McQuay SWP023 User Manual

Self-Contained Air Conditioning Systems
Type SWP Vintage H with R-410A Refrigerant
Capacity: 20 through 130 tons
Catalog 860-9
Engineered for flexibility and performance™
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Self-Contained Systems Design s . . . . . . . . . . . . . . .3
McQuay Self-Contained Systems . . . . . . . . . . . . . . . 4
SWP 012–130 Features and Options . . . . . . . . . . . . 4
Cabinet, Casing and Frame . . . . . . . . . . . . . . . . . 6
Compressor/ Condensing Section . . . . . . . . . . . . 7
Cooling Coil Section . . . . . . . . . . . . . . . . . . . . . . .8
Supply Fan Section . . . . . . . . . . . . . . . . . . . . . . . .8
Acoustical Discharge Plenum . . . . . . . . . . . . . . . 10
Variable Air Volume Control . . . . . . . . . . . . . . . . 10
Economizer Options . . . . . . . . . . . . . . . . . . . . . .10
Condenser Head Pressure Control . . . . . . . . . . .11
Filter Section . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Blank Sections . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Heating Section . . . . . . . . . . . . . . . . . . . . . . . . . .12
System Flexibility with Unit Options . . . . . . . . . . . . 13
Selection/Application Flexibility . . . . . . . . . . . . . .13
Arrangement Flexibility . . . . . . . . . . . . . . . . . . . .13
Optimal Discharge Air Temperature . . . . . . . . . .13
Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
R-410A Refrigerant . . . . . . . . . . . . . . . . . . . . . . . 14
MicroTech III Unit Controls . . . . . . . . . . . . . . . . . . . . 15
Open Choices Benefits for Easy Integration . . . . 15
Alarm Management and Control . . . . . . . . . . . . . 21
Application Considerations . . . . . . . . . . . . . . . . . . .23
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Unit Location . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Acoustical Considerations . . . . . . . . . . . . . . . . . .24
Equipment Room . . . . . . . . . . . . . . . . . . . . . . . .24
Ductwork . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Condenser Water Piping . . . . . . . . . . . . . . . . . . . 25
Head Pressure Control . . . . . . . . . . . . . . . . . . . . 25
Variable Air Volume . . . . . . . . . . . . . . . . . . . . . . 25
Variable Frequency Drives . . . . . . . . . . . . . . . . .26
Duct Static Pressure Sensor Placement . . . . . . .26
Zone Sensor Placement . . . . . . . . . . . . . . . . . . .26
Filtration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
System Operating Limits . . . . . . . . . . . . . . . . . . .27
Airflow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Fan Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Condenser Water Flow . . . . . . . . . . . . . . . . . . . . 27
Coil Freeze Protection . . . . . . . . . . . . . . . . . . . . 28
Air Density Correction . . . . . . . . . . . . . . . . . . . . . 28
Unit Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
Terms of Sale . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . 29
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
DX Cooling Capacity Data . . . . . . . . . . . . . . . . . 36
Waterside Economizer Capacity . . . . . . . . . . . . 44
Heating Capacity Data . . . . . . . . . . . . . . . . . . . . 45
Component Pressure Drops . . . . . . . . . . . . . . . 46
Total Unit Water Pressure Drop . . . . . . . . . . . . . 49
Fan Curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Recommended Clearances . . . . . . . . . . . . . . . . 61
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Supply Power Wiring . . . . . . . . . . . . . . . . . . . . . 65
Unit Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
2 McQuay Catalog 860-9

Introduction

Introduction

Continued Leadership in Self-Contained Systems Designs

McQuay SWP self contained air conditioning systems trace their history to the late 1970s. The first self contained variable air volume systems with waterside economizer cycle was developed by us for the prestigious 499 Park Avenue office building in New York City. McQuay SWP, with decades of innovation, design flexibility, durable construction, low capitol and operating cost, make us the leader of self contained system market and the preferred HVAC solution for thousand of most prominent building projects.
SWP water cooled self-contained air conditioner is an ideal option for a job where energy efficiency, reliability, indoor air quality and acoustic are top priorities. Along with providing high quality and state-of-the-art technology, SWP self­contained systems offer the following valuable features and benefits to satisfy a wide range of diverse applications.
• Comfort and Redundancy
– Occupants enjoy individual control over comfort condi-
tions and off-hour system operation.
– Tenants benefit from their indivi dual efforts to control
energy costs.
– Routine service is located where it minimizes tenant
inconvenience.
– Individual or dual systems per floor provide system
redundancy and standby.
• Economical First Cost
– VAV system flexibility uses building diversity to reduce
system tonnage and first cost.
– Factory-packaged concept reduces field labor, installation
time and expense. – No expensive chilled water piping or chiller room. – Individually tested, factory-designed systems reduce
startup and installation expense. – Reduced penthouse and equipment room requirements. – Centralized condenser water and condensate piping and
streamlined system layout. – Modular units design make renovation projects easier
since individual section designed for narrow hallways,
elevators and doorways. – Optional acoustical discharge plenum is an available
option in any height to match your job needs and mini-
mizes supply duct transition losses.
• Energy Efficient System
– Reduces fan kW and operating costs at part load condi-
tions. – Savings maximized through use of variable speed fan
control. – Individual zone control.
• Improving Indoor Air Quality
For better filtration filter selection flexibility includes: – MERV 7, 8, 11, 13, or 14 options with & without pre-fil-
ter. Microbial-resistant filter option is also an available option.
– Featured Double-wall panel construction that eliminates
fibers in the supply air stream and is easy to clean.
– Provided with double-sloped, galvanized or stainless steel
drain pans eliminate stagnant water and minimizes bacte­rial growth.
• Quiet System Operation
– Provided by structural quality and specialized design. – Recognized for quiet operation by renowned U.S. acous-
tical consultants.
– Provided with a SWSI airfoil plenum fan for excellent
acoustics and better efficiency
– Unit featured discharge plenum with sound baffles is an
available option for sound sensitive job
• Free Cooling
– Water or air economizer capability for optimized energy
savings.
– Economizer reduces compressor operating hours and
energy costs.
– Year-round “free cooling” capability.
• Efficient Part Load Operation
– System energy at part load operation is more efficient
than to central chilled water systems.
– Multiple systems and compressors versus a single, large
central plant.
– Efficient and reliable system for partial occupancy and
after hours operation.
– Operates only the system(s) on the floor(s) requiring after
hours use.
• Economical Integrated or Stand Alone DDC controls
– Monitoring and diagnostics reduce the potential for
expensive field repairs.
– Industry leading Protocol Selectability™ feature provides
effective BAS selection flexibility.
• Maintenance Costs Reduction
– No complicated central chiller plant to maintain. – Service and maintenance are performed out of the occu-
pied space.
– Control and product reliability functions designed by the
equipment manufacturer for single source responsibility and improved reliability.
• System Versatility
– Applicable to schools, offices, shopping centers, manu-
facturing facilities, etc. – Prime candidate for floor by floor building renovation. – Retrofit alternative where existing chiller cannot be
ed for replacement.
access
McQuay Catalog 860-9 3

