McQuay SWP023 User Manual

Self-Contained Air Conditioning Systems
Type SWP Vintage H with R-410A Refrigerant
Capacity: 20 through 130 tons
Catalog 860-9
Engineered for flexibility and performance™
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Self-Contained Systems Design s . . . . . . . . . . . . . . .3
McQuay Self-Contained Systems . . . . . . . . . . . . . . . 4
SWP 012–130 Features and Options . . . . . . . . . . . . 4
Cabinet, Casing and Frame . . . . . . . . . . . . . . . . . 6
Compressor/ Condensing Section . . . . . . . . . . . . 7
Cooling Coil Section . . . . . . . . . . . . . . . . . . . . . . .8
Supply Fan Section . . . . . . . . . . . . . . . . . . . . . . . .8
Acoustical Discharge Plenum . . . . . . . . . . . . . . . 10
Variable Air Volume Control . . . . . . . . . . . . . . . . 10
Economizer Options . . . . . . . . . . . . . . . . . . . . . .10
Condenser Head Pressure Control . . . . . . . . . . .11
Filter Section . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Blank Sections . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Heating Section . . . . . . . . . . . . . . . . . . . . . . . . . .12
System Flexibility with Unit Options . . . . . . . . . . . . 13
Selection/Application Flexibility . . . . . . . . . . . . . .13
Arrangement Flexibility . . . . . . . . . . . . . . . . . . . .13
Optimal Discharge Air Temperature . . . . . . . . . .13
Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
R-410A Refrigerant . . . . . . . . . . . . . . . . . . . . . . . 14
MicroTech III Unit Controls . . . . . . . . . . . . . . . . . . . . 15
Open Choices Benefits for Easy Integration . . . . 15
Alarm Management and Control . . . . . . . . . . . . . 21
Application Considerations . . . . . . . . . . . . . . . . . . .23
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Unit Location . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Acoustical Considerations . . . . . . . . . . . . . . . . . .24
Equipment Room . . . . . . . . . . . . . . . . . . . . . . . .24
Ductwork . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Condenser Water Piping . . . . . . . . . . . . . . . . . . . 25
Head Pressure Control . . . . . . . . . . . . . . . . . . . . 25
Variable Air Volume . . . . . . . . . . . . . . . . . . . . . . 25
Variable Frequency Drives . . . . . . . . . . . . . . . . .26
Duct Static Pressure Sensor Placement . . . . . . .26
Zone Sensor Placement . . . . . . . . . . . . . . . . . . .26
Filtration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
System Operating Limits . . . . . . . . . . . . . . . . . . .27
Airflow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Fan Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Condenser Water Flow . . . . . . . . . . . . . . . . . . . . 27
Coil Freeze Protection . . . . . . . . . . . . . . . . . . . . 28
Air Density Correction . . . . . . . . . . . . . . . . . . . . . 28
Unit Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
Terms of Sale . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . 29
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
DX Cooling Capacity Data . . . . . . . . . . . . . . . . . 36
Waterside Economizer Capacity . . . . . . . . . . . . 44
Heating Capacity Data . . . . . . . . . . . . . . . . . . . . 45
Component Pressure Drops . . . . . . . . . . . . . . . 46
Total Unit Water Pressure Drop . . . . . . . . . . . . . 49
Fan Curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Recommended Clearances . . . . . . . . . . . . . . . . 61
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Supply Power Wiring . . . . . . . . . . . . . . . . . . . . . 65
Unit Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
2 McQuay Catalog 860-9

Introduction

Introduction

Continued Leadership in Self-Contained Systems Designs

McQuay SWP self contained air conditioning systems trace their history to the late 1970s. The first self contained variable air volume systems with waterside economizer cycle was developed by us for the prestigious 499 Park Avenue office building in New York City. McQuay SWP, with decades of innovation, design flexibility, durable construction, low capitol and operating cost, make us the leader of self contained system market and the preferred HVAC solution for thousand of most prominent building projects.
SWP water cooled self-contained air conditioner is an ideal option for a job where energy efficiency, reliability, indoor air quality and acoustic are top priorities. Along with providing high quality and state-of-the-art technology, SWP self­contained systems offer the following valuable features and benefits to satisfy a wide range of diverse applications.
• Comfort and Redundancy
– Occupants enjoy individual control over comfort condi-
tions and off-hour system operation.
– Tenants benefit from their indivi dual efforts to control
energy costs.
– Routine service is located where it minimizes tenant
inconvenience.
– Individual or dual systems per floor provide system
redundancy and standby.
• Economical First Cost
– VAV system flexibility uses building diversity to reduce
system tonnage and first cost.
– Factory-packaged concept reduces field labor, installation
time and expense. – No expensive chilled water piping or chiller room. – Individually tested, factory-designed systems reduce
startup and installation expense. – Reduced penthouse and equipment room requirements. – Centralized condenser water and condensate piping and
streamlined system layout. – Modular units design make renovation projects easier
since individual section designed for narrow hallways,
elevators and doorways. – Optional acoustical discharge plenum is an available
option in any height to match your job needs and mini-
mizes supply duct transition losses.
• Energy Efficient System
– Reduces fan kW and operating costs at part load condi-
tions. – Savings maximized through use of variable speed fan
control. – Individual zone control.
• Improving Indoor Air Quality
For better filtration filter selection flexibility includes: – MERV 7, 8, 11, 13, or 14 options with & without pre-fil-
ter. Microbial-resistant filter option is also an available option.
– Featured Double-wall panel construction that eliminates
fibers in the supply air stream and is easy to clean.
– Provided with double-sloped, galvanized or stainless steel
drain pans eliminate stagnant water and minimizes bacte­rial growth.
• Quiet System Operation
– Provided by structural quality and specialized design. – Recognized for quiet operation by renowned U.S. acous-
tical consultants.
– Provided with a SWSI airfoil plenum fan for excellent
acoustics and better efficiency
– Unit featured discharge plenum with sound baffles is an
available option for sound sensitive job
• Free Cooling
– Water or air economizer capability for optimized energy
savings.
– Economizer reduces compressor operating hours and
energy costs.
– Year-round “free cooling” capability.
• Efficient Part Load Operation
– System energy at part load operation is more efficient
than to central chilled water systems.
– Multiple systems and compressors versus a single, large
central plant.
– Efficient and reliable system for partial occupancy and
after hours operation.
– Operates only the system(s) on the floor(s) requiring after
hours use.
• Economical Integrated or Stand Alone DDC controls
– Monitoring and diagnostics reduce the potential for
expensive field repairs.
– Industry leading Protocol Selectability™ feature provides
effective BAS selection flexibility.
• Maintenance Costs Reduction
– No complicated central chiller plant to maintain. – Service and maintenance are performed out of the occu-
pied space.
– Control and product reliability functions designed by the
equipment manufacturer for single source responsibility and improved reliability.
• System Versatility
– Applicable to schools, offices, shopping centers, manu-
facturing facilities, etc. – Prime candidate for floor by floor building renovation. – Retrofit alternative where existing chiller cannot be
ed for replacement.
access
McQuay Catalog 860-9 3

McQuay Self-Contained Systems

McQuay Self-Contained Systems

SWP 012–130 Features and Options

Airfoil Plenum Fans
SWSI fans more energy efficient and quieter than forward
curved fans
Premium high efficiency open, drip-proof standard
motors and TEFC motors, an available option
Seismic control restrained spring isolators are available
Aerodynamically designed fan also available with 12
blades for even lower sound levels
Coils
High efficiency enhanced corrugated fin design
High coil performance and reduced static
pressure losses
Interlaced and/or row split circuiting to keep
full face of the coil active and to eliminate air temperature stratification and optimum part load performance
Durable Construction
Pre-painted or G90 galvanized steel exterior
cabinet panels
Standard foam injected panels with R-13
insulation provide superior rigid double wall construction and minimizes air leakage
For better acoustics, an additional 2", 1. 5# density
R-8 fiberglass insulation is an available option for fan and plenum sections
Double-sloped drain pans help eliminates
standing stagnant water
Blank Sections
Available to mount air blenders, carbon or
charcoal filters, sound attenuators or other specialty equipment
Allow customization for maximum system
performance and efficiency
Can reduce design and installation costs
Scroll Compressor(s)
Durable and reliable multiple compressors
Lower operating cost with High EERs
Customize selections to match specific
application
Mounted on resilient rubber isolation for
smooth and quiet operation
Access Panels and Doors
All panels and access doors shall be sealed
with permanently applied bulb-type gasket
Access doors are flush mounted to cabinetry,
with hinges, latch and handle assembly
4 McQuay Catalog 860-9
Refrigerant Circuits
Suction and discharge service valves, an available
option, to isolate each compressor
Hot gas bypass, an available option, on units with
two refrigerant circuits
McQuay Self-Contained Systems
Shell and Tube Condensers
Carbon steel Shell and Tube Condenser , non-
ferrous water channels and enhanced tubing for high performance
Integral sub-cooling circuit is provided as
standard to maximize efficiency
Mechanically cleanable condenser and water
piping is rated for standard 300 psig waterside working pressure & 450 psig is an available option
Two-way valve for head pressure control is
available for low condenser water temperatures
Multiple Filter Options
2" 30% (MERV7) and 75% (MERV13) filter s
4" 30% (MERV8), 65% (MERV1 1), 75% (MERV13)
and 85% (MER V14) longer lasting filters available
4" primary filters also available with 2" or 4" with
pre-filter
Economizer Options
W aterside economizer effectively uses low cooling tower
water temperatures to offload compressor operation
An airside economizer control package is available for
controlling field installed mixing dampers capable of 100% outside airflow.
MicroTech® III Control System
Factory-installed and tested to help minimize costly field
commissioning.
Open Choices™ feature for easy integration into the BAS of
your choice using open, standard protocols such as BACnet® or LONTALK®.
Easily accessed for system diagnostics and adjustments via a
keypad/display on unit.
Optionally add a remote keypad and display that is identical to
the unit mounted user interface.
Factory-Mounted Variable Frequency Drives
Controlling fan motor speed can lower fan operating
costs and sound levels
All VFD selections are plenum rated
Manually activated bypass contactor is available to
allow system operation in the event of drive service
McQuay Catalog 860-9 5
McQuay Self-Contained Systems
McQuay Self -Contained SWP systems are built to perform, with features and options that provide for lower installed and operating costs, good indoor air quality, quiet operation and longevity.

Cabinet, Casing and Frame

Unit base constructed of 15-gauge and 10-gauge galvanized
steel for vibration control and rigging strength.
Heavy-duty lifting brackets strategically placed for balanced
cable or chain hook lifting.
Figure 1: Low Leak Gasketed Frame and Foam Panels
Unit cabinet constructed with foam insulation standard and
heavy gauge [pre-painted] [galvanized steel] exterior panels for long equipment life.
All sections have galvanized steel internal lining.
2-inch thick panels and access doors are thermal broke
double wall assembly, with [R-13 foam] [R-8 fiberglass].
System components strategically located for ease of
inspection, serviceability and maintenance.
Refrigeration components positioned out of the airstream so
adjustments and readings can be made without disrupting system operation.
Access doors flush mounted to cabinetry, with hinges, latch
and handle assembly.
Doors on positive pressure sections are provided with
secondary latches to relieve pressure and prevent injury upon access.
Figure 2: Hinged Access Doors with double latches
Low leak gasketed frame channels minimize air leakage and
eliminates metal-to-metal contact between paneling and frame work. Air leakage is only 0.5 cfm/square foot at 5" cabinet pressure.
6 McQuay Catalog 860-9
McQuay Self-Contained Systems
Control Panel
Coil/Access Section
Supply Fan Section
Compressor/ Condenser Section
Base Plates
Modular Design
Optional modular construction unit shipped with a nitrogen
holding charge.
Four distinct sections; coil/access section, supply fan
section, compressor/condenser section and the control panel.
Figure 3: SWP Modular Sections
Insulated and segregated condensing section from the air
handling section to avoid transmission of noise to the circulated air stream.
Each refrigerant circuit is furnished with filter-drier, liquid
moisture indicator/sight glass , th erm a l ex pansion valve, liquid line shutoff valve with charging port, high pressure relief device and high and low pressure cutouts.
If any compressor is made inoperable, the remaining
compressors are still allowed to operate.
Thermal expansion valve capable of modulation from 100-
25% of its rated capacity.
Hot gas bypass also available on units with two refrigerant
circuits.
Condensers
All units feature carbon steel mechanically cleanable shell
and tube condenser.
Includes non-ferrous water channels and enhanced tubing
for high performance.
Serves an independent refrigerant circuit and includes a
spring loaded high pressure relief valve
Integral sub-cooling circuit provided as standard to
maximize efficiency.

Compressor/ Condensing Section

Compressors
All units feature multiple reliable scroll compressors for
Suction and discharge service valves and gauge ports,
Individual branch circuit fusing protects each compressor.
T o prevent compressor short cycling, MicroTech® III
Compressors mounted on resilient rubber isolation for
Figure 4: Compresors
efficient system part load control, quiet operation and system redundancy.
available option, on each compressor.
control system incorporates timing functions.
smooth and quiet operation.
Figure 5: Condensers
All units are leak tested, evacuated and shipped with a [full
operating charge of R-410A] [for modular design nitrogen holding charge] and POE oil.
Condenser assembly and all factory water piping rated for a
waterside working pressure of 300 psig as standard [450 psig] tested before shipment.
Provided with a single supply and return water connections
Unit available in both right-hand and left-hand piping
locations.
Optional two-way valve provides accurate head pressure
control for condenser entering water temperatures as low as 40ºF.
McQuay Catalog 860-9 7
McQuay Self-Contained Systems
Refrig. Flow Ckt 1 Refrig. Flow Ckt 2
Ckt 2
Ckt 1
Ckt 1
Ckt 1
Ckt 1
Ckt 1
Ckt 1
Ckt 1
Ckt 1
Ckt 2
Ckt 2
Ckt 2
Ckt 2
Ckt 2
Ckt 2
Ckt 2
Airflow
Cooling Coils

Cooling Coil Section

Large face area coils with high efficiency , enhanced copper
tubing and ripple corrugated aluminum fins.
Features interlaced and/or row split circuiting to keep the
full face of the coil active and eliminate air temperature stratification and optimum part load performance.
Figure 6: Evaporator Coil Circuiting
5 or 6 row evaporator coil with 12 fins/ inch spacing and
multiple face areas allows a custom match to specific design loads.
Provides low air pressure drop, high full and part load
operating efficiencies.
Mounted in a [galvanized] [stainless steel ] cross broke and
double sloped drain pan with a full 2 inches of insulation.
Compressor staging sequenced to take maximum advantage
of available coil surface.
Each evaporator coil circuit furnished with a wide range
thermostatic expansion valve with an adjustable superheat setting and external equalizer.
An intermediate drain pan in the coil bank helps to provide
condensate removal without carryover.
Figure 7: Cooling Coil Section Shown

Supply Fan Section

Single width, single inlet (SWSI) airfoil supply air fan
selections provide efficient, quiet operation at wide ranging static pressure and air flow requirements.
Each fan assembly is dynamically trim balanced at the
factory for quiet operation before shipment.
All fan drives are factory sized according to job specific
airflow, static pressure, and power requirements.
For seismic sensitive regions, spring fan isolators are
available with seismic restraints.
150% service factor drives extend service life of the fan
belts. Drive components and fan bearings are easily accessed for periodic maintenance.
Mounted on 2 inch deflection spring isolators for excellent
isolation effectiveness.
Solid steel shafts rotating in 200,000 hour pillow block ball
bearings with grease fittings.
Motor availability includes premium efficiency, open, drip-
proof, and totally enclosed selections; EPACT compliant premium efficiency selections.
8 McQuay Catalog 860-9
Figure 8: Airfoil Fan
McQuay Self-Contained Systems
McQuay Plenum Fan
Least turbulance
and best acoustics
* Ceiling heights restrict “h” and increase the problem with housed fans
Competitive Housed Fan
Excessive turbulance
and mediocre acoustics
Competitive Housed Fan
Worst turbulance
and worst acoustics
h*
Acoustical Advantages
McQuay SWP Self-contained units are provided with a high efficient, SWSI airfoil plenum fan and have several acousti cal advantages:
Airfoil fans are more efficient than forward curved fans
contributing to less noise.
For specific unit sizes, several fan diameters are available,
fan selection provides optimal efficiency.
Figure 9: Supply Fan Comparison
Competitive supply duct work normally involves
discharging air vertically into a ceiling, then routing it horizontally, Figure 10. McQuay’s plenum fan discharge has far less velocity pressure than competitive housed fan discharge, resulting in:
• 90º duct elbows that generate far less turbulance.
• Air flow that can be routed in any direction.
McQuay Catalog 860-9 9
McQuay Self-Contained Systems
McQuay Optional Plenum
“h” can be varied to match ceiling height
h
Competition
Expansion Loss
90° Elbow Loss
Standard Exterior Galvanized Surface
Standard Galvanized Liner
Standard Injected Foam Panel
Optional Fiberglass Insulation
Perforated Liner
Interior Optional

Acoustical Discharge Plenum

McQuay offers an optional acoustical discharge plenum,
Figure 10, that minimizes supply duct transition losses and
noise:
Plenum fans pressurize the entire cabinet and have no
significant plenum air pressure drop (housed fans have expansion, contraction and 90º elbow losses).
Discharge plenums offered in any height to match ceiling
height.
Custom size duct connections are available on any size
plenum.
Discharge Plenum with Foam Insulation and Sound Baffles
Optional discharge plenum with foaminjected panels can be provided with the additional sound attenuating baffle option consisting of:
Additional 2" of fiberglass insulation.
Perforated liners, Figure 11.
Figure 10: Acoustical Discharge Plenum

Variable Air Volume Control

Energy saving advanced technology variable frequency
drive (VFD), fan speed control is available with the convenience and cost savings of factory mounting and testing.
Figure 12: Variable Frequency Drive Controller
Figure 11: Foam Insulation and Sound Baffles
All VFD selections are plenum rated and are conveniently
mounted within the control panel.
MicroTech III controls provide advanced duct static pressure
control and controlled by either single or two-duct static pressure sensors.
A manually activated bypass contactor is available to allow
system operation even in the event of drive service.
All VAV systems include an adjustable, duct high-limit
switch to protect duct work from excessive pressure.

Economizer Options

Waterside Economizer
An energy saving, waterside economizer package, an
available option on all return air unit.
Includes factory mounted 4-row [chemically cleanable coil]
[mechanically cleanable coil], control valves and piping.
Rated for 300 psig as standard [450 psig] waterside working
pressure and the entire coil and piping assembly is factory leak tested.
Factory integrated MicroTech III controller to control
economizer operation and maximize free cooling potential.
Unit enables economizer operation whenever cooling tower
water temperature is less than the unit entering air temperature by a field adjustable value, generally 5-7°F.
10 McQuay Catalog 860-9
McQuay Self-Contained Systems
Mechanically Cleanable
Economizer Coil
To save energy with a variable pumping system control
valves operation can be selected to maintain full flow through the unit at all times or to isolate the unit from the condenser water loop when there is no call for cooling.
To extend free cooling savings, economizer operation can be
enabled during mechanical cooling.
Unit enables mechanical cooling only when the economizer
valve is driven 90% open and cooling load is not satisfied.
Economizer control will maintain full free cooling capability
until disabled by the economizer changeover set point.
T o help protect against coil freeze-up an optional factory
mounted freeze stat is available.
Figure 13: Mechanically Cleanable Waterside Economizer Coil
To extend free cooling savings, economizer operation can be
enabled during mechanical cooling.
Unit enables mechanical cooling only when the economizer
damper is driven 90% open and cooling load is not satisfied.
Economizer control will maintain full free cooling capability
until disabled by the economizer changeover set point.

Condenser Head Pressure Control

Unit requires condenser head pressure control for
applications where a waterside economizer package is not being used and entering condenser water temperatures can be less than 55°F.
Optional two-way valve provides accurate head pressure
control for condenser entering water temperatures as low as 40degree F

Filter Section

Selection flexibility includes face loaded rack with non-
gasketed frames and filter clips.
Unit features 2-inch filter option available in 30% (MERV 7)
& 75% (MERV 13) nominal efficiency
Longer lasting 4-inch filters higher filtration option is
available in 30% (MERV 8) & 65% (MERV 11), 75% (MER V 13) & 85% (MERV 14) nominal efficiency with and without 2-inch or 4-inch 30% pre-filter.
Airside Economizer
A mixing box containing outdoor air, return air and exhaust
air dampers are available using the McQuay Vision™ air handling unit platform.
Factory integrated MicroTech III controller controls
economizer operation and maximize free cooling potential.
Airside economizer control package available to control
field installed mixing dampers capable of 100% outside airflow.
Unit enables economizer operation whenever outside air
enthalpy , comparative enthalpy or dry bulb temperature changeover provides control flexibility to bring in most amount of outside air for free cooling.
Economizer damper control actuator modulates in response
to the cooling load.
MicroTech III controller positions outside air damper to
maintain minimum ventilation requirements when economizer is not in operation.
Figure 14: 4 Inch Filters

Blank Sections

Available to mount air blenders, pre-heat coils, sound
attenuators or other specialty equipment using the McQuay Vision™ air handling unit platform and shipped loose.
Allow customization for maximum system performance and
efficiency and reduce design and installation costs.
McQuay Catalog 860-9 11
McQuay Self-Contained Systems

Electrical

Units are completely wired and tested at the factory prior
shipment.
Wiring complies with NEC requirements and all applicable
UL standards.
For ease of use, wiring and electrical components are
number coded and labeled according to the electrical diagram whenever applicable.
Supply air fan motors, compressor motors and electric heat
all branch circuits have individual short circuit protection.
Control circuit power is supplied through a factory installed,
low voltage transformer.
The supply fan motor circuit includes a three phase
contactor and ambient compensated overload protection with manual reset.
Each refrigerant circuit includes both a high and low
pressure cutout switch.
A terminal block is provided for the single, main power
connection and a terminal board is provided for low voltage control wiring.
A factory mounted, non-fused main circuit interrupter is
available for disconnecting the main electrical power to the unit.
Dual power blocks or disconnect switches are available to
accommodate requirements for standby, emergency power supplies.

