McQuay ST010 Installation Manual

Page 1
Page 2
GENERAL
The Model ST air cooled condensing units are com­plete assemblies, factory tested and shipped with a
Refrigerant 22 holding charge. They have been de­signed to operate in conjunction with remote direct expansion evaporator(s) and are available for operation on three phase power supplies (see the published catalog data for power ratings available). All units have
115 volt control circuits with provision for connection
of a remote mounted 24 volt thermostat. Additional
information on the units is covered on the pages
following.
McQUAY
RESPONSIBILITIES
The Model ST condensing units when applied within
the performance and application limits specified on the
sales and installation data will provide safe and
dependable service.
Details on the Model ST product warranty are included in the information envelope packed with the unit.
RECEIVING EQUIPMENT
1. CHECK EQUIPMENT before removing it from the delivery vehicle. The unit nameplate (shown below)
indicates the unit model number, power character­istics, serial number, etc. Be sure to check the nameplate data against the shipping papers and pay particular attention to the unit model number (size) and power characteristics.
2.3.INSPECT the unit while it is still on the delivery vehicle, make a note of any damage on the delivery receipt. Be sure to carefully check for hidden damage. If damage is found, have it checked and noted by the representative of the transportation company before accepting or removing the unit from the vehicle.
NOTE
All equipment furnished by McQuay is shipped F.O.B. the factory and all claims for handling and shipping damage are the responsibility of the consignee.
If an item is missing from the shipment notify your nearest McQuay Sales office.
RIGGING - The STO08, 010, 013, and 015 should be lifted by the skid, the ST020, 025, and 030 from the lifting holes at the base corners. When lifting use a spreader bar to prevent damage. If the unit is to be skidded, be sure an adequate number of rollers are used and be careful when moving the unit not to drop it. Under no circumstances should the unit be dragged with or without the skid.
NOTE
Unit mounting legs are shipped in a sepa­rate carton and are located in the compres­sor compartment. Before setting the unit at its final location, attach the support legs at each corner with the bolts provided.
5/8” anchor holes are provided in the legs for securing the unit to its base.
When requesting information about this unit please forward the unit model number, style and serial numbers with your inquiry.
UNIT MODEL NUMBER INTERPRETATION
ST 020 A
PRODUCT FAMILY
NOMINAL CAPACITY-TONS
CONDENSING MEDIUM A = AIR
J
2 s 00
SPECIAL MODIFICATIONS
UNIT POWER CHARACTERISTICS
DESIGN MODIFICATION
CLEARANCES
The unit has been designed to permit slab or roof mounting and care must be taken to provide adequate clearance for air flow in and out of the unit.
TOP CLEARANCE - The unit has a draw through air circuit with vertical air discharge from the top of the
unit. It is important that the areas above and below are clear of any obstructions that could impede or divert the air flow and cause recirculation back to the air
inlet.
SIDE CLEARANCE - A minimum clearance of 36
inches is required with the exception of the compres-
sor access end of the unit, where 42 inches is
recommended.
VIBRATION ISOLATION
Internal isolation of the fan motors generally make it unneces-
sary to provide additional vribration isolation for the
unit. However, additional isolation could be required depending on the installation location and building construction.
Wherever possible locate the unit away from or over
occupied areas and provide adequate piping isolation. Be where it passes through walls, roof or floors.
spring
mounting of the compressor and
careful
not to allow piping to touch the structure
2
Page 3
TABLE 1
ST008,010,013
ST020,025,030
m]
AND 015

