McQuay Suite Incremental Installation Manual

Installation & Maintenance Data
IM 368-7
Group: PTAC Part No.: 106018472 Date: November 2003
Suite™ Incremental
®
PTAC/PTHP Conditioner
©2003 McQuay International
®
Table of Contents
Installation ......................................................................... 2
Inspection..........................................................................2
Nomenclature....................................................................3
Wall Opening Requirements .............................................3
Wall Sleeve Installation
Frame & Brick ............................................................4
Panel Wall Construction.............................................5
Thick Wall Construction .............................................6
Wall Sleeve Extension
Louver Frame.............................................................7
Subbase Installation..........................................................8
Installation of Optional Condensate Drain Kit ................... 9
Installation of Louvers .....................................................10
Installation of Chassis .....................................................10
Adjusting Temperature Limiting Device........................... 11
Electrical Service............................................................. 1 1
Equipment Startup .......................................................... 11
Remote Mounted Thermostat ......................................... 12
Scheduled Maintenance .................................................12
Recommended Spare Parts............................................13
Refrigeration Cycle .........................................................13
Troubleshooting Chart...............................................14, 15
Approximate Shipping Weights ....................................... 15
Wiring Diagrams............................................16, 17, 18, 19
Installation
The installation of this equipment shall be in accordance with the regulations of authorities having jurisdiction and all applicable codes. It is the responsibility of the installer to determine and f ollow the applicable codes. Sheetmetal parts, sel f­tapping screws, clips and such items inherently have sharp edges, and it is necessary that the installer exercise caution. This equipment is to be installed only by an experienced installation company which employs trained personnel.
Inspection
When the equipment is received all items should be carefully checked against the bill of lading to be sure all crates and cartons have been received. All units should be carefully inspected for damage when received. If any damage is noticed, the carrier should make the proper notation on the delivery receipt acknowl­edging the damage. The carrier should also fill out a Carrier Inspection Report. The McQuay International Traffic Department should then be contacted.
The unit nameplate should be checked to make sure the voltage agrees with the power supply available.
Suite II Series Comfort Conditioner is designed and built for through-the-wall installation in either new or existing buildings
The self-contained refrigerant system delivers cooling to the de­sired space. Heating can be accomplished with electric resistance, hydronic or with reverse cycle heating options.
Each conditioner consists of the following components:
1. Heating/Cooling Chassis — Shipped separate.
2. Cabinet/Wall Sleeve — Shipped separate.
3. Outdoor Louver — Shipped in a separate carton.
4. Subbase (not shown) — Optional on all 208V and 230V heat pump and electric heat units. Standard for all 265V and for hydronic heater option. Shipped in a separate carton.
Figure 1. Exploded View of Complete Unit (Shown Without Subbase)
IM 368 / Page 2 of 20 (Rev 11/03)
MCQUA Y PT AC/PTHP
P DES 1 009 E Z 60
Product Category
P = PTAC
Product Identifier
see box below (Suite)
Design Series
1 = A Design
Nominal Capacity
007 = 7,000 009 = 9,000 012 = 12,000 015 = 15,000
McQuay PTAC/PTHP Product Identifiers
DEA = Suite II, 2 motor, automatic damper DEC = A/C & Elec/Hyd Htg Chassis w/Corr. Protection DEH = Suite II, 2 motor, hydronic w/standby DEI = Suite II, 2 motor, IAQ DES = A/C & Heating (Elec/Hyd) Chassis DHA = Suite II, 2 motor, heat pump, automatic damper DHC = H/P w/ Electric Heat & Corrosion Protection DHI = Suite II, 2 motor, heat pump, IAQ DHS = H/P w/ Electric Heat
Heating Options
35 = 2.5 kw 41 = 3.5 kw 48 = 5.0 kw 62 = Hydronic, normally open 63 = Hydronic, normally closed
Coil Options
(None)
Voltage
A = 115 - 60 - 1 C = 208 - 60 - 1 J = 265 - 60 - 1
SEA = A/C w/Electric Heat & Automatic OA Damper SEC = A/C w/Electric Heat & Corrosion Protection SEH = A/C w/Hydronic Heat & Standby
(Emergency) Power SEI = A/C w/Electric Heat & IAQ Power Vent Kit SES = A/C & Heating (Elec/Hyd) Chassis SHA = A/P w/Electric Heat & Automatic OA Damper SHC = H/P w/ Electric Heat & Corrosion Protection SHI = H/P w/ Electric Heat & IAQ Power Vent Kit SHS = H/P w/Electric Heat
Wall Opening Requirement
Before installing the unit, check the wall opening to be sure the cabinet/wall sleeve will slide into the opening unobstructed. For masonry walls, a lintel must be used to provide support over each opening. The rough opening should measure 16
1
42
/4" (1073mm) wide (see note ). When no subbase is used,
the opening should be a minimum of 3" (76mm) off the floor . This
Figure 2. Suite Unit with Electric Subbase
1
/4" (413mm) X
distance may vary when a subbase is supplied. The standard subbase is available in 3" (76mm) or 4" (102mm) heights. For units with hydronic heat, the subbase is 81/4" (210mm). Each subbase has leveling legs providing for up to 1" (25.4mm) additional height.