Heating Section

Hot Water Heat
Multiple coil selections offered to size heating output to
application needs.
Hot water coils are 5/8-in. O.D. copper tube/ aluminum fin
design with patented HI-F5 fins.
Rated in accordance with ARI Standard 430.
Pre-heating control fully integrated into the unit’s
MicroTech III control system is available using the McQuay Vision™ air handling unit platform.
Available with factory-mounted freezestat.
Steam Heat
Steam heating coils are 5/8-in. O.D. copper tube/aluminum
fin jet distributing type with patented HI-F5 fin design.
Rated in accordance with ARI Standard 430.
Multiple different steam coil selections offered to size
heating output to application needs.
Pre-heating control fully integrated into the unit’s
MicroTech III control system is available using the McQuay Vision™ air handling unit platform.
Available with factory-mounted freezestat.
Electric Heat
Factory assembled, installed and tested.
Two stage capability for application flexibility.
Durable low watt density nickel chromium elements for
longer life.
Entire heat bank protected by a linear high limit control with
each heater element protected by an automatic reset high limit control.
Fuses provided in each branch circuit.
12 McQuay Catalog 860-9

System Flexibility with Unit Options

Along with providing high quality and state-of-the-art innovation, SWP self-contained systems offer customized flexibility to satisfy a wide range of diverse applications.
System Flexibility with Unit Options
discharge orientations. Piping and fan arrangement flexibility can simplify mechanical equipment room arrangement, improve installation costs, and total system performance.

Selection/Application Flexibility

Nominal cooling capacities range from 12 to 130 tons. In addition, all units offer multiple compressor selections to meet exacting system requirements. The flexibility to optimize the self-contained system to fit the application is a McQuay SWP advantage. Available system applications include the following:
• VAV dischar ge air temperature control with static pres­sure control.
• Discharge air temperature control with constant air vol­ume.
• Constant volume, zone temperature control.
• 100% outside air control.
• Dehumidification control, with or without reheat control.
In addition to compressor/coil flexibility, SWP systems offer single width, single inlet, air foil fans with factory-mounted variable frequency drives for maximizing VAV system fan performance. High efficiency fan capability coupled with extensive compressor flexibility provide the right system selection for the application.

Arrangement Flexibility

All SWP systems offer the flexibility of right-hand and left­hand piping and control panel arrangements and multiple fan

Optimal Discharge Air Temperature

More and more system engineers are designing optimal discharge air temperature systems to improve system performance and system first cost; the McQuay SWP provides the flexibility to do it successfully. Optimal discharge air temperature systems are designed to provide unit leaving air temperature selections of 52°F to 53°F versus more conventional systems that supply air at temperatures closer to 58°F . This five to six degree reduction in air temperature to the room diffusers can subsequently reduce the required supply air volume to the room by 20% to 25%.
The benefits of optimal discharge air temperature systems become quite apparent with a look at the advantages offered with reduced supply air cfm airflow:
• Reduced first cost and installation cost by allowing smaller duct sizes and a smaller air distribution system.
• Reduced bhp requirements. Depending on changes in duct size and the resulting total static pressure, a 20% reduction in supply air cfm can reduce fan bhp require­ments by 25% or more.
• Reduced fan sound power generation and a quieter room environment.
• Reduced equipment room size may be possible due to using a physically smaller unit size.
• Filtration Flexibility.
McQuay Catalog 860-9 13
System Flexibility with Unit Options

Controllers

MicroTech III DDC control systems provide constant volume, variable air volume, 100% outside air, and/or dehumidification control flexibility . See “MicroTech III Unit Controller” section for more information.
Summary of Available Options
• Multiple different compressor/coil capacity selections
• Mult ip le control options: VAV, CV, 100% O A, dehumidi­fication
• Nonfused main power disconnect switch
• Dual nonfused main disconnect switches
• Nonaveraging freezestat for hot water or waterside econ­omizer coil protection
• Unit phase failure/under voltage protection
• Premium efficiency fan motors
• TEFC fan motors
• Condenser water flow switch
• 4-row waterside economizer system
• Air cycle economizer system
• Modulating hot water heat control
• Staged electric heat
• Multi direction, acoustic discharge plenum
• Factory-mounted and factory-controlled variable fre­quency drives
• High efficiency filtration options
• Right-hand and left-hand piping se lections
• Multiple fan discharge arrangements
• Head pressure control valve
• Special coil coatings
• Double wall cabinet construction
• Seismic fan isolation
• Independent refrigerant circuit units offer the following options:
• Five-row or six-row DX coils with enhanced heat trans­fer surfaces
• R-410A refrigerant
• Service and shut off valves on liquid and discharge
Figure 15: MicroTech III DDC Co ntroller

R-410A Refrigerant

McQuay SWP units with independent refrigerant circuits are available with non-ozone depleting R-410A refrigerant.
Features
• R-410A refrigerant is environmentally friendly with zero ozone depleting allowance (ODP). Customers have no phase out and replacement concerns.
• Units are factory engineered for proper cooling perfor­mance using R-410A.
• R-410A efficiency is excellent. McQuay R-410A SWP units are available with EERs that exceed ASHRAE 90.1-
2010.
• Units are factory charged with R-410A and synthetic oil (such as POE), and they include components and controls specifically tailored to R-410A.
• R-410A refrigerant is a blend, but the glide is negligible. This is not true for R-407C. If R-407C leaks, the remain­ing charge may not have a proper mix of components. R­410A does not have this problem so leaks are easier to repair.
• Units are factory tested prior to shipment.
14 McQuay Catalog 860-9

MicroTech III Unit Controls

McQuay SWP systems continue to provide industry leading performance, equipped with a complete MicroTech III control system. In addition to providing stable, efficient temperature, and static pressure control, the controller is capable of providing comprehensive diagnostics, alarm monitoring, and alarm specific component shutdown if critical equipment conditions occur. The unit controllers are factory mounted and configured for stand-alone operation or integration with a building automation system (BAS) through an optional communication module with our Open Choices feature.

Open Choices Benefits for Easy Integration

Easy, low cost integration into most building automation systems without costly gateway panels.
Flexibility to select either BACnet® or L
communication. Units are LonMark® 3.4 certified with the appropriate communications module for L networks.
Comprehensive unit control and status information is
available at the BAS regardless of communication protocol.
Long-term choices for equipment adds or replacements, and
for service support.
Flexible alarm notification and prioritization with Intrinsic
Alarm Management (BACnet).
Simplified BAS integration with the ability to set network
parameters at the unit controller, reducing installation time and costs.
Easy monitoring and troubleshooting of communication
status from the unit controller to the BAS.
ONWORKS®
ONWORKS
MicroTech III Unit Controls
Components
Each SWP self-contained system is equipped with a complete MicroTech III unit control system that is pre-engineered, preprogrammed, and factory tested prior to shipment. Each of the MicroTech III unit control systems is composed of several components that are individually replaceable for ease of service. These components include:
• Unit controller with user interface display and navigation wheel
• Optional expansion modules
• Communication module (optional)
• Pressure transducers
• Unit-mounted temperature sensors
• Zone temperature sensor packages
• Humidity sensor
Main Control Board (MCB)
The main control board (MCB) contains a microprocessor that is preprogrammed with the software necessary to control the unit. This provides that schedules, set points and parameters are not lost, even during a long-term power outage. The microprocessor board processes system input data and then determines and controls output responses. An RS-232 communication port is provided as standard to allow for direct or modem access with a PC-based service tool.
Expansion Modules
These boards are used to expand the input and output capability of the unit controller. Each board communicates via serial data communications. These microprocessor based boards provide independent operation and alarm response even if communication is lost with the unit controller.
Communication Module
An optional communication module provides the means to factory or field configure MicroTech III unit controls for interoperability with an independent BAS. Communication modules are available to support industry recognized communication protocols including BACnet MS/TP, BACnet/ IP and L
Figure 16: MicroTech III Keypad Display
McQuay Catalog 860-9 15
ONWORKS.
MicroTech III Unit Controls
Keypad/Display
All MicroTech III unit controllers include a push/pull navigation wheel and display. The display is a supertwist nematic type with highly visible black characters on a yellow background. The 5-line by 22-character format allows for easy to understand plain English display messages. All operating conditions, system alarms, control parameters and schedules can be monitored from the keypad/display. If the correct password has been entered, any adjustable parameter or schedule can be modified from the keypad.
Temperature and Humidity Sensors
With the exception of the zone, outside air and return air sensors, all temperature sensors are factory installed and tested. Zone sensor packages are available to suit any application. A humidity sensor is available for field installation.
Static Pressure Transducers
All pressure transducers are factory installed and tested. Connection and routing of field-supplied sampling tubes is done at time of unit installation.
Zone Temperature Sensors
Two optional zone temperature sensors are available:
• Zone sensor with tenant override switch
• Zone sensor with tenant override switch and remote set point adjustment
Timed tenant override is a standard MicroTech III control feature.
Zone sensors are required for the controller’s purge cycle, space reset of supply air set point, and night setback or setup features. All zone sensors are field installed with field wiring terminated at a separate, clearly marked terminal strip.
Stand-alone Controller Features
MicroTech III applied rooftop unit controls includ e all of th e essential features required to make them capable of completely independent, stand-alone operation.
Internal Time Clock
An internal, battery-backed time clock is included in the MicroTech III unit controller. Current date and time can be quickly and easily set at the user interface keypad.
Internal Schedule
Seven daily schedules and one holiday schedule can be entered at the keypad of all unit controllers. For each of these eight schedules, one start and one stop time can be entered. Up to 10 holiday periods, of any duration, can be designated. The unit will automatically run according to the holiday schedule on the holiday dates. To handle special occasions, an additional ‘one event’ schedule can also be used.
In lieu of its internal schedule, the unit can be operated according to a network schedule from a BAS.
External Time Clock or Tenant Override Input
An input is supplied that can be used to accept a field wired start/stop signal from a remote source. An external time clock, a tenant override switch, or both may be connected. Whenever the external circuit is closed, the controller overrides the internal schedule (if activated) and places the unit into the occupied mode.
If the internal schedule or a BAS network schedule is used, field wiring is not required.
Timed Tenant Override
Off-hour operation flexibility is a must in today’s office environments and even stand-alone MicroTech III controls handle it with ease. When unit operation is desired during unoccupied hours, initiate timed tenant override by pressing the tenant override button on either of the optional zone sensor packages. The unit then starts and runs in the occupied mode for a keypad-adjustable length of time (up to five hours ). If th e button is pressed again while the unit is operating, the timer resets to the full time allowance without interrupting unit operation. Tenant override operation also can be initiated by a BAS.
Three Remote Set Point Adjustment Options
1 Remote user interface option (RUI). 2 Building automation system (BAS). See “Open Choices
Benefits for Easy Integration” on page 15.
3
All constant air volume-zone temperature control (CAV­ZTC) unit controllers include an input that can be used to remotely adjust the zone cooling and heating set points. To use this feature, wire the optional zone sensor package with set point adjustment to the controller. The remote set point adjustment feature can be enabled or disabled from the keypad at any time. When enabled, remote set point adjustment is available even if the return temperature is selected to be the Control Temperature.
16 McQuay Catalog 860-9
MicroTech III Unit Controls
Auto/Manual Operation Selection
Automatic or manual operation can be controlled either remotely or at the keypad.
All controllers include three inputs that can be used to enable or disable cooling, heating, and fan operation from remote switches. With the “heat enable” and “cool enable” terminals, the operator can enable cooling, heating, or both as desired. Using the system “off” terminals, the operator can disable the fans, and thus the entire unit.
From the keypad, there are a variety of occupancy and auto! manual control mode selections available to the operator:
• Occupancy modes – Auto – Occupied – Unoccupied – Bypass (tenant override)
• Control modes – Off manual – Auto – Heat/cool – Cool only – Heat only – Fan only
Compressor Lead-lag Selection
All unit controllers are capable of automatic compressor, lead­lag control.
Waterside Economizer Changeover
On units equipped with a waterside economizer package, the MicroTech III unit controller includes an internal changeover strategy that compares entering cooling tower water temperature to the unit’s mixed air temperature. If the entering water temperature is less than the mixed air temperature by a field-adjustable differential (typically 5°F to 7ºF), the economizer control valve modulates in response to the cooling load.
Airside Economizer Changeover Selection
On units equipped with an economizer, there are three methods of determining whether the outdoor air is suitable for free cooling: two methods sense enthalpy (dry bulb temperature and humidity) and one senses outdoor air dry bulb temperature.
The two enthalpy changeover methods use external, factory installed controls. One compares the outdoor ambient enthalpy to a set point; the other is a solid state device that compares the outdoor ambient enthalpy to the return air enthalpy. This
comparative enthalpy control can improve total economizer performance.
All unit controls include an internal dry bulb changeover strategy that can be selected at the keypad. When this method is selected, the controller compares the outdoor air dry-bulb temperature to a keypad programmable set point. The external enthalpy control input is then ignored.
Cooling and Heating Lockout Control
All unit controls include separate keypad programmable set points for locking out mechanical cooling and heating. Mechanical cooling is locked out when the outdoor temperature is below the cooling lockout set point; heating is locked out when the outdoor temperature is above the heating lockout set point. This feature can save energy cost by eliminating unnecessary heating and cooling during warm-up or cool-down periods or when the outdoor ai r tem perature is mild.
Night Setback and Setup Control
When one of the zone temperature sensors is connected to the unit controller, night setback heating and night setup cooling control are available. Separate, keypad programmable night heating and cooling set points are used to start the unit when necessary. After the unit starts, night setback and setup control is similar to normal occupied control except that the minimum outside air damper position is set to zero. If the outside air is suitable for free cooling, it is used during night setup operation.
Except for 100% outside air applications, night setback control is available even if the unit is not equipped with any heating equipment. When the space temperature falls to the night setback set point, the fans simply start and run until the temperature rises above the differential. This feature might be useful for applications that use, for example, duct-mounted reheat coils.
Morning Warm-up Control
If the Control Temperature (space or return) is below set point when the unit enters the occupied mode, the morning warm-up control function will keep the outs heat is supplied to satisfy set point. The outside air damper will remain closed until either the space temperature rises to the
heating set point or the keypad adjustable morning warm-up timer expires (default is 90 minutes). The morning warm-up timer supplies the minimum required amount of outdoor air after a certain time regardless of the space temperature.
Morning warm-up control is automatically included on all except 100% outside air units. It is available even if the unit is
ide air dampers closed while
McQuay Catalog 860-9 17
MicroTech III Unit Controls
Condenser Head Pressure Control (units without waterside economizer only)
Mechanical cooling is allowed whenever the entering cooling tower water temperature is 55ºF or warmer, without the use of head pressure control. When the entering water temperature is below 55ºF , a factory-installed and factory-controlled two-way modulating head pressure control valve can be utilized. The regulating valve is controlled by the MicroTech III controller to maintain refrigerant head pressure.
Outdoor Air Purge Control (units with airside economizer only)
Purge control is designed to take advantage of cool early morning outside air conditions. It starts the fans and modulates the economizer dampers to maintain occupied cooling requirements during unoccupied periods, if conditions are appropriate. This provides the opportunity to flush the space with fresh outdoor air prior to occupancy. Purge operation is possible only during a keypad-adjustable time window prior to occupancy (0 to 240 minutes). When the purge-cycle is active, mechanical cooling is disabled. To use the purge feature, connect one of the zone temperature sensors to the unit controller. Below is a description of purge control operation.
During the purge time window, the unit starts and runs whenever these three requirements are met:
• The space temperature must be warm enough to enable occupied cooling.
• The outside air enthalpy must be low enough to enable the economizer.
• The outside air temperature must be at least 3°F less than the space temperature.
When any one of these conditions is no longer true, the unit shuts down. As conditions allow, purge cycles the unit in this manner until it enters the occupied mode.
Proportional Integral (PI) Control
The Proportional Integral (PI) control algorithm controls modulating actuators to maintain a measured variable (temperature or pressure) at or near its set point. For example, it controls economizer dampers to maintain the discharge cooling set point and it controls the supply fan variable frequency drives to maintain the duct static pressure set point. The integral control feature effectively eliminates “proportional droop” (load dependent offset) resulting in the tightest possible control.
For each PI loop, four keypad adjustable parameters allow the control loop to be properly tuned for any application:
•Period
• Dead band
• Proportional band
• Integral time
Appropriate default values for these parameters are loaded into each controller. These default values will provide proper control for most applications; therefore, field tuning is usually not required and thus start-up time is reduced.
Change Algorithm
The PI function is also used to adjust set points instead of controlling variable speed drives or actuators directly. For example, in zone control applications, the PI loop automatically “changes” the discharge temperature set point (cooling or heating) as the Control Temperature deviates from the zone set point. Another PI loop then controls the economizer actuator or heating valve actuator using the current discharge temperature set point. Unlike a typical “mastersubmaster” reset strategy, this “cascade control” continuously adjusts the discharge set point, even if the Control Temperature’s deviation from set point remains constant. This means that the unit’s cooling or heating output is set according to the actual load, not just the current zone temperature. The tightest possible zone temperature control results because “proportional droop” (load dependent offset) is eliminated.
Calibrate
When initiated at the keypad by an operator, the Calibrate function automatically calibrates all actuator position feedback inputs and all pressure transducer inputs. It does this by shutting the unit down and then driving all actuators to the full closed and full open positions. The controller records the input voltage values that correspond to these positions. The pressure transducer input voltages, which are assumed for 0.00-in. W.C., are also recorded. When Calibrate is finished, enter an operator command at the keypad to start the unit.
Field Output Signals
All MicroTech III controls include two solid-state relay outputs that are available for field connection to any
suitable device: the remote alarm output and the occupied output. These two outputs are used to signal field equipment of unit status.
Remote Alarm Output: The remote alarm output can be used to operate a 24 volt relay to provide a remote alarm signal to a light, audible alarm, alarm condition exists at the unit. Fan Operation Output: The fan operation output is used to operate a 24 volt relay to control field equipment that depends on fan operation; for instance, to open field installed isolation dampers or VAV boxes. To allow actua­tors enough time to stroke, the fan operation output is energized three minutes before the fans start. It then remains energized until thirty seconds after the unit air­flow switch senses no airflow. The fan operation output is on whenever the unit airflow switch senses airflow. Outside Air Damper output: Use to signal an outside air damper actuator to open whenever the unit is in an occu­pied cooling or heating condition.
or other device when an
18 McQuay Catalog 860-9
MicroTech III Unit Controls
Standard Control Options
SWP Self-Contained systems are available for most any constant or variable air volume application. MicroTech III controls offer three basic control configurations that use sophisticated state change control logic to provide stable, reliable and efficient control:
• Variable air volume with discharge temperature control (DAC)
• Constant air volume with zone temperature control (S CC)
• Constant air volume with discharge temperature control (DAC)
When combined with MicroTech III’s many available control capabilities, both factory-installed and keypad-programmable, these three basic configurations can be customized to meet the requirements of the most demanding applications.
Variable Air Volume with Discharge Temperature Control (DTC)
All VAV units provide true discharge temperature control in addition to duct static pressure control. Cooling only, cooling with single-stage “morning warm-up” heat, and cooling with modulating heat configurations are available.
Control Temperature
The Control Temperature make s the heat/cool changeover decision. It determines whether cooling or heating is enabled; the discharge temperature then determines whether cooling or heating is actually supplied. At the keypad, the operator can choose the source of the Control Temperature from among the following selections.
• Space temperature sensor
• Return temperature sensor
• Outside air temperature sensor (modulating heat only)
• Network communication
The operator enters separate cool and heat enable set points and deadbands that the Control Te mperature is compared with (see Figure 17). When the Control Temperature is greater than or equal to the cooling set point plus DB/2, cooling is enabled. When the Control Temperature is less than or equal to the heat set point minus DB/2, heating is enabled. If desired, these set points and differentials can be set so that there is a dead band in which both cooling and heating are disabled. The controller’s software prevents simultaneous cooling and heating.
Figure 17: Control Temper a ture Logi c
Constant Air Volume with Zone Temperature Control (SCC)
SCC units are available in either cooling only or cooling with modulating heat configurations. Either of these configurations is available for 100% recirculated, mixed, or 100% outdoor air applications.
Constant Air Volume with Discharge Temperature Control (DTC)
DTC units are available in cooling only, cooling with single­stage “morning warm-up” heat, or cooling with modulating heat configurations. This unit configuration can be used for applications that have zone controlled terminal heating coils or for constant volume, 100% outdoor air applications. The discharge temperature control strategies used with the hybrid DTC unit are identical to those used with the DTC unit.
Discharge Temperature Control
MicroTech III VAV-DTC and CAV-DTC controls provide sophisticated and flexible discharge air temperature control that is only possible with DDC systems. Separate discharge air temperature set points are used for cooling and modulating heating control. At the keypad, the operator can either enter the desired set points or select separate reset methods and parameters for each set point.
Proportional Integral Modulation
When operating in economizer free cooling or unit heating, the previously described PI algorithm maintains discharge temperature control. It provides precise control of the economizer dampers, modulating gas heat, steam or hot water valves.
Compressor Staging
Two staging algorithms are available to control a unit’s multiple steps of capacity control, Degree-Time (also known as “average”) and Nearest. These control algorithms provide reliable discharge temperature control while managing compressor cycling rates. Constraints on compressor staging are essential for preventing short cycling, which can reduce compressor life by causing improper oil return and excessive heat buildup in the motor windings.
The Degree-Time Compressor staging algorithm keeps track of the discharge temperature and stages cooling up or down to maintain an average temperature that is equal to the discharge
McQuay Catalog 860-9 19
MicroTech III Unit Controls
cooling set point. A stage change can occur only (1) after the keypad adjustable inter-stage timer has expired (f ive minute default setting) and (2) if the discharge temperature is outside a keypad programmed dead band. After these two conditions have been met, staging occurs as the controller attempts to equalize two running totals: degree-time above set point and degree-time below set point. The result is that the average discharge temperature is maintained at the cooling set point.
The Nearest Compressor staging algorithm keeps track of the discharge temperature and stages cooling up or down to maintain the discharge temperature as close as possible to set point. A stage change can occur only (1) after the keypad adjustable inter-stage timer has expired (five minute default setting) and (2) if the control logic calculates that a stage change will result in a discharge temperature closer to set point than the existing condition. The controller logic continually calculates the expected effect of a stage change and uses this information before making a change. A change is made only if it will bring the discharge temperature closer to set point, resulting in a more consistent discharge temperature, reduced compressor cycling and more stable control VAV box control.
Supply Air Reset
By automatically varying the discharge air temperature to suit a building’s cooling or heating needs, supply air temperature reset can increase the energy efficiency of VAV and CA V-DTC systems. MicroTech III controllers offer a variety of different reset strategies that can be selected at the keypad. Because they are keypad programmable, reset strategies can be changed or eliminated as desired. Separate strategies can be selected for both cooling and modulating heat. If reset is not desired, a fixed discharge cooling or heating set point can be entered.
The following reset methods are available:
• Space temperature
• Return temperature
• Outdoor air temperature
• Supply airflow (VAV, cooling set point only)
• External 0–10 VDC or 0–20 mA signal
• Network communication
For all temperature reset methods, the mini mum and maximum cooling and heating set points are keypad programmable along with the corresponding minimum and maximum space, return or outdoor air temperature parameters. For the supply airflow method, the discharge set point will be reset as the supply fan modulates between 30% adjustable and 100% adjustable. For the external method, the discharge set point will be reset as the voltage or current signal varies over its entire range. For units
in a BAS network, the discharge set points are reset via the communication signal.
Zone Temperature Control
MicroTech III CAV-ZTC controls provide the sophisticated and flexible zone temperature control that is only possible with DDC systems. Zone temperature sensors are available with or without a remote set point adjustment. With the remote adjustment model, the space set point can be set at the keypad or at the zone sensor package. Even if a zone sensor is connected, remote set point adjustment can be enabled or disabled as desired at the keypad.
Control Temperature
The Control Temperature is the representative zone temperature. When compared with the zone set points, the Control Temperature determines whether the unit supplies heating, cooling, or neither. It also determines the amount of cooling or heating required to satisfy the load. Its source can be selected at the keypad from among the following selections:
• Zone temperature sensor
• Return temperature sensor
Because it is the representative zone temperature, the Control Temperature is the primary input to the MicroTech III zone temperature control algorithms. Control Temperature parameters are described below. The controller’s software will prevent cooling and heating from being inadvertently enabled at the same time.
Change and Proportional Integral Modulation
When economizer “free” cooling or unit heating is required, the two MicroTech III PI loops combine for cascade-type control, providing the tightest possible zone temperature control. By controlling the discharge temperature along with the zone temperature, these functions eliminate temperature variations near the diffusers that could otherwise occur as a result of traditional zone control’s inherent lag effect.
Change: If the Control Temperatur e is above or below the set point by more than the dead band, the Change PI loop periodically adjusts the cooling temperature set point either up or down as necessary. The amount of this set point change corresponds to the Control Temperature’s position in the modulation range. The far­ther the Control Temperature is from the set point, the greater the discharge set point change will be. The Change-adjusted discharge cooling and heating set points are limited to ranges defined by keypad programmable maximum and minimum values. PI: Using the Change function’s current discharge set point, the PI function maintains precise discharge temper-
or heating discharge air
20 McQuay Catalog 860-9
MicroTech III Unit Controls
Compressor Staging
Compressor staging is controlled directly by the Control Temperature. When the Control Temperature is warmer than the zone cooling set point, cooling is staged up; when the Control Temperature is cooler than the zone cooling set point, cooling is staged down. However, a stage change can only occur when the Control Temperature is outside the dead band (see Figure 18). Staging is constrained by an inter-stage delay timer (five minute default setting) and minimum and maximum discharge air temperature limits (all keypad programmable). These constraints protect the compressors from short cycling while eliminating temperature variations near the diffusers.
Figure 18: Compressorized Logic
Project Ahead Algorithm
Because the inherent lag effect in zone temperature control applications can cause overshoot during warm-up or cool­down periods, MicroTech III features a “Project Ahead” control algorithm. Project Ahead calculates the rate at which the Control Temperature is changing and reduces the unit’s cooling or heating output as the zone temperature nears its set point, essentially eliminating overshoot.
Duct Static Pressure Control
On all VAV-DTC units, duct static pressure control is maintained by the PI algorithm, which provides precise control of the supply fan variable speed drive. The keypad programmable set point can be set between 0.20-in. W.C. and
4.00-in. W.C. On larger buildings with multiple floors, multiple trunk runs or
large shifts in load due to solar effects (east/west building orientation), an optional second duct static sensor is offered. The MicroT ech III controller automatically selects and uses the lower of the two sensed pressures to control fan volume to provide adequate static pressure to the most demanding space at all times.
Operating States
Operating states define the current overall status of the self­contained system. At the user interface, the operator can display the current operating state and thereby quickly assess the unit’s operating condition.