McQuay Self-Contained Systems

McQuay Self-Contained Systems

SWP 012–130 Features and Options

Airfoil Plenum Fans
SWSI fans more energy efficient and quieter than forward
curved fans
Premium high efficiency open, drip-proof standard
motors and TEFC motors, an available option
Seismic control restrained spring isolators are available
Aerodynamically designed fan also available with 12
blades for even lower sound levels
Coils
High efficiency enhanced corrugated fin design
High coil performance and reduced static
pressure losses
Interlaced and/or row split circuiting to keep
full face of the coil active and to eliminate air temperature stratification and optimum part load performance
Durable Construction
Pre-painted or G90 galvanized steel exterior
cabinet panels
Standard foam injected panels with R-13
insulation provide superior rigid double wall construction and minimizes air leakage
For better acoustics, an additional 2", 1. 5# density
R-8 fiberglass insulation is an available option for fan and plenum sections
Double-sloped drain pans help eliminates
standing stagnant water
Blank Sections
Available to mount air blenders, carbon or
charcoal filters, sound attenuators or other specialty equipment
Allow customization for maximum system
performance and efficiency
Can reduce design and installation costs
Scroll Compressor(s)
Durable and reliable multiple compressors
Lower operating cost with High EERs
Customize selections to match specific
application
Mounted on resilient rubber isolation for
smooth and quiet operation
Access Panels and Doors
All panels and access doors shall be sealed
with permanently applied bulb-type gasket
Access doors are flush mounted to cabinetry,
with hinges, latch and handle assembly
4 McQuay Catalog 860-9
Refrigerant Circuits
Suction and discharge service valves, an available
option, to isolate each compressor
Hot gas bypass, an available option, on units with
two refrigerant circuits
McQuay Self-Contained Systems
Shell and Tube Condensers
Carbon steel Shell and Tube Condenser , non-
ferrous water channels and enhanced tubing for high performance
Integral sub-cooling circuit is provided as
standard to maximize efficiency
Mechanically cleanable condenser and water
piping is rated for standard 300 psig waterside working pressure & 450 psig is an available option
Two-way valve for head pressure control is
available for low condenser water temperatures
Multiple Filter Options
2" 30% (MERV7) and 75% (MERV13) filter s
4" 30% (MERV8), 65% (MERV1 1), 75% (MERV13)
and 85% (MER V14) longer lasting filters available
4" primary filters also available with 2" or 4" with
pre-filter
Economizer Options
W aterside economizer effectively uses low cooling tower
water temperatures to offload compressor operation
An airside economizer control package is available for
controlling field installed mixing dampers capable of 100% outside airflow.
MicroTech® III Control System
Factory-installed and tested to help minimize costly field
commissioning.
Open Choices™ feature for easy integration into the BAS of
your choice using open, standard protocols such as BACnet® or LONTALK®.
Easily accessed for system diagnostics and adjustments via a
keypad/display on unit.
Optionally add a remote keypad and display that is identical to
the unit mounted user interface.
Factory-Mounted Variable Frequency Drives
Controlling fan motor speed can lower fan operating
costs and sound levels
All VFD selections are plenum rated
Manually activated bypass contactor is available to
allow system operation in the event of drive service
McQuay Catalog 860-9 5
McQuay Self-Contained Systems
McQuay Self -Contained SWP systems are built to perform, with features and options that provide for lower installed and operating costs, good indoor air quality, quiet operation and longevity.

Cabinet, Casing and Frame

Unit base constructed of 15-gauge and 10-gauge galvanized
steel for vibration control and rigging strength.
Heavy-duty lifting brackets strategically placed for balanced
cable or chain hook lifting.
Figure 1: Low Leak Gasketed Frame and Foam Panels
Unit cabinet constructed with foam insulation standard and
heavy gauge [pre-painted] [galvanized steel] exterior panels for long equipment life.
All sections have galvanized steel internal lining.
2-inch thick panels and access doors are thermal broke
double wall assembly, with [R-13 foam] [R-8 fiberglass].
System components strategically located for ease of
inspection, serviceability and maintenance.
Refrigeration components positioned out of the airstream so
adjustments and readings can be made without disrupting system operation.
Access doors flush mounted to cabinetry, with hinges, latch
and handle assembly.
Doors on positive pressure sections are provided with
secondary latches to relieve pressure and prevent injury upon access.
Figure 2: Hinged Access Doors with double latches
Low leak gasketed frame channels minimize air leakage and
eliminates metal-to-metal contact between paneling and frame work. Air leakage is only 0.5 cfm/square foot at 5" cabinet pressure.
6 McQuay Catalog 860-9
McQuay Self-Contained Systems
Control Panel
Coil/Access Section
Supply Fan Section
Compressor/ Condenser Section
Base Plates
Modular Design
Optional modular construction unit shipped with a nitrogen
holding charge.
Four distinct sections; coil/access section, supply fan
section, compressor/condenser section and the control panel.
Figure 3: SWP Modular Sections
Insulated and segregated condensing section from the air
handling section to avoid transmission of noise to the circulated air stream.
Each refrigerant circuit is furnished with filter-drier, liquid
moisture indicator/sight glass , th erm a l ex pansion valve, liquid line shutoff valve with charging port, high pressure relief device and high and low pressure cutouts.
If any compressor is made inoperable, the remaining
compressors are still allowed to operate.
Thermal expansion valve capable of modulation from 100-
25% of its rated capacity.
Hot gas bypass also available on units with two refrigerant
circuits.
Condensers
All units feature carbon steel mechanically cleanable shell
and tube condenser.
Includes non-ferrous water channels and enhanced tubing
for high performance.
Serves an independent refrigerant circuit and includes a
spring loaded high pressure relief valve
Integral sub-cooling circuit provided as standard to
maximize efficiency.

