 4-Row Econo. 6-Row DX 1-Row HW
4500 0.14 0.27 0.28 0.52 0.11
SWT018C
SWT023C
SWT028C
SWT035C
SWT040C
Note: DX pressure drops are wet coil and economizer are dry coil.
All units must have a DX coil pressure drop.
5000 0.17 0.31 0.34 0.61 0.13 6000 0.23 0.41 0.46 0.81 0.17 7000 0.29 0.52 0.60 1.04 0.22 6000 0.15 0.28 0.29 0.54 0.10 7000 0.19 0.35 0.38 0.69 0.13 8000 0.23 0.43 0.48 0.85 0.16 9000 0.28 0.51 0.59 1.03 0.20 8000 0.17 0.31 0.34 0.61 0.11
9000 0.20 0.37 0.41 0.74 0.13 10000 0.24 0.44 0.49 0.86 0.16 11000 0.28 0.50 0.58 1.00 0.19
8000 0.12 0.23 0.23 0.44 0.08 10000 0.17 0.32 0.34 0.62 0.11 12000 0.23 0.42 0.47 0.83 0.15 14000 0.29 0.52 0.61 1.04 0.19 10000 0.14 0.27 0.28 0.52 0.08 12000 0.19 0.35 0.38 0.68 0.11 14000 0.24 0.44 0.50 0.86 0.15 16000 0.30 0.55 0.63 1.05 0.19
McQuay Catalog 865-5 31
W a t e r F l o w R a t e - g p m ( L / s )
4 0
( 2 . 5 )
5 0
( 3 . 2 )
6 0
( 3 . 8 )
7 0
( 4 . 4 )
8 0
( 5 . 1 )
9 0
( 5 . 7 )
1 0 0
( 6 . 3 )
1 5 0
( 9 . 5 )
2 0 0
( 1 2 . 6 )
W a t e r P r e s s u r e D r o p ( k P a ) f t . w . g .
( 6 0 ) 2 0
( 4 5 ) 1 5
( 3 0 ) 1 0
( 2 7 ) 9 ( 2 4 ) 8
( 2 1 ) 7
( 1 8 ) 6
( 1 5 ) 5
3 0
( 1 . 9 )
2 0
( 1 . 2 )
( 9 ) 3
( 1 2 ) 4
( 9 0 ) 3 0
( 1 2 0 ) 4 0
( 1 5 0 ) 5 0
( 1 8 0 ) 6 0
( 2 1 0 ) 7 0
0 1 8 - 0 2 8
0 3 5 - 0 4 0
( 6 ) 2
Performance Data
Figure 17. Condenser Water Pressure Drop, SWT 018C through SWT 040C
40
O)
12 HP
20
2
18 HP
28 HP
24 HP
32 HP
36 HP
10
8
Pressure Drop (H
6
4 3
20 40 60 80 100 200 300
Condenser Flow Rate (gpm)
Note: HP = Total unit compressor horsepower.
Figure 18. Economizer System Water Pressure Drop, SWT 018C through 040C
40 HP
Note: Includes coil, Control valves, and interconnecting piping. Note: Add this P to condenser P to obtain unit P for pump selection.
32 McQuay Catalog 865-5
W a t e r F l o w R a t e - g p m ( L / s )
4 0
( 2 . 5 )
5 0
( 3 . 2 )
6 0
( 3 . 8 )
8 0
( 5 . 1 )
1 0 0
( 6 . 3 )
1 5 0
( 9 . 5 )
3 0
( 1 . 9 )
2 0
( 1 . 2 )
W a t e r P r e s s u r e D r o p ( k P a ) f t . w . g .
( 6 0 ) 2 0
( 3 0 ) 1 0
( 2 4 ) 8
( 1 8 ) 6
( 1 5 ) 5
( 9 ) 3
( 1 2 ) 4
( 9 0 ) 3 0
( 1 2 0 ) 4 0
( 1 5 0 ) 5 0
( 1 8 0 ) 6 0
( 2 1 0 ) 7 0
0 1 8
0 2 3
0 3 5
0 2 8
0 4 0
N o t e : I n c l u d e s c o i l , c o n t r o l v a l v e a n d i n t e r c o n n e c t i n g p i p i n g .
Pressure Drop (H
2
O)
Condenser Flow Rate (gpm)
10 100 500
0.1
1
10
100
0.01
018C - 028C
035C - 040C
Performance Data
Figure 19. Hot Water Coil Water Pressure Drop (1-row), SWT018C through SWT040C
Figure 20. Water Regulating Valve Pressure Drop
McQuay Catalog 865-5 33
CFM
0 1000 2000 3000 4000 5000 6000 7000 8000
Static Pressure (inches of water)
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
5.5
6.0
10 HP
7.5
5.0
3.0
2.0
1.5
600
700
800
900
1000
1100
1200
1300
1400
1500
1600 RPM
CFM
0 1000 2000 3000 4000 5000 6000 7000 8000
Static Pressure (inches of water)
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
5.5
6.0
10 HP
7.5
5.0
3.0
2.0
1.5
600
700
800
900
1000
1100
012 0
1300
1400
1500
1600 RPM
Performance Data

