McQuay SWP 018, SWP 023, SWP 028, SWP 035, SWP 040 Installation Manual

...
Installation and Maintenance IM-708
Self-contained Air Conditioning System
Type SWP Vintage Sizes 18D thru 95D, 105E
MEA
Group: Applied Systems Part Number: IM708 Date: February 2002
© 2001 McQuay International
Table of Contents
Introduction
General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Inspection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
SWP-055-D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Vibration Isolators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Setting Factory Supplied Plenum. . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Location/Service Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Removal of Shipping Restraints . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Refrigerant Piping . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Pressure Relief Valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Water Connections . . . . . . . . . . . . . . . . . . . . . . . . . 6
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Condenser Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Condensate Drain Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Duct Connections . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Supply Air. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Return Air . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . . 11
Unit Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Field Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Unit Disconnect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Return Air and Outside Air Sensor. . . . . . . . . . . . . . . . . . . . . . . . . 14
Supply Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Lug Sizes For Single Disconnect or Power Block . . . . . . . . . . . . . 16
Control Center . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Electrical Legend . . . . . . . . . . . . . . . . . . . . . . . . . 18
Typical Wiring Schematics . . . . . . . . . . . . . . . . . . 19
Figure 19. Power Schematic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Figure 20. Input Schematic, Discharge Air Control (DAC). . . . . . . 20
Figure 21. Input Schematic, Zone or Space Comfort Control (SCC) 21
Figure 22. Output Schematic, Actuator Control . . . . . . . . . . . . . . 22
Figure 23. Output Schematic, Auxiliary Fan Start/Stop Control . . 23
Figure 24. Output Schematic, Actuator Control . . . . . . . . . . . . . . 24
Figure 25. Output Schematic, Compressor Control (4 Compressors/4,
5 or 6 Stage) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Figure 26. Output Schematic, Compressor Control (6 Compressors /
6 Stage) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Standard Controls . . . . . . . . . . . . . . . . . . . . . . . . . 27
High Pressure Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Low Pressure Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Compressor Motor Protector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Proof of Airflow Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Frost Protection Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Clogged Filter Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Unit Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Duct High Limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Phase Fail/Under Voltage Protection . . . . . . . . . . . . . . . . . . . . . . 28
Duct Static Pressure Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Mounting instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Building Static Pressure Sensor. . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Building pressurization applications . . . . . . . . . . . . . . . . . . . . 29
Freezestat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Condenser Water Flow Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Water Side Economizer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Condenser Water, Head Pressure Control. . . . . . . . . . . . . . . . . . . 30
Variable Inlet Vanes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Adjustable Frequency Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Disconnect Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Dual Power Supply. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Battery Pack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Electric Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Hot Water Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
System Check, Test and Start . . . . . . . . . . . . . . . 31
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Pre Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Fan start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Compressor start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Economizer start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Hot water start-up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Expansion valve superheat adjustment . . . . . . . . . . . . . . . . . 32
Refrigerant Charge. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Variable air volume (VAV) start-up . . . . . . . . . . . . . . . . . . . . 34
Rpm changes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Drive sheave alignment and belt tension . . . . . . . . . . . . . . . . 34
Final control settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Maintaining control parameter records . . . . . . . . . . . . . . . . . 35
System Maintenance . . . . . . . . . . . . . . . . . . . . . . . 36
Preventative Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Motor Bearings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . 37
Service and Warranty Procedure . . . . . . . . . . . . . 38
In Warranty Return Material Procedure . . . . . . . . . . . . . . . . . . . . . 38
Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Product Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Check, Test and Start Procedure Form . . . . . . . . 39
Copyright © 2001 McQuay International. All rights reserved throughout the world.
2 IM708
Introduction
General Description
Models SWP018 through 105 are factory assembled, refrig­erant charged and tested, water cooled packaged air condi­tioning units designed for ducted applications.
Each unit contains multiple hermetic compressors, water cooled condensers, multi-circuit evaporator, thermal expan­sion valves, interconnecting refrigerant piping, forward curved centrifugal fan, belt drive, fan motor, pleated filters and all necessary operating and safety controls.