Compressor/ Condensing Section

Compressors
All units feature multiple reliable scroll compressors for
Suction and discharge service valves and gauge ports,
Individual branch circuit fusing protects each compressor.
T o prevent compressor short cycling, MicroTech® III
Compressors mounted on resilient rubber isolation for
Figure 4: Compresors
efficient system part load control, quiet operation and system redundancy.
available option, on each compressor.
control system incorporates timing functions.
smooth and quiet operation.
Figure 5: Condensers
All units are leak tested, evacuated and shipped with a [full
operating charge of R-410A] [for modular design nitrogen holding charge] and POE oil.
Condenser assembly and all factory water piping rated for a
waterside working pressure of 300 psig as standard [450 psig] tested before shipment.
Provided with a single supply and return water connections
Unit available in both right-hand and left-hand piping
locations.
Optional two-way valve provides accurate head pressure
control for condenser entering water temperatures as low as 40ºF.
McQuay Catalog 860-9 7
McQuay Self-Contained Systems
Refrig. Flow Ckt 1 Refrig. Flow Ckt 2
Ckt 2
Ckt 1
Ckt 1
Ckt 1
Ckt 1
Ckt 1
Ckt 1
Ckt 1
Ckt 1
Ckt 2
Ckt 2
Ckt 2
Ckt 2
Ckt 2
Ckt 2
Ckt 2
Airflow
Cooling Coils

Cooling Coil Section

Large face area coils with high efficiency , enhanced copper
tubing and ripple corrugated aluminum fins.
Features interlaced and/or row split circuiting to keep the
full face of the coil active and eliminate air temperature stratification and optimum part load performance.
Figure 6: Evaporator Coil Circuiting
5 or 6 row evaporator coil with 12 fins/ inch spacing and
multiple face areas allows a custom match to specific design loads.
Provides low air pressure drop, high full and part load
operating efficiencies.
Mounted in a [galvanized] [stainless steel ] cross broke and
double sloped drain pan with a full 2 inches of insulation.
Compressor staging sequenced to take maximum advantage
of available coil surface.
Each evaporator coil circuit furnished with a wide range
thermostatic expansion valve with an adjustable superheat setting and external equalizer.
An intermediate drain pan in the coil bank helps to provide
condensate removal without carryover.
Figure 7: Cooling Coil Section Shown

Supply Fan Section

Single width, single inlet (SWSI) airfoil supply air fan
selections provide efficient, quiet operation at wide ranging static pressure and air flow requirements.
Each fan assembly is dynamically trim balanced at the
factory for quiet operation before shipment.
All fan drives are factory sized according to job specific
airflow, static pressure, and power requirements.
For seismic sensitive regions, spring fan isolators are
available with seismic restraints.
150% service factor drives extend service life of the fan
belts. Drive components and fan bearings are easily accessed for periodic maintenance.
Mounted on 2 inch deflection spring isolators for excellent
isolation effectiveness.
Solid steel shafts rotating in 200,000 hour pillow block ball
bearings with grease fittings.
Motor availability includes premium efficiency, open, drip-
proof, and totally enclosed selections; EPACT compliant premium efficiency selections.
8 McQuay Catalog 860-9
Figure 8: Airfoil Fan
McQuay Self-Contained Systems
McQuay Plenum Fan
Least turbulance
and best acoustics
* Ceiling heights restrict “h” and increase the problem with housed fans
Competitive Housed Fan
Excessive turbulance
and mediocre acoustics
Competitive Housed Fan
Worst turbulance
and worst acoustics
h*
Acoustical Advantages
McQuay SWP Self-contained units are provided with a high efficient, SWSI airfoil plenum fan and have several acousti cal advantages:
Airfoil fans are more efficient than forward curved fans
contributing to less noise.
For specific unit sizes, several fan diameters are available,
fan selection provides optimal efficiency.
Figure 9: Supply Fan Comparison
Competitive supply duct work normally involves
discharging air vertically into a ceiling, then routing it horizontally, Figure 10. McQuay’s plenum fan discharge has far less velocity pressure than competitive housed fan discharge, resulting in:
• 90º duct elbows that generate far less turbulance.
• Air flow that can be routed in any direction.
McQuay Catalog 860-9 9
McQuay Self-Contained Systems
McQuay Optional Plenum
“h” can be varied to match ceiling height
h
Competition
Expansion Loss
90° Elbow Loss
Standard Exterior Galvanized Surface
Standard Galvanized Liner
Standard Injected Foam Panel
Optional Fiberglass Insulation
Perforated Liner
Interior Optional

Acoustical Discharge Plenum

McQuay offers an optional acoustical discharge plenum,
Figure 10, that minimizes supply duct transition losses and
noise:
Plenum fans pressurize the entire cabinet and have no
significant plenum air pressure drop (housed fans have expansion, contraction and 90º elbow losses).
Discharge plenums offered in any height to match ceiling
height.
Custom size duct connections are available on any size
plenum.
Discharge Plenum with Foam Insulation and Sound Baffles
Optional discharge plenum with foaminjected panels can be provided with the additional sound attenuating baffle option consisting of:
Additional 2" of fiberglass insulation.
Perforated liners, Figure 11.
Figure 10: Acoustical Discharge Plenum

Variable Air Volume Control

Energy saving advanced technology variable frequency
drive (VFD), fan speed control is available with the convenience and cost savings of factory mounting and testing.
Figure 12: Variable Frequency Drive Controller
Figure 11: Foam Insulation and Sound Baffles
All VFD selections are plenum rated and are conveniently
mounted within the control panel.
MicroTech III controls provide advanced duct static pressure
control and controlled by either single or two-duct static pressure sensors.
A manually activated bypass contactor is available to allow
system operation even in the event of drive service.
All VAV systems include an adjustable, duct high-limit
switch to protect duct work from excessive pressure.

Economizer Options

Waterside Economizer
An energy saving, waterside economizer package, an
available option on all return air unit.
Includes factory mounted 4-row [chemically cleanable coil]
[mechanically cleanable coil], control valves and piping.
Rated for 300 psig as standard [450 psig] waterside working
pressure and the entire coil and piping assembly is factory leak tested.
Factory integrated MicroTech III controller to control
economizer operation and maximize free cooling potential.
Unit enables economizer operation whenever cooling tower
water temperature is less than the unit entering air temperature by a field adjustable value, generally 5-7°F.
10 McQuay Catalog 860-9
McQuay Self-Contained Systems
Mechanically Cleanable
Economizer Coil
To save energy with a variable pumping system control
valves operation can be selected to maintain full flow through the unit at all times or to isolate the unit from the condenser water loop when there is no call for cooling.
To extend free cooling savings, economizer operation can be
enabled during mechanical cooling.
Unit enables mechanical cooling only when the economizer
valve is driven 90% open and cooling load is not satisfied.
Economizer control will maintain full free cooling capability
until disabled by the economizer changeover set point.
T o help protect against coil freeze-up an optional factory
mounted freeze stat is available.
Figure 13: Mechanically Cleanable Waterside Economizer Coil
To extend free cooling savings, economizer operation can be
enabled during mechanical cooling.
Unit enables mechanical cooling only when the economizer
damper is driven 90% open and cooling load is not satisfied.
Economizer control will maintain full free cooling capability
until disabled by the economizer changeover set point.