Notes:
Unit pictured with subbase installed. Subbase is optional on 208V and 230V units. Subbase is standard on all 265V units and units with hydronic heat.Subbase extends to front edge of unit when furnished with hydronic heat.Opening needs to be 16 Subbase side channels are adjustable from 43/8" to 133/4" (111mm to 349mm).
5
/8" (422mm) x 425/8" (1083mm) when using a louver frame. See page 7.
IM 368 / Page 3 of 20 (Rev. 11/03)
Wall Slee ve Installation — Frame and Brick
A heavy-gauge, corrosion resistant cabinet/wall sleeve is provided for each unit. The cabinet/wall sleeve is either shipped in a separate carton, shipped in a multi-pack of 15 or in a single carton with the heating/cooling chassis.
The standard cabinet/wall sleeve is designed to be easily installed in a variety of wall constructions. Note: The center of gravity is
1
10
/4" (260mm) from the rear face of the wall sleeve. The wall sleeve must be inserted into the wall at least 101/4" (260mm) or other support must be employed. Support can be from a factory supplied subbase or from other field supplied materials. Recommended installation procedures are described below.
1. Clean the opening of all debris that may interfere with
installation.
2. If the unit is to be supplied with a subbase, refer to page 8 for
installation procedures. Install subbase before installing
cabinet/wall sleeve.
3. If the optional drain kit is to be employed (heat pump only),
refer to page 8 before proceeding.
4. Place a thin pad of soft mortar on the bottom of the opening
and slide in the cabinet/wall sleeve. Be sure to recess the wall
sleeve enough to accommodate outside louver. This recess
3
is
/8" (9.5mm) for stamped louvers and 11/4" (32mm) for architectural louver. Louver should be flush to exterior surface when complete. Note: The wall sleeve is not intended to replace the lintel.
5. Level cabinet/wall sleeve in both directions and secure by anchoring with appropriate fasteners (as shown in Figure C, page 7). A
5
/16" (8mm) hole is provided on each side, 2" (51mm) down from the top and 2" (51mm) in from the rear of the cabinet/wall sleeve. Additional holes may be required to firmly secure the cabinet/wall sleeve. Caution: Do not drill holes in the base of the cabinet/wall sleeve. Where a subbase is used, secure wall sleeve to subbase with clips provided.
6. Caulk the cabinet/wall sleeve to the wall opening on both the inside and outside perimeter. Be careful not to plug the weep holes. Caulking should be resilient, non hardening type such as silicone.
Figure 3. Frame & Brick with Cord Connection
Figure 4. Frame & Brick with Standard Electrical Subbase
IM 368 / Page 4 of 20 (Rev 11/03)
Figure 5. Frame & Brick with Hydronic Subbase
Wall Sleeve Installation — Panel Wall Construction
For panel wall and thin wall construction, it is recommended that a louver frame be used. Refer to page 7 for installaton of louver frame before continuing.
Panel wall and thin wall construction varies only slightly from frame and brick construction. Note: The center of gravity is 10
1
/4" (260mm) from the rear face of the wall sleeve. The wall sleeve must be inserted into the wall at least 10
1
/4" (260mm) or other support must be employed. Support can be from a factory sup­plied subbase or from other field supplied materials. Installation for this application is as follows:
1. Clean the opening of all debris that may interfere with in-
stallation.