All rigging, installation, power and control wiring external to the unit, and condenser water and condensate piping are the responsibility of the installer.
The MicroTech II self-contained unit controller is standard equipment. For a detailed description of the MicroTech II components, input/output configurations, field wiring options and requirements, and service procedures, refer to Bulletin No. IM 710, "MicroTech II Self-contained Unit Controller." For a description of operation and information on using and programming the MicroTech II unit controller, refer to the appropriate operation manual (see Table 1).
Table 1: Self-contained unit operation manual literature
UNIT CONTROL CONFIGURATION
Variable Air Volume (VAV) Discharge Air Control (DAC)
Constant Air Volume Space Comfort Control (SCC)
Constant Air Volume Discharge Air Control (DAC)
OPERATION MANUAL
BULLETIN NUMBER
OM711
OM712
OM711
Inspection
When the equipment is received, all items should be care­fully checked against the bill of lading to insure a complete shipment. The shipping receipt should not be signed until all items have been accounted for. All units should be carefully inspected for damage upon arrival. All shipping damage should be reported to the carrier and a claim filed. The unit serial plate should be checked before unloading the unit to be sure that it agrees with the power supply available.
Nomenclature
SWP-055-D
Self-contained Water cooled Plenum discharge
IM708 3
Vintage
Nominal tons
Installation
Note: Installation and maintenance are to be performed
only by qualified personnel who are familiar with local codes and regulations, and experienced with
this type of equipment.
CAUTION
Sharp edges and coil surfaces are a potential injury hazard. Avoid contact with them.
Handling
Units are shipped with a protective covering which should remain in place while the unit is being moved to its final location. Note: Check for concealed damage as soon as pos­sible.
Never allow any part of the unit to fall during unloading or moving as this may result in serious damage. Units are pro­vided with lifting lugs for rigging with a crane. If units are lifted by crane, protection against chaffing damage by slings or cable must be provided and spreader bars must be used across the top of the cabinet to prevent any structural damage to the frame.
The unit base frame will accept dollies or Johnson bars for transporting the unit. Furniture dollies can be placed at both ends of the chassis or at one end and a Johnson bar used at the other end for maneuvering.
CAUTION
required. Foam rubber gasket is provided around the perime­ter of unit top. Carefully set plenum. Attach with mounting hardware provided with the plenum.
Location/Service Access
For good installation, service and maintenance access the following recommended clearances should be followed. Minimum clearances required by local, state, or federal codes, such as the NEC take precedence over those listed below. Clearance is required to allow room for side filter access, mechanical cleaning of the condenser tubes and economizer coil, access to expansion valves and other con­trol components and to allow for possible fan shaft or com­pressor removal.
Unit front - 42" Unit rear - 24"
Motor location side - 36" Piping location side - 36"
Side without motor or piping -24"
Figure1. Recommended Service and Maintenance
Clearance
Airflow
24"
Do not attempt to install dollies in the center of the unit.
CAUTION
Units must not be moved in an upended position.
Floor surfaces must be protected when equipment is moved across finished flooring. Plywood sheeting may be used to protect surfaces and distribute weight loading.
Vibration Isolators
All units are provided with 1” neoprene isolation pads, shipped separately. Pads are to be installed beneath the unit and located at each corner and the center of each base chan­nel. For units provided with more than six (6) isolator pads, evenly space the additional pads under the front and rear base channels.
Setting Factory Supplied Plenum
If the unit is provided with a factory plenum for field mount­ing, a forklift, slings or other suitable lifting means is
Evapora tor C oil
24"
or
36"
Compressors
1
35642
VFD
42"
36"
Removal of Shipping Restraints
Mechanical restraints are used to secure the spring mounted fan during shipment. Restraints and shipping blocks must be removed after unit has been set in its final location.
4 IM708
Refrigerant Piping
Pressure Relief Valves
All units have individual condensers per refrigerant circuit and each condenser is provided with a spring loaded relief valve. The valve is set to open when refrigerant pressure reaches 400 psig. The relief valve will accommodate a 1/2"
flare connection for applications where it is necessary to connect vent piping and run it outside the building.