Condenser Head Pressure Control

Unit requires condenser head pressure control for
applications where a waterside economizer package is not being used and entering condenser water temperatures can be less than 55°F.
Optional two-way valve provides accurate head pressure
control for condenser entering water temperatures as low as 40degree F

Filter Section

Selection flexibility includes face loaded rack with non-
gasketed frames and filter clips.
Unit features 2-inch filter option available in 30% (MERV 7)
& 75% (MERV 13) nominal efficiency
Longer lasting 4-inch filters higher filtration option is
available in 30% (MERV 8) & 65% (MERV 11), 75% (MER V 13) & 85% (MERV 14) nominal efficiency with and without 2-inch or 4-inch 30% pre-filter.
Airside Economizer
A mixing box containing outdoor air, return air and exhaust
air dampers are available using the McQuay Vision™ air handling unit platform.
Factory integrated MicroTech III controller controls
economizer operation and maximize free cooling potential.
Airside economizer control package available to control
field installed mixing dampers capable of 100% outside airflow.
Unit enables economizer operation whenever outside air
enthalpy , comparative enthalpy or dry bulb temperature changeover provides control flexibility to bring in most amount of outside air for free cooling.
Economizer damper control actuator modulates in response
to the cooling load.
MicroTech III controller positions outside air damper to
maintain minimum ventilation requirements when economizer is not in operation.
Figure 14: 4 Inch Filters

Blank Sections

Available to mount air blenders, pre-heat coils, sound
attenuators or other specialty equipment using the McQuay Vision™ air handling unit platform and shipped loose.
Allow customization for maximum system performance and
efficiency and reduce design and installation costs.
McQuay Catalog 860-9 11
McQuay Self-Contained Systems

Electrical

Units are completely wired and tested at the factory prior
shipment.
Wiring complies with NEC requirements and all applicable
UL standards.
For ease of use, wiring and electrical components are
number coded and labeled according to the electrical diagram whenever applicable.
Supply air fan motors, compressor motors and electric heat
all branch circuits have individual short circuit protection.
Control circuit power is supplied through a factory installed,
low voltage transformer.
The supply fan motor circuit includes a three phase
contactor and ambient compensated overload protection with manual reset.
Each refrigerant circuit includes both a high and low
pressure cutout switch.
A terminal block is provided for the single, main power
connection and a terminal board is provided for low voltage control wiring.
A factory mounted, non-fused main circuit interrupter is
available for disconnecting the main electrical power to the unit.
Dual power blocks or disconnect switches are available to
accommodate requirements for standby, emergency power supplies.

Heating Section

Hot Water Heat
Multiple coil selections offered to size heating output to
application needs.
Hot water coils are 5/8-in. O.D. copper tube/ aluminum fin
design with patented HI-F5 fins.
Rated in accordance with ARI Standard 430.
Pre-heating control fully integrated into the unit’s
MicroTech III control system is available using the McQuay Vision™ air handling unit platform.
Available with factory-mounted freezestat.
Steam Heat
Steam heating coils are 5/8-in. O.D. copper tube/aluminum
fin jet distributing type with patented HI-F5 fin design.
Rated in accordance with ARI Standard 430.
Multiple different steam coil selections offered to size
heating output to application needs.
Pre-heating control fully integrated into the unit’s
MicroTech III control system is available using the McQuay Vision™ air handling unit platform.
Available with factory-mounted freezestat.
Electric Heat
Factory assembled, installed and tested.
Two stage capability for application flexibility.
Durable low watt density nickel chromium elements for
longer life.
Entire heat bank protected by a linear high limit control with
each heater element protected by an automatic reset high limit control.
Fuses provided in each branch circuit.
12 McQuay Catalog 860-9

System Flexibility with Unit Options

Along with providing high quality and state-of-the-art innovation, SWP self-contained systems offer customized flexibility to satisfy a wide range of diverse applications.
System Flexibility with Unit Options
discharge orientations. Piping and fan arrangement flexibility can simplify mechanical equipment room arrangement, improve installation costs, and total system performance.

Selection/Application Flexibility

Nominal cooling capacities range from 12 to 130 tons. In addition, all units offer multiple compressor selections to meet exacting system requirements. The flexibility to optimize the self-contained system to fit the application is a McQuay SWP advantage. Available system applications include the following:
• VAV dischar ge air temperature control with static pres­sure control.
• Discharge air temperature control with constant air vol­ume.
• Constant volume, zone temperature control.
• 100% outside air control.
• Dehumidification control, with or without reheat control.
In addition to compressor/coil flexibility, SWP systems offer single width, single inlet, air foil fans with factory-mounted variable frequency drives for maximizing VAV system fan performance. High efficiency fan capability coupled with extensive compressor flexibility provide the right system selection for the application.

Arrangement Flexibility

All SWP systems offer the flexibility of right-hand and left­hand piping and control panel arrangements and multiple fan

Optimal Discharge Air Temperature

More and more system engineers are designing optimal discharge air temperature systems to improve system performance and system first cost; the McQuay SWP provides the flexibility to do it successfully. Optimal discharge air temperature systems are designed to provide unit leaving air temperature selections of 52°F to 53°F versus more conventional systems that supply air at temperatures closer to 58°F . This five to six degree reduction in air temperature to the room diffusers can subsequently reduce the required supply air volume to the room by 20% to 25%.
The benefits of optimal discharge air temperature systems become quite apparent with a look at the advantages offered with reduced supply air cfm airflow:
• Reduced first cost and installation cost by allowing smaller duct sizes and a smaller air distribution system.
• Reduced bhp requirements. Depending on changes in duct size and the resulting total static pressure, a 20% reduction in supply air cfm can reduce fan bhp require­ments by 25% or more.
• Reduced fan sound power generation and a quieter room environment.
• Reduced equipment room size may be possible due to using a physically smaller unit size.
• Filtration Flexibility.
McQuay Catalog 860-9 13
System Flexibility with Unit Options