Alarm Management and Control

MicroTech III unit controllers are capable of sophisticated alarm management and controlled response functions. Each alarm is prioritized, indicated, and responded to with the appropriate action. The active alarm (up to 10 alarms, arranged by alarm priority) and previous alarm (up to 25 alarms, arrange by date/time cleared), each with a time and date stamp, can be displayed at the user interface. Generally speaking, whenever a current alarm is cleared, it is logged as a previous alarm and the oldest previous alarm is removed.
Alarm Priority
The various alarms that can occur are prioritized according to the severity of the problem. See Table 1. Three alarm categories are used: faults, problems, and warnings.
1 Faults are the highest priority alarms. If a fault condition
occurs, the complete unit shuts down until the alarm condition is gone and the fault is manually cleared at the keypad. A fault example is Fan Fail alarm.
2 Problems are the next lower priority to alarms. If a
problem occurs, the complete unit does not shut down, but its operation is modified to compensate for the alarm condition. A problem automatically clears when the alarm condition that caused it is gone. Compressor Fail is an example of a problem where only the affected compressor is shut down.
3 Warnings are the lowest priority alarms. No control
action is taken when a warning occurs; it is indicated to alert the operator that the alarm condition needs attention. To make sure that they are read, the operator must manually clear all warnings. Dirty Filter indication is an example of a warning.
Generally, a specific alarm condition generates an alarm that falls into only one of these categories. Under different sets of circumstances, however, the freezestat and most of the sensor failure alarm conditions can generate alarms that fall into multiple categories.
McQuay Catalog 860-9 21
MicroTech III Unit Controls
Adjustable Alarm Limits
Four alarm indications have adjustable limits that are used to trigger the alarm. The high return temperature alarm and the high and low supply temperature alarms are adjusted at the user interface. The dirty filter alarm(s) is adjusted at the sensing device.
Table 1: MicroTech III Alarm Summary
Alarm Name Fault Problem Warning
Freeze X X Smoke X
Temperature Sensor
Failure
Duct High Limit X
High Return Temperature X
High Discharge
Temperature
Low Discharge
Temperature
Fan Failure X
Fan Retry X
Discharge Air Capacity
Feedback
Economizer Stuck X X
Auxillary Control Board
Enabled
Low Airflow X
Circuit 1–8
High Pressure
Circuit 1–8
Low Pressure/Frost
Compressor 1–8 Motor
Protection
Compressor 1–8 Failure X
Airflow Switch (False Airflow)
Dirty Filter X
XX
X
X
X
X
X
X
X
X
22 McQuay Catalog 860-9

Application Considerations

Evaporator Coil
Motor
Control Panel
Airflow
24"
See Note
18"
or
24"
36"
42"
Rear Side
Front Side
Opposite
Access
Side
Access
Side
NOTE: If water and condenser drains are on the motor side, 24" is required.
This section contains basic application and installation guidelines to consider as part of the detailed analysis of any project.

General

Units are intended for use in normal heating, ventilating, and air conditioning applications. Consult your local McQuay sales representative for
• Applications involving operation at high entering con­denser water temperatures; high altitudes; or noncata­loged voltages.
• Applications requiring modified or special control sequences.
• Job-specific unit selections that fall outside of the range of the catalog tables, such as 100% outside air applica­tions.
For proper operation, rig units following instructions in IM
1032. If fire dampers are required, install them in the ductwork according to local codes. Space is not provided for these dampers in the unit.
Explicitly follow factory check, test, and start procedures for satisfactory start-up and operation (see IM 1032).
Many self-contained system applications take advantage of the significant energy savings provided by the use of economizer operation. When a water economizer system is used, mechanical refrigeration typically is not required below an entering condenser water temperature of 55°F. Standard McQuay self-contained systems are designed to operate with entering water temperatures down to 50°F when a water economizer is used and 55°F with no water economizer. For applications where a water economizer system cannot be used, a modulating head pressure control system is available to permit operation at entering condenser water temperatures below 55°F.
Application Considerations

Unit Location

The floor must be structurally strong enough to support the unit with minimum deflection (see “Unit Weights” starting on
page 66). Provide proper structural support to minimize sound
and vibration transmission. Consider a concrete floor. Extra design consideration is required when installing on a wooden structure. Install units level from front-to-back and over their length.
Locate unit fresh air intakes away from building flue stacks, exhaust ventilators, and areas containing automot i ve or other exhaust to prevent the possible introduction of contaminated air to the system. Consult code requirements for minimum fresh air volumes.
Allow sufficient space around the unit for service and maintenance clearance. Refer to Figure 19 for recommended service/maintenance clearances and “Recommended Clearances” on page 61. Locate equipment room access doors in a manner that can assist in service access if needed (e.g., coil removal). Contact your local McQuay sales representative if reduced service/maintenance clearances are required.
Where code considerations such as the NEC require extended clearances, they take precedence over minimum service/ maintenance clearances.
Figure 19: Recommended Service and Maintainance Clearances
McQuay Catalog 860-9 23
Application Considerations

Acoustical Considerations

Good acoustical design is a critical part of any successful installation and should start at the earliest stages in the design process. Each of the four common sound paths must be addressed. They are:
• Radiated sound through the casing of the unit
• Structure-borne vibration
• Airborne sound through the supply air duct
• Airborne sound through the return air duct
Basic guidelines for good acoustical performance include:
1 Always provide proper structural support under the unit. 2 Provide adequate mass in the floor structure, especially
when located over an occupied space where good acoustics are essential.
3 Seal all supply and return air duct penetrations once the
duct is installed.
4 Don’t overlook the return air path. Always include some
duct work (acoustically-lined drop down elbow) at the return inlet.
5 Minimize system static pressure losses to reduce fan
sound generation.
6 Select the appropriate unit/fan for the application. Select
fans as close as possible to their peak static efficiency . T o assist you, peak static efficiency is identified by the first system curve to the right of the shaded “Do not select” region on each fan curve. See page 54 through page 60.
7 Design duct systems to minimize turbulence. 8 Account for low frequency duct breakout noise in system
design. Route the first 20' of rectangular duct over nonsensitive areas and avoid large duct aspect ratios. Consider round or oval duct to reduce breakout.

Equipment Room

Locate the equipment room away from sound sensitive areas. Whenever possible, isolate the equipment room from these areas by locating restrooms, utility rooms, stairwells, hallways, elevators, etc. around its perimeter. This allows not only isolation from radiated sound but provides the capability to route ductwork over less sensitive areas.
Acoustically seal the equipment room with a high quality, flexible material to prevent air and noise from escaping. Even a small leak compromises the acoustic performance of the installation. Design the equipment room door to seal tightly on a perimeter gasket.
Equipment room wall construction should be concrete block or offset, double stud. The decision depends on the critical nature of the application. If offset, use double stud construction. Line the cavity with glass fiber insulation and use a double layer of wallboard on each side of the wall.

Ductwork

Fan noise travels through the ductwork to occupied spaces; it likely is the most challenging to control. Careful duct design and routing practice is required. The ASHRAE Applications Handbook discusses sound attenuation relevant to self­contained system applications. Advances in acoustical science allow for designing sound levels in a given space if equipment sound power data is available. Contact your local McQuay sales representative for sound power data for your specific application.
Return Duct
The return duct is often overlooked. Duct return air directly to the unit or into the equipment room. If ducted to the equipment room, install an elbow within the equipment room. Running a return air drop near the floor of the room provides added attenuation. Extend a length of lined ductwork from the equipment room to a length of 15 feet. The maximum recommended return air duct velocity is 1000 feet per minute.
Supply Duct
Extend a lined section of supply air duct at least 15 feet from the equipment room. Using round duct significantly reduces low frequency sound near the equipment room. If rectangular duct is used, keep the aspect ratio of the duct as small as possible. The large flat surfaces associated with large aspect ratios transmit sound to the space and increase the potential for duct generated noise such as oil canning. The maximum recommended supply air duct velocity is 2000 feet per minute.
Factory-designed and factory-built acoustic discharge plenums are available with multiple outlets to minimize difficult transitions, tight radius duct connections, and the sound compromises they can cause. Multiple factory-fabricated outlet opening sizes are available as well as multiple openings in a single plenum.
Duct Protection
An adjustable duct high limit switch is standard equipment on all SWP systems with VAV controls. This is of particular importance when using fast-acting, normally closed boxes. The switch is field adjustable; set it to meet the specific rating of the system ductwork.
24 McQuay Catalog 860-9
Application Considerations
Two-Way Head Pressure
Control Valve
Vibration Isolation
Make duct connections to the unit or to the acoustic discharge plenum with a flexible connection. Though flexible piping and electrical connections are not required, pay attention to these areas to avoid vibration transmission from outside sources to the SWP unit.

Condenser Water Piping

Always follow good industry practice in the water piping system design. Attention to water treatment and proper strainer application are always necessary. All SWP systems feature mechanically cleanable condensers and optional waterside economizer coils. T o allow periodic cleaning of the condensers and economizer coils, provide isolation valves. Condensers, economizer coils and hot water coils are provided with vent and drain connections.
Always review for possible requirements for condenser piping insulation, especially if cold entering condenser water conditions (<55°F) will be experienced.
Figure 20: Condensers

Head Pressure Control

If cold entering condenser water conditions (<55°F) will be experienced, use a waterside economizer or a condenser head pressure control valve. A two-way, head pressure activated control valve is available factory installed for these applications. The head pressure control allows entering condenser water temperatures as low as 40°F. A head pressure control valve is not required when the SWP unit is applied with a factory waterside economizer package.
Figure 21: Head Pressure Control Valves

Variable Air Volume

McQuay SWP units offer variable frequency drives for fan speed control. VFDs offer reliable operation over a wide range of airflow, with variable frequency drives offering advantages
McQuay Catalog 860-9 25
in sound and energy performance. In addition, McQuay offers the ability to sense duct static pressure in multiple locations, enhancing control accuracy and helping minimize energy use.
Application Considerations
hp2 = hp
1
density
2
density
1
rpm
2
rpm
1
3

Variable Frequency Drives

Variable frequency drives provide the most efficient means of variable volume control by taking advantage of the fan law relation between fan speed (rpm) and fan brake horsepower (bhp). Also, since airflow reduction is accomplished by changing fan speed, the noise penalties often associated with mechanical control devices, e.g., inlet vanes, are not introduced. The following equation illustrates how fan bhp varies as the cube of the change in fan speed:
In an ideal system, at 50% fan speed, brake horsepower is reduced to 12.5% of that at full speed.
Variable frequency control varies the speed of the fan by adjusting the frequency and voltage to the motor. Keeping a constant volts/frequency ratio (constant magnetic flux) to the motor allows the motor to run at its peak efficiency over a wide range of speeds and resulting fan airflow volumes.
Figure 22: Variable Frequency Drive

Duct Static Pressure Sensor Placement

Static pressure should be sensed near the end of the main duct trunk(s). Adjust the MicroTech III static pressure control so that at full airflow all of the terminals receive the minimum static pressure required plus any downstream resistance. Control is to the lowest static pressure set point that satisfies airflow requirements. Lower static pressure set points reduce fan brake horsepower requirements and fan sound generation.
Locate the static pressure sensor tap in the ductwork in an area free from turbulence effects and at least 10 duct diameters downstream and several duct diameters upstream from any major interference, including branch takeoffs. The SWP MicroTech III control system can receive a second duct static pressure sensor in installations having multiple duct trunks or significantly varying zones. The control logic maintains static pressure at both sensors.

Zone Sensor Placement

Placement of the zone temperature sensor is extremely important to provide proper and economical operation of the heating and cooling system. Generally, McQuay recommends locating the space sensor on an inside wall (3 to 5 feet from an outside wall) in a space having a floor area of at least 400 square feet. Do not locate the sensor below the outlet of a supply air diffuser, in the direct rays of the sun, on a wall adjacent to an unheated or abnormally warm room (boiler or incinerator room), or near any heat producing equipment. Where zone sensor placement is a problem, all SWP zone control systems have, as standard, the capability to use the return air sensor for heating and cooling control.

Filtration

Routinely replace filters to minimize filter loading. As filters get dirty, the filter pressure drop increases, affecting system airflow and energy requirements. The effect of filter loading is the most critical when using high efficiency filters.
When making a fan selection, include a pressure drop component in the system total static pressure to account for dirty filters. Use a value midway between clean and dirty filter ratings. If a minimum airflow is critical, make the fan selection using the higher, dirty filter pressure drop value. For VAV systems, consider setting the fan control device so part of its modulation range can be used to maintain airflow as filters become dirty. Following these recommendations should limit airflow fluctuation as the filters load.
26 McQuay Catalog 860-9
Application Considerations
Fan temperature rise =
(fan heat (MBh))
(1.085 × fan cfm)
52°F + 3°F
leaving coil temperature
fan temperature rise
= 55°F
discharge air temperature
Example:

System Operating Limits

SWP units can be applied in a wide range of system needs. High cfm/ton or high/low discharge temperature applications are available. However, for proper system operation, some application limits do apply.

Airflow

Maximum cfm limits based on coil face velocity are listed in the Physical Data tables starting on page 31.
Separate minimum design cfm limits by unit size are listed in the physical data table for constant and variable air volume applications. Limit fan modulation to 40% of the minimum design cfm limit. Minimum airflow conditions are dependent on fan selection criteria also. Contact your McQuay sales representative to answer questions on minimum airflow capability or for conditions not shown in this catalog.
VAV box minimum airflow settings should correspond with the minimum VAV fan operating point. All units are provided with multigroove, fixed pitch sheaves. During system air balance, alternate fixed pitch sheaves may be needed to match final system requirements. Alternate sheaves are available from McQuay.

Fan Heat

Sensible heat gain from the fan, fan motor, and drives occurs in all fan systems; consider its effect during equipment selection. It is an added load in cooling and an added source when in heating. The majority of the heat gain occurs through the fan itself, as the air elevates from the low-pressure side to the high-pressure side of the fan. Moving the motor out of the air stream has a negligible effect on overall fan heat gain. A unit with higher fan power requirements/higher fan heat has less net cooling capability and may not have enough left to satisfy system loads.
As a rule, typical supply fan heat gain is 3°F. However, fan heat gain can be calculated quickly once the fan is selected and the fan brake horsepower is determined. Using Figure 23, select your fan brake horsepower on the horizontal axis and move up vertically until you intersect with the heat gain curve. Then move horizontally to find the fan heat gain in MBh.
Figure 23: Fan and Motor Heat Gain
A draw-through unit has the fan located after the DX cooling coil. In this arrangement, fan heat is applied as reheat to the cold, conditioned air coming off of the coil. This arrangement has a lower sensible heat ratio and higher dehumidification capability than a blow-through coil arrangement. The discharge temperature available to the supply duct is always the sum of the coil leaving air temperature plus the fan temperature rise. Consider this when selecting the supply air volume required to satisfy space requirements.