CAUTION
When refrigerant is vented to the outside of the building, the vent piping should be installed as recommended in ASHRAE Standard 15-1994.
IM708 5
W ater Connections
General
Due to the variety of piping practices, it is advisable to fol­low the recommendations of local authorities. They can sup­ply the installer with the proper building and safety codes required for a safe and proper installation.
The piping should be installed with a minimum number of bends and elevation changes for best performance. Piping should contain:
1. Vibration eliminators to reduce vibration and noise transmission to the building.
2. Shutoff valves to isolate the unit from the piping system during unit servicing.
3. Manual or automatic air vent valves at the high points of the system.
4. Some means of maintaining adequate system water pressure (e.g., expansion tank or regulating valve).
5. Temperature and pressure indicators located at the unit to aid in servicing.
6. A strainer or some means of removing foreign matter from the water before it enters the pump. It should be placed far enough upstream to prevent cavitation at the pump inlet (consult pump manufacturer for recommen­dations). The use of a strainer will prolong pump life and help maintain system performance.
7. Size piping to minimize system pressure drop.
mizer will typically elevate the water temperature by 5 to 10°F before entering the condenser, allowing suitable condenser water temperatures whenever the tower sup­ply temperature is 50°F or higher. Mechanical cooling is locked out below 55°F EWT.
6. Head pressure control must be provided if entering con­denser water temperatures will go below 55°F. Fan cycling and/or modulating discharge dampers on the cooling tower are often used, or a 3-way bypass around the tower to maintain condenser water temperature. Cooling tower control to maintain the temperature at >55°F is generally more cost effective if multiple units are in the loop. If valves are installed on the individual SWP units, a single water regulating valve controlled by circuit #1 head pressure should be used. The Lead/Lag option needs to equal “NO”. When Lead/Lag equals “NO” circuit #1 is always first on and last off. The refrigerant pressure line from the valve should be con­nected to a gauge port on any liquid line service valve located in the compressor #1 refrigerant circuit. Com­pressor #1 is located at the far left of the cabinet.
If the water regulating valve is placed in service with the
unit condensers, it should be installed in the water line leav­ing the condenser and should shut down to prevent water from siphoning out of the condensers. For systems where a constant pumping head is required, the water regulating valve may be installed in a bypass line around the condens­ers. It must then open on falling discharge pressu re.
Condenser Piping
1. Units may be specified with water and condensate con­nections on either the left or right side of the unit.
2. All units have an individual condenser per refrigerant
circuit. All condensers are factory piped for a common condenser water supply and a common condenser water return connection.
3. Field piping connections are made to factory provided
piping located as indicated on the unit submittal draw­ings. The piping connections are run to the outside of the unit cabinet. Connections are located behind a fac­tory mounted shipping cover. All connections are cop­per sweat connections as indicated on unit dimensional drawings.
4. Supply and return water connections must be made at the proper locations as indicated by the dimensional drawings. Supply (water in) connection is always the lower connection.
5. Units with factory mounted water side economizer
should not require head pressure control. The econo-
These typical systems, depending on the specific appli­cation, must maintain a constant condensing pressure regard­less of temperature conditions and must assure adequate head pressure for proper thermal expansion valve operation. A minimum head pressure of 180 psi (95°F condensing tem­perature) is recommended.
7. Condenser tube velocities must not exceed 10 feet per
second.
Figure2. Condenser Regulating Valve (refrigerant
pressure controlled
)
6 IM708
Figure3. Condenser water pressure drop SWP018 -
SWP040
40
24 HP
28 HP
12 HP
18 HP
32 HP
36 HP
40 HP
Figure5. Economizer water pressure drop, SPW018-
SPW105
50
035-040
045-095
105
018-028
20
O)
2
10
8
Pressure Drop (ft H
6
4
3
20
60 80
40
Condenser Flow Rate (gpm)
100
200 300
Note: HP = total unit compressor horsepower.