REFRIGERANT PIPING

Piping between the condensing unit and the cooling
coil must be designed and installed to minimize
pressure drop, prevent liquid refrigerant carryover to
the compressor and to assure a continuous return of
compressor oil from the system. Piping sketches and tables are not intended to provide information on all of the possible arrangements. For example, when dual
circuit evaporators are used with an unloading com-
UNIT WEIGHT
Unit
Size
ST008
STDlO
ST013 ST015
ST020
ST025
-4
ST630 453
1
180 190 145 150
394 421
Gorn*r
1
2 f
I
210
465 277 270
aide.
I
-
POUNDS
3
I
115
0
4’
110
W&&t
I
Tti
615 645 745 775
1230 1365 1465
pressor, two liquid line solenoid valves may be used to reduce coil capacity with compressor unloading. Note
especially that dual circuit evaporators should not be
piped with common liquid and suction lines to more
than one compressor. Separate evaporators, evapora­tor circuits and piping must be run for each compres­sor.
TABLE 2
SUCTION AND LIQUID LINE SIZES FOR EACH COMPRESSOR
MAXIMUM EQUIVALENT FEET OF COPPER TUBING
-
NOTES
Equivalent line lengths shown in above table are suitable for unit operating condenser entering air temperature of 95F. When design conditions vary the table values should be rechecked.
0
Compressors used in the ST008 and 020 have no capacity reduction.
@
The compressors used in the
@
When refrigerant required to charge a circuit exceeds the pump down capacity of that circuit the use of a separate refrigerant storage receiver will be required. The pump down capacity is based on the condenser 80% full at
@
Wherever vertical rise occurs in the piping, the minimum tonnage for oil entrainment should be checked and where necessary double suction risers should be utilized. See Table 4, page 4.
@
Total equivalent feet for a given piping layout must include the equivalent length of straight pipe for fittings, valves and specialties added to the total run of straight pipe.
ST010,
013, 015,025 and 030 have a single 50% capacity reduction step.
-
conditions
between 40 and 45F saturated suction temperature and
8OF.
3
Page 4
TABLE 3
EQUIVALENT FEET OF STRAIGHT TUBING FOR COPPER
16 20
10 14 25 32 08 09
22
ws
_.qQtq":?&qt
14
0.9 23 07
TABLE 4
Minimum Tonnage (R-22)
To Carry Oil Up Suction Riser
NOTE. When compressor minimum tonnage is less than shown in the
above table for a given line size, double suction risers will be required.
To preclude potential problems that could be traced to
piping,
standard accepted piping practices as de-
scribed below and in the ASHRAE handbooks are
recommended.
Piping recommendations include:
The use of type K or L clean copper tubing. All joints should be thoroughly cleaned and brazed with high temperature solder.
Piping sizes should be based on temperature/ pressure limitations as recommended in the follow­ing paragraphs. Under no circumstances should pipe size be based upon the coil or condensing unit piping connection size.
Suction line piping pressure drop should not exceed the pressure equivalent of
2’F
per 100 feet of
equivalent pipe length. After the suction line size
has been determined, the vertical suction risers
should be checked to verify that oil will be carried
up the riser and back to the compressor. The
suction
line(s)
should be pitched in the direction of refrigerant flow and adequately supported. Lines should be free draining and fully insulated between the evaporator(s) and the compressor. Table 2, page 3 shows piping information for units operating at suction temperatures between 40 and 45 and a condenser entering air temperature of 95. If operat­ing conditions are expected to vary substantially from these operating levels, the pipe sizing should be rechecked.
Vertical suction risers should be checked using Table 4, page 4 to determine the minimum tonnage required to carry oil up suction risers of various sizes.
I
26 33
17
41
13
I 29
2.3
5.6
1.7
I
38
FlTTlNGS AND
I
4.0
2.6 63
2.1
I
43
VALVES
5.0 6.0
3.3 82
2.6 3.2
55
I
I
69
5. The liquid line should be sized for a pressure drop not to exceed the pressure equivalent of saturated temperature. The liquid
line(s)
on all units must include a liquid solenoid valve wired into the circuit as shown on the applicable unit wiring diagrams. The valve must be connected as follows:
1.
On model ST008, 010, 013, and 015 the solenoid
must be wired between terminals “P and N.”
2. Models ST020, 025, and 030 will require two sole
noid
valves, one in each liquid line. Make wiring connections between terminals “P and N” for circuit number 1 and “PI and N1" for circuit
number 2.
The unit control circuit for all compressors has been designed to include a one time pump down cycle. The use of a liquid line solenoid is required for
proper unit operation. In addition, a filter/drier should be located between the liquid line service valve and the solenoid valve and a combination
moisture indicator/sight glass should be located in the liquid line ahead of the expansion valve.
6. Suggested piping arrangements are shown on page
5.
All
multiple compressor units require a separate
refrigerant circuit for each compressor.
7. If Dual Suction Risers are Used: A.
The combined cross sectional areas of the two risers must be capable of maintaining adequate refrigerant velocity for oil return at full unit tonnage.
B.
The extra risers should be of a smaller diameter than the main riser. The extra riser must include its own trap at the bottom and should enter the main suction header at twelve o’clock.
C.
The trap serving the extra riser must be as short as fittings permit. A “U” fitting or the combina­tion of a
90’
standard
ell
and a
90’
street
recommended.
D.
The suction line leaving the coil should also include a trap if the expansion valve control bulb is to be on the horizontal section leaving the coil outlet. See the piping sketches on page 5.
4
4.1
10.0
ell
I
2’F
is
Page 5
Page 6