Controllers

MicroTech III DDC control systems provide constant volume, variable air volume, 100% outside air, and/or dehumidification control flexibility . See “MicroTech III Unit Controller” section for more information.
Summary of Available Options
• Multiple different compressor/coil capacity selections
• Mult ip le control options: VAV, CV, 100% O A, dehumidi­fication
• Nonfused main power disconnect switch
• Dual nonfused main disconnect switches
• Nonaveraging freezestat for hot water or waterside econ­omizer coil protection
• Unit phase failure/under voltage protection
• Premium efficiency fan motors
• TEFC fan motors
• Condenser water flow switch
• 4-row waterside economizer system
• Air cycle economizer system
• Modulating hot water heat control
• Staged electric heat
• Multi direction, acoustic discharge plenum
• Factory-mounted and factory-controlled variable fre­quency drives
• High efficiency filtration options
• Right-hand and left-hand piping se lections
• Multiple fan discharge arrangements
• Head pressure control valve
• Special coil coatings
• Double wall cabinet construction
• Seismic fan isolation
• Independent refrigerant circuit units offer the following options:
• Five-row or six-row DX coils with enhanced heat trans­fer surfaces
• R-410A refrigerant
• Service and shut off valves on liquid and discharge
Figure 15: MicroTech III DDC Co ntroller

R-410A Refrigerant

McQuay SWP units with independent refrigerant circuits are available with non-ozone depleting R-410A refrigerant.
Features
• R-410A refrigerant is environmentally friendly with zero ozone depleting allowance (ODP). Customers have no phase out and replacement concerns.
• Units are factory engineered for proper cooling perfor­mance using R-410A.
• R-410A efficiency is excellent. McQuay R-410A SWP units are available with EERs that exceed ASHRAE 90.1-
2010.
• Units are factory charged with R-410A and synthetic oil (such as POE), and they include components and controls specifically tailored to R-410A.
• R-410A refrigerant is a blend, but the glide is negligible. This is not true for R-407C. If R-407C leaks, the remain­ing charge may not have a proper mix of components. R­410A does not have this problem so leaks are easier to repair.
• Units are factory tested prior to shipment.
14 McQuay Catalog 860-9

MicroTech III Unit Controls

McQuay SWP systems continue to provide industry leading performance, equipped with a complete MicroTech III control system. In addition to providing stable, efficient temperature, and static pressure control, the controller is capable of providing comprehensive diagnostics, alarm monitoring, and alarm specific component shutdown if critical equipment conditions occur. The unit controllers are factory mounted and configured for stand-alone operation or integration with a building automation system (BAS) through an optional communication module with our Open Choices feature.