Figure4. Condenser water pressure drop SWP045 -
SWP105
60
O)
Pressure Drop (ft H
40
20
2
10
8 6
40HP
46HP
52HP
56HP
60HP
70HP
80HP
78HP
84HP 90HP
105HP 120HP
O)
2
10
Pressure Drop (ft H
1
Note:
10
Condenser Flow Rate (gpm)
!
Includes coil, control valves and interconnecting
100 500
piping.
"
Add thisP to condenser P to obtain unit ∆P
for pump selection.
Figure6. Water regulating valve pressure drop.
Head pressure control
40
10
O)
2
018-040
4
2
80 100
200 300
Condenser Flow Rate (gpm)
Note: HP = total unit compressor horsepower.
IM708 7
400 500
Pressure Drop (ft H
0.1
045-095
1
10
100
500
Condenser Flow Rate (gpm)
Figure7. Hot water coil pressure drop, SWP018 -
SWP040
100
018
035
023-028
040
O)
2
10
Pressure Drop (ft H
1
10
100
Water Flow Rate (gpm)
Hot water coil pressure drop, SWP045 - SWP105
100
Condensate Drain Connection
The condensate drain connection is 1 1/8" O.D.S. copper and is located on the same end of the unit as the condenser water connections. The drain is internally trapped at the factory requiring no external trap. The condensate line should be pitched away from the unit with a minimum slope of 1/8" per foot.
Drain pans and the drain trap should be kept clean by peri­odic cleaning. A cleanout is provided as standard in the trap to aid in cleaning.
200
O)
2
10
Pressur e Drop (ft H
1
10 100
Water Flow Rate (gpm)
055
045
065-095
105
200
8 IM708
Duct Connections
Supply Air
For connection of supply ductwork directly to the unit, a duct collar must first be mounted at the fan outlet, avoiding the mounting screws located around the perimeter of the fan discharge opening (see Figure 8). Fan discharge opening sizes are indicated on the unit dimensional drawings. When connecting ductwork to the unit, a canvas type connecting collar is recommended.
Units are available in two fan configurations and should be ducted as shown in Figure 9. Duct take-offs which go oppo­site to the direction of fan rotati on will result in an associated system effect loss and reduced fan performance.
If a field fabricated plenum is used, duct take-off locations should again be correctly oriented to the rotation of the fan to minimize system losses. Refer to unit dimensional drawings and Figure 8 for plenum mounting size requirements. Can­vas type connectors are recommended at the duct connection to the plenum.
Units are also available with a factory provided discharge plenum. Supply duct connections to the plenum opening(s) should include a canvas type connector. Plenum opening sizes and locations will be indicated on the job submittal.
Figure8. Unit top detail
Figure9. Discharge duct configurations
Return Air
Return air to the unit can be arranged in two ways.
1. Ducted return
Return ductwork may be attached to the 2" flange around the perimeter of the unit's return air opening (Refer to Figure
10). A canvas type duct connecting collar is recommended. All ductwork connected to the unit should be of adequate size and construction for the application. A canvas type con­nector is also recommended where the duct penetrates the machine room wall(s). This will prevent vibration generated by air movement in the duct from being transmitted out to the occupied spaces.
Note: Do not obstruct unit access panel located below the
return opening.
2. Free return
The mechanical equipment room may be used as a return plenum with no hard connection at the unit.
Note: Some building codes do not allow the use of the
mechanical room as a return plenum. Applicable local codes should be checked for each installation.