Condenser Water Flow

System capacity tables provide selections for a condenser flow rate of 3 gpm/ton. For a given entering condenser water temperature, 3 gpm/ton provides maximum unit performance. Reducing condenser water flow rates to 2.5 or 2 gpm/ton can significantly reduce pumping energy costs and reduce piping costs. Compare and evaluate the reduction in pumping energy to the change in unit performance. Use the SWP capacity tables (Table 8, page 36) for condenser flow rates from 2 to 3 gpm/ton, using the appropriate leaving condenser water temperature column (interpolation is allowed). The minimum condenser flow rate is 2 gpm/ton.
McQuay Catalog 860-9 27
Application Considerations

Coil Freeze Protection

Always consider coil freeze protection when applying units in geographic areas that experience subfreezing temperatures. Careful design of outside air/return air mixing systems is critical to minimizing freeze potential. Some applications may require using glycol and/or preheat coils. No control sequence

Air Density Correction

Fan performance data is based on standard 70°F air temperature and zero feet altitude (sea level). For applications other than standard, multiply the density ratio to actual static pressure values. Density correction factors are expressed as a function of temperature and altitude in Table 2.
can prevent coil freezing in the event of power failure. A nonaveraging freezestat control is a factory installed
available option with hot water heat or a waterside economizer. If a potential freeze condition is sensed, unit water valves are driven to the full open position, the supply fan de­energizes, and an alarm is indicated.
In nonducted return applications, where the equipment room is the mixing plenum, consider some form of heat within the equipment room.

Unit Wiring

All units require 3-phase, 60 Hz, 208, 230, 460, or 575 volt power or 3-phase, 50 Hz, 400-volt power. Units will operate satisfactorily at ±10% of rated voltage at the power connection terminals of the unit. All units include individual branch circuit fusing of all motor loads and have a single-point power connection. A factory-mounted, nonfused disconnect switch is an available option. Install all wiring in accordance with the NEC and local codes.

Terms of Sale

All products are offered pursuant to McQuay’s standard terms and conditions of sale including limited product warranty, which can be accessed at www.McQuay.com.
Table 2: Temperature and Altitude Conversion Factors
Air
Temperature
–20ºF 1.20 1.16 1.12 1.08 1.04 1.00 0.97 0.93 0.89
0ºF 1.15 1.10 1.08 1.02 0.99 0.95 0.92 0.88 0.85 20ºF 1.11 1.06 1.02 0.98 0.95 0.92 0.88 0.85 0.82 40ºF 1.06 1.02 0.98 0.94 0.91 0.88 0.84 0.81 0.78 60ºF 1.02 0.98 0.94 0.91 0.88 0.85 0.81 0.79 0.76 70ºF 1.00 0.96 0.93 0.89 0.86 0.83 0.80 0.77 0.74 80ºF 0.98 0.94 0.91 0.88 0.84 0.81 0.78 0.75 0.72
100ºF 0.94 0.91 0.88 0.84 0.81 0.78 0.75 0.72 0.70 120ºF 0.92 0.88 0.85 0.81 0.78 0.76 0.72 0.70 0.67 140ºF 0.89 0.85 0.82 0.79 0.76 0.73 0.70 0.78 0.65
0 1000 2000 3000 4000 5000 6000 7000 8000
Altitude (ft)
28 McQuay Catalog 860-9

Selection Procedure

Achieving the optimal performance of any system requires both accurate system design and proper equipment selection. Factors that control unit selection include applicable codes, ventilation and filtration requirements, heating and cooling loads, acceptable temperature differentials, and installation limitations. McQuay SWP units offer a wide selection of component options providing the capability to meet diverse application needs.
The McQuay SelectTools ™ software selection program allows your local McQuay sales representative to provide you with a fast, accurate, and complete selection of McQuay SWP units. Unit selection also can be accomplished through reference to physical, performance, dimensional and unit weight data included in this catalog. Due to the variety of cooling system options available, only a sampling of cooling capacity data is presented here.
To properly select equipment, follow these steps:
1 Select the unit size and compressor combination. 2 Select the heating system. 3 Select the fan and motor.
The following example illustrates the catalog selection procedure.
Selection Example:
Scheduled design requirements:
Supply air volume . . . . . . . . . . . . . . . . . . . . . . . . . 21,000 cfm
Maximum face velocity . . . . . . . . . . . . . . .550 fpm is chosen*
Supply fan external . . . . . . . . . . . . . . . . . . . . . . . SP 2.00" w.g.
Altitude . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . sea level
Variable air volume system with fan speed control Hot water heat Water economizer system 4" 30% (MERV8) pleated filters 460 V/60 Hz/3 Ph Double wall construction R-410A refrigerant Premium efficiency motor *600 fpm is the design limit per page with tables starting on
page 31
Summer design:
DX coil mixed air dry bulb . . . . . . . . . . . . . . . . . . . . . . . 80°F
DX coil mixed air wet bulb . . . . . . . . . . . . . . . . . . . . . . . 67°F
Sensible load . . . . . . . . . . . . . . . . . . . . . . . . . . 575,000 Btu/hr
Total load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 750,000 Btu/hr
Supply fan sensible heat . . . . . . . . . . . . . . . . . . . . . . . . 3 °F rise
Entering condenser water . . . . . . . . . . . . . . . . . . . . . . . . . 85°F
Leaving condenser water . . . . . . . . . . . . . . . . . . . . . . . . . 95°F
Minimum condenser water . . . . . . . . . . . . . . . . . . . . . . . . 55°F
Winter design:
Return air temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . 60°F
Space heating load . . . . . . . . . . . . . . . . . . . . . . . . . 1,000-MBh
Entering hot water temperature . . . . . . . . . . . . . . . . . . . 180°F
Selection Procedure
Step 1: Unit Size Selection
Unit size is based on coil face area and cooling capacity requirements. Use supply air capacity and maximum face velocity constraints as a guide for selecting coil dimensions and cabinet size.
Based on the given data, the appropriate coil face area is determined as follows:
Minimum face area = cfm/maximum face ve locity = 21,000 cfm/550 fpm = 38.2 square feet
Note: Unit data is based on standard air conditions of 70°F at
sea level. See “Application Considerations” on page 23 for temperature/altitude conversion factors for nonstandard conditions.
Referring to the “Physical Data” tables starting on page 31, the
40.8 square foot coil of the SWP 062HSM satisfies the requirements.
Step 2: Unit DX Cooling Selection
Since the design cfm is less than the nominal value in the DX Cooling Capacity Data table, adjust the capacities per tables on starting on page 36.
cfm correction factor = design cfm/nominal cfm = 21,000 / 21,500 = 97.7%
Total heat correction multiplier = 0.995 Sensible heat correction multiplier = 0.987 Using the “Performance Data” starting on page 36, the unit
selection is a SWP 062 HS with (2) 13 hp and (2) 15 hp compressors. Unit performance from the table equals 806.0 TMBh / 587.0 SMBh at 190 gpm. Adjusting for the specified cfm yields:
Total capacity = 806.0 MBh ×0.995 = 800.9 MBh Sensible capacity = 587.0 MBh × 0.987 = 579.2 MBh Coil LAT = 80ºF – 579.0 MBh/(1.085 × 21,000
1,000
Condenser flow rate = 196 gpm × 0.995 = 195 gpm
Step 3: Economizer Capacity Selection
Determine waterside economizer capacity by referring to the appropriate table. See “Waterside Economizer Capacity” on
page 44 for 40.8 sq.ft. coil. Use entering air of 80/67°F and
entering water of 55°F at 185 gpm. Interpolating for the required gpm, economizer performance equals 497.8 TMBh /
473.0 SMBh at the unit’s nominal cfm. See tables starting on
page 45, “Waterside Economizer Capacity Correction
Factors,” to find performance at the specified cfm.
Total capacity = 415.2 MBh × 1.12 = 465.0 MBh Sensible capacity = 363.8 MBh × 1.19 = 432.9 MBh
cfm) = 54.7°F
McQuay Catalog 860-9 29
Selection Procedure
Step 4: Heating Selection
Determine hot water capacity from the tables starting on
page 45. After interpolating for the specified cfm, Table 16
indicates a capacity of 1,002.0 MBh.
Step 5: Fan/Motor Selection
Fan/motor selection is based on unit total static pressure and design airflow. Total static pressure includes the internal air pressure drops of unit components and external air pressure drops of supply and return air duct systems. See “Component Pressure Drops” starting on page 46 for internal pressure drops of unit components. Values in the table may be interpolated for the specified cfm.
Internal pressure drops:
DX coil (wet surface) . . . . . . . . . . . . . . . . . . . . . .0.80" w.g.
Economizer coil (dry surface) . . . . . . . . . . . . . . .0.49" w.g.
Hot water coil . . . . . . . . . . . . . . . . . . . . . . . . . . . .0.52" w.g.
4", 30% efficient filters . . . . . . . . . . . . . . . . . . . . .0.29" w.g.
Total internal pressure drop . . . . . . . . . . . . . . . . . .2.1" w.g.
External pressure drop:
Supply + return duct . . . . . . . . . . . . . . . . . . . . . . .2.00" w.g.
Total static pressure = internal drops + external drops
= 2.1" + 2.00" = 4.10" w.g.
Entering the fan curve for the SWP 062 HSM at 21,000 cfm and 4.10" w.g. yields 18.35 required fan brake horsepower. A 20 horsepower motor can be selected with a 33" diameter fan.
Step 6: Calculating Unit Weight
Referring to the tables starting on page 66. For an SWP 062 HS:
Unit weight: SWP basic unit . . . . . . . . . . . . . . . . . . . . . . .6179
+ 30% filters . . . . . . . . . . . . . . . . . . . . . . . . .22
+ 6-row evaporator coil . . . . . . . . . . . . . . . .668
+ economizer coil . . . . . . . . . . . . . . . . . . . .557
+ water (econ. coil). . . . . . . . . . . . . . . . . . . .250
+ hot water coil . . . . . . . . . . . . . . . . . . . . . .200
+ water (HW coil). . . . . . . . . . . . . . . . . . . . . .49
+ SAF motor. . . . . . . . . . . . . . . . . . . . . . . . .235
+ VFD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
+ SAF assembly . . . . . . . . . . . . . . . . . . . . . .592
= 8,752 lbs.
Step 7: Supply Power Wiring
Supply power wire sizing for a unit is based on the circuit with the highest amperage draw . All electrical equipment is wired to a central control panel for either single or optional dual power connections. Refer to “Electrical Data” on page 65 for FLA and RLA ratings. Determine Minimum Circuit Ampacity (MCA) as follows:
MCA = [1.25 × RLA or FLA of largest motor] + [1.00 × RLA or FLA of all other loads] + [2 amps (controls)]
RLA/FLA
(2) 13 horsepower compressors . . . . . . . . . . . . 18.3 amps each
(2) 15 horsepower compressors . . . . . . . . . . . . 18.5 amps each
25 horsepower premium efficiency
supply fan motor . . . . . . . . . . . . . . . . . . . . . . . . . 24.5 amps
MCA = [1.25×24.5 amps] + [18.3+18.3+18.5+18.5] + [2] = 106.2 amps
Note: If a unit is selected with non-concurrent electric heat,
calculate the MCA for both the heating mode and the cooling mode and the larger value used.
30 McQuay Catalog 860-9

Physical Data

Physical Data
Table 3: SWP 012 through SWP 033 Physical Data
Data
023 028 033
Compressor
Quantity 2 Size (HP) 6, 15 6, 15 10, 15 10, 15 15 (2) 15 (2) Number of refrigeration circuits 2
Evaporator coil
Coil size Standard Large Standard Large Standard Large Face area (ft
2
)
17.2 25.2 17.2 25.2 17.2 25.2 Number of rows 5 FPI 12
Performance
Total capacity Unit EER
2
1
(MBH)
312 334 357 386 411 448
14.3 14.7 13.8 14.4 13.3 14.0
Pre-heating coil
Minimum hot water coil face area (ft
2
) Available rows 1 through 12 Minimum steam coil face area (ft
2
) Available rows 1 through 4 FPI 6 through 14
Waterside economizer coil
Face area (ft
2
)
17.2 25.2 17.2 25.2 17.2 25.2 Rows 4 FPI 12 Maximum working pressure (PSIG) 300 standard, 450 optional
Face loaded filters
(Quantity) Size (9) 24 2" filter options 30% (MERV7), 75% (MERV13) 4" filter options 30% (MERV8), 75% (MERV11), 85% (MERV14) Pre-filter options 2"-30% with 4"-65%, 2"-30% with 4"-75%, 2"-30% with 4"-85%
Evaporator fan
3
Quantity 1 Available diameter (Inches) 12, 15, 18, 20, 22, 24 Maximum motor size (HP) 20 CAV minimum design (CFM) VAV minimum design (CFM) Maximum design (CFM)
4
4
4
3440 5040 3440 5040 3440 5040 6880 10080 6880 10080 6880 10080
10320 15120 10320 15120 10320 15120
Electric heat
Nominal output (kW) 34 Control sequence 2-stage
Condenser
Maximum working pressure (PSIG) 300 standard, 450 optional Mechanical cooling minimum EWT (ºF) 55 Minimum flow rate (GPM) 52 56 59 64 69 75 Maximum flow rate (GPM) 78 84 89 96 103 112
Note: 1. Based on AHRI 340/360 standard rating conditions, 80/67ºF to the coil, 85/95ºF condenser water.
2. Based on AHRI 340/360 standard rating conditions.
3. Standard fan TSP limit is 6.0 inches of water. Consult your local McQuay sales representative for applications beyond this range.
4. Minimum design airflow calculated for CAV at 200 fpm, VAV at 400 fpm and a maximum design airflow calculated at 600fpm.
Small Cabinet
19.8
19.8
×
24
McQuay Catalog 860-9 31
Physical Data
Table 4: SWP 039 through SWP 050 Physical Data
Data
039 044 050
Compressor
Quantity 3 Size (HP) 10(2), 15 10(2), 15 10, 15(2) 10(2), 15 15(3) Number of refrigeration circuits 3
Evaporator coil
Coil size Standard Large Standard Large Large Face area (ft
2
)
25.2 29.8 25.2 29.8 29.8 Number of rows 5 FPI 12
Performance
Total capacity Unit EER
2
1
(MBH)
516 535 589 645 645
14.4 14.6 14.2 14.4 13.6
Pre-heating coil
Minimum hot water coil face area (ft
2
) Available rows 1 through 12 Minimum steam coil face area (ft
2
) Available rows 1 through 4 FPI 6 through 14
Waterside economizer coil
Face area (ft
2
)
25.2 29.8 25.2 29.8 29.8 Rows 4 FPI 12 Maximum working pressure (PSIG) 300 standard, 450 optional
Face loaded filters
(Quantity) Size (9) 24 2" filter options 30% (MERV7), 75% (MERV13) 4" filter options 30% (MERV8), 75% (MERV11), 85% (MERV14) Pre-filter options 2"-30% with 4"-65%, 2"-30% with 4"-75%, 2"-30% with 4"-85%
Evaporator fan
3
Quantity 1 Available diameter (Inches) 18, 20, 22, 24, 27 Maximum motor size (HP) 20 CAV minimum design (CFM) VAV minimum design (CFM) Maximum design (CFM)
4
4
4
5040 5960 5040 5960 5960 10080 11920 10080 11920 11920 15120 17880 15120 17880 17880
Electric heat
Nominal output (kW) 34 Control sequence 2-stage
Condenser
Maximum working pressure (PSIG) 300 standard, 450 optional Mechanical cooling minimum EWT (ºF) 55 Minimum flow rate (GPM) 86 89 98 107 107 Maximum flow rate (GPM) 129 134 147 161 161
Note: 1. Based on AHRI 340/360 standard rating conditions, 80/67ºF to the coil, 85/95ºF condenser water.
2. Based on AHRI 340/360 standard rating conditions.
3. Standard fan TSP limit is 6.0 inches of water. Consult your local McQuay sales representative for
XXapplications beyond this range.
4. Minimum design airflow calculated for CAV at 200 fpm, VAV at 400 fpm and a maximum design airflow XXcalculated at 600fpm.
Small Tall Cabinet
19.8
19.8
×
24
32 McQuay Catalog 860-9
Physical Data
Table 5: SWP 044 through SWP 055 Physical Data
Data
044 050 056 062 065
Compressor
Quantity 3 4 Size (HP) 10(2), 15 (3)15 (4)13 13(2), 15(2) 15(4) Number of refrigeration circuits 3 4
Evaporator coil
Coil size Standard Standard Large Standard Large Standard Large Standard Large Face area (ft
2
)
40.8 40.8 45.8 40.8 45.8 40.8 45.8 40.8 45.8 Number of rows 5 FPI 12
Performance
Total capacity Unit EER
2
1
(MBH)
624 690 705 774 792 816 834 865 884
14.5 14.2 14.3 14.8 14.9 14.2 14.3 13.8 14.0
Pre-heating coil
Minimum hot water coil face area (ft
2
) Available rows 1 through 12 Minimum steam coil face area (ft
2
) Available rows 1 through 4 FPI 6 through 14
Waterside economizer coil
Face area (ft
2
)
40.8 40.8 45.8 40.8 45.8 40.8 45.8 40.8 45.8 Rows 4 FPI 12 Maximum working pressure (PSIG) 300 standard, 450 optional
Face loaded filters
(Quantity) Size (4) 12 2" filter options 30% (MERV7), 75% (MERV13) 4" filter options 30% (MERV8), 75% (MERV11), 85% (MERV14) Pre-filter options 2"-30% with 4"-65%, 2"-30% with 4"-75%, 2"-30% with 4"-85%
Evaporator fan
3
Quantity 1 Available diameter (Inches) 18, 20, 22, 24, 27, 30, 33, 37 Maximum motor size (HP) 40 CAV minimum design (CFM) VAV minimum design (CFM) Maximum design (CFM)
4
4
4
8160 8160 9160 8160 9160 8160 9160 8160 9160 16320 16320 18320 16320 18320 16320 18320 16320 18320 24480 24480 27480 24480 27480 24480 27480 24480 27480
Electric heat
Nominal output (kW) Control sequence 2-stage
Condenser
Maximum working pressure (PSIG) 300 standard, 450 optional Mechanical cooling minimum EWT (ºF) 55 Minimum flow rate (GPM) 104 115 118 129 132 136 139 144 147 Maximum flow rate (GPM) 156 173 176 194 198 204 209 216 221
Note: 1. Based on AHRI 340/360 standard rating conditions, 80/67ºF to the coil, 85/95ºF condenser water.
2. Based on AHRI 340/360 standard rating conditions.
3. Standard fan TSP limit is 6.0 inches of water. Consult your local McQuay sales representative for applications beyond this range.
4. Minimum design airflow calculated for CAV at 200 fpm, VAV at 400 fpm and a maximum design airflow calculated at 600fpm.
5. Available for 460 volt and 575 volt units only
Medium Cabinet
32.25
32.25
×
24 and (12) 24×24
5
34, 68
McQuay Catalog 860-9 33
Physical Data
Table 6: SWP 062 through SWP 088 Physical Data
Data
062 073 080 088
Compressor
Quantity 4 6 Size (HP) 13(2), 15(2) 10(4), 13(2) 10(2), 13(4) 13(6) Number of refrigeration circuits 4 6
Evaporator coil
Coil size Standard Face area (ft
2
) Number of rows 5 6 FPI 12
Performance
Total capacity Unit EER
2
1
(MBH)
866 1021 1093 1164
14.6 14.1 14.6 14.4
Pre-heating coil
Minimum hot water coil face area (ft
2
) Available rows 1 through 12 Minimum steam coil face area (ft
2
) Available rows 1 through 4 FPI 6 through 14
Waterside economizer coil
Face area (ft
2
) Rows 4 FPI 12 Maximum working pressure (PSIG) 300 standard, 450 optional
Face loaded filters
(Quantity) Size ( 5) 12 2" filter options 30% (MERV7), 75% (MERV13) 4" filter options 30% (MERV8), 75% (MERV11), 85% (MERV14) Pre-filter options 2"-30% with 4"-65%, 2"-30% with 4"-75%, 2"-30% with 4"-85%
Evaporator fan
3
Quantity 1 Available diameter (Inches) 22, 24, 27, 30, 33, 37 Maximum motor size (HP) 50 CAV minimum design (CFM) VAV minimum design (CFM) Maximum design (CFM)
4
4
4
Electric heat
Nominal output (kW) 68 Control sequence 2-stage
Condenser
Maximum working pressure (PSIG) 300 standard, 450 optional Mechanical cooling minimum EWT (ºF) 55 Minimum flow rate (GPM) 144 170 182 194 Maximum flow rate (GPM) 217 255 573 291
Note: 1. Based on AHRI 340/360 standard rating conditions, 80/67ºF to the coil, 85/95ºF condenser water.
2. Based on AHRI 340/360 standard rating conditions.
3. Standard fan TSP limit is 6.0 inches of water. Consult your local McQuay sales representative for XXapplications beyond this range.
4. Minimum design airflow calculated for CAV at 200 fpm, VAV at 400 fpm and a maximum design airflow XXcalculated at 600fpm.
Large Cabinet
52.5
36, 67
36, 67
52.5
×
24 and (15) 24×24
10500 21000 31500
34 McQuay Catalog 860-9
Physical Data
Table 7: SWP 065 through SWP 130 Physical Data
Data
065 073 080 088 099 105 120 130
Compressor
Quantity 4 6 8 Size (HP) 15(4)
10(4),
13(2)
10(2),
13(4)
13(6) 15(6) 13(8) 13(4), 15(4) 15(8)
Number of refrigeration circuits 4 6 8
Evaporator coil
Coil size Std StdLgStdLgStdLgStdLg Face area (ft
2
)
60.9 60.9 71.3 60.9 71.3 60.9 71.3 60.9 71.3 Number of rows 6 FPI 12
Performance
Total capacity Unit EER
2
1
(MBH)
946 1052 1128 1202 1343 1381 1451 1527 1526 1606 1621 1701
14.5 15.1 14.9 14.7 13.7 14.0 13.6 14.3 13.2 13.7 12.8 13.3
Pre-heating coil
Minimum hot water coil face area (ft
2
) Available rows 1 through 12 Minimum steam coil face area (ft
2
) Available rows 1 through 4 FPI 6 through 14
Waterside economizer coil
Face area (ft
2
)
60.9 60.9 71.3 60.9 71.3 60.9 71.3 60.9 71.3 Rows 4 FPI 12 Maximum working pressure (PSIG) 300 standard, 450 optional
Face loaded filters
(Quantity) Size (20) 24 2" filter options 30% (MERV7), 75% (MERV13) 4" filter options 30% (MERV8), 75% (MERV11), 85% (MERV14) Pre-filter options 2"-30% with 4"-65%, 2"-30% with 4"-75%, 2"-30% with 4"-85%
Evaporator fan
3
Quantity 1 Available diameter (Inches) 24, 27, 30, 33, 37, 40, 44 Maximum motor size (HP) 50 CAV minimum design (CFM) VAV minimum design (CFM) Maximum design (CFM)
4
4
4
12180 12180 14260 12180 14260 12180 14260 12180 14260 24360 24360 28520 24360 28520 24360 28520 24360 28520 36540 36540 42780 36540 42780 36540 42780 36540 42780
Electric heat
Nominal output (kW) 68 Control sequence 2-stage
Condenser
Maximum working pressure (PSIG) 300 standard, 450 optional Mechanical cooling minimum EWT (ºF) 55 Minimum flow rate (GPM) 158 175 188 200 224 230 242 254 254 268 270 284 Maximum flow rate (GPM) 237 263 282 300 336 345 363 382 382 402 405 425
Note: 1. Based on AHRI 340/360 standard rating conditions, 80/67ºF to the coil, 85/95ºF condenser water.
2. Based on AHRI 340/360 standard rating conditions.
3. Standard fan TSP limit is 6.0 inches of water. Consult your local McQuay sales representative for applications beyond this range.
4. Minimum design airflow calculated for CAV at 200 fpm, VAV at 400 fpm and a maximum design airflow calculated at 600fpm.
Large Tall Cabinet
45.83
45.83
×
24
McQuay Catalog 860-9 35