2. If the unit is to be supplied with a subbase, refer to page 8 for
installation procedures. Install subbase before installing cabi­net/wall sleeve.
3. If the optional drain kit is to be employed (heat pump only),
refer to page 9 before proceeding.
4. Be sure the cabinet/wall sleeve is mechanically attached to
the wall and caulked to assure a proper seal. It is recom­mended that the louver frame be used for this purpose. (See Figure B, page 7.)
5. Recess the wall sleeve so that the louver is flush with the
exterior of the building.
6. Level cabinet/wall sleeve in both directions and secure by
anchoring with appropriate fasteners (as shown in Figure C, page 7) or drill additional holes as required to secure firmly.
Caution: Do not drill holes in the base of the cabinet/wall sleeve. Where a subbase is used, secure wall sleeve to sub-
base with clips provided.
7. If no subbase is employed, proper support by installer must
be provided under wall sleeve, as shown in Figure 6.
8. Caulk the cabinet/wall sleeve to the wall opening on both the
inside and outside perimeter. Be careful not to plug the weep holes. Caulking should be resilient, non-hardening type such as silicon.
Figure 6. Panel Wall Construction with Cord Connection
Figure 7. Panel Wall Construction with Standard Electrical
Subbase
Figure 8. Panel Wall Installation with Hydronic Subbase
IM 368 / Page 5 of 20 (Rev. 11/03)
Wall Sleeve Installation — Thick Wall Construction
Installation of cabinet/wall sleeves for thick walls requires special consideration. Table 1 should be used to determine the maximum wall thickness allowed for the standard cabinet/wall sleeve. For thicker walls, cabinet/wall sleeve extensions are available from your representative. Refer to page 7 for proper installation of cabinet/wall sleeve extensions.
Cabinet/wall sleeve installation in thick walls is similar to frame and brick installation. Install as follows:
1. Clean the opening of all debris that may interfere with installation.
2. If the unit is to be supplied with a subbase, refer to page 8 for installation procedures. Install subbase before installing cabinet/wall sleeve.
3. If the optional drain kit is to be employed (heat pump only), refer to page 9 before proceeding.
4. If wall thickness exceeds dimensions shown in Table 1, a cabinet/wall sleeve extension must be used. Install the extension as described on page 7. Once the extension is attached to the cabinet/wall sleeve, place a thin pad of soft mortar on the bottom of the opening and slide in the wall sleeve/extension assembly . Be sure to recess the wall sleeve
3
enough to accommodate outside louver. This recess is
/8" (9.5mm) for stamped louvers and 11/4" (32mm) for architec­tural louvers. Louver should be flush to exterior surface when completed. Note: The wall sleeve is not intended to replace the lintel.
5. Level cabinet/wall sleeve in both directions and secure by anchoring with appropriate fasteners (as shown in Figure C, page 7) or drill additional holes as required to secure firmly.
Caution: Do not drill holes in the base of the cabinet/wall sleeve. Where a subbase is used, secure wall sleeve to sub-
base with clips provided.
6. Caulk the cabinet/wall sleeve to the wall opening on both the inside and outside perimeter. Be careful not to plug the weep holes. Caulking should be resilient, non-hardening type such as silicone.
Table 1. Maximum Wall Thickness without Sleeve Extensions
Maximum Wall Thickness
Louver Type
Stamped
Architectural
No
Subbase
14" (356mm)
147/8" (378mm)
Standard Subbase
1
/2" (241mm)
9
3
10
/8" (264mm)
Hydronic Subbase
1
/8" (333mm)
13
14" (356mm)
Figure 9. Thick Wall Construction with Cord Connection
Figure 10. Thick Wall Construction with Standard Electric
Subbase
Note: 1. Subbase is available in 3" (76mm) or 4" (102mm) height. Leveling legs provide for
adjustment of 1" (25.4mm).
2. Wall sleeve extension is available in various depths and supplied as required.
IM 368 / Page 6 of 20 (Rev 11/03)
Figure 11. Thick Wall Installation with Hydronic Subbase
Loading...
+ 14 hidden pages