Figure10.Back Elevation
(Optional) Multi-Directional Plenum
29”
K x L
Return Air Opening
D
B
Mechanical Access
(See Notes)
(See Notes)
2.0” Typical
2.0”
M
1” Neoprene Isolation Pads, Shipped Separately
B25
IM708 9
Physical Data
Table 2: SWP 018 Through SWP 105
Data
Compressor Quantity 2, 3, 4 3, 4 4 4 4 4 4 4 4 4 4, 6 6 Size See Unit Data Plate Evaporator Coil
Face Area (Ft.2) Rows 4, 6 4, 6 4, 6 4, 6 4, 6 4, 6 6 6 6 6 6 6 Fpi 12 12 12 12 12 12 12 12 12 12 12 12 Waterside Economizer Coil
Face Area (Ft.2) Rows 4444 4 4 4 4 4 4 4 4 Fpi 12 12 12 12 12 12 12 12 12 12 12 12 Maximum Working Pressure
(psig) Hot Water Heating Coil
Face Area (Ft.2) Rows 1, 2 1, 2 1, 2 1, 2 1, 2 1, 2 1, 2 1, 2 1, 2 1 1 1 Fpi 12 12 12 12 12 12 12 12 12 12 12 12 Electric Heat Kw 34 34 34 34 34 68 68 68 68 68 68 68 Filters
(Quantity) Size 4” Depth
Evaporator Fan Quantity 1111 1 1 1 1 1 1 1 1 Size 15 18 18 20 20 22 25 25 25 27 27 33 Minimum Horsepower 5 7.5 10 10 15 15 20 20 20 25 30 40 Maximum Horsepower 10 15 20 20 25 30 40 40 40 50 60 60 Minimum Design cfm, CV 2950 3825 4425 5825 6925 7675 9025 10375 11575 12775 13975 15800 Minimum Design cfm, VAV 4720 6120 7080 9320 11080 12280 14440 16600 18520 20440 22360 25280 Maximum Design cfm 7080 9180 10620 13980 16620 18420 21660 24900 27780 30660 33540 37920 Condenser Quantity 2, 3, 4 3, 4 4 4 4 4 4 4 4 4 4, 6 6 Waterside Working Pressure
(psig) Minimum Entering
Temperature (F) Minimum GPM 25 41 53 66 69 94 105 105 121 134 138 180 Maximum GPM 88 108 125 159 166 215 237 237 251 349 358 493
a
a. Standard fan TSP limit is 5.5 inch of water. Consult your local McQuay sales representative for applications beyond this range.
018 023 028 035 040 045 055 065 070 080 095 105
11.8 15.3 17.7 23.3 27.7 30.7 36.1 41.5 46.3 51.1 55.9 63.2
11.8 15.3 17.7 23.3 27.7 30.7 36.1 41.5 46.3 51.1 55.9 63.2
400 400 400 400 400 400 400 400 400 400 400 400
9.3 12.8 15.2 20.2 24.5 26.8 30.4 35.8 39.9 44.4 48.3 51.9
(6)20x20x4 (2)25x20x4
(6)20x20x4 (2)25x20x4
400 400 400 400 400 400 400 400 400 400 400 400
55° 55° 55° 55° 55° 55° 55° 55 55° 55° 55° 55°
(6)20x20x4 (2)25x20x4
(10)25x20x4 (10)25x20x4 (12)25x20x4 (12)25x20x4 (18) 20x20x4 (6)16x20x4
SWP Model Size
(12)25x20x4
(3)20x20x4 (15)25x20x4
(6)16x20x4 (15)25x20x4
(4)16x20x4 (17)20x25x4 (1)16x25x4
Table 3: Compressor circuit charge
COMPRESSOR
(HP)
69 lbs.66 10 14 lbs. 112 13 18 lbs. 128 15 22 lbs. 256 20 27 lbs. 256
*Charge quantities listed are average. Actual cha rg e qu an tity is dependent on
individual unit evaporator coil circu iting. Actual char ge quantities are st amped on each unit nameplate.
10 IM708
*REFRIGERANT
CHARGE PER
CIRCUIT (R-22)
OIL CHARGE PER CIRCUIT
(OZ.)