Fan Curves

Figure 21. SWT018C, 15"x15" Fan Without Variable Inlet Vanes
Note: Fan TSP limit is 5.5" of water. Consult your local McQuay sales representative for applications beyond this range.
Figure 22. SWT018C, 15"x15" Fan, with Variable Inlet Vanes
34 McQuay Catalog 865-5
Figure 23. SWT023C/028C, 18"x18" Fan, without Variable Inlet Vanes
CFM
0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 11000 12000
Static Pressure (inches of water)
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
5.5
6.0
10.0
7.5
5.0
3.0
2.0
1.5
600
700
800
900
1000
1100
1200
1300
1400 RPM
15.0
20.0 HP
CFM
0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 11000 12000
Static Pressure (inches of water)
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
5.5
6.0
10.0
7.5
5.0
3.0
2.0
1.5
600
700
800
900
1000
1100
1200
1300
1400 RPM
15.0
20.0 HP
Performance Data
Note: Fan TSP limit is 5.5" of water. Consult your local McQuay sales representative for applications beyond this range.
Figure 24. SWT023C/028C. 18"x18" Fan with Variable Inlet Vanes
McQuay Catalog 865-5 35
CFM
0
1000
2000
3000
4000
5000
6000
7000
8000
9000
10000
11000
12000
13000
14000
15000
16000
17000
18000
Static Pressure (inches of water)
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
5.5
6.0
10.0
7.5
5.0
3.0
2.0
1.5
600
700
800
900
1000
1100
1200
15.0
20.0
25.0
30.0 HP
1300
1400
1500
1600 RPM
Performance Data
Figure 25. SWT 035C/040C. Dual 15"x15" Fan, Without Variable Inlet Vanes
Note: Fan TSP limit is 5.5" of water. Consult your local McQuay sales representative for applications beyond this range.
36 McQuay Catalog 865-5
3.25
23.58
19.33
9.58
18.25
33.75
L
G x H
Return air
FILTER SECTION
ECONOMIZER
EVAPORATOR
HEATER
ELECTRICAL PANEL
A
Sloped S. S. drain pans
Condenser
Compressor
Sloped S. S. drain pans
3.25
23.58
19.33
9.58
18.25
33.75
L
G x H
Return air
FILTER SECTION
ECONOMIZER
EVAPORATOR
HEATER
ELECTRICAL PANEL
Condenser
Compressor
A
Dimensional Data
Figure 26. Left Side, Front (CW) Discharge Figure 27. Left Side, Back (CCW) Discharge
Note: Select unit arrangement on the unit selection.
Table 22. SWT018C - 040C Dimensions
BASIC UNIT 018C 023C 028C 035C 040C A B C D Fan Discharge 18.62 21.88 21.88 18.62 18.62 E Fan Discharge 15.88 18.88 18.88 15.88 15.88 F Unit Side to Fan 32.69 31.06 31.06 23.88 23.88 G Return Duct Height 45.94 45.94 45.94 45.94 45.94 H Return Duct Length 80.00 80.00 80.00 96.00 96.00 J Water Out/In (ODS) 2-1/8 2-1/8 2-1/8 2-5/8 2-5/8 K Hot Water Out/In (ODS) 1-5/8 1-5/8 1-5/8 1-5/8 1-5/8 L To Fan Discharge 2.0 2.0 2.0 6.46 6.46
a. Dimensions do not include lifting lugs, handle, latch, or fastener extensions. b. For shipping dimensions add 4" (102mm) to depth, 8" (204mm) to length, and 4" (102mm) to height.
Depth Length Height
a b
a b
52.00 52.00 52.00 52.00 52.00
a b
84.00 84.00 84.00 100.00 100.00
112.75 112.75 112.75 112.75 112.75
McQuay Catalog 865-5 37
F FDD
15.0
(381)
E
34.0
(864)
78.5
(199.4)
B
72.0
(182.8)
Mechanical
Access
Power entry 7/8" (2.2) KO
Electrical Access
MicroTech II System Indicator Panel
Fan
Outlets
1.0 (25)Neoprene Isolation Pads
shipped separately
Connection Plate
Return Air
Unit Front Plan
Left side piping connections
Right side piping connections (optional)
Supply fan motor
Front Elevation
(For dimentions B, D, E and F see Table 5)
AFD (Optional)
L
3.125 (79)
Power Entry
Dimensional Data
Figure 28. Unit Front Plan and Front Elevation
Note: 1. See Table 25 for dimensions B, D, E, F and L.
2. Service connections determined when facing the front of the unit. Left-hand standard, right-hand optional. Please indicate on the unit submittal.
3. Unit sizes 018C, 023C, and 028C have single fan.
4. Unit sizes 018C, 023C, and 028C have single mechanical access panel in bottom front and bottom back.
38 McQuay Catalog 865-5
Figure 29. Back Elevation and Left Side (typical SWT018C - 040C)
Mechanical access
Connection plate
2.0 TYP
G x H
Return air opening
Mechanical acces s (3 ) (4 )
26.63
1.0 Neoprene Isolation pads shipped separately
C
B(2)
Back Elevation
23.81
(K) Hot Water Out
(K) Hot Water In
10.38
A
A
36.5
Main
Lifting rod (by others) Place through base channel
Filter/water economizer
1.12 ODS drain (J) Water out
(J) Water in
G x H
Retun air
Left Elevation
Main and filter/waterside economizer connection
Section A-A
Dimensional Data
Note: 1. Filters are removable from the rear of the unit or through a side filter access door, located on piping connection side.
2. Length will be increased by approximately 3-1/2”, for piping connections when water economizer option is ordered
3. Mechanical access panels(s) in the back of the unit start 2” below return duct opening. Do not obstruct the access panel(s).
4. There are two access doors on 018C, 023C, and 028C instead of three as shown.
5. All dimensions are given in inches.
6. All dimensions are ±0.25”.
Note: Note:
McQuay Catalog 865-5 39
Electrical Data
Table 23. SAF Motor Nameplate Amp Table
Horsepower TYPE
3
5
7.5
10
15
20
25
a. 460/60/3 motors are used. Derate nameplate horsepower to 0.83 to obtain actual horsepower.
High Efficiency 9.9 9.0 4.5 4.5 3.4
Premium Efficiency 9.3 8.2 4.1 4.1 3.1
High Efficiency 16.1 14.0 7.0 7.0 5.3
Premium Efficiency 15.7 13.6 6.8 6.8 5.2
High Efficiency 25.0 21.6 10.8 10.8 8.2
Premium Efficiency 22.3 20.0 10.0 10.0 7.4
High Efficiency 33.0 28.0 14.0 14.0 11.0
Premium Efficiency 29.0 25.8 12.9 12.9 10.3
High Efficiency 44.8 40.6 20.3 20.3 16.2
Premium Efficiency 43.4 37.8 18.9 18.9 14.1
High Efficiency 61.0 50.0 25.0 25.0 20.0
Premium Efficiency 57.0 49.0 24.5 24.5 18.9
High Efficiency 74.0 62.0 31.0 31.0 24.3
Premium Efficiency 70.0 61.0 30.5 30.5 24.2
208/60/3 230/60/3
FLA FLA FLA FLA FLA
Table 24. Compressor Amperages
Compressor
HP
10 R-407C 30.1 239.0 27.2 216.0 13.6 125.0 10.9 80.0
Refrigerant
6 R-407C
208/60/3 230/60/3 460/60/3 575/60/3
RLA LRA RLA LRA RLA LRA RLA LRA
16.3 173.0 14.7 156.0 7.3 75.0 5.9 54.0
400/50/3
a
460/60/3 575/60/3
Table 25. Electric Heat
SWT UNIT SIZE
018C - 040C
208V/60HZ/3PH 230V/60HZ/3PH 400V/50HZ/3PH 460V/60HZ/3PH 575V/60HZ/3PH
kW MBH FLA kW MBH FLA kW MBH FLA kW MBH FLA kW MBH FLA
27.8 94 77.2 34 116 85.6 25.7 88 37.2 34 116 42.8 34 116 34.2
40 McQuay Catalog 865-5
Electrical Data