LEAK TESTING

All model ST condensing units are evacuated leak
tested and provided with a holding charge of R-22 at
the factory. Check the unit when it arrives at the job site for damage or leaks in the refrigerant circuit. If the refrigerant charge has been lost, locate and repair the leak at the same time the connecting system is checked. When you are ready to leak test, charge enough R-22 into the system to raise the pressure to about 30 psig; then add dry nitrogen and bring the
pressure up to a maximum of 150 psig. The system can now be checked for leaks. Before attempting to repair
any leaks that may have been found, be sure to relieve
the test pressure from the system.
IMPORTANT CAUTION
Always use a pressure regulating valve on the nitrogen drum and be sure to
nect the drum from the system after the maximum of 150 psig test pressure is reached. Under no circumstances should you exceed the maximum leak test pressure of 150 psig. DO NOT USE OXYGEN TO
BUILD UP PRESSURE, A SERIOUS EX­PLOSION COULD RESULT.
discon-

EVACUATION

After all leaks have been repaired the system can be evacuated, proceed as follows:
Connect a good quality manometer or gauge (capable of measuring one millimeter of vacuum) into the system and locate it as far away as possible
from the vacuum pump. The triple evacuation method is recommended.
Evacuate the system to 29” vacuum, then add enough R-22 to break the vacuum and bring the system up to 10 psig pressure. Repeat this evacuation ‘two more times and on the third evacuation break the vacuum by feeding R-22 into the system through the gauge port on the condenser liquid shut off valve. With the refrigerant cylinder up ended, it should be possible to install close to 75% of the required charge into the system in this manner without starting the com- pressor. Do not start the compressor until the following checks have been made.
PRELIMINARY CHECKS BEFORE STARTING COMPRESSOR(S)
1.
With the unit disconnect switch off, check to be sure that the starter contacts meet evenly and that
all operating starter parts move freely. Check that the time delay fuses are of the proper size.
2.
Open all refrigerant charge, and liquid).
3.
With the thermostat room thermostat below the design temperature. Check that the air handling unit fans are rotating in the proper direction.
in the unit disconnect switch
service valves (suction, dis-
in the “off” position, set the
Close the disconnect switch which energizes the
4. crankcase heaters. These heaters must be ener-
gized 8 hours before attempting to start the compressor(s).
Check that line voltage is within
5. compressor nameplate voltage rating.
+ 10 percent of the
CHARGING
With the cylinder still up ended, charge as much
1.
refrigerant as possible into the system. When the
system will no longer accept refrigerant in this
manner, disconnect the drum from the liquid valve and reconnect it to the gauge port on the suction service valve.
Check the compressor oil level. If the oil level is
2.
over the top of the glass, be prepared when the compressor starts to shut it down if sounds of liquid pumping are evident.
Recheck that the suction, liquid and discharge line
3.
shut off valves are open. Close the unit disconnect switch and set the room thermostat to call for cooling.
With the compressor operating, continue to allow
4.
refrigerant to enter until the estimated charge has been weighed in and/or the sight glass clears. At this point, check the liquid line temperature leaving the condenser, it should indicate 10 to 12 degrees of subcooling.
Another method of checking the refrigerant charge after the initial 75% has been added to the unit would be to block the condenser coil until the head
pressure is built up to about 300 psig. Continue to add refrigerant until the sight glass clears and 10 to
12 degrees subcooling is obtained.
Regardless of the method used to charge the unit, refer to the charging and operating curves applica­ble to the unit involved and check operating pressures against the curve values.
After about one hour of operation, check the compres­sor amperage being drawn. It should not exceed the
Full Load Amperes listed on the unit nameplate.
Also check that the combination sight glass/moisture indicator is showing a dry condition. If moisture is indicated, a refrigerant drier will have to be added into the system.
TABLE 5
APPROXIMATE OPERATING CHARGE
FOR COMPRESSOR CIRCUIT
NOTE: Approximate charge includes evaporator coil, condensing
unit, liquid line drier and approximately 25 ft. of liquid line per circuit. Refrigerant charging should be performed as described under “Charging” on Page 6.
-
R-22, LBS
suction
and
6
Page 7
Page 8
Page 9
Page 10
Page 11
Page 12
Page 13
Page 14
Page 15
TYPICAL SCHEMATIC WIRING FOR MODELS
ST 025 AND
030
FUSE ~
115V.
BUSSMAN
FUSE PRIMARY CON
TRANSFORMER BUSS
4AMP
TYPE
NEC CLASS 2
MDX
COB WkllNG
-
X2 SYS
ONLY.
ON~OFF
FUSE
2.5A
SEE NOTES, PAGE 13
schematic diagram shown on page 16
BEHIND TERM
HOUSING
BLOCK
TYPE S
UNIT LAYOUT
REFERENCE DRAWING
Xl COMPRESSOR
598C686-SUB
6
OPTIONAL
EQUIPMENT
ACCESSORY ITEMS
LOW AMBIENT FAN SPEED CONTROL - By adding an accessory fan speed control to the last operating fan motor on all model ST008 through 015 units, the minimum operating ambient temperature as shown on Table 6, page 7 can be reduced to
O’F for all
unit operating capacities. This control is a standard
accessory available from McQuay for field installation. TIME DELAY RELAY - On two compressor units
(models ST020 through
030),