Open Choices Benefits for Easy Integration

Easy, low cost integration into most building automation systems without costly gateway panels.
Flexibility to select either BACnet® or L
communication. Units are LonMark® 3.4 certified with the appropriate communications module for L networks.
Comprehensive unit control and status information is
available at the BAS regardless of communication protocol.
Long-term choices for equipment adds or replacements, and
for service support.
Flexible alarm notification and prioritization with Intrinsic
Alarm Management (BACnet).
Simplified BAS integration with the ability to set network
parameters at the unit controller, reducing installation time and costs.
Easy monitoring and troubleshooting of communication
status from the unit controller to the BAS.
ONWORKS®
ONWORKS
MicroTech III Unit Controls
Components
Each SWP self-contained system is equipped with a complete MicroTech III unit control system that is pre-engineered, preprogrammed, and factory tested prior to shipment. Each of the MicroTech III unit control systems is composed of several components that are individually replaceable for ease of service. These components include:
• Unit controller with user interface display and navigation wheel
• Optional expansion modules
• Communication module (optional)
• Pressure transducers
• Unit-mounted temperature sensors
• Zone temperature sensor packages
• Humidity sensor
Main Control Board (MCB)
The main control board (MCB) contains a microprocessor that is preprogrammed with the software necessary to control the unit. This provides that schedules, set points and parameters are not lost, even during a long-term power outage. The microprocessor board processes system input data and then determines and controls output responses. An RS-232 communication port is provided as standard to allow for direct or modem access with a PC-based service tool.
Expansion Modules
These boards are used to expand the input and output capability of the unit controller. Each board communicates via serial data communications. These microprocessor based boards provide independent operation and alarm response even if communication is lost with the unit controller.
Communication Module
An optional communication module provides the means to factory or field configure MicroTech III unit controls for interoperability with an independent BAS. Communication modules are available to support industry recognized communication protocols including BACnet MS/TP, BACnet/ IP and L
Figure 16: MicroTech III Keypad Display
McQuay Catalog 860-9 15
ONWORKS.
MicroTech III Unit Controls
Keypad/Display
All MicroTech III unit controllers include a push/pull navigation wheel and display. The display is a supertwist nematic type with highly visible black characters on a yellow background. The 5-line by 22-character format allows for easy to understand plain English display messages. All operating conditions, system alarms, control parameters and schedules can be monitored from the keypad/display. If the correct password has been entered, any adjustable parameter or schedule can be modified from the keypad.
Temperature and Humidity Sensors
With the exception of the zone, outside air and return air sensors, all temperature sensors are factory installed and tested. Zone sensor packages are available to suit any application. A humidity sensor is available for field installation.
Static Pressure Transducers
All pressure transducers are factory installed and tested. Connection and routing of field-supplied sampling tubes is done at time of unit installation.
Zone Temperature Sensors
Two optional zone temperature sensors are available:
• Zone sensor with tenant override switch
• Zone sensor with tenant override switch and remote set point adjustment
Timed tenant override is a standard MicroTech III control feature.
Zone sensors are required for the controller’s purge cycle, space reset of supply air set point, and night setback or setup features. All zone sensors are field installed with field wiring terminated at a separate, clearly marked terminal strip.
Stand-alone Controller Features
MicroTech III applied rooftop unit controls includ e all of th e essential features required to make them capable of completely independent, stand-alone operation.
Internal Time Clock
An internal, battery-backed time clock is included in the MicroTech III unit controller. Current date and time can be quickly and easily set at the user interface keypad.
Internal Schedule
Seven daily schedules and one holiday schedule can be entered at the keypad of all unit controllers. For each of these eight schedules, one start and one stop time can be entered. Up to 10 holiday periods, of any duration, can be designated. The unit will automatically run according to the holiday schedule on the holiday dates. To handle special occasions, an additional ‘one event’ schedule can also be used.
In lieu of its internal schedule, the unit can be operated according to a network schedule from a BAS.
External Time Clock or Tenant Override Input
An input is supplied that can be used to accept a field wired start/stop signal from a remote source. An external time clock, a tenant override switch, or both may be connected. Whenever the external circuit is closed, the controller overrides the internal schedule (if activated) and places the unit into the occupied mode.
If the internal schedule or a BAS network schedule is used, field wiring is not required.
Timed Tenant Override
Off-hour operation flexibility is a must in today’s office environments and even stand-alone MicroTech III controls handle it with ease. When unit operation is desired during unoccupied hours, initiate timed tenant override by pressing the tenant override button on either of the optional zone sensor packages. The unit then starts and runs in the occupied mode for a keypad-adjustable length of time (up to five hours ). If th e button is pressed again while the unit is operating, the timer resets to the full time allowance without interrupting unit operation. Tenant override operation also can be initiated by a BAS.
Three Remote Set Point Adjustment Options
1 Remote user interface option (RUI). 2 Building automation system (BAS). See “Open Choices
Benefits for Easy Integration” on page 15.
3
All constant air volume-zone temperature control (CAV­ZTC) unit controllers include an input that can be used to remotely adjust the zone cooling and heating set points. To use this feature, wire the optional zone sensor package with set point adjustment to the controller. The remote set point adjustment feature can be enabled or disabled from the keypad at any time. When enabled, remote set point adjustment is available even if the return temperature is selected to be the Control Temperature.
16 McQuay Catalog 860-9
MicroTech III Unit Controls
Auto/Manual Operation Selection
Automatic or manual operation can be controlled either remotely or at the keypad.
All controllers include three inputs that can be used to enable or disable cooling, heating, and fan operation from remote switches. With the “heat enable” and “cool enable” terminals, the operator can enable cooling, heating, or both as desired. Using the system “off” terminals, the operator can disable the fans, and thus the entire unit.
From the keypad, there are a variety of occupancy and auto! manual control mode selections available to the operator:
• Occupancy modes – Auto – Occupied – Unoccupied – Bypass (tenant override)
• Control modes – Off manual – Auto – Heat/cool – Cool only – Heat only – Fan only
Compressor Lead-lag Selection
All unit controllers are capable of automatic compressor, lead­lag control.
Waterside Economizer Changeover
On units equipped with a waterside economizer package, the MicroTech III unit controller includes an internal changeover strategy that compares entering cooling tower water temperature to the unit’s mixed air temperature. If the entering water temperature is less than the mixed air temperature by a field-adjustable differential (typically 5°F to 7ºF), the economizer control valve modulates in response to the cooling load.
Airside Economizer Changeover Selection
On units equipped with an economizer, there are three methods of determining whether the outdoor air is suitable for free cooling: two methods sense enthalpy (dry bulb temperature and humidity) and one senses outdoor air dry bulb temperature.
The two enthalpy changeover methods use external, factory installed controls. One compares the outdoor ambient enthalpy to a set point; the other is a solid state device that compares the outdoor ambient enthalpy to the return air enthalpy. This
comparative enthalpy control can improve total economizer performance.
All unit controls include an internal dry bulb changeover strategy that can be selected at the keypad. When this method is selected, the controller compares the outdoor air dry-bulb temperature to a keypad programmable set point. The external enthalpy control input is then ignored.
Cooling and Heating Lockout Control
All unit controls include separate keypad programmable set points for locking out mechanical cooling and heating. Mechanical cooling is locked out when the outdoor temperature is below the cooling lockout set point; heating is locked out when the outdoor temperature is above the heating lockout set point. This feature can save energy cost by eliminating unnecessary heating and cooling during warm-up or cool-down periods or when the outdoor ai r tem perature is mild.
Night Setback and Setup Control
When one of the zone temperature sensors is connected to the unit controller, night setback heating and night setup cooling control are available. Separate, keypad programmable night heating and cooling set points are used to start the unit when necessary. After the unit starts, night setback and setup control is similar to normal occupied control except that the minimum outside air damper position is set to zero. If the outside air is suitable for free cooling, it is used during night setup operation.
Except for 100% outside air applications, night setback control is available even if the unit is not equipped with any heating equipment. When the space temperature falls to the night setback set point, the fans simply start and run until the temperature rises above the differential. This feature might be useful for applications that use, for example, duct-mounted reheat coils.
Morning Warm-up Control
If the Control Temperature (space or return) is below set point when the unit enters the occupied mode, the morning warm-up control function will keep the outs heat is supplied to satisfy set point. The outside air damper will remain closed until either the space temperature rises to the
heating set point or the keypad adjustable morning warm-up timer expires (default is 90 minutes). The morning warm-up timer supplies the minimum required amount of outdoor air after a certain time regardless of the space temperature.
Morning warm-up control is automatically included on all except 100% outside air units. It is available even if the unit is
ide air dampers closed while
McQuay Catalog 860-9 17
MicroTech III Unit Controls
Condenser Head Pressure Control (units without waterside economizer only)
Mechanical cooling is allowed whenever the entering cooling tower water temperature is 55ºF or warmer, without the use of head pressure control. When the entering water temperature is below 55ºF , a factory-installed and factory-controlled two-way modulating head pressure control valve can be utilized. The regulating valve is controlled by the MicroTech III controller to maintain refrigerant head pressure.
Outdoor Air Purge Control (units with airside economizer only)
Purge control is designed to take advantage of cool early morning outside air conditions. It starts the fans and modulates the economizer dampers to maintain occupied cooling requirements during unoccupied periods, if conditions are appropriate. This provides the opportunity to flush the space with fresh outdoor air prior to occupancy. Purge operation is possible only during a keypad-adjustable time window prior to occupancy (0 to 240 minutes). When the purge-cycle is active, mechanical cooling is disabled. To use the purge feature, connect one of the zone temperature sensors to the unit controller. Below is a description of purge control operation.
During the purge time window, the unit starts and runs whenever these three requirements are met:
• The space temperature must be warm enough to enable occupied cooling.
• The outside air enthalpy must be low enough to enable the economizer.
• The outside air temperature must be at least 3°F less than the space temperature.
When any one of these conditions is no longer true, the unit shuts down. As conditions allow, purge cycles the unit in this manner until it enters the occupied mode.
Proportional Integral (PI) Control
The Proportional Integral (PI) control algorithm controls modulating actuators to maintain a measured variable (temperature or pressure) at or near its set point. For example, it controls economizer dampers to maintain the discharge cooling set point and it controls the supply fan variable frequency drives to maintain the duct static pressure set point. The integral control feature effectively eliminates “proportional droop” (load dependent offset) resulting in the tightest possible control.
For each PI loop, four keypad adjustable parameters allow the control loop to be properly tuned for any application:
•Period
• Dead band
• Proportional band
• Integral time
Appropriate default values for these parameters are loaded into each controller. These default values will provide proper control for most applications; therefore, field tuning is usually not required and thus start-up time is reduced.
Change Algorithm