Supply Power Wiring

1. Units require three-phase power supply.
2. Allowable voltage tolerances: a. 60 Hertz
i. Nam eplate 208V: Min. 187V, Max. 229V ii. Nameplate 230V: Min. 207V, Max. 253V iii. Nameplate 460V: Min. 414V, Max. 506V iv. Nameplate 575V: Min. 518V, Max. 632
b. 50 Hertz
i. Nam eplate 400V: Min. 342V, Max. 418V
3. Power lead wire sizing: a. For units with cooling capability (all concurrent
loads) with or without hot water heating and cir­cuits with motor loads only:
MCA = 1.25 (largest motor RLA or FLA) + other loads + 2 amps
b. For units with cooling capability and non concur-
rent electric heat capability: In the cooling mode, the loads will be composed of supply fan motor and compressors. In heating mode, the loads will be compose of supply fan motor and electric heater. The MCA is calculated for unit running in either mode; the highest value obtained is used for the MCA. i. Fo r unit in cooling mode:
MCA = 1.25 (largest RLA or FLA) + other loads + 2 amps
ii. For unit in heating mode:
MCA = 1.25 (electric heat FLA + supply fan motor FLA) + 2 amps
Note: Use copper wire only.
4. Size wires in accordance with T able 310-16 or 310-19 of the National Electrical Code.
5. Wires should be sized for a maximum of 3% voltage drop. See Table 27 and Table 28 for Single Disconnect or Power Block lug sizes.
Table 26. Single Disconnect
UNIT VOLTAGE SIZE (AMPS)
018-028 018-028 400/460 100 018-028 575 100 035-040 208/230 225 035-040 400/460 150
035 575 100 040 575 150
208/230 225
Table 27. Lug Sizes For Single Disconnect
DISCONNECT SIZE LUG SIZE
100 150 #2-3/0 225 #3-300 MCM 250 #4-350 MCM
#6-2/0
Table 28. Lug Sizes For Power Block
UNIT VOLTAGE LUG SI ZE
018-040
ALL #6-400 MCM
McQuay Catalog 865-5 41
Unit Weights
Table 29. Unit and Component Weights in lbs.
Unit Weights
Basic Configuration
SWT basic unit 1314 1314 1314 1473 1473
Filters
4" - 30% efficiency (Included in basic unit weight) 4" - 65% efficiency (Included in basic unit weight)
Evaporator Coil
6 Row, 12 fpi 250 294 347 417 450
Water Economizer Coil (1)
Hot Water Coil (2)
Electric Heat
Compressor / Condenser Assembly
Supply Fan (3)
Supply Fan Motors
Variable Frequency Drive 208/230V
Variable Frequency Drive 380/460V
Note: Notes: 1. Water economizer coil weight includes valves and piping.
4 Row, 12 fpi 206 238 278 333 354
4 Row, 12 fpi 266 298 340 393 410 Water weight 51 65 75 94 11 1
1 Row, 12 fpi 71 97 119 130 152 Water weight 16 20 23 28 32
34 KW 20 20 20 20 20
Water
(4) 6 43 856 856 856 856 — (3) 6 (1)10 57 987 987 987 987 (2) 6 (2)10 66 1105 1105 1105 (1) 6 (3)10 74 1233 1233
(4)10 95 1368 1368
15"x15" FC 900 — 18"x18" FC 930 930
(2) 15"x15" FC 1120 1120
3 HP ODP 71 — 5 HP ODP 82
7.5 HP ODP 124 124 — 10 HP ODP 144 144 144 144 — 15 HP ODP 185 185 185 185 20 HP ODP 214 214 214 25 HP ODP ——— —266 3 HP TEFC 72 — 5 HP TEFC 85
7.5 HP TEFC 140 140 — 10 HP TEFC 170 170 170 170 — 15 HP TEFC 235 235 235 235 20 HP TEFC 300 300 300 25 HP TEFC 330
3 HP 25———— 5 HP 25————
7.5 HP 40 40 — 10 HP 50 50 50 50 — 15 HP —50505050 20 HP 75 75 75 25 HP 75
3 HP 20———— 5 HP 20————
7.5 HP 25 25 — 10 HP 25 25 25 25 — 15 HP —40404040 20 HP 50 50 50 25 HP 50 50
2. Hot water coil weight includes valves and piping.
3. Supply fan weight does not includ e motor or VFD.
018C 023C 028C 035C 040C
Unit Size
42 McQuay Catalog 865-5
Engineering Guide Specifications