it may be desirable to prevent simultaneous starting of both compressors on a call for cooling. An accessory time delay relay is available for field installation in the unit operating control circuit. This relay will add a short time delay and only allow one compressor to start at a time.
SUCTION LINE ACCUMULATOR - Some systems, depending on line length, solenoid valve leakage, etc., may require the use of a suction line accumulator to prevent damage to the compressor from liquid
carry-
CONTROL CIRCUIT OPERATION
Refer to the schematic diagram shown on page 16. A single line voltage fused disconnect switch must be
field supplied in the wiring supplying power to the unit.
With the disconnect switch closed, power is supplied to the primary of the control transformer located on
over when the compressor first starts. A standard accessory accumulator with a liquid capacity of 31 pounds is available for field installation in the suction line of each compressor circuit.
PRESSURE GAUGES - Are available in kit form for field installation.
HOT GAS BYPASS - This accessory option is available for field installation on units where the minimum capacity step does not reduce sufficiently to meet the minimum load requirement. The use of hot gas bypass is recommended on systems where eva­porator air flow is varied or where the load at standard air flow reduces sufficiently to cause a low suction
pressure condition. The kit contains all parts required to adapt model ST units to hot gas bypass. It must be
used on systems with side outlet distributors on the
coil or on systems where it is permissible to introduce
hot gas between the expansion valve and evaporator
unit.
line 47, a secondary control voltage of 115 volts is
generated by the transformer.
A second transformer (115 to 24V) is located on line
74. On a call for cooling by either or both of the room
thermostats “1TC” or
relays
“1CR”
and “2CR”
2TC,”
on lines 78 and 80 are energized through the indoor
unit fan coil unit interlock contacts
(5MA).
15
Page 16
Page 17
Assume thermostat contacts
cooling, relay coil “ICR” contacts on lines 56 and 59
will be closed. Closing the
energize the compressor starter holding coil through the high pressure cutout switch pressure cutout gized, the contacts on lines I, 3 and 5 and auxiliary contacts sor number 1 and auxiliary contacts 1MA line 54 pro­vide an interlock circuit parallel to the on line 56. A second set of close and energize liquid line solenoid valve “1 LS”. In addition, the closing of relay “1CR” contacts on line 56 also provides voltage to the (line 53).
After actuated contacts necessary to load the compressor.
When either the first or second stage of the thermostat calls for cooling the compressor starter auxiliary contacts the condenser fan motor
Contactors through outdoor ambient thermostats as the outdoor temperature changes. See table 7 on page 8 for details on the action of the head pressure control.
To insure that the indoor fan starter is energized, before the condensing unit can be started, indoor fan starter auxiliary contacts must be installed in the open section of the control circuit between terminals Yl-Sl and identified on the schedmtic diagram as 5MA2.”
The unit control circuit incorporates a one time
down control. For example, when the second step on
(SWS1),
1CR
Y2-S2
overload contacts
(1
LP). With holding coil
“1MA”
contacts have closed the suction pressure
1MA or
on line 54 close. This starts compres-
“1CC”
2MA
on lines 70 and 72 will energize
“4M”
and
on lines 78 and 80. These contacts are
“1TC”
are calling for
1CR
contacts on line 56 will
“1M”
(1HP),
the system
(1OL
and the low
“1M”
ener-
“1CR”
contacts
1CR
contacts on line 59
“1OL”
overload module
on line 53 can open when
contactors 3M,
“5M”
can also be cycled
4M and 5M.
“1TA
and
“5MA1”
pump-
2TA”
and
the two-stage thermostat is satisfied and opens con­tacts 2TC on line 80, cooling relay 2CR is de-energized opening relay contacts on lines 64 and 67. The circuit on line 65 is maintained by the 2MA starter auxiliary contacts on line 62. The liquid line solenoid valve on line 67 is de-energized when the 2CR relay contacts ahead of it are opened. De-energizing the solenoid valve cuts off the flow of refrigerant to the number 2 expansion valve. The compressor continues to run be­cause the circuit to compressor starter holding coil 2M is maintained by the 2MA auxiliary contacts on line 62.
The compressor continues to run and pump refrigerant from the system until the setting of low pressure cutout “2LP” on line 65 is reached and the contacts of this control are opened. When this occurs the com­pressor starter holding coil 2M is de-energized, open­ing the starter contacts on lines 7, 9 and 11 and auxiliary contacts 2MA on line 62. Suction pressure
switch “2LP” is automatic reset and when it does reset, the compressor will not restart because both relay contacts 2CR (Line 64) and starter auxiliary contacts 2MA (Line sor cannot be restarted until the 2TC thermostat again calls for cooling and relay coil 2CR is energized again closing 2CR contacts on lines 64 and 67. A similar sequence will occur when thermostat contacts open.
Also built into the compressor control circuit is a timed off provision to prevent the compressor from restarting after it has cycled off. A period of 3 to 5 minutes must elapse before the compressor can restart. This function
is built into all model ST condensing units. On all units except models ST010 and 020, this time delay is built into the solid state control, on the ST010 and 020 it is provided by separate time delay relays
“2TD.”
62)
are both open. The compres-
“1TD”
1TC
and