The PI function is also used to adjust set points instead of controlling variable speed drives or actuators directly. For example, in zone control applications, the PI loop automatically “changes” the discharge temperature set point (cooling or heating) as the Control Temperature deviates from the zone set point. Another PI loop then controls the economizer actuator or heating valve actuator using the current discharge temperature set point. Unlike a typical “mastersubmaster” reset strategy, this “cascade control” continuously adjusts the discharge set point, even if the Control Temperature’s deviation from set point remains constant. This means that the unit’s cooling or heating output is set according to the actual load, not just the current zone temperature. The tightest possible zone temperature control results because “proportional droop” (load dependent offset) is eliminated.
Calibrate
When initiated at the keypad by an operator, the Calibrate function automatically calibrates all actuator position feedback inputs and all pressure transducer inputs. It does this by shutting the unit down and then driving all actuators to the full closed and full open positions. The controller records the input voltage values that correspond to these positions. The pressure transducer input voltages, which are assumed for 0.00-in. W.C., are also recorded. When Calibrate is finished, enter an operator command at the keypad to start the unit.
Field Output Signals
All MicroTech III controls include two solid-state relay outputs that are available for field connection to any
suitable device: the remote alarm output and the occupied output. These two outputs are used to signal field equipment of unit status.
Remote Alarm Output: The remote alarm output can be used to operate a 24 volt relay to provide a remote alarm signal to a light, audible alarm, alarm condition exists at the unit. Fan Operation Output: The fan operation output is used to operate a 24 volt relay to control field equipment that depends on fan operation; for instance, to open field installed isolation dampers or VAV boxes. To allow actua­tors enough time to stroke, the fan operation output is energized three minutes before the fans start. It then remains energized until thirty seconds after the unit air­flow switch senses no airflow. The fan operation output is on whenever the unit airflow switch senses airflow. Outside Air Damper output: Use to signal an outside air damper actuator to open whenever the unit is in an occu­pied cooling or heating condition.
or other device when an
18 McQuay Catalog 860-9
MicroTech III Unit Controls
Standard Control Options
SWP Self-Contained systems are available for most any constant or variable air volume application. MicroTech III controls offer three basic control configurations that use sophisticated state change control logic to provide stable, reliable and efficient control:
• Variable air volume with discharge temperature control (DAC)
• Constant air volume with zone temperature control (S CC)
• Constant air volume with discharge temperature control (DAC)
When combined with MicroTech III’s many available control capabilities, both factory-installed and keypad-programmable, these three basic configurations can be customized to meet the requirements of the most demanding applications.
Variable Air Volume with Discharge Temperature Control (DTC)
All VAV units provide true discharge temperature control in addition to duct static pressure control. Cooling only, cooling with single-stage “morning warm-up” heat, and cooling with modulating heat configurations are available.
Control Temperature
The Control Temperature make s the heat/cool changeover decision. It determines whether cooling or heating is enabled; the discharge temperature then determines whether cooling or heating is actually supplied. At the keypad, the operator can choose the source of the Control Temperature from among the following selections.
• Space temperature sensor
• Return temperature sensor
• Outside air temperature sensor (modulating heat only)
• Network communication
The operator enters separate cool and heat enable set points and deadbands that the Control Te mperature is compared with (see Figure 17). When the Control Temperature is greater than or equal to the cooling set point plus DB/2, cooling is enabled. When the Control Temperature is less than or equal to the heat set point minus DB/2, heating is enabled. If desired, these set points and differentials can be set so that there is a dead band in which both cooling and heating are disabled. The controller’s software prevents simultaneous cooling and heating.
Figure 17: Control Temper a ture Logi c
Constant Air Volume with Zone Temperature Control (SCC)
SCC units are available in either cooling only or cooling with modulating heat configurations. Either of these configurations is available for 100% recirculated, mixed, or 100% outdoor air applications.
Constant Air Volume with Discharge Temperature Control (DTC)
DTC units are available in cooling only, cooling with single­stage “morning warm-up” heat, or cooling with modulating heat configurations. This unit configuration can be used for applications that have zone controlled terminal heating coils or for constant volume, 100% outdoor air applications. The discharge temperature control strategies used with the hybrid DTC unit are identical to those used with the DTC unit.
Discharge Temperature Control
MicroTech III VAV-DTC and CAV-DTC controls provide sophisticated and flexible discharge air temperature control that is only possible with DDC systems. Separate discharge air temperature set points are used for cooling and modulating heating control. At the keypad, the operator can either enter the desired set points or select separate reset methods and parameters for each set point.
Proportional Integral Modulation
When operating in economizer free cooling or unit heating, the previously described PI algorithm maintains discharge temperature control. It provides precise control of the economizer dampers, modulating gas heat, steam or hot water valves.
Compressor Staging
Two staging algorithms are available to control a unit’s multiple steps of capacity control, Degree-Time (also known as “average”) and Nearest. These control algorithms provide reliable discharge temperature control while managing compressor cycling rates. Constraints on compressor staging are essential for preventing short cycling, which can reduce compressor life by causing improper oil return and excessive heat buildup in the motor windings.
The Degree-Time Compressor staging algorithm keeps track of the discharge temperature and stages cooling up or down to maintain an average temperature that is equal to the discharge
McQuay Catalog 860-9 19
MicroTech III Unit Controls
cooling set point. A stage change can occur only (1) after the keypad adjustable inter-stage timer has expired (f ive minute default setting) and (2) if the discharge temperature is outside a keypad programmed dead band. After these two conditions have been met, staging occurs as the controller attempts to equalize two running totals: degree-time above set point and degree-time below set point. The result is that the average discharge temperature is maintained at the cooling set point.
The Nearest Compressor staging algorithm keeps track of the discharge temperature and stages cooling up or down to maintain the discharge temperature as close as possible to set point. A stage change can occur only (1) after the keypad adjustable inter-stage timer has expired (five minute default setting) and (2) if the control logic calculates that a stage change will result in a discharge temperature closer to set point than the existing condition. The controller logic continually calculates the expected effect of a stage change and uses this information before making a change. A change is made only if it will bring the discharge temperature closer to set point, resulting in a more consistent discharge temperature, reduced compressor cycling and more stable control VAV box control.
Supply Air Reset
By automatically varying the discharge air temperature to suit a building’s cooling or heating needs, supply air temperature reset can increase the energy efficiency of VAV and CA V-DTC systems. MicroTech III controllers offer a variety of different reset strategies that can be selected at the keypad. Because they are keypad programmable, reset strategies can be changed or eliminated as desired. Separate strategies can be selected for both cooling and modulating heat. If reset is not desired, a fixed discharge cooling or heating set point can be entered.
The following reset methods are available:
• Space temperature
• Return temperature
• Outdoor air temperature
• Supply airflow (VAV, cooling set point only)
• External 0–10 VDC or 0–20 mA signal
• Network communication
For all temperature reset methods, the mini mum and maximum cooling and heating set points are keypad programmable along with the corresponding minimum and maximum space, return or outdoor air temperature parameters. For the supply airflow method, the discharge set point will be reset as the supply fan modulates between 30% adjustable and 100% adjustable. For the external method, the discharge set point will be reset as the voltage or current signal varies over its entire range. For units
in a BAS network, the discharge set points are reset via the communication signal.
Zone Temperature Control
MicroTech III CAV-ZTC controls provide the sophisticated and flexible zone temperature control that is only possible with DDC systems. Zone temperature sensors are available with or without a remote set point adjustment. With the remote adjustment model, the space set point can be set at the keypad or at the zone sensor package. Even if a zone sensor is connected, remote set point adjustment can be enabled or disabled as desired at the keypad.
Control Temperature
The Control Temperature is the representative zone temperature. When compared with the zone set points, the Control Temperature determines whether the unit supplies heating, cooling, or neither. It also determines the amount of cooling or heating required to satisfy the load. Its source can be selected at the keypad from among the following selections:
• Zone temperature sensor
• Return temperature sensor
Because it is the representative zone temperature, the Control Temperature is the primary input to the MicroTech III zone temperature control algorithms. Control Temperature parameters are described below. The controller’s software will prevent cooling and heating from being inadvertently enabled at the same time.
Change and Proportional Integral Modulation
When economizer “free” cooling or unit heating is required, the two MicroTech III PI loops combine for cascade-type control, providing the tightest possible zone temperature control. By controlling the discharge temperature along with the zone temperature, these functions eliminate temperature variations near the diffusers that could otherwise occur as a result of traditional zone control’s inherent lag effect.
Change: If the Control Temperatur e is above or below the set point by more than the dead band, the Change PI loop periodically adjusts the cooling temperature set point either up or down as necessary. The amount of this set point change corresponds to the Control Temperature’s position in the modulation range. The far­ther the Control Temperature is from the set point, the greater the discharge set point change will be. The Change-adjusted discharge cooling and heating set points are limited to ranges defined by keypad programmable maximum and minimum values. PI: Using the Change function’s current discharge set point, the PI function maintains precise discharge temper-
or heating discharge air
20 McQuay Catalog 860-9
MicroTech III Unit Controls
Compressor Staging
Compressor staging is controlled directly by the Control Temperature. When the Control Temperature is warmer than the zone cooling set point, cooling is staged up; when the Control Temperature is cooler than the zone cooling set point, cooling is staged down. However, a stage change can only occur when the Control Temperature is outside the dead band (see Figure 18). Staging is constrained by an inter-stage delay timer (five minute default setting) and minimum and maximum discharge air temperature limits (all keypad programmable). These constraints protect the compressors from short cycling while eliminating temperature variations near the diffusers.
Figure 18: Compressorized Logic
Project Ahead Algorithm
Because the inherent lag effect in zone temperature control applications can cause overshoot during warm-up or cool­down periods, MicroTech III features a “Project Ahead” control algorithm. Project Ahead calculates the rate at which the Control Temperature is changing and reduces the unit’s cooling or heating output as the zone temperature nears its set point, essentially eliminating overshoot.
Duct Static Pressure Control
On all VAV-DTC units, duct static pressure control is maintained by the PI algorithm, which provides precise control of the supply fan variable speed drive. The keypad programmable set point can be set between 0.20-in. W.C. and
4.00-in. W.C. On larger buildings with multiple floors, multiple trunk runs or
large shifts in load due to solar effects (east/west building orientation), an optional second duct static sensor is offered. The MicroT ech III controller automatically selects and uses the lower of the two sensed pressures to control fan volume to provide adequate static pressure to the most demanding space at all times.
Operating States
Operating states define the current overall status of the self­contained system. At the user interface, the operator can display the current operating state and thereby quickly assess the unit’s operating condition.