General

Furnish and install, as shown on plans, McQuay model SWT self­contained packaged air conditioning system(s). Unit perfor­mance, electrical characteristics and unit arrangement shall be per the job schedule.
[Each unit shall be completely factory assembled and shipped in one piece.] [Each unit shall be shipped in two pieces, a base unit section and the unit fan section.] All units shall be shipped with a full charge of Refrigerant 22 or 407C and oil. Unit ratings shall be in accordance with the latest update of ARI Standard 360.
All units shall have decals and tags to indicate caution areas and to aid in unit service. A unit nameplate shall be fixed to a perma­nent panel next to the main control panel access. Electrical wiring diagrams shall be supplied with each unit. Installation, operating and maintenance bulletins and start-up forms shall be supplied with each unit.
Factory Run Test
Each unit shall undergo a rigorous factory run test prior to ship­ment and factory test sheets shall be available upon request. The factory test shall include dynamic trim balancing of the completed fan assembly, a compressor run check, a complete run test of all electrical components and safeties, including proper control sequencing, a leak check of all refrigerant circuits, a leak check of all water circuits and a final unit inspection.

Safety Agency Listed

The complete unit(s) shall be ETL-US and ETL-Canada listed by Intertek Testing Services, Inc. Units shall conform to bi-national standard ANSI/UL Standard 1995/CSA Standard C22.2 No. 236. Unit(s) shall be accepted for use in the City of New York by the Department of Building, MEA #368-93-E Vol. II.

Cabinet, Casing and Frame

Each unit shall have a welded 3/16" structural steel base inte­grated with formed members of 10, 12 and 14 gauge continuous galvanized steel. Exterior frame and panels shall be constructed of pre-painted galvanized steel for aesthetics and long term durabil­ity. Paint finish to include a base primer with a high quality, poly­ester resin topcoat of a neutral beige color. Finished surface to withstand a minimum 750-hour salt spray test in accordance with ASTM B117 standard for salt spray resistance. Lifting brackets capable of handling the unit shipping weight shall be welded to the unit base with holes to accept cable or chain hooks.
Each unit shall be compartmentalized for ease of service and shall be designed to permit adjustment of system electrical and refriger­ation components while the unit is in operation. The unit shall incorporate removable access panels tightly set on neoprene gas­kets. Access panels shall be a minimum of 18-gauge galvanized steel and shall be located on all sides of the unit for complete accessibility. The airside cabinet shall be insulated with 1", 1.5 pound density coated glass fiber insulation. [Solid galvanized steel liners shall be provided, allowing no exposed insulation within the air stream.]
The unit shall be comprised of three distinct sections: 1) Main cooling/heating, 2) Filter/waterside economizer and 3) Fan sec­tion. Each unit shall be designed for disassembly into the three distinct sections for access to the mechanical equipment room. Disassembly of the unit shall not require the breaking of any refrigeration lines. Separation of water piping shall be through the
use of factory installed grooved couplings. The maximum allow­able section width, including fastener heads, shall not exceed 34.5 inches.

Filter/Economizer Section:

Filters
Each unit shall be provided with an integral filter section com­plete with 4" panel filters. The filters shall be removable from the rear of the unit and shall have side access capability through [access panels] [hinged and latched access doors] on each end of the unit. The use of 2" filters is not acceptable.
[4" thick, 30% efficient, UL Std. 900, Class II, AmericanAirFilter filters shall be provided. Filters shall be frame mounted and shall slide into galvanized steel tracks contained within the unit.]
[4" thick, 60-65% efficient, UL Std. 900, Class II, AmericanAir­Filter Varicel filters shall be provided. Filters shall be frame mounted and shall slide into galvanized steel tracks contained within the unit.] [An auxiliary pre-filter rack, with 2" thick 30% efficient filters, shall be provided to upstream of the high effi­ciency filters.]
[4" thick, 80-85% efficient, UL Std. 900, Class II, AmericanAir­Filter Varicel filters shall be provided. Filters shall be frame mounted and shall slide into galvanized steel tracks contained within the unit.] [An auxiliary pre-filter rack, with 2" thick 30% efficient filters, shall be provided to upstream of the high effi­ciency filters.]
Waterside Economizer
A complete waterside economizer package shall be provided including a mechanically cleanable [chemically cleanable] coil, control valves and factory piping complete with cleanouts. Coils shall be fabricated of seamless 1/2" diameter copper tubing that is mechanically expanded into high efficiency aluminum plate fins. Coils shall be a minimum 4-row, staggered tube design with 12 fins per inch. The complete economizer package shall be rated for 400psig waterside working pressure.
The economizer section shall be complete with an insulated stain­less steel drain pan. The drain pan shall be sloped in two direc­tions to provide positive drainage. Access panels on both sides of the unit shall provide convenient access to the coil, valves and drain pan for inspection and cleaning. A factory installed drain line, with trap and cleanout, shall be provided for convenient con­nection at the unit exterior.
Economizer operation shall be controlled to maximize free cool­ing. Economizer operation shall be enabled whenever the entering water temperature is less than the entering air temperature by a field adjustable value. The economizer control valve shall modu­late in response to the cooling load. Control valve operation shall [maintain full flow through the unit at all times.] [isolate the unit from the condenser water loop when there is no call for cooling, allowing for the use of an energy saving, variable pumping sys­tem.]
Mechanical cooling shall be enabled during economizer opera­tion. If the economizer control valve is driven 90% open and the cooling load is not satisfied, compressors will stage on to main­tain set point. To maximize energy savings, economizer control will maintain full water flow until the differential between enter­ing water and entering air temperatures falls below set point.
A factory installed, non-averaging type freezestat shall provide some protection against coil freeze-up.
McQuay Catalog 865-5 43
Engineering Guide Specifications
The completed economizer assembly shall be factory leak tested.
Airside Economizer Control (External Mixing Box)
Integrated airside economizer control capability of a separate unit or remote mounted mixing box shall be provided. Economizer operation shall be controlled to maximize free cooling operation. Economizer shall be enabled whenever the remote [outside air enthalpy sensor] [comparative enthalpy sensors] [outside air tem­perature sensor] indicates that outside air is suitable for free cool­ing. The remote economizer damper actuator shall modulate in response to the cooling load.
Mechanical cooling shall be enabled during economizer opera­tion. If the outside air damper is driven to 90% open and the cool­ing load is not satisfied, compressors will stage on to maintain set point. To maximize energy savings, the economizer control will maintain 100% outdoor airflow until disabled by the enthalpy or temperature cutout. Outside air will reset to minimum position at that time.

Fan Section

Fan Assembly
All fan assemblies shall be statically and dynamically balanced at the factory, including a final trim balance, prior to shipment. All fan assemblies shall employ solid steel fan shafts. Heavy-duty pil­low block type, self-aligning, grease lubricated ball bearings shall be used. Bearings shall be sized to provide an L-50 life at 200,000 hours and shall be no smaller than the main shaft diameter. The entire fan, drive and motor assembly shall be mounted on a welded, heavy-gauge tubular steel frame and shall be mounted on [spring isolators] [spring isolators with seismic restraints]. The fan assembly shall further be isolated from the unit with a flexible connection at the fan discharge. Fixed pitch V-belt drives with matching belts shall be provided. V-belt drives shall be selected at [the manufacturer's standard service factor] [1.5 times fan brake horsepower].
The fan assembly shall feature a gradual expansion, aerodynamic duct outlet to reduce system sound generation.
Fan (SWT018C-028C)
The supply air fan shall be a double width, double inlet (DWDI) forward curved centrifugal fan, with hub and shaft secured with mating keyways. The fan wheel and housing shall be constructed from painted steel and shall be Class II construction to satisfy the specified application.
Fan (SWT035C & 040C)
The supply air fan system shall be dual, double width, double inlet (DWDI) forward curved centrifugal fans, with hubs and shaft secured with mating keyways. The fan wheels and housings shall be constructed from painted steel and shall be Class II construc­tion to satisfy the specified application.
Fan Motor
Fan motors shall be heavy-duty 1800 rpm [open drip-proof (ODP)] [totally enclosed fan cooled (TEFC)] type with grease lubricated ball bearings. [Motors shall be high efficiency and meet applicable EPACT requirements.] [Motors shall be premium effi­ciency.] Motors shall be NEMA, T-frame, Class B. Motors shall be mounted on an adjustable base that provides for proper align­ment and belt tension adjustment.
Variable Frequency Drives (SWT18C-040C)
An electronic variable frequency drive shall be provided for the supply air fan. Variable frequency drives shall be latest generation pulse width modulation type utilizing IGBT technology. The drive shall be factory installed in a designated location that pro­vides ready access to the drive and does not void unit accessibil­ity. Drives shall meet UL Standard 95-5V and the variable frequency drive manufacturer shall have specifically approved them for plenum duty application. The completed unit assembly shall be listed by a recognized safety agency, such as ETL.
The unit manufacturer shall install all power and control wiring. A manually activated bypass contactor arrangement shall be pro­vided. The bypass arrangement will allow fan operation at full design CFM, even if the drive has been removed for service.
The supply air fan drive output shall be controlled by the factory installed main unit control system and drive status and operating speed shall be monitored and displayed at the main unit control panel. A factory mounted, field adjustable duct high-limit control shall be provided to protect ductwork from excessive duct pres­sure. The installer shall provide and install sensor tubing from [a single unit mounted pressure sensor] [two unit mounted pressure sensors] to the duct location(s).
All drives shall be factory run tested prior to unit shipment.

