McQuay ST010 Installation Manual

GENERAL
The Model ST air cooled condensing units are com­plete assemblies, factory tested and shipped with a
Refrigerant 22 holding charge. They have been de­signed to operate in conjunction with remote direct expansion evaporator(s) and are available for operation on three phase power supplies (see the published catalog data for power ratings available). All units have
115 volt control circuits with provision for connection
of a remote mounted 24 volt thermostat. Additional
information on the units is covered on the pages
following.
McQUAY
RESPONSIBILITIES
The Model ST condensing units when applied within
the performance and application limits specified on the
sales and installation data will provide safe and
dependable service.
Details on the Model ST product warranty are included in the information envelope packed with the unit.
RECEIVING EQUIPMENT
1. CHECK EQUIPMENT before removing it from the delivery vehicle. The unit nameplate (shown below)
indicates the unit model number, power character­istics, serial number, etc. Be sure to check the nameplate data against the shipping papers and pay particular attention to the unit model number (size) and power characteristics.
2.3.INSPECT the unit while it is still on the delivery vehicle, make a note of any damage on the delivery receipt. Be sure to carefully check for hidden damage. If damage is found, have it checked and noted by the representative of the transportation company before accepting or removing the unit from the vehicle.
NOTE
All equipment furnished by McQuay is shipped F.O.B. the factory and all claims for handling and shipping damage are the responsibility of the consignee.
If an item is missing from the shipment notify your nearest McQuay Sales office.
RIGGING - The STO08, 010, 013, and 015 should be lifted by the skid, the ST020, 025, and 030 from the lifting holes at the base corners. When lifting use a spreader bar to prevent damage. If the unit is to be skidded, be sure an adequate number of rollers are used and be careful when moving the unit not to drop it. Under no circumstances should the unit be dragged with or without the skid.
NOTE
Unit mounting legs are shipped in a sepa­rate carton and are located in the compres­sor compartment. Before setting the unit at its final location, attach the support legs at each corner with the bolts provided.
5/8” anchor holes are provided in the legs for securing the unit to its base.
When requesting information about this unit please forward the unit model number, style and serial numbers with your inquiry.
UNIT MODEL NUMBER INTERPRETATION
ST 020 A
PRODUCT FAMILY
NOMINAL CAPACITY-TONS
CONDENSING MEDIUM A = AIR
J
2 s 00
SPECIAL MODIFICATIONS
UNIT POWER CHARACTERISTICS
DESIGN MODIFICATION
CLEARANCES
The unit has been designed to permit slab or roof mounting and care must be taken to provide adequate clearance for air flow in and out of the unit.
TOP CLEARANCE - The unit has a draw through air circuit with vertical air discharge from the top of the
unit. It is important that the areas above and below are clear of any obstructions that could impede or divert the air flow and cause recirculation back to the air
inlet.
SIDE CLEARANCE - A minimum clearance of 36
inches is required with the exception of the compres-
sor access end of the unit, where 42 inches is
recommended.
VIBRATION ISOLATION
Internal isolation of the fan motors generally make it unneces-
sary to provide additional vribration isolation for the
unit. However, additional isolation could be required depending on the installation location and building construction.
Wherever possible locate the unit away from or over
occupied areas and provide adequate piping isolation. Be where it passes through walls, roof or floors.
spring
mounting of the compressor and
careful
not to allow piping to touch the structure
2
TABLE 1
ST008,010,013
ST020,025,030
m]
AND 015