MAINTENANCE AND SERVICE

CRANKCASE HEATERS - The unit power supply must be kept on at all times during the operating season to keep the compressor crankcase heaters energized. If the power is disconnected the com­pressor(s) could be damaged.
-
COMPRESSOR LUBRICATION sealed compressors used in the model ST unit assem-
bly will not require additional lubrication once the unit has been checked out and placed in operation. In the event a large quantity of oil is lost as the result of refrigerant leak, the system may require the
addition of oil.
CONDENSER FAN MOTORS used on model ST008, 010, 013, 015 and 020 are supplied with ings. These motor bearings should be checked an­nually and lubricated with 20 weight non-detergent oil.
The model ST025 and 030 units utilize permanently lubricated ball bearing type motors.
CONDENSER COIL - The condenser coil should be inspected and cleaned on a regular basis. Accumu­lation of leaves, paper and surface dirt should be brushed from the finned surface. Annually the finned
prelubricated
sealed sleeve type bear-
The hermetically
-
The fan motors
surface should be cleaned using a fin cleaner. A dirty
condenser coil can increase unit power consumption by as much as twenty percent.
INDOOR FAN AND EVAPORATOR COIL
indoor air handling system must be inspected and serviced on a regular basis. Filters should be clean,
“V” belt tension adjusted and the evaporator coil
surface clean. In addition, the drain pan should be clear of algea and the condensate should drain freely.
-
SEASONAL SHUTDOWN need be made for end of season shutdown.
SEASONAL STARTUP
The crankcase heater circuit must be energized at least eight hours before attempting to start the compressor.
The air handling serviced.
The unit condenser coil should be clean and free of any debris that mav have accumulated during the shutdown period.
Check and tighten all electrical connections.
Refer to section Starting,” (page 6).
17
unit(s)
No special provisions
-
should be inspected and
“Preliminary Checks
-
The
before
Page 18