Alarm Management and Control

MicroTech III unit controllers are capable of sophisticated alarm management and controlled response functions. Each alarm is prioritized, indicated, and responded to with the appropriate action. The active alarm (up to 10 alarms, arranged by alarm priority) and previous alarm (up to 25 alarms, arrange by date/time cleared), each with a time and date stamp, can be displayed at the user interface. Generally speaking, whenever a current alarm is cleared, it is logged as a previous alarm and the oldest previous alarm is removed.
Alarm Priority
The various alarms that can occur are prioritized according to the severity of the problem. See Table 1. Three alarm categories are used: faults, problems, and warnings.
1 Faults are the highest priority alarms. If a fault condition
occurs, the complete unit shuts down until the alarm condition is gone and the fault is manually cleared at the keypad. A fault example is Fan Fail alarm.
2 Problems are the next lower priority to alarms. If a
problem occurs, the complete unit does not shut down, but its operation is modified to compensate for the alarm condition. A problem automatically clears when the alarm condition that caused it is gone. Compressor Fail is an example of a problem where only the affected compressor is shut down.
3 Warnings are the lowest priority alarms. No control
action is taken when a warning occurs; it is indicated to alert the operator that the alarm condition needs attention. To make sure that they are read, the operator must manually clear all warnings. Dirty Filter indication is an example of a warning.
Generally, a specific alarm condition generates an alarm that falls into only one of these categories. Under different sets of circumstances, however, the freezestat and most of the sensor failure alarm conditions can generate alarms that fall into multiple categories.
McQuay Catalog 860-9 21
Loading...
+ 49 hidden pages