Dimensional Data
Figure 1 1. Left Side Front (CW) Disch arge with 0ptional Multi-Directional Plenum
(Optional)
Multi-Directional
Plenum
(See Notes)
K x L Return Air
3.25”
19.0"
14.75”
8.75”
Filter Section
Outlet
Inlet
G
Heater
Evaporator
Economizer
A
J
Electrical Panel
A21
Figure 12. Left Side Back (CCW) Discharge with 0ptional Multi-Directional Plenum
9.63"
(18-95)
10.31
(Optional)
Multi-Directional
Plenum
(See Notes)
K x L Return Air
3.25”
19.0"
14.75”
Heater
Evaporator
Economizer
Filter Section
Outlet
Inlet
A
8.75”
(105)
Electrical Panel
A22
Note: Select unit arrangement on the unit selection.
Plenum can be shipped separately. Please indicate on the unit submittal. Indicate size and location of plenum openings on the unit submittal. All open­ings are on plenum centerline. For additional information refer to plenum certified drawing .
Table 4:
BASIC UNIT 018 023 028 035 040 045 055 065 070 080 095 105
A B
D FFan Disch. 18.62 21.88 21.88 24.75 24.75 27.25 31.25 31.25 31.25 34.25 34.25 47.25
G Fan Disch. ^ Opening 15.88 18.88 18.88 24.75 24.75 27.25 31.25 31.25 31.25 34.25 34.25 34.94
H Fan Disch. Location 32.69 31.06 31.06 37.62 37.62 46.38 44.38 44.38 50.38 54.88 60.88 54.40 J Fan Disch. Location 22.50 18.81 18.81 20.12 20.12 21.06 21.32 21.32 21.32 23.82 23.82 33.46 K Return Opening Height 41.44 41.44 41.44 51.44 51.44 51.44 51.44 62.20 62.20 62.20 62.20 70.20 L Return Opening Length 80.00 80.00 80.00 96.00 96.00 116.00 116.00 116.00 128.00 140.00 152.00 152.00
M Base of Return Opening 28.62 28.62 28.62 28.62 28.62 28.62 28.62 23.87 23.87 23.87 23.87 23.87
N Water Out/In (ODS) 2-1/8 2-1/8 2-1/8 2-5/8 2-5/8 2-5/8 3-1/8 3-1/8 3-1/8 3-1/8 3-1/8 3-1/8 P 1 Row HW Donn (ODS) 1-5/8 1-5/8 1-5/8 1-5/8 1-5/8 1-5/8 1-5/8 1-5/8 2-1/8 2-1/8 2-1/8 2-1/8 P 2 Row HW Conn (ODS) 1-5/8 1-5/8 1-5/8 1-5/8 1-5/8 2-1/8 2-1/8 2-1/8 2-1/8 - - -
b
Deptha
b
Lengtha
b
Heighta
a. Dimensions do not include handle, latch or fastener extensions. b. For shipping dimensions add 4" (102mm) to depth, 8" (204mm) to length, and 4" (102mm) to height.
72.00 72.00 72.00 72.00 72.00 81.00 81.00 81.00 81.00 84.00 84.00 96.00
84.00 84.00 84.00 100.00 100.00 120.00 120.00 120.00 132.00 144.00 156.00 156.00
82.00 82.00 82.00 82.00 82.00 82.00 82.00 88.00 88.00 88.00 88.00 96.00
IM708 11
Figure 13. Unit Front Plan
Return Air
Left Side
Piping Connections
(See Notes)
Figure 14. Front Elevation
ASD (Optio nal)
MicroT ech II Panel
D
Supply Fan Motor
Disconnect Switch (Optional)
Power Entry 7/8" Pilot K.O.
Electrical Access
(Optional) Right Side Piping Connections (See Notes)
A23
72"
Figure 16. Left Side
K x L Return Air
1-1/8” ODS Drain
(N) W a te r O ut
(N) W ater In
Lifting Lug
1” Typ.
A/2
A
Figure 17. Discharge Plenum (Optional)
Plan View
Depth
Multi-Directional
(Optional)
Plenum (See Notes, Page 11)
(P) Ho t W a te r O u t
(P) Ho t W a te r In
44.5”
38.5”
Mechanical Access
B
Note: Service connections determined when facing the front of the
unit. Left-hand standard, right-hand optional. Please indicate on the unit submittal.
Note: Unit sizes 018, 023 and 028 have a single mechanical access
panel in bottom front and bottom back.