Performance Data

Performance Data

DX Cooling Capacity Data

Table 8: SWP 012–SWP033 (Small Cabinet) Cooling Capacity
EAT
Unit
SWP 023HS DB/WB (ºF) EWB (ºF) TMBH SMBH LDB LWB GPM
6 hp & 13 hp Compressors
5-row Standard DX Coil
8,000 cfm
410 A
SWP 023HL DB/WB (ºF) EWB (ºF) TMBH SMBH LDB LWB GPM
6 hp & 13 hp Compressors
5-row Large DX Coil
8,300 cfm
410 A
SWP 028HS DB/WB (ºF) EWB (ºF) TMBH SMBH LDB LWB GPM
10 hp& 15 hp Compressors
5-row Standard DX Coil
59,500 cfm
410 A
SWP 028HL DB/WB (ºF) EWB (ºF) TMBH SMBH LDB LWB GPM
10 hp & 15 hp Compressors
5-row Large DX Coil
9,800 cfm
410 A
SWP 033HS DB/WB (ºF) EWB (ºF) TMBH SMBH LDB LWB GPM
2 × 15 hp Compressors 5-row Standard DX Coil
10,500 cfm
410 A
SWP 033HL DB/WB (ºF) EWB (ºF) TMBH SMBH LDB LWB GPM
2 × 15 hp Compressors
5-row Large DX Coil
11,500 cfm
410 A
Note: See Table 14, page 45 to determine unit capacity at other than nominal cfm.
For a computer-generated, job-specific selection, contact your local McQuay sales representative. For 50 Hz applications, derate the total capacity by
0.89; derate the sensible capacity by 0.94. All capacities are gross and do not account for fan motor heat. Altitude and/or glycol selections are also available.
DB/WB Total Sensible DB WB
(ºF) (ºF) (MBH) (MBH) (ºF) (ºF) (GPM)
75.0/62.0
80.0/67.0
85.0/72.0
75.0/62.0
80.0/67.0
85.0/72.0
75.0/62.0
80.0/67.0
85.0/72.0
75.0/62.0
80.0/67.0
85.0/72.0
75.0/62.0
80.0/67.0
85.0/72.0
75.0/62.0
80.0/67.0
85.0/72.0
EWT
75 291 228 48.9 48.9 87 85 279 223 49.5 49.5 85 95 266 217 50.2 50.1 84 75 318 226 54.2 54.1 94 85 305 221 54.8 54.7 92 95 291 215 55.4 55.4 90 75 346 223 59.5 59.5 102 85 332 218 60.1 60.1 100 95 316 212 60.8 60.7 97
75 298 236 49.1 49.1 71 85 285 230 49.7 49.7 70 95 272 224 50.4 50.3 68 75 325 233 54.3 54.3 77 85 311 227 55.0 54.9 75 95 296 221 55.6 55.6 74 75 353 230 59.7 59.7 83 85 338 224 60.3 60.3 81 95 321 218 61.0 60.9 79
75 338 267 49.3 49.2 81 85 325 261 49.9 49.7 80 95 309 254 50.5 50.4 79 75 369 264 54.5 54.4 88 85 354 258 55.1 55.0 86 95 337 252 55.8 55.6 85 75 401 261 59.9 59.8 95 85 385 255 60.5 60.3 93 95 367 249 61.1 60.9 91
75 350 277 49.2 49.1 84 85 335 270 49.8 49.7 82 95 320 263 50.4 50.3 81 75 381 274 54.4 54.4 90 85 365 268 55.0 55.0 89 95 348 261 55.7 55.6 87 75 414 270 59.8 59.8 97 85 396 264 60.3 60.3 95 95 378 257 61.0 60.9 94
75 394 304 48.6 48.4 95 85 379 297 49.2 49.0 94 95 361 289 49.9 49.7 92 75 431 301 53.7 53.6 103 85 413 294 54.4 54.2 103 95 394 286 55.1 54.9 100 75 468 296 59.1 59.0 112 85 449 290 59.7 59.6 109 95 429 282 60.4 60.3 107
75 414 326 49.1 49.0 100 85 397 318 49.7 49.6 98 95 379 310 50.3 50.3 96 75 452 323 54.4 54.3 108 85 433 315 54.9 54.9 106 95 413 307 55.6 55.5 104 75 491 318 59.7 59.7 116 85 470 310 60.3 60.2 114 95 448 302 60.9 60.9 111
Capacity LAT
Flow Rate
36 McQuay Catalog 860-9
Performance Data
Table 9: SWP 039–SWP050 (Small Tall Cabinet) Cooling Capacity
EAT
Unit
SWP 039HS DB/WB (ºF) EWB (ºF) TMBH SMBH LDB LWB GPM
(2) 10 hp, 15 hp Compressors
5-row Standard DX Coil
13,500 cfm
410 A
SWP 039HL DB/WB (ºF) EWB (ºF) TMBH SMBH LDB LWB GPM
(2) 10 hp, 15 hp Compressors
5-row Large DX Coil
14,000 cfm
410 A
SWP 044HS DB/WB (ºF) EWB (ºF) TMBH SMBH LDB LWB GPM
10 hp, (2) 15 hp Compressors
5-row Standard DX Coil
15,000 cfm
410 A
SWP 044HL DB/WB (ºF) EWB (ºF) TMBH SMBH LDB LWB GPM
10 hp, (2) 15 hp Compressors
5-row Large DX Coil
15,500 cfm
410 A
SWP 050HL DB/WB (ºF) EWB (ºF) TMBH SMBH LDB LWB GPM
(32) 15 hp Compressors
5-row Large DX Coil
17,000 cfm
410 A
Note: See Table 14, page 45 to determine unit capacity at other than nominal cfm.
For a computer-generated, job-specific selection, contact your local McQuay sales representative. For 50 Hz applications, derate the total capacity by
0.89; derate the sensible capacity by 0.94. All capacities are gross and do not account for fan motor heat. Altitude and/or glycol selections are also available.
DB/WB Total Sensible DB WB
(ºF) (ºF) (MBH) (MBH) (ºF) (ºF) (GPM)
75.0/62.0
80.0/67.0
85.0/72.0
75.0/62.0
80.0/67.0
85.0/72.0
75.0/62.0
80.0/67.0
85.0/72.0
75.0/62.0
80.0/67.0
85.0/72.0
75.0/62.0
80.0/67.0
85.0/72.0
EWT
75 491 383 49.0 48.8 118 85 471 374 49.6 49.4 116 95 449 365 50.3 50.1 114 75 531 379 54.3 54.2 126 85 510 370 54.9 54.8 124 95 486 360 55.6 55.4 122 75 576 373 59.7 59.6 136 85 552 364 60.3 60.2 133 95 526 355 60.9 60.8 130
75 502 395 49.2 49.1 120 85 481 386 49.8 49.6 118 95 459 376 50.5 50.3 116 75 542 390 54.5 54.5 129 85 520 381 55.1 55.0 126 95 496 371 55.8 55.6 124 75 586 383 60.0 59.9 138 85 563 375 60.5 60.4 135 95 536 365 61.1 61.0 133
75 548 426 49.0 48.7 132 85 527 416 49.6 49.3 130 95 503 405 50.3 50.0 128 75 594 422 54.3 54.1 142 85 571 412 54.9 54.7 139 95 545 401 55.5 55.3 137 75 643 415 59.7 59.5 152 85 617 406 60.3 60.1 150 95 589 395 60.9 60.7 146
75 561 439 49.1 48.9 135 85 539 429 49.7 49.5 133 95 514 418 50.4 50.1 130 75 607 434 54.4 54.3 145 85 583 424 55.0 54.8 142 95 557 413 55.6 55.4 139 75 657 427 59.8 59.9 155 85 630 417 60.4 60.3 152 95 601 406 61.0 60.9 149
75 623 483 49.0 48.7 150 85 598 472 49.6 49.3 148 95 571 459 50.3 49.9 145 75 675 478 54.3 54.1 161 85 648 466 54.9 54.7 158 95 618 454 55.6 55.3 155 75 729 470 59.7 59.6 173 85 699 459 60.3 60.1 170 95 667 447 60.9 60.7 166
Capacity LAT
Flow Rate
McQuay Catalog 860-9 37
Performance Data
Table 10: SWP 044–SWP065 (Medium Cabinet) Cooling Capacity
EAT
Unit
SWP 044HS DB/WB (ºF) EWB (ºF) TMBH SMBH LDB LWB GPM
(2) 10 hp, 15 hp Compressors
5-row Standard DX Coil
16,000 cfm
410 A
SWP 050HS DB/WB (ºF) EWB (ºF) TMBH SMBH LDB LWB GPM
(3) 15 hp Compressors 5-row Standard DX Coil
17,500 cfm
410 A
SWP 050HL DB/WB (ºF) EWB (ºF) TMBH SMBH LDB LWB GPM
(3) 15 hp Compressors
5-row Large DX Coil
18,000 cfm
410 A
SWP 056HS DB/WB (ºF) EWB (ºF) TMBH SMBH LDB LWB GPM
(4) 13 hp Compressors 5-row Standard DX Coil
20,500 cfm
410 A
SWP 056HL DB/WB (ºF) EWB (ºF) TMBH SMBH LDB LWB GPM
(4) 13 hp Compressors
5-row Large DX Coil
20,500 cfm
410 A
Note: See Table 14, page 45 to determine unit capacity at other than nominal cfm.
For a computer-generated, job-specific selection, contact your local McQuay sales representative. For 50 Hz applications, derate the total capacity by
0.89; derate the sensible capacity by 0.94. All capacities are gross and do not account for fan motor heat. Altitude and/or glycol selections are also available.
DB/WB Total Sensible DB WB
(ºF) (ºF) (MBH) (MBH) (ºF) (ºF) (GPM)
75.0/62.0
80.0/67.0
85.0/72.0
75.0/62.0
80.0/67.0
85.0/72.0
75.0/62.0
80.0/67.0
85.0/72.0
75.0/62.0
80.0/67.0
85.0/72.0
75.0/62.0
80.0/67.0
85.0/72.0
EWT
75 583 457 48.9 48.8 139 85 559 446 49.5 49.4 137 95 532 434 50.2 50.1 134 75 630 450 54.3 54.2 150 85 605 440 54.9 54.8 147 95 576 428 55.5 55.4 144 75 680 442 59.7 59.7 160 85 652 432 60.3 60.2 157 95 621 421 60.9 60.9 154
75 592 479 50.0 49.9 140 85 568 468 50.5 50.4 138 95 541 456 51.2 51.0 136 75 639 475 55.3 55.3 150 85 613 462 55.9 55.8 148 95 584 450 56.5 56.4 145 75 691 464 60.7 60.7 161 85 663 455 61.2 61.2 158 95 631 444 61.8 61.8 155
75 656 513 48.9 48.8 157 85 629 501 49.6 49.4 154 95 599 487 50.2 50.1 151 75 710 506 54.3 54.4 169 85 681 494 54.9 54.8 166 95 648 481 55.6 55.4 162 75 766 497 59.7 59.7 181 85 734 486 60.3 60.2 177 95 699 473 61.0 60.9 173
75 729 576 49.3 49.2 174 85 699 563 49.9 49.8 171 95 667 548 50.5 50.4 168 75 794 571 54.5 54.5 188 85 759 556 55.2 55.1 184 95 723 542 55.8 55.7 180 75 864 563 59.9 59.8 203 85 825 549 60.5 60.4 198 95 784 534 61.2 61.1 193
75 736 580 49.1 49.0 175 85 705 566 49.8 49.6 172 95 673 552 60.4 50.3 169 75 801 574 54.4 54.3 189 85 766 560 55.0 55.0 185 95 729 545 55.7 55.6 181 75 872 566 59.8 59.7 204 85 832 552 60.4 60.3 199 95 790 537 61.0 61.0 194
Capacity LAT
Flow Rate
38 McQuay Catalog 860-9
Performance Data
Table 10: SWP 044–SWP065 (Medium Cabinet) Cooling Capacity
SWP 062HS DB/WB (ºF) EWB (ºF) TMBH SMBH LDB LWB GPM
75 773 608 49.1 49.0 186
75.0/62.0
(2) 13 hp, (2) 15 hp Compressors
5-row Standard DX Coil
21,500 cfm
410 A
SWP 062HL DB/WB (ºF) EWB (ºF) TMBH SMBH LDB LWB GPM
(2) 13 hp, (2) 15 hp Compressors
5-row Large DX Coil
21,500 cfm
410 A
SWP 065HS DB/WB (ºF) EWB (ºF) TMBH SMBH LDB LWB GPM
(4) 15 hp Compressors 5-row Standard DX Coil
22,750 cfm
410 A
SWP 065HL DB/WB (ºF) EWB (ºF) TMBH SMBH LDB LWB GPM
(4) 15 hp Compressors
5-row Large DX Coil
23,000 cfm
410 A
Note: See Table 14, page 45 to determine unit capacity at other than nominal cfm.
For a computer-generated, job-specific selection, contact your local McQuay sales representative. For 50 Hz applications, derate the total capacity by
0.89; derate the sensible capacity by 0.94. All capacities are gross and do not account for fan motor heat. Altitude and/or glycol selections are also available.
80.0/67.0
85.0/72.0
75.0/62.0
80.0/67.0
85.0/72.0
75.0/62.0
80.0/67.0
85.0/72.0
75.0/62.0
80.0/67.0
85.0/72.0
85 741 594 49.7 49.6 182 95 707 579 50.4 50.2 179 75 842 602 54.4 54.3 200 85 806 587 55.0 54.9 196 95 768 572 55.7 55.5 192 75 915 593 59.8 59.7 216 85 875 579 60.4 60.3 211 95 833 564 61.0 60.9 206
75 783 619 49.3 49.2 188 85 751 605 49.9 49.8 184 95 717 589 50.5 50.4 181 75 852 612 54.5 54.5 202 85 816 598 55.2 55.1 198 95 777 582 55.8 55.7 194 75 926 604 59.9 59.8 219 85 885 589 60.5 60.4 213 95 842 574 61.2 61.1 208
75 825 646 49.0 48.9 199 85 792 631 49.6 49.5 195 95 756 615 50.3 50.1 192 75 896 638 54.3 54.2 214 85 859 624 54.9 54.8 210 95 819 607 55.6 55.4 206 75 972 629 59.7 59.6 231 85 931 614 60.3 60.2 221 95 887 598 61.0 60.8 221
75 835 654 49.0 48.9 201 85 801 639 49.6 49.5 197 95 765 622 50.3 50.1 194 75 906 646 54.3 54.2 216 85 869 631 54.9 54.8 212 95 828 615 55.6 55.4 208 75 982 636 59.7 59.6 233 85 941 621 60.3 60.2 228 95 896 605 60.9 60.8 223
McQuay Catalog 860-9 39
Performance Data
Table 11: SWP 062–SWP088 (Large Cabinet) Cooling Capacity
EAT
Unit
SWP 062HS DB/WB (ºF) EWB (ºF) TMBH SMBH LDB LWB GPM
(2) 13 hp, (2)15 hp Compressors
5-row Standard DX Coil
22,000 cfm
410 A
SWP 073HS DB/WB (ºF) EWB (ºF) TMBH SMBH LDB LWB GPM
(4) 13 hp, (2) 15 hp Compressors
6-row Standard DX Coil
27,000 cfm
410 A
SWP 080HS DB/WB (ºF) EWB (ºF) TMBH SMBH LDB LWB GPM
(2) 13 hp, (4) 15 hp Compressors
6-row Standard DX Coil
29,000 cfm
410 A
SWP 088HS DB/WB (ºF) EWB (ºF) TMBH SMBH LDB LWB GPM
6 hp & 13 hp Compressors
6-row Standard DX Coil
31,000 cfm
410 A
Note: See Table 14, page 45 to determine unit capacity at other than nominal cfm.
For a computer-generated, job-specific selection, contact your local McQuay sales representative. For 50 Hz applications, derate the total capacity by
0.89; derate the sensible capacity by 0.94. All capacities are gross and do not account for fan motor heat. Altitude and/or glycol selections are also available.
DB/WB Total Sensible DB WB
(ºF) (ºF) (MBH) (MBH) (ºF) (ºF) (GPM)
75.0/62.0
80.0/67.0
85.0/72.0
75.0/62.0
80.0/67.0
85.0/72.0
75.0/62.0
80.0/67.0
85.0/72.0
75.0/62.0
80.0/67.0
85.0/72.0
EWT
75 799 627 48.9 48.9 191 85 765 612 49.6 49.5 187 95 729 596 50.2 50.1 184 75 868 620 54.2 54.2 206 85 830 604 54.9 54.8 202 95 790 588 55.5 55.5 197 75 943 610 59.6 59.6 222 85 900 595 60.3 60.2 217 95 855 579 60.9 60.9 211
75 969 765 49.1 49.0 230 85 928 747 49.7 49.6 226 95 884 727 50.4 50.3 221 75 1048 754 54.5 54.4 247 85 1004 737 55.0 55.0 242 95 957 718 55.7 55.6 237 75 1133 742 59.9 59.9 265 85 1085 724 60.5 60.4 259 95 1032 706 61.1 61.1 253
75 1046 823 49.0 48.9 248 85 1001 803 49.7 49.6 244 95 953 782 50.3 50.2 239 75 1134 813 54.4 54.3 267 85 1085 793 55.0 54.9 262 95 1033 772 55.6 55.5 256 75 1227 800 59.8 59.7 287 85 1173 780 60.4 60.3 281 95 1116 760 61.0 61.0 274
75 1122 881 49.0 48.9 267 85 1074 860 49.6 49.5 262 95 1024 837 50.3 50.1 257 75 1218 871 54.3 54.2 287 85 1165 850 54.9 54.8 281 95 1110 827 55.6 55.5 275 75 1320 858 59.7 59.6 309 85 1261 836 60.3 60.3 302 95 1200 814 61.0 60.9 295
Capacity LAT
Flow Rate
40 McQuay Catalog 860-9
Performance Data
Table 12: SWP 065–SWP130 (Large Tall Cabinet) Cooling Capacity
EAT
Unit
SWP 065HS DB/WB (ºF) EWB (ºF) TMBH SMBH LDB LWB GPM
(4) 15 hp Compressors 6-row Standard DX Coil
24,000 cfm
410 A
SWP 073HS DB/WB (ºF) EWB (ºF) TMBH SMBH LDB LWB GPM
(4) 10 hp, (2) 13 hp Compressors
6-row Standard DX Coil
27,500 cfm
410 A
SWP 080HL DB/WB (ºF) EWB (ºF) TMBH SMBH LDB LWB GPM
(2) 10 hp, (4) 13 hp Compressors
6-row Standard DX Coil
29,500 cfm
410 A
SWP 088HS DB/WB (ºF) EWB (ºF) TMBH SMBH LDB LWB GPM
(6) 13 hp Compressors 6-row Standard DX Coil
31,500 cfm
410 A
SWP 099HS DB/WB (ºF) EWB (ºF) TMBH SMBH LDB LWB GPM
(6) 15 hp Compressors
6-row Large DX Coil
36,250 cfm
410 A
Note: See Table 14, page 45 to determine unit capacity at other than nominal cfm.
For a computer-generated, job-specific selection, contact your local McQuay sales representative. For 50 Hz applications, derate the total capacity by
0.89; derate the sensible capacity by 0.94. All capacities are gross and do not account for fan motor heat. Altitude and/or glycol selections are also available.
DB/WB Total Sensible DB WB
(ºF) (ºF) (MBH) (MBH) (ºF) (ºF) (GPM)
75.0/62.0
80.0/67.0
85.0/72.0
75.0/62.0
80.0/67.0
85.0/72.0
75.0/62.0
80.0/67.0
85.0/72.0
75.0/62.0
80.0/67.0
85.0/72.0
75.0/62.0
80.0/67.0
85.0/72.0
EWT
75 868 682 49.0 48.9 208 85 832 666 49.6 49.5 204 95 794 649 50.3 50.2 200 75 940 673 54.3 54.3 224 85 900 657 55.0 54.9 219 95 856 640 55.6 55.6 214 75 1017 662 59.8 59.7 241 85 973 646 60.4 60.3 235 95 925 629 61.0 61.0 229
75 983 778 49.1 49.1 233 85 941 759 49.7 49.7 229 95 896 739 50.4 50.3 224 75 1050 761 54.6 54.6 24.7 85 1018 749 55.1 55.1 245 95 969 730 55.7 55.7 240 75 1148 754 59.9 59.9 268 85 1099 736 60.5 60.5 262 95 1046 717 61.2 61.1 256
75 1062 837 49.0 49.0 252 85 1016 817 49.7 49.6 247 95 967 795 50.4 50.3 242 75 1151 827 54.4 54.3 271 85 1101 806 55.0 54.9 265 95 1047 785 55.7 55.6 259 75 1245 813 59.8 59.8 291 85 1190 793 60.4 60.4 284 95 1132 773 61.1 61.0 277
75 1140 897 49.0 48.9 271 85 1091 874 49.6 49.5 265 95 1039 851 50.3 50.2 260 75 1238 886 54.3 54.2 292 85 1183 864 54.9 54.9 285 95 1126 841 55.6 55.5 279 75 1340 872 59.7 59.7 314 85 1280 850 60.3 60.3 306 95 1217 828 61.0 60.9 299
75 1297 1024 49.2 49.0 311 85 1244 1000 49.8 49.6 306 95 1186 974 50.4 50.3 300 75 1403 1010 54.5 54.4 334 85 1346 987 55.1 55.0 328 95 1282 961 55.8 55.6 321 75 1514 992 60.0 59.9 358 85 1451 969 60.6 60.5 351 95 1382 945 61.2 61.1 343
Capacity LAT
Flow Rate
McQuay Catalog 860-9 41
Performance Data
Table 12: SWP 065–SWP130 (Large Tall Cabinet) Cooling Capacity
SWP 099HL DB/WB (ºF) EWB (ºF) TMBH SMBH LDB LWB GPM
75 1313 1032 49.0 48.9 314
75.0/62.0
(6) 15 hp Compressors
6-row Large DX Coil
36,250 cfm
410 A
SWP 105HS DB/WB (ºF) EWB (ºF) TMBH SMBH LDB LWB GPM
(8) 13 hp Compressors 6-row Standard DX Coil
36,500 cfm
410 A
SWP 105HL DB/WB (ºF) EWB (ºF) TMBH SMBH LDB LWB GPM
(8) 13 hp Compressors
6-row Large DX Coil
41,000 cfm
410 A
SWP 120HS DB/WB (ºF) EWB (ºF) TMBH SMBH LDB LWB GPM
(4) 13 hp, (4) 15 hp Compressors
6-row Standard DX Coil
36,500 cfm
410 A
SWP 120HL DB/WB (ºF) EWB (ºF) TMBH SMBH LDB LWB GPM
(4) 13 hp, (4) 15 hp Compressors
6-row Large DX Coil
42,000 cfm
410 A
Note: See Table 14, page 45 to determine unit capacity at other than nominal cfm.
For a computer-generated, job-specific selection, contact your local McQuay sales representative. For 50 Hz applications, derate the total capacity by
0.89; derate the sensible capacity by 0.94. All capacities are gross and do not account for fan motor heat. Altitude and/or glycol selections are also available.
80.0/67.0
85.0/72.0
75.0/62.0
80.0/67.0
85.0/72.0
75.0/62.0
80.0/67.0
85.0/72.0
75.0/62.0
80.0/67.0
85.0/72.0
75.0/62.0
80.0/67.0
85.0/72.0
85 1259 1008 49.6 49.5 309 95 1200 982 50.2 50.1 303 75 1420 1018 54.3 54.3 338 85 1362 994 54.9 54.8 331 95 1297 969 55.6 55.5 324 75 1531 999 59.8 59.8 362 85 1468 976 60.4 60.3 355 95 1398 952 61.0 60.9 346
75 1390 1070 48.2 48.1 333 85 1334 1045 48.8 48.8 328 95 1275 1018 49.5 49.4 323 75 1517 1060 53.5 53.4 360 85 1454 1034 54.1 54.1 353 95 1387 1007 54.8 54.7 347 75 1654 1046 58.8 58.8 390 85 1583 1020 59.4 59.4 381 95 1508 993 60.1 60.1 373
75 1470 1161 49.1 49.1 350 85 1407 1132 49.7 49.7 344 95 1341 1103 50.4 50.3 337 75 1600 1148 54.4 54.3 378 85 1528 1119 55.0 55.0 369 95 1452 1090 55.7 55.6 361 75 1741 1133 59.7 59.7 408 85 1660 1104 60.4 60.3 398 95 1576 1074 61.1 61.0 388
75 1458 1101 47.4 47.4 352 85 1401 1075 48.1 48.0 347 95 1339 1047 48.8 48.7 342 75 1592 1091 52.7 52.6 381 85 1528 1064 53.3 53.3 374 95 1459 1036 54.0 54.0 368 75 1736 1076 58.0 58.0 412 85 1664 1050 58.7 58.7 403 95 1586 1021 59.4 59.4 395
75 1547 1208 48.7 48.7 371 85 1481 1178 49.4 49.3 364 95 1411 1147 50.0 50.0 357 75 1685 1195 54.0 53.9 401 85 1611 1165 54.6 54.6 392 95 1533 1134 55.3 55.3 384 75 1833 1178 59.4 59.3 433 85 1750 1148 60.0 60.0 422 95 1663 1117 60.7 60.6 412
42 McQuay Catalog 860-9
Performance Data
Table 12: SWP 065–SWP130 (Large Tall Cabinet) Cooling Capacity
SWP 130HS DB/WB (ºF) EWB (ºF) TMBH SMBH LDB LWB GPM
75 1546 1142 46.4 46.3 375
75.0/62.0
(8) 15 hp Compressors 6-row Standard DX Coil
36,500 cfm
410 A
SWP 130HL DB/WB (ºF) EWB (ºF) TMBH SMBH LDB LWB GPM
(8) 15 hp Compressors
6-row Large DX Coil
42,000 cfm
410 A
Note: See Table 14, page 45 to determine unit capacity at other than nominal cfm.
For a computer-generated, job-specific selection, contact your local McQuay sales representative. For 50 Hz applications, derate the total capacity by
0.89; derate the sensible capacity by 0.94. All capacities are gross and do not account for fan motor heat. Altitude and/or glycol selections are also available.
80.0/67.0
85.0/72.0
75.0/62.0
80.0/67.0
85.0/72.0
85 1488 1115 47.1 47.0 370 95 1423 1085 47.8 47.7 364 75 1687 1131 51.7 51.6 405 85 1622 1103 52.4 52.3 399 95 1550 1073 47.8 47.8 364 75 1835 1114 57.1 57.1 438 85 1763 1087 57.8 57.7 429 95 1683 1057 58.5 58.5 422
75 1637 1248 47.8 47.8 394 85 1569 1217 48.5 48.4 387 95 1495 1184 49.2 49.2 380 75 1781 1234 53.1 53.1 426 85 1706 1203 53.8 53.8 409 95 1624 1170 54.5 54.5 409 75 1934 1215 58.5 58.5 459 85 1851 1185 59.2 59.2 449 95 1761 1152 59.9 59.9 439
McQuay Catalog 860-9 43
Performance Data