REFRIGERANT PIPING

Piping between the condensing unit and the cooling
coil must be designed and installed to minimize
pressure drop, prevent liquid refrigerant carryover to
the compressor and to assure a continuous return of
compressor oil from the system. Piping sketches and tables are not intended to provide information on all of the possible arrangements. For example, when dual
circuit evaporators are used with an unloading com-
UNIT WEIGHT
Unit
Size
ST008
STDlO
ST013 ST015
ST020
ST025
-4
ST630 453
1
180 190 145 150
394 421
Gorn*r
1
2 f
I
210
465 277 270
aide.
I
-
POUNDS
3
I
115
0
4’
110
W&&t
I
Tti
615 645 745 775
1230 1365 1465
pressor, two liquid line solenoid valves may be used to reduce coil capacity with compressor unloading. Note
especially that dual circuit evaporators should not be
piped with common liquid and suction lines to more
than one compressor. Separate evaporators, evapora­tor circuits and piping must be run for each compres­sor.
TABLE 2
SUCTION AND LIQUID LINE SIZES FOR EACH COMPRESSOR
MAXIMUM EQUIVALENT FEET OF COPPER TUBING
-
NOTES
Equivalent line lengths shown in above table are suitable for unit operating condenser entering air temperature of 95F. When design conditions vary the table values should be rechecked.
0
Compressors used in the ST008 and 020 have no capacity reduction.
@
The compressors used in the
@
When refrigerant required to charge a circuit exceeds the pump down capacity of that circuit the use of a separate refrigerant storage receiver will be required. The pump down capacity is based on the condenser 80% full at
@
Wherever vertical rise occurs in the piping, the minimum tonnage for oil entrainment should be checked and where necessary double suction risers should be utilized. See Table 4, page 4.
@
Total equivalent feet for a given piping layout must include the equivalent length of straight pipe for fittings, valves and specialties added to the total run of straight pipe.
ST010,
013, 015,025 and 030 have a single 50% capacity reduction step.
-
conditions
between 40 and 45F saturated suction temperature and
8OF.
3
TABLE 3
EQUIVALENT FEET OF STRAIGHT TUBING FOR COPPER
16 20
10 14 25 32 08 09
22
ws
_.qQtq":?&qt
14
0.9 23 07
TABLE 4
Minimum Tonnage (R-22)
To Carry Oil Up Suction Riser
NOTE. When compressor minimum tonnage is less than shown in the
above table for a given line size, double suction risers will be required.
To preclude potential problems that could be traced to
piping,
standard accepted piping practices as de-
scribed below and in the ASHRAE handbooks are
recommended.
Piping recommendations include:
The use of type K or L clean copper tubing. All joints should be thoroughly cleaned and brazed with high temperature solder.
Piping sizes should be based on temperature/ pressure limitations as recommended in the follow­ing paragraphs. Under no circumstances should pipe size be based upon the coil or condensing unit piping connection size.
Suction line piping pressure drop should not exceed the pressure equivalent of
2’F
per 100 feet of
equivalent pipe length. After the suction line size
has been determined, the vertical suction risers
should be checked to verify that oil will be carried
up the riser and back to the compressor. The
suction
line(s)
should be pitched in the direction of refrigerant flow and adequately supported. Lines should be free draining and fully insulated between the evaporator(s) and the compressor. Table 2, page 3 shows piping information for units operating at suction temperatures between 40 and 45 and a condenser entering air temperature of 95. If operat­ing conditions are expected to vary substantially from these operating levels, the pipe sizing should be rechecked.
Vertical suction risers should be checked using Table 4, page 4 to determine the minimum tonnage required to carry oil up suction risers of various sizes.
I
26 33
17
41
13
I 29
2.3
5.6
1.7
I
38
FlTTlNGS AND
I
4.0
2.6 63
2.1
I
43
VALVES
5.0 6.0
3.3 82
2.6 3.2
55
I
I
69
5. The liquid line should be sized for a pressure drop not to exceed the pressure equivalent of saturated temperature. The liquid
line(s)
on all units must include a liquid solenoid valve wired into the circuit as shown on the applicable unit wiring diagrams. The valve must be connected as follows:
1.
On model ST008, 010, 013, and 015 the solenoid
must be wired between terminals “P and N.”
2. Models ST020, 025, and 030 will require two sole
noid
valves, one in each liquid line. Make wiring connections between terminals “P and N” for circuit number 1 and “PI and N1" for circuit
number 2.
The unit control circuit for all compressors has been designed to include a one time pump down cycle. The use of a liquid line solenoid is required for
proper unit operation. In addition, a filter/drier should be located between the liquid line service valve and the solenoid valve and a combination
moisture indicator/sight glass should be located in the liquid line ahead of the expansion valve.
6. Suggested piping arrangements are shown on page
5.
All
multiple compressor units require a separate
refrigerant circuit for each compressor.
7. If Dual Suction Risers are Used: A.
The combined cross sectional areas of the two risers must be capable of maintaining adequate refrigerant velocity for oil return at full unit tonnage.
B.
The extra risers should be of a smaller diameter than the main riser. The extra riser must include its own trap at the bottom and should enter the main suction header at twelve o’clock.
C.
The trap serving the extra riser must be as short as fittings permit. A “U” fitting or the combina­tion of a
90’
standard
ell
and a
90’
street
recommended.
D.
The suction line leaving the coil should also include a trap if the expansion valve control bulb is to be on the horizontal section leaving the coil outlet. See the piping sketches on page 5.
4
4.1
10.0
ell
I
2’F
is