Coils

Drain Pan
The main coil section shall be complete with an insulated stainless steel drain pan. The drain pan shall be sloped in two directions to provide positive drainage. Access panels on both sides of the unit shall provide convenient access to the coil and drain pan for inspection and cleaning. A factory installed drain line, with trap and cleanout, shall be provided for convenient connection at the unit exterior.
Cooling Coil
Direct expansion (DX) cooling coils shall be fabricated of seam­less 1/2" diameter high efficiency copper tubing that is mechani­cally expanded into high efficiency aluminum plate fins. Coils shall be a 6-row, staggered tube design with 12 fins per inch. All units shall have an independent refrigerant circuit per compressor and shall use a combination row/interlaced circuiting for efficient part load operation and to prevent air temperature stratification at partial load conditions. Each circuit shall be fed by an adjustable thermal expansion valve, with external equalizer, sized to provide efficient operation at full and at part load operating points. Plastic sleeves shall protect all distributor tubes.
All coils shall be factory leak tested with high pressure air under water.
Hot Water Coil
A 1 row hot water heating coil shall be factory installed. Coils shall be fabricated of seamless 1/2" diameter copper tubing that is mechanically expanded into high efficiency aluminum plate fins. All coil vents and drains shall be factory installed. Access panels shall provide convenient access to the coil and valve for inspec­tion and cleaning.
A factory installed two-way [modulating] [on/off] control valve and actuator shall provide control of the hot water coil. The valve actuator shall be controlled by the factory installed main unit con­trol system.
44 McQuay Catalog 865-5
Engineering Guide Specifications
[Propylene glycol shall be added to the hot water circuit to protect against coil freeze-up.]
[A factory installed, non-averaging type freezestat shall provide some protection against coil freeze-up.]
Coils shall be factory leak tested with high pressure air under water.
Electric Heat
Staged electric heating coils shall be factory installed in the unit heat section. Heating coils shall be visible and easily accessed for inspec­tion and service. Heating coils shall be constructed of low watt den­sity, nickel-chromium elements. Equipment protection controls shall include automatic reset high limit control for each heater element with manual reset backup line break protection in each heater ele­ment branch circuit. Heating element branch circuits shall be indi­vidually fused to a maximum of 48 Amps per NEC requirements.
Multiple full magnetic line break contactors shall be controlled by the factory installed main unit control system to provide multiple stages of control.
Condensers
Condensers shall be a counter flow, tube and tube design with all nonferrous water channels. Each condenser shall be on an inde­pendent refrigerant circuit and shall provide liquid sub-cooling for optimum system performance. Condensers shall be rated for 400psig refrigerant working pressure. Each condenser shall be suitable for 400psig waterside working pressure and shall be mechanically cleanable. All factory piping shall be capable of a waterside working pressure of 400 psig. Condensers shall be fac­tory piped to provide for single field condenser water supp ly and return connections.
Units provided with condensers that are not mechanically clean­able will not be acceptable.
Condensers shall be factory leak tested with high pressure air under water. The completed condenser and interconnecting pip­ing assembly shall be factory leak tested.
Condenser head pressure control (Not available with Water Economizer)
Mechanical cooling shall be available whenever entering con­denser water temperatures are 55ºF or warmer, without the use of head pressure control. For entering condenser water temperatures below 55ºF, a factory installed and controlled 2-way modulating head pressure control valve shall be provided. The valve actuator shall be controlled through the factory installed main unit control system to maintain refrigerant head pressure at entering condenser water temperatures as low as 40°F.
Compressors
Each unit shall have multiple, heavy-duty scroll compressors. Each compressor shall be on an independent refrigerant circuit and include [suction and discharge service valves with gauge ports], sight-glass, anti-slug protection, motor overload protection and a time delay to prevent short cycling and simultaneous start­ing of compressors following a power failure. Compressors shall be isolated on resilient rubber isolators to decrease noise transmis­sion. The number of compressors shall be as shown on the unit schedule.
Refrigeration Controls
Each unit shall have multiple independent refrigeration circuits. Each circuit shall include a filter-drier, liquid moisture indica­tor/sight-glass, thermal expansion valve, liquid line shutoff valve with charging port and high pressure relief device. The thermal expansion valve shall be capable of modulation from 100% to 25% of its rated capacity. [Shutoff valves shall isolate each filter­drier and sight-glass. (Units with compressor service valves only.)] Sight-glasses shall be accessible for viewing without dis­rupting unit operation. Each circuit shall be dehydrated and fac­tory charged with Refrigerant 407C and oil.
Each refrigerant circuit shall have a high and low-pressure cutout switch and a coil frost protection thermostat. The high pressure cutout shall be a manual reset control. Each low pressure control (loss of charge) and frost protection thermostat shall require a manual reset if the alarm condition occurs three times within any 24 hour period.
Refrigeration Capacity Control
Refrigeration capacity control shall be accomplished by staging of the unit's multiple compressors. To maintain desired temperature control, the unit shall have a minimum of [two] [three] [four] steps of capacity control.
All compressor capacity control staging shall be controlled by the factory installed main unit control system.