Waterside Economizer Capacity

Table 13: Waterside Economizer Coil Face Area
17.2 Square Feet 25.2 Square Feet
Nominal
EWT EAT
DB/WB
(ºF)
(ºF) (Btu/hr) (Btu/hr) (Btu/hr) (Btu/hr) (ºF) (Btu/hr) (Btu/hr) (Btu/hr) (Btu/hr)
75.0/
62.0
45
80.0/
67.0
75.0/
62.0
55
80.0/
67.0
Nominal
Airflow
EWT EAT
(ºF) DB/WB (cfm) (Btu/hr) (Btu/hr) (cfm) (Btu/hr) (Btu/hr) (ºF) (Btu/hr) (Btu/hr) (Btu/hr) (Btu/hr)
75.0/
62.0
45
80.0/
67.0
75.0/
62.0
55
80.0/
67.0
EWT EAT
DB/WB
(ºF)
(ºF) (Btu/hr) (Btu/hr) (Btu/hr) (Btu/hr) (ºF) (Btu/hr) (Btu/hr) (Btu/hr) (Btu/hr)
75.0/
62.0
45
80.0/
67.0
75.0/
62.0
55
80.0/
67.0
EWT EAT
DB/WB
(ºF)
(ºF) (Btu/hr) (Btu/hr) (Btu/hr) (Btu/hr) (ºF) (Btu/hr) (Btu/hr) (Btu/hr) (Btu/hr)
75.0/
62.0
45
80.0/
67.0
75.0/
62.0
55
80.0/
67.0
Flow
Airflow
Rate
(cfm) (gpm)
43.0 118215 104308
35.7 105670 98166 81.7 231712 204722 58.8 158718 140000 168.0 307473 268743
28.4 89506 88546 65.0 210613 194026 46.8 137193 129347 133.4 278405 254363
43.0 153149 113374 98.4 325916 233385
35.7 133765 105547 81.7 301172 223270 58.8 205708 152163 168.0 400795 293543
28.4 109640 95570 65.0 268225 209766 46.8 172394 138737 133.4 355858 275180
4300
43.0 76546 76546 98.4 15226 152261
35.7 71725 71725 81.7 147128 147128 58.8 103013 103013 168.0 193879 193879
28.4 63936 63936 98.4 138920 138920 46.8 94517 94517 133.4 183078 183078
43.0 997707 92120 81.7 201228 183427
35.7 91330 87908 65.0 190980 178438 58.8 134265 12384 168.0 253334 234147
28.4 80220 80201 98.4 176565 170614 46.8 119858 116468 133.4 234216 224149
Flow
Nominal
Rate
Airflow
(gpm)
120.1 300141 252991
99.7 277844 242600 125.1 345207 300757 115.0 297133 260929 166.8 490321 413441
79.4 247291 227625 99.2 311526 284209 91.3 275216 249921 132.4 450026 394389
120.1 396773 279042 150.6 488735 344393
99.7 361929 264763 125.1 450654 328782 115.0 387874 285299 166.8 647073 455704
79.4 314626 245527 99.2 376624 298517 91.3 353829 271344 132.4 584177 429857
10000
120.1 183343 183343 150.6 224803 224803
99.7 176480 176480 125.1 217345 217345 115.0 186084 186084 166.8 297975 297975
79.4 165073 165073 99.2 204979 204979 91.3 177930 177930 132.4 285222 285222
120.1 246079 219190 150.6 300807 269528
99.7 231002 212437 125.1 284619 262106 115.0 242136 225955 166.8 398913 356710
79.4 210726 202139 99.2 262399 250687 91.3 227979 218163 132.4 372003 344165
Nominal
Flow
Airflow
Rate
(cfm) (gpm)
155.4 410014 333157
129.0 382469 320590 168.0 495046 416563 158.9 504119 410660 221.0 696784 572268
102.3 344216 302774 133.4 453219 396846 126.1 464227 392287 176.2 647897 549552
155.4 546475 370822 202.5 699525 478358
129.0 505143 353584 168.0 654992 459848 158.9 669318 455923 221.0 925183 634763
102.3 445328 329064 133.4 588178 432393 126.1 608158 430457 176.2 847943 602685
12500
155.4 240254 240254 202.5 309206 309206
129.0 233413 233413 168.0 301287 301287 158.9 295956 295956 221.0 411289 411289
102.3 221426 221426 133.4 287860 287860 126.1 285323 285323 176.2 397647 397647
155.4 332781 285581 202.5 425016 368879
129.0 314692 278020 168.0 404552 360100 158.9 408475 351794 221.0 562770 490066
102.3 288623 266420 133.4 375762 346898 126.1 381148 340123 176.2 529279 475352
Nominal
Flow
Airflow
Rate
(cfm) (gpm)
207.3 571870 453820
172.0 542915 440594 325.6 958766 800336 259.3 797101 650336 333.0 991370 818465
136.5 498560 420239 258.3 903504 774109 264.8 1119379 747621 264.8 931326 790353
207.3 768359 509542 391.7 1339061 913508
172.0 720933 489427 325.6 1277444 887940 259.3 1059374 722329 333.0 1318009 907963
136.5 653719 461401 258.3 1183607 849179 264.8 755519 681094 264.8 1221011 867762
16500
207.3 324297 324297 391.7 584577 584577
172.0 317813 317813 325.6 572669 572669 259.3 466859 466859 333.0 585855 585855
136.5 306263 306263 258.3 554618 554618 264.8 669195 566903 264.8 568232 568232
207.3 461349 385934 391.7 804567 700005
172.0 439485 377081 325.6 773282 686291 259.3 642967 555976 333.0 797971 700186
136.5 410083 364614 258.3 732310 667233 264.8 732310 667233 264.8 755519 681094
Capacity
Total Sensible
29.8 Square Feet 40.8 Square Feet
Capacity
Total Sensible
45.2 Square Feet 52.5 Square Feet
Capacity
Total Sensible
60.9 Square Feet 71.3 Square Feet
Capacity
Total Sensible
Nominal
Flow
Airflow
Rate
(cfm) (gpm)
98.4 247233 212158
8750
Flow
Nominal
Rate
Airflow
(gpm)
150.6 369070 311969
12500
Nominal
Flow
Airflow
Rate
(cfm) (gpm)
202.5 526221 430876
16500
Nominal
Flow
Airflow
Rate
(cfm) (gpm)
391.7 1003513 820997
32000
Capacity
Total Sensible
Capacity
Total Sensible
Capacity
Total Sensible
Capacity
Total Sensible
Note: See Table 15, page 45 to determine capacity at other than nominal cfm.
Nominal
Airflow
EWT EAT
DB/WB
(ºF)
75.0/
62.0
45
80.0/
67.0
75.0/
62.0
55
80.0/
67.0
Nominal
Airflow
EWT EAT
DB/WB
(ºF)
75.0/
62.0
45
80.0/
67.0
75.0/
62.0
55
80.0/
67.0
Nominal
Airflow
EWT EAT
DB/WB
(ºF)
75.0/
62.0
45
80.0/
67.0
75.0/
62.0
55
80.0/
67.0
Nominal
Airflow
EWT EAT
DB/WB
(ºF)
75.0/
62.0
45
80.0/
67.0
75.0/
62.0
55
80.0/
67.0
Nominal
Flow
Airflow
Rate
(cfm) (gpm)
70.8 174932 147468
70.8 230503 162275 202.5 434409 307307
5750
70.8 107987 107987 202.5 200490 200490
70.8 145162 128577 202.5 267384 240686
Nominal
Flow
Airflow
Rate
(cfm) (gpm)
138.4 312851 268478
138.4 414192 296028 200.9 689345 473235
11250
138.4 191437 191437 200.9 305575 305575
138.4 252970 231305 200.9 418034 365034
Nominal
Flow
Airflow
Rate
(cfm) (gpm)
191.3 530260 422617
191.3 711594 473799 267.1 979631 657637
15500
191.3 301945 301945 267.1 419653 419653
191.3 426964 359394 267.1 586400 500035
Nominal
Flow
Airflow
Rate
(cfm) (gpm)
312.1 834084 667291
312.1 1119379 747621 402.0 1388369 937345
24750
312.1 475642 475642 402.0 597600 597600
312.1 669195 566903 402.0 829035 713591
Capacity
Total Sensible
Capacity
Total Sensible
Capacity
Total Sensible
Capacity
Total Sensible
Nominal
Flow
Airflow
Rate
(cfm) (gpm)
202.5 328039 278466
11250
Nominal
Flow
Airflow
Rate
(cfm) (gpm)
200.9 518514 426470
16500
Nominal
Flow
Airflow
Rate
(cfm) (gpm)
267.1 731367 588143
22000
Nominal
Flow
Airflow
Rate
(cfm) (gpm)
402.0 1037546 839692
32000
Capacity
Total Sensible
Capacity
Total Sensible
Capacity
Total Sensible
Capacity
Total Sensible
44 McQuay Catalog 860-9
Performance Data
Table 14: Waterside Economizer Capacity Correction Factors
Description
Total Capacity 0.892 0.920 0.947 0.975 1.000 1.025 1.048 1.071 1.093
Sensible Capacity 0.848 0.886 0.925 0.963 1.000 1.037 1.072 1.107 1.142
–20% –15% –10% –5% Standard 5% 10% 15% 20%
Table 15: DX Cooling Capacity Correction Multipliers
Description
Total Capacity 0.957 0.969 0.981 0.991 1.000 1.009 1.017 1.023 1.030
Sensible Capacity 0.895 0.921 0.948 0.974 1.000 1.026 1.052 1.077 1.102
Compressor Motor kW 0.987 0.989 0.996 0.998 1.000 1.004 1.006 1.008 1.011
–20% –15% –10% –5% Standard 5% 10% 15% 20%

Heating Capacity Data

Hot Water Coil Capacity (2-row)
Table 16: Entering Water 160ºFand Entering Air 60ºF
Minimum
Cabinet Size
Small 19.8
Small Tall 19.8
Medium 32.3
Large 36.7
Large Tall 45.8
Note: 1 Based on 12 fpi aluminum HI-F5 fins with single serpentine.
2 Smallest standard coil face area available using McQuay Vision™ air handling unit platform.
Coil Face
Area (ft
2)2
1
Nominal Air Flow
(cfm)
4300 241.3 125.8 111.3 14 0.09 5750 312.2 126.9 109.7 19 0.15 8750 441.4 129.2 106.1 29 0.30
5750 312.2 126.9 109.7 19 0.15 10000 490.2 130.1 104.8 33 0.37 11250 537.0 130.9 103.7 37 0.45 12500 581.8 131.6 102.6 41 0.53 11250 613.3 126.8 109.9 37 0.20 12500 667.9 127.4 108.9 41 0.24 16500 831.8 129.3 106.1 54 0.38 15500 836.5 127.1 109.4 51 0.34 16500 879.0 128.5 108.7 54 0.38 22000 1097.8 129.6 105.6 72 0.61 16500 919.2 126.0 110.9 54 0.21 24750 1266.3 128.8 106.8 81 0.41 32000 1536.9 130.7 103.9 105 0.63 32500 1554.6 130.8 103.7 107 0.65
Total
Capacity
(MBH)
Percent Standard CFM
Percent Standard CFM
LWT
(ºF)
LBD
(ºF)
Flow Rate
(gpm)
Air Pressure
Drop
(in. wg)
Steam Coil Capacity
1
Table 17: Steam Pressure 5 psi and Entering Air 60ºF
Cabinet Size
Small 19.8
Small Tall 19.8
Medium 32.3
Large 36.7
Large Tall 45.8
Note: 1 Based on 5 psi steam pressure and 6 fpi aluminum HI-F5 fins.
2 Smallest standard coil face area available using McQuay Vision™ air handling unit platform.
Minimum Coil Face
Area (ft2)
2
Nominal
Air Flow (cfm)
4300 227.5 119.0 0.03 5750 330.1 112.5 0.05 8750 420.1 103.9 0.10
5750 330.1 112.5 0.05 10000 452.0 101.3 0.13 11250 481.4 99.1 0.16 12500 508.9 97.2 0.20 11250 598.2 108.6 0.07 12500 635.4 106.5 0.08 16500 740.8 101.1 0.13 15500 758.5 104.8 0.12 16500 785.3 103.5 0.13 22000 916.9 98.1 0.23 16500 865.8 108.0 0.07 24750 1083.9 100.0 0.15 32000 1239.8 95.4 0.24 32500 1249.7 95.2 0.24
Total Capacity
(MBH)
LBD (ºF)
Air Pressure Drop
(in. wg)
McQuay Catalog 860-9 45
Performance Data
Electric Heat
Table 18: Electric Heat – 60 Hz, 3 Phase
SWP Unit Size
023 through 035 27.8 94 77.2 34.0 116 85.6 34.0 116 42.8 34.0 116 34.2 039 through 050 27.8 94 77.2 34.0 116 85.6 68.0 232 85.6 68.0 232 68.4 044 through 066 27.8 94 77.2 34.0 116 85.6 68.0 232 85.6 68.0 232 68.4 062 through 088 55.6 190 154.4 68.0 232 170.9 68.0 232 85.6 68.0 232 68.4 065 through 130 55.6 190 154.4 68.0 232 170.9 68.0 232 85.6 68.0 232 68.4