Figure 15. Back Elevation
H H
29”
D
Mechanical (See Notes)
F
K x L
Return Air O pening
B
Access
Multi-Directional Plenum (See Notes, Page 11)
2.0” Typical
2.0”
M
1” Neoprene Isolation Pads, Shipped Separately
(Optional)
Length
29”
Front/Back Elevation
H
A
3”
2” Min
29”
Left/Right Elevation
H
B
Table 5. Discharge Plenum
Unit Size Length (in.) Depth (in.) Height (in.) 018D-028D 84 72 29 035D-040D 100 72 29 045D-065D 120 81 29
070D 132 81 29 080D 144 84 29
095D-105D 156 84 29
3”
A27
2” Min
12 IM708
Unit Weights
Table 6. Unit and Component Weight in lbs.
Unit Weights
Basic Configuration SWP basic unit
Filters
4" 30% or 65% efficiency 38 38 38 55 55 66 66 79 87 96 104 112
Evaporator Coil
6 Row, 12 fpi 250 294 321 417 468 506 577 642 693 755 819 926 4 Row, 12 fpi 206238257333368395------
Water Economizer Coil
4 Row, 12 fpi 306 338 357 458 493 520 598 648 678 723 820 927 Water weight 51 66 75 94 111 119 150 168 187 203 218 281
Hot Water Coil
1 Row, 12 fpi 71 97 114 130 158 160 170 200 328 337 345 371 Water weight 16 20 23 28 32 37 41 49 55 59 62 62
Electric Heat
34 KW 2020202020------­68 KW -----40404040404040
Supply Fan Motors
3 HP ODP 71------ ---­5 HP ODP 82------ ----
7.5 HP ODP 124124----- -- -­10 HP ODP 144 144 144 144 - - - - - - ­15 HP ODP - 185 185 185 185 185 - - - - ­20 HP ODP - - 214 214 214 214 214 214 214 - - ­25 HP ODP - - - - 266 266 266 266 266 266 - ­30 HP ODP - - - - - 310 310 310 310 310 310 ­40 HP ODP ------404404404404404404 50 HP ODP ------- -452452452 60 HP ODP ------- --620620 75 HP ODP ------- ---836 3 HP TEFC 72------ ---­5 HP TEFC 85------ ----
7.5 HP TEFC 140140----- ---­10 HP TEFC 170 170 170 170 - - - - - - ­15 HP TEFC - 235 235 235 235 235 - - - - ­20 HP TEFC - - 300 300 300 300 300 300 300 - - ­25 HP TEFC - - - - 330 330 330 330 330 330 - ­30 HP TEFC - - - - - 390 390 390 390 390 390 ­40 HP TEFC ------510510510510510510 50 HP TEFC ------- -570570570 60 HP TEFC ------- --850850 75 HP TEFC ------- ---900
Compressor/Condens e r As sembly
(2)6HP 26 368------ ---­(3)6HP 35 538538----- ---­(4)6HP 43 699 699 699 699 - - - - - - ­(3)6HP, (1)10HP 57 - 843 843 843 843 - - - - - ­(2)6HP, (2)10HP 66 - - 974 974 974 - - - - - ­(1)6HP, (3)10HP 74 - - - 1115 1115 - - - - - ­(4)10HP 95 - - - 1263 1263 1263 1263 1263 - - - ­(2)10HP, (2)13HP 106 - - - - - 1404 1404 1404 - - - ­(4)13HP 118 - - - - - 1549 1549 1549 1549 - - ­(2)13HP, (2)15HP 129 - - - - - 1709 1709 1709 1709 1709 1709 ­(4)15HP 141 - - - - - 1867 1867 1867 1867 1867 1867 ­(2)15HP, (2)20HP 152 -------198219821982 1982 ­(4)20HP 190 ------- -2096 2096 ­(6)13HP 167 ------- --22652265 (3)13HP, (3)15HP 178 ------- --24792479 (6)15HP 188 ------- --26932693 (3)15HP, (3)20HP 209 ------- --29142914 (6)20HP 229 ------- --31353135
Discharge Plenum
Factory Installed, 29” 636 636 636 711 711 862 862 862 922 1003 1064 1064
a. Base Weight includes supply fan without motor. b. Water economizer weight includes valves and piping. c. The values in this table do not include water weight.