Electrical

Unit wiring shall comply with NEC requirements and with all applicable UL standards. All electrical components shall be UL recognized, where applicable. To provide for easy identification, all wiring and electrical components shall be numbered, color­coded and labeled according to the electrical diagrams provided with each unit. The main unit control panel shall be completely factory wired and contained in an accessible enclosure. The main control panel shall be provided with dead front covers over all line voltage components. A terminal board shall be provided for low voltage control wiring. Branch circuit fusing, 115V control cir­cuit transformer with fuse, system switches and high temperature sensor shall also be provided.
Pilot knockouts shall be provided at the main control panel for field wiring entrance. The unit shall have a [single] [dual] [termi­nal block] [non-fused disconnect] for main unit power connection.
Each compressor shall be controlled by its own dedicated contac­tor, shall be individually fused and shall have thermal overload protection. The supply fan motor circuit shall include a dedicated contactor, external line break overload protection and dedicated fuse protection. Group fusing of components in lieu of individual fuse protection for each component is not acceptable.
The unit control system shall permit starting and stopping of the unit locally or remotely . The keypad/display and monitoring panel shall include a three position "on", "off", "auto" switch, an Alarm indication light and a Power indication light. The Alarm light shall provide a visual indication whenever a malfunction occurs and it shall remain until the malfunction is corrected. The control system shall be capable of providing a remote alarm indication. The unit control system shall provide for pump start, outside air damper actuation, smoke shutdown, emergency shutdown, remote heat enable/disable, remote cool enable/disable, heat indication, cool indication, fan interlock and fan operation.
McQuay Catalog 865-5 45
Engineering Guide Specifications
Non-fused Disconnect Switch
[A single non-fused disconnect switch shall be provided for dis­connecting electrical power at the unit. The switch handle shall be visible, located at the front of the unit, and shall be accessible without unit entrance.]
[Dual non-fused disconnect switches shall be provided for discon­necting electrical power at the unit. One switch will service the supply fan plus the unit control system. The second switch will service the condensing unit section. Disconnect switch handles shall be visible, located at the front of the unit, and shall be acces­sible without unit entrance.]
Phase Failure/Under Voltage Protection
A phase failure/under voltage protection device shall be provided to protect three-phase motors from damage due to single phasing, phase reversal and low voltage conditions.
Water Flow Switch
A water flow switch shall be provided, factory installed, to verify water flow status at the unit. Compressor operation shall be dis­abled and an alarm signal provided if condenser water flow is lost. Unit operation will be restored when water flow has again been sensed. Water flow status shall be displayed at the unit's main controller.
Freezestat (Units with Waterside Economizer)
A non-averaging type freezestat shall be factory installed on the entering face of the economizer coil. Upon sensing a freeze condi­tion, the unit supply air fan will be shut down, the [economizer] [heating] [economizer and heating] valve will be driven to the full open position and an alarm signal will be provided. Unit operation will be restored following the manual reset of the freezestat.
Freezestat (Units without Waterside Economizer)
A non-averaging type freezestat shall be factory installed on the leaving face of the hot water heating coil. Upon sensing a freeze condition, the unit supply air fan will be shut down, the heating valve will be driven to the full open position and an alarm signal will be provided. Unit operation will be restored following the manual reset of the freezestat.
Battery Pack
The unit shall be provided with a factory mounted and wired rechargeable battery pack. The battery pack shall be available to provide control power to unit actuators in the event of a power failure.
UV Lights
Unit to have factory-mounted UV lights located on the leaving air side of the cooling coil. Unit to have view port to allow for visual indication of operation through UV resistant glass. Unit to have door interlocks on each removable panel accessing UV light. Interlock to kill power to UV light when panel is removed.
Lamp and fixture to consist of a housing, power source, lamp sockets, and lamp. All components are to be constructed to with­stand typical HVAC environmen ts and are UL/C-UL listed. Hous­ings are to be constructed of type 304 stainless steel and are to be equipped with both male and female power plugs with one type at each end to facilitate simple fixture-to-fixture plug-in for AC power.
Power source shall be an electric, rapid-type with overload pro­tections and is to be designed to maximize radiance and reliability at UL/C-UL listed temperatures of 55°F–135°F. Power source will include RF and EMI suppression.
Sockets shall be medium bi-pin, single click safety, twist lock type and are to constructed of a UVC-resistant polycarbonate.
Lamp shall be a high output, hot cathode, T8 diameter, medium bi-pin that produces UVGI of 254 nm. Each tube produces the specified output at 500 fpm and air temperatures of 55°F–135°F.