Component Pressure Drops

Table 19: SWP 023 through 033 (pressure drop in inches wg)
Nominal Air Flow
(cfm)
4000 0.26 0.13 0.09 0.11 0.09 0.14 0.07 0.24 0.01 0.00 6000 0.48 0.25 0.18 0.20 0.16 0.25 0.13 0.43 0.01 0.01 8000 0.73 0.41 0.31 0.31 0.25 0.40 0.21 0.64 0.03 0.01
10000 1.02 0.6 0.45 0.42 0.34 0.57 0.29 0.88 0.04 0.01
Nominal Air Flow
(cfm)
6000 0.27 0.13 0.09 0.11 0.10 0.14 0.08 0.25 0.01 0.01
8000 0.41 0.21 0.16 0.17 0.14 0.22 0.12 0.37 0.02 0.01 10000 0.58 0.31 0.23 0.24 0.20 0.32 0.16 0.51 0.04 0.01 12000 0.75 0.43 0.32 0.32 0.26 0.42 0.21 0.66 0.06 0.02 14000 0.95 0.56 0.42 0.40 0.32 0.53 0.27 0.82 0.08 0.03 16000 1.11 0.6 0.53 0.48 0.39 0.65 0.33 0.99 0.10 0.04
Note: DX pressure drops are wet coil and economizers are dry coil.
All units must have a DX coil pressure drop. Based on 32" high plenum with maximum allowed opening.
Standard Coil Filters Discharge Plenum
Evaporator Economizer
Evaporator Economizer
208 V/60 Hz/3 Phase 230 V/60 Hz/3 Phase 460 V/60 Hz/3 Phase 575 V/60 Hz/3 Phase
kW MBH FLA kW MBH FLA kW MBH FLA kW MBH FLA
2
17.2 ft 2", 30% 2", 75% 4", 30% 4", 65% 4", 75% 2", 85%
Left &
Right
Large Coil Filters Discharge Plenum
2
25.2 ft 2", 30% 2", 75% 4", 30% 4", 65% 4", 75% 2", 85%
Left &
Right
Front
& Back
Front
& Back
Table 20: SWP 039 through 050 (pressure drop in inches wg)
Nominal Air Flow
(cfm)
6000 0.27 0.13 0.09 0.11 0.10 0.14 0.08 0.25 0.01 0.01
8000 0.41 0.21 0.16 0.17 0.14 0.22 0.12 0.37 0.03 0.01 10000 0.55 0.31 0.23 0.24 0.20 0.32 0.16 0.51 0.04 0.01 12000 0.72 0.43 0.32 0.32 0.26 0.42 0.21 0.66 0.06 0.02 16000 0.88 0.56 0.42 0.40 0.32 0.53 0.27 0.82 0.08 0.03
Nominal Air Flow
(cfm)
10000 0.45 0.24 0.17 0.19 0.16 0.24 0.13 0.40 0.04 0.01 12000 0.59 0.32 0.24 0.25 0.20 0.32 0.17 0.52 0.06 0.02 14000 0.74 0.42 0.31 0.31 0.25 0.41 0.21 0.65 0.08 0.03 16000 0.88 0.53 0.39 0.38 0.31 0.50 0.25 0.78 0.10 0.04
Note: DX pressure drops are wet coil and economizers are dry coil.
All units must have a DX coil pressure drop. Based on 32" high plenum with maximum allowed opening.
Standard Coil Filters Discharge Plenum
2
25.2 ft
Evaporator Economizer
2", 30% 2", 75% 4", 30% 4", 65% 4", 75% 2", 85%
Left &
Right
Large Coil Filters Discharge Plenum
2
29.8 ft
Evaporator Economizer
2", 30% 2", 75% 4", 30% 4", 65% 4", 75% 2", 85%
Left &
Right
Front
& Back
Front
& Back
46 McQuay Catalog 860-9
Performance Data
Table 21: SWP 044 through 065 (pressure drop in inches wg)
Nominal Air Flow
(cfm)
10000 0.28 0.14 0.10 0.12 0.10 0.15 0.08 0.26 0.03 0.01 12000 0.37 0.19 0.14 0.16 0.13 0.20 0.10 0.33 0.05 0.01 14000 0.46 0.24 0.18 0.20 0.16 0.25 0.13 0.42 0.06 0.02 16000 0.48 0.31 0.23 0.24 0.19 0.31 0.16 .050 0.08 0.02 18000 0.65 0.38 0.28 0.28 0.23 0.37 0.19 0.59 0.10 0.03 20000 0.76 0.45 0.34 0.33 0.27 0.44 .022 0.69 0.13 0.04 22000 0.86 0.53 0.40 0.38 0.31 0.51 0.26 0.79 0.16 0.04 24000 0.98 0.61 0.46 0.43 0.35 0.58 0.29 0.89 0.18 0.05
Nominal Air Flow
(cfm)
12000 0.32 0.16 0.11 0.13 0.11 0.17 0.09 .028 0.05 0.01 14000 0.40 0.21 0.15 0.17 0.14 0.21 0.11 0.35 0.06 0.02 16000 0.55 0.26 0.19 0.20 0.17 0.26 0.13 0.43 0.08 0.02 18000 0.56 0.32 0.23 0.24 0.20 0.31 0.16 0.50 0.10 0.03 20000 0.64 0.38 0.27 0.28 0.23 0.37 0.19 0.58 0.13 0.04 22000 0.74 0.44 0.32 0.32 0.26 0.42 0.22 0.67 0.16 0.04 24000 0.84 0.51 0.38 0.36 0.29 0.48 0.25 0.76 0.18 0.05 26000 0.94 0.59 0.43 0.41 0.33 0.55 0.28 0.85 0.22 0.06
Note: DX pressure drops are wet coil and economizers are dry coil.
All units must have a DX coil pressure drop. Based on 32" high plenum with maximum allowed opening.
Standard Coil Filters Discharge Plenum
2
40.8 ft
Evaporator Economizer
2", 30% 2", 75% 4", 30% 4", 65% 4", 75% 2", 85%
Left &
Right
Large Coil Filters Discharge Plenum
2
45.8 ft
Evaporator Economizer
2", 30% 2", 75% 4", 30% 4", 65% 4", 75% 2", 85%
Left &
Right
Front
& Back
Front
& Back
Table 22: SWP 062 through 088 (pressure drop in inches wg)
Nominal Air Flow
(cfm)
12000 0.26 0.12 0.09 0.11 0.09 0.14 0.07 0.23 0.03 0.01 14000 0.38 .012 0.12 0.14 0.11 0.17 0.09 0.29 0.04 0.01 16000 0.45 0.16 0.15 0.16 0.14 0.21 0.11 0.35 0.05 0.01 18000 0.53 0.19 0.18 0.20 0.16 0.25 0.13 0.42 0.07 0.02 20000 0.62 0.23 0.22 0.23 0.19 0.30 0.15 0.48 0.09 0.02 22000 0.70 0.27 0.26 0.26 0.21 0.34 0.18 0.55 0.10 0.03 24000 0.80 0.31 0.30 0.30 0.24 0.39 0.20 .062 0.12 0.03 26000 0.91 0.35 0.34 0.33 0.27 0.44 0.23 0.70 0.14 0.04 28000 1.01 0.40 0.39 0.37 0.30 0.50 0.25 0.78 0.17 0.04 30000 1.13 0.45 0.44 0.41 0.33 0.55 0.28 0.86 0.19 0.05
Note: DX pressure drops are wet coil and economizers are dry coil.
All units must have a DX coil pressure drop. Based on 32" high plenum with maximum allowed opening.
Standard Coil Filters Discharge Plenum
2
52.5 ft
Evaporator Economizer
2", 30% 2", 75% 4", 30% 4", 65% 4", 75% 2", 85%
Left &
Right
Front
& Back
McQuay Catalog 860-9 47
Performance Data
Table 23: SWP 065 through 130 (pressure drop in inches wg)
Nominal Air Flow
(cfm)
16000 0.36 0.16 0.11 0.13 0.11 0.17 0.09 0.29 0.04 0.01 18000 0.43 0.19 0.14 0.16 0.13 0.20 0.11 0.34 0.05 0.02 20000 0.52 0.23 0.17 0.18 0.15 0.24 0.12 0.39 0.06 0.02 22000 0.60 0.27 0.20 .021 0.17 0.27 0.14 0.45 0.08 0.03 24000 0.68 0.31 0.23 0.24 0.20 0.31 0.16 0.51 0.09 0.03 26000 0.77 0.35 0.26 0.27 0.22 0.35 0.18 0.57 0.11 0.04 28000 0.86 0.40 0.30 0.30 0.24 0.40 0.20 0.63 0.13 0.04 30000 0.94 0.45 0.34 0.33 0.27 0.44 0.22 0.69 0.15 0.05 32000 1.03 0.51 0.38 0.37 0.30 0.49 0.25 0.75 0.17 0.06 34000 1.13 0.56 0.42 0.40 0.32 0.53 0.27 0.83 0.19 0.06 36000 1.22 0.62 0.47 0.43 0.35 0.58 0.29 0.90 0.21 0.07
Nominal Air Flow
(cfm)
18000 0.34 0.15 0.10 0.12 0.10 0.16 0.08 0.27 0.05 0.02 20000 0.41 0.17 0.13 0.15 0.12 0.19 0.10 0.31 0.06 0.02 22000 0.48 0.20 0.15 0.17 0.14 0.21 0.11 0.36 0.08 0.03 24000 0.54 0.24 0.17 0.19 0.16 0.25 0.13 0.40 0.09 0.03 26000 0.61 0.27 0.20 0.21 0.18 0.28 0.14 0.45 0.11 0.04 28000 0.68 0.31 0.23 0.24 0.20 0.31 0.16 0.50 0.13 0.04 30000 0.75 0.35 0.26 0.26 0.22 0.35 0.18 0.55 0.15 0.05 32000 0.83 0.39 0.29 0.29 0.24 0.38 0.19 0.61 0.17 0.06 34000 0.90 0.43 0.32 0.32 0.26 0.42 0.21 0.66 0.19 0.06 36000 0.97 0.47 0.35 0.34 0.28 0.46 0.23 0.72 0.21 0.07 38000 1.04 0.52 0.39 0.37 0.30 0.50 0.25 0.78 0.23 0.08 40000 1.13 0.57 0.43 0.40 .032 0.54 0.27 0.83 0.26 0.09 42000 1.21 0.62 0.46 0.43 0.35 0.58 0.29 0.89 0.28 0.10
Note: DX pressure drops are wet coil and economizers are dry coil.
All units must have a DX coil pressure drop. Based on 32" high plenum with maximum allowed opening.
Standard Coil Filters Discharge Plenum
2
60.9 ft
Evaporator Economizer
2", 30% 2", 75% 4", 30% 4", 65% 4", 75% 2", 85%
Left &
Right
Large Coil Filters Discharge Plenum
2
71.3 ft
Evaporator Economizer
2", 30% 2", 75% 4", 30% 4", 65% 4", 75% 2", 85%
Left &
Right
Front
& Back
Front
& Back
48 McQuay Catalog 860-9

Total Unit Water Pressure Drop

SWP023 through SWP033
Performance Data
Figure 24: Mechanical Cooling Only
Figure 25: Standard Economizer Coil
Figure 26: Mechanical Cooling and WRV
Figure 27: Large Economizer Coil
NOTE: Total water pressure drop varies depending on a units selected options. Only use the specific chart which reflects your unit. The above figures illustrate total water pressure drop (WPD) for each associated model number.
Use Figure 24 if no water side economizer coil or water regulating valve is provided.
Use Figure 25 for standard economizer coils and Figure 27 for large economizer coils.
Use Figure 26 if a water regulating valve is provided.
McQuay Catalog 860-9 49
Performance Data
SWP039 through SWP050
Figure 28: Mechanical Cooling Only
Figure 29: Standard Economizer Coil
Figure 30: Mechanical Cooling and WRV
Figure 31: Large Economizer Coil
NOTE: Total water pressure drop varies depending on a units selected options. Only use the specific chart which reflects your unit. The above figures illustrate total water pressure drop (WPD) for each associated model number.
Use Figure 28 if no water side economizer coil or water regulating valve is provided.
Use Figure 29 for standard economizer coils and Figure 31 for large economizer coils.
Use Figure 30 if a water regulating valve is provided.
50 McQuay Catalog 860-9
SWP044 through SWP055
Performance Data
Figure 32: Mechanical Cooling Only
Figure 33: Standard Economizer Coil
Figure 34: Mechanical Cooling and WRV
Figure 35: Large Economizer Coil
NOTE: Total water pressure drop varies depending on a units selected options. Only use the specific chart which reflects your unit. The above figures illustrate total water pressure drop (WPD) for each associated model number.
Use Figure 32 if no water side economizer coil or water regulating valve is provided.
Use Figure 33 for standard economizer coils and Figure 35 for large economizer coils.
Use Figure 34 if a water regulating valve is provided.
McQuay Catalog 860-9 51
Performance Data
SWP062 through SWP088
Figure 36: Mechanical Cooling Only
Figure 37: Standard Economizer Coil
Figure 38: Mechanical Cooling and WRV
NOTE: Total water pressure drop varies depending on a units selected options. Only use the specific chart which reflects your unit. The above figures illustrate total water pressure drop (WPD) for each associated model number.
Use Figure 36 if no water side economizer coil or water regulating valve is provided.
Use Figure 37 for standard economizer coils.
Use Figure 38 if a water regulating valve is provided.
52 McQuay Catalog 860-9
SWP065 through SWP130
Performance Data
Figure 39: Mechanical Cooling Only
Figure 40: Standard Economizer Coil
Figure 41: Mechanical Cooling and WRV
Figure 42: Large Economizer Coil
NOTE: Total water pressure drop varies depending on a units selected options. Only use the specific chart which reflects your unit. The above figures illustrate total water pressure drop (WPD) for each associated model number.
Use Figure 39 if no water side economizer coil or water regulating valve is provided.
Use Figure 40 for standard economizer coils and Figure 42 for large economizer coils.
Use Figure 41 if a water regulating valve is provided.
McQuay Catalog 860-9 53
Performance Data
1
.
5
bhp
2 bhp
3
b
h
p
h
p
hp
0
b
h
p
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
5.5
6.0
6.5
7.0
7.5
8.0
8.5
STATIC PRESSURE (IN. OF WATER)
0.0
2.0
4.0
CFM (IN 1,000's)
McQUAY INTERNATIONAL FAN SELECTION
3
6
0
0
r
p
m
3
4
0
0
r
p
m
3
2
0
0
r
p
m
3
0
0
0
r
p
m
2
8
0
0
r
p
m
2
6
0
0
r
p
m
2
4
0
0
r
p
m
2200 rpm
2000 rpm
1
8
0
0
r
p
m
1
6
0
0
r
p
m
1
4
0
0
r
p
m
1
2
0
0
r
p
m
1000 rpm
4
0
0
0
r
p
m
3
8
0
0
r
p
m
2
b
h
p
hp
5
b
h
p
h
p
p
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
5.5
6.0
6.5
7.0
7.5
8.0
8.5
9.0
STATIC PRESSURE (IN. OF WATER)
0.0
2.0
4.0
6.0
CFM (IN 1,000's)
McQUAY INTERNATIONAL FAN SELECTION
3
4
0
0
r
p
m
3
6
0
0
r
p
m
3
2
0
0
r
p
m
3
0
0
0
r
p
m
2
8
0
0
r
p
m
2
6
0
0
r
p
m
2
4
0
0
r
p
m
2200 rpm
2000 rpm
1
8
0
0
r
p
m
1
6
0
0
rp
m
1
4
0
0
r
p
m
1
2
0
0
r
p
m
8
0
0
r
p
m
1000 rpm

Fan Curves

Figure 43: 13.5" Diameter, 9-Blade Fan
1
bhp
1
7
.
5
b
5
b
Figure 44: 15.0" Diameter, 9-Blade Fan
1
0
b
h
7
.
5
b
1
p
.
5
b
h
p
1
b
h
3
b
54 McQuay Catalog 860-9
Figure 45: 16.5", 9-Blade Fan
1
b
h
p
2
b
h
p
hp
hp
h
p
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
5.5
6.0
6.5
7.0
7.5
STATIC PRESSURE (IN. OF WATER)
0.0
2.0
4.0
6.0
8.0
CFM (IN 1,000's)
McQUAY INTERNATIONAL FAN SELECTION
2
6
0
0
r
p
m
2
8
0
0
r
p
m
3
0
0
0
r
p
m
2
4
0
0
r
p
m
2
2
0
0
r
p
m
2
0
0
0
r
p
m
1
8
0
0
r
p
m
1
6
0
0
r
p
m
1
4
0
0
r
p
m
1
2
0
0
r
p
m
1
0
0
0
r
p
m
8
0
0
r
p
m
6
0
0
r
p
m
1
b
h
p
1
.
5
b
h
p
5
bhp
hp
hp
hp
h
p
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
5.5
6.0
6.5
7.0
7.5
8.0
8.5
9.0
STATIC PRESSURE (IN. OF WATER)
0.0
2.0
4.0
6.0
8.0
10.0
CFM (IN 1,000's)
McQUAY INTERNATIONAL FAN SELECTION
2
8
0
0
r
p
m
3
0
0
0
r
p
m
2
6
0
0
r
p
m
2
4
0
0
r
p
m
2
2
0
0
r
p
m
2
0
0
0
r
p
m
1
8
0
0
r
p
m
1600 rpm
1400 rpm
1
2
0
0
r
p
m
1
0
0
0
r
p
m
8
0
0
r
p
m
600 rpm
Performance Data
1
.
5
b
h
p
3
b
h
p
1
0
b
7
.
5
b
5
b
Figure 46: 18.2", 9-Blade Fan
2
0
b
1
5
b
1
0
b
7
.
5
b
3
2
b
h
p
bhp
McQuay Catalog 860-9 55
Performance Data
1
b
h
p
1
.
5
b
h
p
2
b
h
p
h
p
hp
hp
h
p
2
5
b
h
p
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
5.5
6.0
6.5
7.0
7.5
8.0
8.5
9.0
STATIC PRESSURE (IN. OF WATER)
0.0
2.0
4.0
6.0
8.0
10.0
12.0
CFM (IN 1,000's)
McQUAY INTERNATIONAL FAN SELECTION
2
6
0
0
r
p
m
2
8
0
0
r
p
m
2
4
0
0
r
p
m
2
2
0
0
r
p
m
2
0
0
0
r
p
m
1
8
0
0
r
p
m
1
6
0
0
r
p
m
1400 rpm
1200 rpm
1
0
0
0
r
p
m
8
0
0
r
p
m
600 rpm 400 rpm
1
b
h
p
1
.
5
b
h
p
2
b
h
p
hp
p
hp
h
p
hp
0
b
h
p
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
5.5
6.0
6.5
7.0
7.5
8.0
8.5
9.0
STATIC PRESSURE (IN. OF WATER)
0.0
2.0
4.0
6.0
8.0
10.0
12.0
14.0
CFM (IN 1,000's)
McQUAY INTERNATIONAL FAN SELECTION
2
6
0
0
r
p
m
2
4
0
0
r
p
m
2
2
0
0
r
p
m
2
0
0
0
r
p
m
1
8
0
0
r
p
m
1
6
0
0
r
p
m
1
4
0
0
r
p
m
1200 rpm
1
0
0
0
r
p
m
8
0
0
r
p
m
6
0
0
r
p
m
400 rpm
Figure 47: 20.0", 9-Blade Fan
2
0
b
1
5
b
1
0
b
7
.
5
3
b
h
p
5
b
h
p
b
Figure 48: 22.2", 9-Blade Fan
2
5
b
2
0
b
1
5
b
1
0
b
h
7
.
5
b
3
b
h
p
5
b
h
p
56 McQuay Catalog 860-9
Figure 49: 24.5", 9-Blade Fan
1
b
h
p
1
.
5
b
h
p
2
b
h
p
p
p
p
p
h
p
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
5.5
6.0
6.5
7.0
7.5
8.0
8.5
9.0
STATIC PRESSURE (IN. OF WATER)
0.0
2.0
4.0
6.0
8.0
10.0
12.0
14.0
16.0
18.0
CFM (IN 1,000's)
McQUAY INTERNATIONAL FAN SELECTION
2
2
0
0
r
p
m
2
0
0
0
r
p
m
1
8
0
0
r
p
m
1
6
0
0
r
p
m
1
4
0
0
r
p
m
1200 rpm
1000 rpm
8
0
0
r
p
m
6
0
0
r
p
m
4
0
0
r
p
m
1
.
5
b
h
p
5
b
h
p
p
p
h
p
h
p
4
0
hp
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
5.5
6.0
6.5
7.0
7.5
8.0
STATIC PRESSURE (IN. OF WATER)
0.0
2.0
4.0
6.0
8.0
10.0
12.0
14.0
16.0
18.0
20.0
22.0
CFM (IN 1,000's)
McQUAY INTERNATIONAL FAN SELECTION
1
8
0
0
r
p
m
2
0
0
0
r
p
m
1
6
0
0
r
p
m
1
4
0
0
r
p
m
1
2
0
0
r
p
m
1000 rpm
800 rpm
6
0
0
r
p
m
4
0
0
r
p
m
Performance Data
3
0
b
2
5
b
h
2
0
b
h
1
5
b
h
1
0
b
7
.
3
b
h
p
5
b
h
p
5
b
h
h
p
Figure 50: 27.0", 9-Blade Fan
1
b
h
p
2
b
3
0
b
3
b
h
b
hp
p
7
.
5
b
h
p
2
5
b
2
0
b
h
1
5
b
h
1
0
b
h
p
McQuay Catalog 860-9 57
Performance Data
1
0
b
h
p
p
p
p
p
p
h
p
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
5.5
6.0
6.5
7.0
7.5
8.0
8.5
9.0
STATIC PRESSURE (IN. OF WATER)
0.0
5.0
10.0
15.0
20.0
25.0
CFM (IN 1,000's)
McQUAY INTERNATIONAL FAN SELECTION
1
7
0
0
r
p
m
1
8
0
0
r
p
m
1
6
0
0
r
p
m
1
5
0
0
r
p
m
1
4
0
0
r
p
m
1
3
0
0
r
p
m
1
2
0
0
r
p
m
1
0
0
0
r
p
m
9
0
0
r
p
m
8
0
0
r
p
m
700 rpm 600 rpm 500 rpm
4
0
0
r
p
m
0
1
1
0
r
p
m
1
b
h
p
2
b
h
p
7
.
5
b
h
p
1
0
bhp
p
p
p
p
h
p
h
p
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
5.5
6.0
6.5
7.0
7.5
8.0
8.5
9.0
STATIC PRESSURE (IN. OF WATER)
0.0
5.0
10.0
15.0
20.0
25.0
30.0
CFM (IN 1,000's)
McQUAY INTERNATIONAL FAN SELECTION
1
6
0
0
r
p
m
1
7
0
0
r
p
m
1500 rpm
1
4
0
0
r
p
m
1
3
0
0
r
p
m
1
2
0
0
r
p
m
1
1
0
0
r
p
m
1
0
0
0
r
p
m
9
0
0
r
p
m
8
0
0
r
p
m
700 rpm
600 rpm 500 rpm
4
0
0
r
p
m
3
0
0
r
p
m
Figure 51: 30.0", 9-Blade Fan
5
0
b
4
0
b
h
3
0
b
h
2
5
b
h
2
0
b
h
1
7
3
2
1
.
1
b
h
p
b
5
b
h
p
h
bh
p
p
5
b
h
p
.
5
b
hp
5
b
h
Figure 52: 33.0", 9-Blade Fan
5
1
.
5
b
h
p
3
b
h
p
b
h
p
6
0
b
5
0
b
4
0
b
h
3
0
b
h
2
5
b
h
2
0
b
h
1
5
bhp
58 McQuay Catalog 860-9
Figure 53: 36.5", 9-Blade Fan
2
b
h
p
5
b
h
p
hp
hp
hp
hp
hp
hp
7
5
h
p
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
5.5
6.0
6.5
7.0
7.5
8.0
8.5
9.0
STATIC PRESSURE (IN. OF WATER)
0.0
5.0
10.0
15.0
20.0
25.0
30.0
35.0
CFM (IN 1,000's)
McQUAY INTERNATIONAL FAN SELECTION
1
4
0
0
r
p
m
1
5
0
0
r
p
m
1
3
0
0
r
p
m
1
2
0
0
r
p
m
1
1
0
0
r
p
m
1
0
0
0
r
p
m
9
0
0
r
p
m
8
0
0
r
p
m
700 rpm
600 rpm
5
0
0
r
p
m
4
0
0
r
p
m
300 rpm
1
b
h
p
1
.
5
b
h
p
5
b
h
p
hp
hp
hp
h
p
h
p
p
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
5.5
6.0
6.5
7.0
7.5
8.0
8.5
9.0
STATIC PRESSURE (IN. OF WATER)
0.0
5.0
10.0
15.0
20.0
25.0
30.0
35.0
40.0
45.0
CFM (IN 1,000's)
McQUAY INTERNATIONAL FAN SELECTION
1
3
0
0
r
p
m
1
4
0
0
r
p
m
1
2
0
0
r
p
m
1
1
0
0
r
p
m
1
0
0
0
r
p
m
9
0
0
r
p
m
8
0
0
r
p
m
7
0
0
rp
m
600 rpm
500 rpm
400 rpm
3
0
0
r
p
m
2
0
0
r
p
m
Performance Data
b
6
0
b
5
0
b
4
0
b
3
0
b
2
5
b
2
0
bhp
b
1
1
1
.
5
b
b
h
h
p
p
3
b
h
p
7
.
5
1
0
b
b
h
h
p
p
5
Figure 54: 40.2", 9-Blade Fan
3
2
b
h
p
b
h
p
7
5
b
bhp
6
0
b
5
0
b
4
0
b
3
0
b
2
5
b
hp
1
5
7
1
.
5
0
b
h
p
b
h
p
2
0
b
hp
McQuay Catalog 860-9 59
Performance Data
1
b
h
p
1
.
5
b
h
p
2
b
h
p
3
b
h
p
1
5
b
h
p
2
5
b
hp
3
0
bhp
hp
hp
hp
h
p
h
p
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
5.5
6.0
6.5
7.0
7.5
8.0
8.5
9.0
STATIC PRESSURE (IN. OF WATER)
0.0
5.0
10.0
15.0
20.0
25.0
30.0
35.0
40.0
45.0
50.0
55.0
CFM (IN 1,000's)
McQUAY INTERNATIONAL FAN SELECTION
1
2
0
0
r
p
m
1
3
0
0
r
p
m
1
1
0
0
r
p
m
1
0
0
0
r
p
m
9
0
0
r
p
m
8
0
0
r
p
m
7
0
0
r
p
m
6
0
0
r
p
m
500 rpm
400 rpm
3
0
0
r
p
m
2
0
0
r
p
m
Figure 55: 44.5", 9-Blade Fan
1
0
0
b
7
5
b
6
0
b
5
0
b
4
0
b
2
7
5
b
h
p
1
.
0
5
b
b
h
h
p
p
0
b
hp
60 McQuay Catalog 860-9