d. Hot water coil weight includes valve and piping.
a
b c
d
c
Water Weight
018 023 028 035 040 045 055 065 070 080 095 105
2226 2313 2318 2638 2643 3110 3279 3406 3734 4021 4246 4673
Unit Size
IM708 13
Field Wiring
General
Wiring must comply with all applicable codes and ordi­nances. Warranty is voided if wiring is not in accordance with specifications. An open fuse indicates a short, ground or overload. Before replacing a fuse or restarting a compressor or fan motor, the trouble must be found and corrected. Cop­per wire is recommended for all power lead terminations. Contact factory for information concerning aluminum wire power lead terminations.
A single power terminal block is provided as standard and wiring within the unit is done in accordance with the National Electric Code. All branch circuits within the control panel are individually fused. A single field supplied discon­nect is required or a unit mounted nonfused disconnect can be ordered with the unit.
A 7/8” knockout is located on the right-hand unit upright for locating unit power entry. 24V field connections are suitable for Class II wiring.
Unit Disconnect
Disconnecting means are addressed by Article 440 of the National Electric Code (NEC) which requires 'disconnecting means capable of disconnecting air conditioning and refrig­erant equipment including motor-compressors, and control­lers, from the circuit feeder." The disconnect switch should be selected and located within the NEC guidelines. Location requirements per NEC are that the disconnect be located in a readily accessible position within sight (50 feet) of the unit.
A factory mounted nonfused disconnect is available.
Table 7. Compressor Motors
Compressor
HP
6 10 13 15 20
208/60/3 230/60/3 400/50/3 460/60/3 575/60/3
RLA LRA RLA LRA RLA LRA RLA LRA RLA LRA
17.9 156.0 16.2 156.0 8.1 70.0 8.1 70.0 6.5 54.0
31.2 239.0 28.2 239.0 14.1 125.0 14.1 125.0 11.3 80.0
35.6 350.0 32.0 350.0 16.0 158.0 16.0 158.0 12.8 125.0
42.1 425.0 38.0 425.0 19.0 187.0 19.0 187.0 15.2 148.0
74.0 360.0 67.2 360.0 33.6 180.0 33.6 180.0 36.9 144.0
Return Air and Outside Air Sensors
All units are provided with a return air sensor. The outside air sensor is optional and can be ordered with the unit. The return air sensor is connected to the input control board and is coiled up and placed in the control box of the unit for ship­ment. The return air sensor must be field installed in the return air stream for proper unit operation. The outside air sensor is shipped loose in a package and is located on the floor of the fan section. The mixed air temperature sensor is already installed at the inlet of the unit.
The sensors must be mounted in areas that are exposed to representative temperature conditions. The sensor should be mounted at a position that has good air mixing and does not have stratification. The sensor can be mounted in the duct­work using a grommet, see Figure 18.
Figure 18. Return/Outside Air Sensor Mounting
Sensor
Ductwork
The return air sensor is connected to the unit’s input board at location AI4, see IM710. The outside air sensor is field wired to terminal strip TB2. The sensor is to be connected at terminals 124 and 125.
Grommet
Table 8. Electric Heaters
SWP UNIT SIZE
018 - 040
045 - 105
14 IM708
208V/60HZ/3PH 230V/60HZ/3PH 400V/50HZ/3PH 460V/60HZ/3PH 575V/60HZ/3PH
kW MBH FLA kW MBH FLA kW MBH FLA kW MBH FLA kW MBH FLA
27.8 94 77.2 34 116 85.6 25.7 88 37.2 34 116 42.8 34 116 34.2
55.6 190 154.4 68 232 170.9 51.4 175 74.4 68 232 85.6 68 232 68.4
Loading...
+ 30 hidden pages