LEAK TESTING

All model ST condensing units are evacuated leak
tested and provided with a holding charge of R-22 at
the factory. Check the unit when it arrives at the job site for damage or leaks in the refrigerant circuit. If the refrigerant charge has been lost, locate and repair the leak at the same time the connecting system is checked. When you are ready to leak test, charge enough R-22 into the system to raise the pressure to about 30 psig; then add dry nitrogen and bring the
pressure up to a maximum of 150 psig. The system can now be checked for leaks. Before attempting to repair
any leaks that may have been found, be sure to relieve
the test pressure from the system.
IMPORTANT CAUTION
Always use a pressure regulating valve on the nitrogen drum and be sure to
nect the drum from the system after the maximum of 150 psig test pressure is reached. Under no circumstances should you exceed the maximum leak test pressure of 150 psig. DO NOT USE OXYGEN TO
BUILD UP PRESSURE, A SERIOUS EX­PLOSION COULD RESULT.
discon-

EVACUATION

After all leaks have been repaired the system can be evacuated, proceed as follows:
Connect a good quality manometer or gauge (capable of measuring one millimeter of vacuum) into the system and locate it as far away as possible
from the vacuum pump. The triple evacuation method is recommended.
Evacuate the system to 29” vacuum, then add enough R-22 to break the vacuum and bring the system up to 10 psig pressure. Repeat this evacuation ‘two more times and on the third evacuation break the vacuum by feeding R-22 into the system through the gauge port on the condenser liquid shut off valve. With the refrigerant cylinder up ended, it should be possible to install close to 75% of the required charge into the system in this manner without starting the com- pressor. Do not start the compressor until the following checks have been made.
PRELIMINARY CHECKS BEFORE STARTING COMPRESSOR(S)
1.
With the unit disconnect switch off, check to be sure that the starter contacts meet evenly and that
all operating starter parts move freely. Check that the time delay fuses are of the proper size.
2.
Open all refrigerant charge, and liquid).
3.
With the thermostat room thermostat below the design temperature. Check that the air handling unit fans are rotating in the proper direction.
in the unit disconnect switch
service valves (suction, dis-
in the “off” position, set the
Close the disconnect switch which energizes the
4. crankcase heaters. These heaters must be ener-
gized 8 hours before attempting to start the compressor(s).
Check that line voltage is within
5. compressor nameplate voltage rating.
+ 10 percent of the
CHARGING
With the cylinder still up ended, charge as much
1.
refrigerant as possible into the system. When the
system will no longer accept refrigerant in this
manner, disconnect the drum from the liquid valve and reconnect it to the gauge port on the suction service valve.
Check the compressor oil level. If the oil level is
2.
over the top of the glass, be prepared when the compressor starts to shut it down if sounds of liquid pumping are evident.
Recheck that the suction, liquid and discharge line
3.
shut off valves are open. Close the unit disconnect switch and set the room thermostat to call for cooling.
With the compressor operating, continue to allow
4.
refrigerant to enter until the estimated charge has been weighed in and/or the sight glass clears. At this point, check the liquid line temperature leaving the condenser, it should indicate 10 to 12 degrees of subcooling.
Another method of checking the refrigerant charge after the initial 75% has been added to the unit would be to block the condenser coil until the head
pressure is built up to about 300 psig. Continue to add refrigerant until the sight glass clears and 10 to
12 degrees subcooling is obtained.
Regardless of the method used to charge the unit, refer to the charging and operating curves applica­ble to the unit involved and check operating pressures against the curve values.
After about one hour of operation, check the compres­sor amperage being drawn. It should not exceed the
Full Load Amperes listed on the unit nameplate.
Also check that the combination sight glass/moisture indicator is showing a dry condition. If moisture is indicated, a refrigerant drier will have to be added into the system.
TABLE 5
APPROXIMATE OPERATING CHARGE
FOR COMPRESSOR CIRCUIT
NOTE: Approximate charge includes evaporator coil, condensing
unit, liquid line drier and approximately 25 ft. of liquid line per circuit. Refrigerant charging should be performed as described under “Charging” on Page 6.
-
R-22, LBS
suction
and
6
Loading...
+ 13 hidden pages