TROUBLE SHOOTING GUIDE

Possible
Cause
FUSE
BLOWN
COMPRESSOR
STARTER
OVERLOAD
RELAY
TRIPPED
LOW
PRESSURE
CUTOUT TRIPPED
T
HIGH
PRESSURE
CUTOUT TRIPPED
Possible Reasons
Motor or Winding
Grounded.
Fuse or Wire
Too Small
Compressor seized
Compressor
Drawing
Excessive
Current
Low Indoor
Refrigerant
Expansion Valve
not Opening
Refrigerant Charge
inoperative
Non-Condensables
in the Condenser
Overcharge
Refrigerant
Airflow
Restricted
Flow
Loss of
Evaporator
Fan
of
Checking
Procedure
Test for grounds, loose wire connections, starter contact adjustment
Check Table 9,
Megger motor
Check wiring for size and/or loose connections
Check whether phase
unbalance exceeds 3%
Reset compressor lockout
Run compressor, check starting, noises, and for amperge drawn
Operate condensing unit, check evaporator coil for slow even frosting
Check liquid line strainer,
liquid line, suction line for temperature change. frost or ice will generally
indicate restriction.
Remove bulb, hold in
hand. Feel distributor to see if valve opened
Check liquid line temperature and sight glass
Verify voltage at motor,
remove belt, spin
motor by hand.
Check air temperature
rise across condenser,
purge condenser,
observe effect on
condensing pressure
Purge refrigerant, check for reduction in head pressure
Page 10
Possible Remedy
Replace wire, tighen con­nections of if is grounded, replace it.
Replace as required
Replace compressor if required
Replace wire if necessary,
tighten
Consult with
power company
Replace compressor
Clean or replace filters,
clean evaporator coil, increase fan speed, correct indoor fan rotation
Remove restriction
Adjust or replace power element.
Leaktest system, repair leak, evacuate when necessary, recharge
Replace or repair motor
Evacuate system
Remove refrigerant until operating pressures are
normal.
compressor
connections.
CONTROL
CIRCUIT
OPEN
MOTOR
TEMPERATURE
SENSOR OPEN
Air Cooled Condenser
Fan(s) Inoperative
Thermostat
Contacts
Open
Protective
Control
Defective Defective
Starter
Coil
Motor
Temperature
too High
Verify voltage at motor, check bearings.
Adjust to lowest setting, check for voltage across compressor starter operating coil
Check switch operation
Check voltage at coil. If burned will generally have burned odor and dark appearance
Check motor for failure, check voltage, check
running current, check refrigerant charge Megger Motor
18
Replace motor or repair defective bearing
If thermostat is defective,
replace
If defective, replace
If defective replace coil
Correct operating
conditions or if motor
is defective, replace.
Page 19
TROUBLE SHOOTING GUIDE
NOISY
COM
PRESSOR
Low Refrigerant
Charge
Low
Air
Deliverv
Compressor
Not
Pumping
Compressor
Running
Unloaded
I
_iquid
refrigerani
flooding back
to compressor
Defective
Compressor
Head
Valves
System Leak
Coil and or Filter Dirty
Fan Speed too Low
Evaporator
Fan
Problem
Head Valves
Broken or
Head Gaskets
Blown
Unloading solenoid
Valve Stuck in
Unloaded Position
Faulty Expansion
Valve or Improper
Suoerheat Settinq
Liquid Refrigerant
Returning to Compressor
Expansion Valve and Liquid Line Problems
Excess Oil in Svstem
Normal Wear
Check operating pressures Leak test, repair and liquid line recharge temperatures
Inspect filters and coil
Check fan speed and duct.Adjust fan speed, if
resistance against design
specifications
Start and stop fan,
observe rotation of
blades.
Check temperatures by
hand. Discharge and
suction lines warm cylinder Replace compressor
hot. Check suction and
discharge pressure
Check unloading solenoid Replace coil or valve
valve for defect
Check super heat
Try to pump system down. Check how fast discharge and suction pressures equalize
Clean or replace filters, clean coil
restriction is in duct may require laraer motor
If fan rotation is wrong correct by fan inter­changing motor connections
Readjust or replace valve
If compressor will not
pump or pressures equalize too fast, replace compressor.
OIL
PRESSURE
PR0BLEMS -
Liquid
Refrigerant
Returning to
Compressor
Oil Trapping
Expansion Valve Not Set Properly, Leaking Liquid Solenoid Valve
Piping Problem
Check valves Adjust or replace
as necessary
Check piping arrangement
and size. Check for
Check for possible traps.
Modify as necessary
valve(s)
19
Loading...