Dimensional Data

Evaporator Coil
Motor
Control Panel
Airflow
24"
See Note
18"
or
24"
36"
42"
Rear Side
Front Side
Opposite
Access
Side
Access
Side
NOTE: If water and condenser drains are on the motor side, 24" is required.
Dimensional Data

Recommended Clearances

For good installation, service and maintenance access, follow the recommended clearances given in this publication. Minimum clearances required by federal, state and local codes, such as the NEC, take precedence over the dimensions given. Clearance is required to allow room for side filter access, mechanical cleaning of condenser tubes, economizer coil access to expansion valves and other control components and allow for possible fan shaft or compressor removal.
Figure 56: Recommended Service and Maintainance Clearances
Table 24: Recommended Minimum Clearances
Location Clearance Length (Inches)
Front 36 Rear 24
Access Side 42
Opposite Access Side 18
Note: For clearance requirements less than those indicated, contact
your local McQuay sales representative.
McQuay Catalog 860-9 61
Dimensional Data
Figure 57: Self-Contained SWP—Front View (Left Hand Access Shown/Optional Plenum)
Table 25: Dimensions (Inche s )
Cabinet and
Unit Sizes
Height
Total Unit
Power and Control Knockouts
Plenum Width Plenum Depth
Condenser Water
Connections (ODS)
Drain Connections (MPT)
Fan Discharge Opening
Fan and Compressor
Section Depth
Coil Section Depth SD2 36.0 36.0 40.0 40.0 40.0 40.0 40.0
Control Panel Width SW1 14.0 14.0 16.0 16.0 16.0 16.0 16.0
Note: 1 Dimensions do not include lifting lugs, handles, latches or fastener extensions.
2 For shipping dimensions, add 4" to the depth, 8" to the length and 4" to the height. 3 Plenum height is user configurable. 4 Plenum opening height and width requires a minimum of 2" clearance on each side.
Width
Depth
EC1 5.5 5.5 7.5 7.5 7.5 7.5 7.5 EC2 71.0 75.0 87.0 87.0 87.0 103.0 103.0
3, 4
PW
3, 4
PD WC1 23.0 23.0 25.0 25.0 27.0 27.0 27.0 WC3 74.0 78.0 90.0 90.0 90.0 106.0 106.0 DIA1 2.125 2.625 2.625 3.125 3.125 3.125 4.125 DIA2 2.125 2.625 2.625 3.125 3.125 3.125 4.125
DC1 18.0 18.0 20.0 20.0 20.0 20.0 20.0 DC2 7.0 7.0 7.0 7.0 9.0 9.0 9.0
DOD 32.0 32.0 32.0 32.0 32.0 40.0 40.0
DOL 10.0 10.0 10.0 10.0 10.0 10.0 10.0
DOW 52.0 52.0 68.0 68.0 92.0 92.0 92.0
SD1 44.0 44.0 48.0 48.0 58.0 58.0 66.0
Small Small Tall Medium Large Large Tall
023-033 039-050 044-051 056-066 062-088 065-099 105-130
1, 2 1, 2 1, 2
80.0 84.0 96.0 96.0 96.0 112.0 112.0
84.0 84.0 102.0 102.0 126.0 126.0 126.0
80.0 80.0 88.0 88.0 98.0 98.0 106.0
70.0 70.0 86.0 86.0 110.0 110.0 110.0
44.0 44.0 48.0 48.0 58.0 58.0 66.0
62 McQuay Catalog 860-9
Dimensional Data
Figure 58: Self-Contained SWP Left Side View (Left Hand Access Shown with Piping and Optional Discharge Plenum)
Figure 59: Self-Contained Top View (Left Hand Access Shown/without Discharge Plenum)
McQuay Catalog 860-9 63
Dimensional Data
Airflow
Height
2.0
Figure 60: SWP Discharge Plenum Dimensions
Table 26: Fan Section Dimens io ns
Cabinet Size Width (Inches) Depth (Inches)
Small 70 44
Small Tall 70 44
Depth
Width
Front/Back Elevation
Left/Right Elev ation
Height
2.0
Table 27: Discharge Plenum Heights
Cabinet Size Available Factory-mounted1 Discharge Plenum Heights (Inches)
Small 202428323640——
Small Tall 20 24 28 32 36
Medium 20 24
Large 2024——————
Large Tall————————
Available Field-mounted2 Discharge Plenum Heights (Inches)
Small 2024283236404448
Small Tall 20 24 28 32 36 40 44 48
Medium 20 24 28 32 36 40 44 48
Large 2024283236404448
Large Tall 20 24 28 32 36 40 44 48
Note: 1 Maximum shipping height is 120" with a step-deck trailer.
2 Total minimum opening size (sq.ft., (H x L)/144) needs to be greater than or equal to CFM/maximum FPM, maximum FPM = 2500.
Medium 86 48
Large 110 58
Large Tall 110 66
Table 28: Duct Opening Heights
Plenum Height Available Duct Opening Heights (Inches)
20 16——————— 24 16 20 — 28 16 20 24 — 32 16 20 24 28 — 36 16 20 24 28 32 — 40 16 20 24 28 32 36 — 44 16 20 24 28 32 36 40 — 48 16 20 24 28 32 36 40 44
Table 29: Left/Right Duct Opening Lengths
Cabinet Size Left/Right Duct Opening Lengths (Inches)
Small 20 24 28 32 36* 40
Small Tall 20 24 28 32 36* 40
Medium 20 24 28 32 36 40* 44
Large2026344250*54—
Large Tall 20 26 34 42 50 54* 62
Note: *If an opening is 8" narrower than the overall cabinet Depth, the opening will be offset 2" from center.
Table 30: Front/Back Duct Opening Lengths
Cabinet Size Front/Back Duct Opening Lengths (Inches)
Small 18263442505866—————
Small Tall 18 26 34 42 50 58 66
Medium 18 26 34 42 50 58 66 74 82
Large 1826344250586674829098106
Large Tall 18 26 34 42 50 58 66 74 82 90 98 106
64 McQuay Catalog 860-9

Electrical Data

Table 31: SAFMotor Nameplate Amperage
Horsepower Type
3 5 Premium efficiency 15.7 13.6 6.8 6.8 5.2
7.5 10 15 20 25 30 40 50 60
Premium efficiency 9.3 8.2 4.1 4.1 3.1
Premium efficiency 22.3 20.0 10.0 10.0 7.4 Premium efficiency 29.0 25.8 12.9 12.9 10.3 Premium efficiency 43.4 37.8 18.9 18.9 14.1 Premium efficiency 57.0 49.0 24.5 24.5 18.9 Premium efficiency 70.0 61.0 30.5 30.5 24.2 Premium efficiency 83.3 72.4 36.2 36.2 29.8 Premium efficiency 110.0 96.0 48.0 48.0 38.0 Premium efficiency 137.0 120.0 60.0 60.0 47.5 Premium efficiency 160.0 140.0 70.0 70.0 56.0
Table 32: Compressor Motor Amperage
Electrical Data
208/60/3 230/60/3 400/50/3
FLA FLA FLA FLA FLA
1
460/60/3 575/60/3
Compressor hp Refrigerant
6 R-410A 21.0 182 19.0 164 8.4 75.0 6.8 54 7 R-410A 20.2 182 19.6 164 11.6 100 9.8 78 8 R-410A 23.2 216 22.5 195 11.3 95.0 9.0 80
9 R-410A 26.9 249 25.0 225 12.6 114.0 9.6 80 10 R-410A 30.3 264 28.2 239 14.2 125.0 10.6 80 1 1 R-410A 35.4 271 32.0 245 15.5 125 12.6 100 13 R-410A 40.8 332 38.5 300 18.3 150.0 17.4 109 15 R-410A 49.8 376 48.4 340 18.5 173.0 20.2 132

Supply Power Wiring

1 Units require three-phase power supply.
208V/60Hz/3Ø 230V/60Hz/3Ø 460V/60Hz/3Ø 575V/60Hz/3Ø
RLA LRA RLA LRA RLA LRA RLA LRA
5 Size wires for a maximum of 3% voltage drop.
Lug Size
2 Allowable voltage tolerances:
a 60 Hertz
Nameplate 208 V: Min. 187 V, Max. 229 V Nameplate 230 V: Min. 207 V, Max. 253 V Nameplate 460 V: Min. 414 V, Max. 506 V Nameplate 575 V: Min. 518 V, Max. 632 V
b 50 Hertz
Nameplate 400 V: Min. 342 V, Max. 418 V
3 Power lead wire sizing:
a For units with cooling capability (all concurrent
loads) with or without hot water heating and circuits with motor loads only:
Table 33: Lug sizes for single disconnect
DIsconnect size Lug size
100 #12-3/0 150 #12-3/0 250 #8-350 MCM 400 (2) #8-600 MCM 600 (2) #8-600 MCM
Table 34: Lug sizes for power block
Power block size Lug size
310 #6- 350 MCM 420 #2- 600 MCM 570 (2) #4-300 MCM
Note: Use copper wire only.
760 (2) #6-500 MCM
MCA = 1.25 (largest motor RLA or FLA) + other loads
4 Size wires in accordance with Table 310-16 or Table
310-19 of the National Electrical Code.
McQuay Catalog 860-9 65

Unit Weights

Unit Weights
Table 35: Unit and Component Weights for Small and Small Tall Cabinets
Small Cabinet
Component Description
Unit Model Size
023 028 033 039 044 050
Basic Cabinet
1
3587 3637 3651 3994 4008 4008
Cooling Coil Section–Drain Pan Only 1045 1081
Supply Fan/Control Panel Section 1061 993
Condenser/Compressor Section 1480 1530 1544 1920 1934 1934
Condenser Water Weight 29 31 35 44 47 50
Face Load Filter Rack
Rack Only 64 67 2"—MERV 7 15 16 4"—MERV 8 15 16
4"—MERV 11 62 63 4"—MERV 13 62 63 4"—MERV 14 62 63
Evaporator Coils
5 row–12 fpi 372 N/A
Large 5 row–12 fpi N/A 440
Waterside Economizer Coils
Large 4 row–12 fpi 316 371
Water Weight 117 152
Electric Heat
34 kW 20 20
Supply Fan Assembly
13" SWSI 106 N/A 15" SWSI 110 N/A 16" SWSI 122 N/A 18" SWSI 181 181 20" SWSI 195 195 22" SWSI 245 245 24" SWSI 267 267 27" SWSI N/A 395
Supply Fan Motor–ODP
3 HP 76 76 5 HP 88 88
7.5 HP 134 134 10 HP 158 158 15 HP 203 203 20 HP 235 235
Supply Fan Motor–TEFC
3 HP 77 77 5 HP 91 91
7.5 HP 150 150 10 HP 184 184 15 HP 253 253 20 HP 321 321
Variable Frequency Drive
3 HP 14 14 5 HP 14 14
7.5 HP 20 20 10 HP 20 20 15 HP 35 35 20 HP 35 35
Discharge Plenum
32" High without Sound Baffles 268
32" High with Sound Baffles 428
Note: 1 Basic unit consists of a cooling coil section without coils, a supply fan/control panel section without supply fans, supply fan motors or VFD and a
condenser/compressor section.
Small Tall Cabinet
66 McQuay Catalog 860-9
Unit Weights
Table 36: Unit and Component Weights for Medium and Large Cabinets
Medium Cabinet Large Cabinet
Component Description
Basic Cabinet
Cooling Coil Section–Drain Pan Only 1288 1542
Supply Fan/Control Panel Section 1377 1853
Condenser/Compressor Section 2067 2081 2470 2470 2470 2784 3506 3534 3562
Condenser Water Weight 52 55 61 64 68 67 85 88 91
Face Load Filter Rack
Rack Only 95 116 2"—MERV 7 22 27 4"—MERV 8 22 27
4"—MERV 11 91 112 4"—MERV 13 91 113 4"—MERV 14 91 113
Evaporator Coils
Large 5 row–12 fpi 668 776
Standard 6 row—12 fpi N/A 776 776 776
Waterside Economizer Coils
Large 4 row–12 fpi 557 654
Water Weight 250 279
Electric Heat
34 kW 20 20 68 kW 40 40
Supply Fan Assembly
18" SWSI 181 N/A 20" SWSI 195 N/A 22" SWSI 245 245 24" SWSI 267 267 27" SWSI 395 395 30" SWSI 434 434 33" SWSI 592 592 36" SWSI 723 723
Supply Fan Motor–ODP
15 HP 203 N/A 20 HP 235 N/A 25 HP 290 290 30 HP 336 336 40 HP 434 434 50 HP N/A 723
Supply Fan Motor–TEFC
15 HP 253 N/A 20 HP 321 N/A 25 HP 354 354 30 HP 416 416 40 HP 538 538 50 HP N/A 612
Variable Frequency Drive
15 HP 35 N/A 20 HP 35 N/A 25 HP 53 53 30 HP 53 53 40 HP 53 53 50 HP N/A 152
Discharge Plenum
32" High without Sound Baffles 320 416
32" High with Sound Baffles 516 680
Note: 1 Basic unit consists of a cooling coil section without coils, a supply fan/control panel section without supply fans, supply fan motors or
VFD and a condenser/compressor section.
1
044 050 056 062 065 062 073 080 088
4733 4747 5136 5136 5136 6179 8507 8563 8619
Unit Model Size
McQuay Catalog 860-9 67
Unit Weights
Table 37: Unit and Componen t Weights for Large Tall Cabinets
Large Tall Cabinet
Component Description
065 073 080 088 099 105 120 130
Basic Cabinet
Cooling Coil Section–Drain Pan Only 1610 1600
Supply Fan/Control Panel Section 2091 2276
Condenser/Compressor Section 2776 3498 3526 3554 3554 4424
Condenser Water Weight 70 85 88 91 102 128 134 141
Face Load Filter Rack
Rack Only 138 2"—MERV 7 32 4"—MERV 8 32
4"—MERV 11 132 4"—MERV 13 132 4"—MERV 14 132
Evaporator Coils
Large 5 row–12 fpi 1054 ——————— Large 6 row–12 fpi 1054 1054 1054 1054 1054 1054 1054
Waterside Economizer Coils
Large 4 row–12 fpi 879
Water Weight 331
Electric Heat
34 kW 20 68 kW 40
Supply Fan Assembly
24" SWSI 267 27" SWSI 395 30" SWSI 434 33" SWSI 592 36" SWSI 723 40" SWSI 856 44" SWSI 1101
Supply Fan Motor–ODP
25 HP 290 30 HP 336 40 HP 432 50 HP 494 60 HP 675
Supply Fan Motor–TEFC
25 HP 354 30 HP 416 40 HP 538 50 HP 612 60 HP 905
Variable Frequency Drive
25 HP 53 30 HP 53 40 HP 53 50 HP 152 60 HP 152
Discharge Plenum
32" High without Sound Baffles 416
32" High with Sound Baffles 680
Note: 1 Basic unit consists of a cooling coil section without coils, a supply fan/control panel section without supply fans, supply fan motors or VFD and a
condenser/compressor section.
1
6476 7199 7227 7255 7255 8300 8300 8300
Unit Model Size
68 McQuay Catalog 860-9
McQuay Training and Development
Now that you have made an investment in modern, efficient McQuay equipment, its care should be a high prior ity . For training information on all McQuay HVAC products, please visit us at www.mcquay.com and click on training, or call 540-248-9646 and ask for the Training Department.
Warranty
All McQuay equipment is sold pursuant to its standard terms and conditions of sale, including Limited Product Warranty. Consult your local McQuay Representative for warranty details. Refer to Form 933-430285Y. T o find your local McQuay Representative, go to www.mcquay.com.
Aftermarket Services
To find your local parts office, visit www.mcquay.com or call 800-37PARTS (800-377-2787). To find your local service office, visit www.mcquay.com or call 800-432-1342.
This document contains the most current product information as of this printing. For the most up-to-date product information, please go to www.mcquay.com.
Products manufactured in an ISO certified facility.
© 2011 McQuay International • www.mcquay.com • 800-432-1342 11/11
Loading...