MicroTech III Unit Controller

Each unit shall be equipped with a complete MicroTech III micro­processor based control system. The unit control system shall include all required temperature and pressure sensors, compressor control boards, heating control board, main microprocessor con­trol board and opera-tor interface. The unit control system shall perform all unit control functions including scheduling, [constant air volume, zone temperature control (SCC)] [constant air vol­ume, discharge temperature control (DAC)] [variable air volume, cooling only discharge temperature control [with single-stage morning warm-up heat] (DAC)] [variable air volume, cool­ing/modulating heating discharge temperature control (DAC)] [duct static pressure control], [building static pressure control], unit diagnostics and safe-ties. All boards shall be individually replaceable for ease of service. All microprocessors, boards, and sensors shall be factory mounted, wired and tested.
The microprocessor shall be a stand-alone DDC controller not dependent on communications with any on-site or remote PC or master control panel. The microprocessor shall maintain existing set points and operate stand alone if the unit loses either direct connect or network communications. The micro-processor mem­ory shall be protected from voltage fluctuations as well as any extended power failures. All factory and user set schedules and control points shall be maintained in nonvolatile memory. No set­tings shall be lost, even during extended power shutdowns.
The main microprocessor shall support an RS-232 direct connec­tion to a product service tool or a modem. A [BACnet [BACnet vided for direct connection into the BAS network.
All digital inputs and outputs shall be protected against damage from transients or wrong voltages. Each digital input and digital output on the main microprocessor shall be equipped with an LED for ease of service. An alarm LED on the user interface shall pro­vide quick visual identification that an alarm condition exists. All field wiring shall be terminated at a separate, clearly marked ter­minal strip.
The microprocessor shall have a built-in time schedule. The schedule shall be programmable from the unit keypad interface. The schedule shall be maintained in nonvolatile memory to insure that it is not lost during a power failure. There shall be one start/stop per day and a separate holiday schedule. The controller shall accept up to sixteen holidays each with up to a 5-day dura­tion. Each unit shall also have the ability to accept a time schedule via BAS network communications.
If the unit is to be programmed with a night setback or setup func­tion, an optional space sensor shall be provided. Space sensors shall be available to support field selectable features. Sensor options shall include:
1. Zone sensor with tenant override switch.
MS/TP] [LonTalk] communications port shall be pro-
/IP]
46 McQuay Catalog 865-5
Engineering Guide Specifications
2. #1 plus a heating and cooling set point adjustment. (CAV-ZTC only)
The unit keypad/display character format shall be 20 characters x 4 lines. The character font shall be 5 x 8 dot matrix. The display shall be a supertwist nematic (STN) LCD display with black char­acters on yellow background for high visibility. For ease of ser­vice, the display format shall be English language readout. Coded formats with look-up tables shall not be acceptable.
The keypad interface shall be equipped with eight individual touch-sensitive membrane key switches that allow convenient navigation and access to all control functions. All control settings shall be password protected against unauthorized changes.
The user interaction with the display shall provide the following information:
1. Return air temperature
2. Supply air temperature
3. Outdoor air temperature (opt.)
4. Space air temperature (opt.)
5. Discharge air temperature
6. Entering condenser water temperature
7. Leaving condenser water temperature
8. Mixed air temperature
9. Outdoor enthalpy high/low (opt.)
10. Dirty filter indication 1 1 . Airflow verification
12. Supply fan status
13. Supply vane position/VFD speed indication
14. Outside air damper position(opt.)
15. Duct static pressure
16. Duct static pressure #2 (opt.)
17. Building static pressure (opt.)
18. Cooling status
19. Cooling control method
a. Nearest b. Average
20. Heating status
21. Dehumidification status
22. Control Temperature (changeover)
23. External exhaust fan status (opt.)
24. VAV output status
25. Fan operation status
26. Unit status
27. Time schedules
28. Up to four active alarms with time and date
29. Previous 8 alarms with time and date
30. Optimal start
31. Purge cycle
32. System operating hours a. Fan b. Cooling c. Individual compressor d. Heating e. Economizer f. Tenant override g. Dehumidification
The user interaction with the keypad shall provide the following set points as a minimum:
1. Control modes a. Off manual b. Auto c. Heat/cool d. Cool only e. Heat only f. Fan only
2. Occupancy mode a. Auto b. Occupied c. Unoccupied d. Tenant override
3. Control temperature (changeover) a. Return air temperature b. Space temperature c. Network signal d. Outdoor air temp. (VAV w/ mo d. heat )
4. Cooling with deadband
5. Heating with deadband
6. Cooling and heating supply
7. Cooling & heating supply reset options a. Return air temperature b. Outdoor air temperature c. Space temperature d. Airflow (VAV) e. No reset f. Network signal g. External (1-5 VDC)
8. Temperature alarm limits a. High supply air temperature b. Low supply air temperature c. High return air temperature
9. Lockout control a. Compressor lockout b. Heat lockout
10. Lead-lag on compressors a. Auto
b. Disabled
11. Compressor Inter-stage timers
12. Night setback and setup space temp.
13. Duct static pressure reset options a. No reset b. Network
14. Building static pressure (opt.)
15. Minimum outdoor airflow reset a. Percent of CFM capacity b. External reset (1-5 VDC)
c. Fixed outdoor damper position
16. Economizer changeover a. Enthalpy b. Dry bulb
17. Current time and date
18. Tenant override time
19. Occupied/unoccupied time schedules
20. One event schedule
McQuay Catalog 865-5 47
Engineering Guide Specifications
21. Holiday dates and duration
22. Service mode a. Timers normal (all time delays normal) b. Timers fast (all time delays 20 sec.) c. Mode normal (unit on)

Open Communications Protocol

The unit control system shall have the ability to communicate to an independent Building Automation System (BAS) through a direct [BACnet tions connection.
[BACnet col (ANSI/ASHRAE135-2001). A protocol implementation con­formance statement (PICS) shall be provided. Multiple units may be connected in a common communications network.]
[Communications shall conform to LonMark Guidelines and shall be certified. Controls shall conform to the [Discharge Air Controller (DAC)] [Space Comfort Controller (SCC)] profile.]
Through communications, the BAS System Integration (SI) con­tractor shall be capable of interacting with the individual self-con­tained unit controllers in the following ways:
/IP] [BACnet MS/TP] [LonTalk] communica-
Communications shall conform to the BACnet proto-
®
Interoperability
1. Access to [quantity and description from specification] “read only” variables and [quantity and description from specifica­tion] “read & and write” variables.
2. Set the un it's operati ng mode.
3. Monitor controller in puts, outputs, setpoints, parameters and alarms.
4. Chan ge contro ller setpoin ts and confi guration
parameters.
5. Clear alarms.
6. Reset the cooling discharge air temperature setpoint (DAC units).
7. Reset the heating discharge air temperature setpoint (DAC units with modulating heat).
8. Reset the duct static pressure setpoint (DAC units).
9. Set the heat/cool changeove r temperature (DAC units).
10.Set the representative zone temperature (DAC units).
It will be the responsibility of the SI Contractor to integrate the
self-contained unit data into the BAS to affect the integrated building control logic and centralized system workstation inter­face.
48 McQuay Catalog 865-5
McQuay Training and Development
Now that you have made an investment in modern, efficient McQuay equipment, its care should be a high priority. For training information on all McQuay HVAC product s, please visit us at www.mcquay.com and click on training, or call 540-248-9646 and ask for the Training Department.
Warranty
All McQuay equipment is sold pursuant to its standard terms and conditions of sale, including Limited Product Warranty. Consult your local McQuay Representative for warranty details. Refer to Form 933-430285Y. To find your local McQuay Representative, go to www.mcquay.com.
Aftermarket Services
To find your local parts office, visit www.mcquay.com or call 800-37PARTS (800-377-2787). To find your local service office, visit www.mcquay.com or call 800-432-1342.
This document contains the most current product information as of this printing. For the most up-to-date product information, please go to www.mcquay.com.
Products manufactured in an ISO certified facility.
© 2011 McQuay International • www.mcquay.com • 800-432-1342 11/11
Loading...