McQuay Skyline OAH 003, Skyline OAC 004, Skyline OAC 003, Skyline OAH 004, Skyline OAH 006 Installation And Maintenance Manual

...
Page 1
Installation and Maintenance Manual IM777
Skyline Outdoor Air Handler
Sizes 003 - 055
Group: Applied AIr Part Number: IM777 Date: April 2003
© 2003 McQuay International
IM777 Page 1
Page 2
Table of Contents
Nomenclature ...................................................................... 2
General Information .................................. .......................... 3
Receiving and Handling .................................................. 3
Unit Storage .....................................................................3
Installation Guidelines ........................................................ 4
Service Clearances .......................................................... 4
Rigging ............................................................................ 4
Curb Mounting and Leveling .......................................... 5
Section Assembly ............................................................5
Access Doors and Panels ................................................. 6
Duct Connections ............................................................ 7
Dampers and Hoods ........................................................ 7
Mounting Actuators ......................................................... 8
Face and Bypass Section Mounting ................................ 8
Piping Vestibules ................................ ............................. 8
Piping and Coils ....................................... ....................... 8
Drain Pan Traps ............................................................. 11
Internal Isolation Assembly Adjustment .......................11
Nomenclature
OAH 003 F D A C
Electrical Installation .....................................................12
Operation Guidelines .........................................................13
Startup Checks ...............................................................13
Fan Wheel Alignment ....................................................14
Fan Operating Limits .....................................................16
Fan Vibration Levels ......................................................17
Service and Maintenance ..................................... ..............18
Periodic Service and Maintenance .................................18
Ball Bearing Lubrication ................................................18
Fan Drive Adjustments ..................................................18
Drive Belt Adjustment ...................................................21
Front Load Filter Option ................................................22
Winterizing Water Coils ................................................23
Coil Maintenance ...........................................................23
Component Removal & Replacement ...........................24
Warranty ............................................................................26
Warranty Return Material Procedure .............................26
Replacement Parts ..........................................................26
Model
OAH = Outdoor air handler OAC = Outdoor component
Nominal Unit Size (nominal square foot of coil)
003, 004, 006, 008, 010, 012, 014, 017, 021, 025, 030, 035, 045, 055
Vintage of McQuay Air Handling Unit
Unit Cross Section
C = Standard unit cross section M = Custom size cross section
Motor Location
A = Motor along side of fan housing D = Motor downstream of belt drive plenum fan F = Motor on inline fan G = Motor downstream of direct drive plenum fan T = Motor behind twin housed fans
Unit T y pe/Co il Positi on
B = Blow-thru cooling coil location D = Draw-thru cooling coil location H = Heating only V = Vent only
Page 2 IM777
Page 3
General Information
The system design and installation must follow accepted industry practice, such as described in the ASHRAE Hand­book, the National Electric Code, and other applicable stan­dards. The installation of this equipment must be in accordance with regulations of authorities having juris­diction and all applicable codes. It is the responsibility of the installer to determine and follow the applicable codes.
Installation and maintenance must be performed by qual­ified personnel familiar with applicable codes and regula­tions, and experienced with this type of equipment. Sheet metal parts, self-tapping screws, clips, and such items inherently have sharp edges, and it is necessary that the
installer exercise caution.
CAUTION
SHARP EDGES AND COIL SURFACES are a potential injury hazard. Avoid contact with them.
ATTENTION
Les bords tranchants et les surfaces des bobines sont un risque de blessure. Ne les touchez pas.
Receiving and Handling
1. Carefully check items against the bills of lading to verify all crates and cartons have been received. Carefully inspect all units for shipping damage when received. Report damage immediately and file a claim for damage with the carrier.
2. Skyline air handler units are constructed of heavy-gauge galvanized steel and are thoroughly inspected before leav­ing the factory. Care must be taken during installati on to prevent damage to units.
3. Take special care when handling the blower section. All fans are dynamically balanced before leaving the factory. Rough handling can cause misalignment or a damaged bearings or shaft. Carefully inspect fans and shaft before unit installation to verify this has not happened.
4. If necessary, screws, bolts, etc., for assembly of sections are supplied in a bag attached to each section. All neces­sary gasketing is applied in the factory for section to sec­tion mounting. Units require caulk sealant between sections.
Unit Storage
Store unit on a level surface. If air handling units are to be stored for any period of time, it is important to periodically rotate the fan wheel. The fan wheel should be periodically rotated to prevent permanent distortion of drive components. In addition, grease may settle in the lower part of the bearing, which may lead to oxidation on the upper portion of the bearing surface. It is also important to keep the fan bearings lubricated.
IM777 Page 3
Page 4
Installation Guidelines
Service Clearances
In addition to providing adequate space around the unit for piping coils and drains, access is always required on at least one side of the unit to allow for regular service and mainte­nance. Filter replacement, drain pan inspection and cleaning, fan bearing lubrication and belt adjustment are examples of routine maintenance that must be performed. Sufficient space must also be provided on the side of the unit for shaft removal and coil removal if necessary . Space at least equal to the length of the coil is required for coil removal. Refer to the
"Coil data" section in Catalog 570 for information about coil sizes. See Figure 1 for servicing space requirements.
At least 54" of clearance must be maintained in front of elec­trical power devices. Electrical power devices that are mounted on the side of the unit are typically up to 12" deep. See Figure 2.
Figure 1. Servicing space requirements
4.00" Lifting Bracket
Width
30.00"
4.00"
Width of coil section
30.00"
Width of
fan section
Figure 2. Service clearance for electrical power devices
1 2 "
5 4 "
Rigging
Skyline air handlers ship completely assembled, or in sec­tions. The unit must be rigged as it ships from the factory. Do not rig units after assembly. Unit s ar e p rovide d wit h a factory installed base rail and can be lifted using the 2" diame­ter lifting holes located in the corners of each shipping section.
To prevent damage to the unit cabinetry, use spreader bars. Spreader bars must be in position to stop cables from rub­bing the frame or panels. Before hoisting into position, test lift for stability and balance. Avoid twisting or uneven lift­ing of the unit.
Figure 3. Unit and section rigging
3
0
.
0
0
"
Page 4 IM777
Height
Page 5
Curb Mounting and Leveling
Do not place a Skyline unit over an open curb unless it is equipped with a curb-ready base. Installation instructions for mounting units on a roof curb are provided in IM770. For a copy , contact your local McQuay Representative or visit www.mcquay.com. Make provisions under the unit to divert any moisture from entering the building below.
For units without roof curb mounting, place the equip­ment on a flat and level surface. Where surface irregular­ities exist, shim the base of the unit at one or more points along the length of the rails to prevent distortion or sag­ging. Uneven or distorted sections will cause misfit or binding of the doors and panels and improper draining of drain pans. See Figure 4.
Figure 5. Apply sealant to mating faces
1 / 4 " d i a m e t e r b e a d c e n t e r e d i n f a c e o f c l e a r a n c e
U s e S p l i c e J o i n t a s a g u i d e
Figure 4. Leveling the unit
Shim sections until they are straight and level
Shim to prevent distortion if width is over 108"
Section Assembly
If the unit is shipped in more than one shipping section, rig each section into position separately. Shipping sections are provided with a connection splice joint attached on the leav­ing air side of the shipping section that seals against the frame channel on the entering-air side of the adjoining sec­tion. The splice joint is insulated, and provides an air-tight seal between two sections once they are assembled together. The Splice Joint must be aligned to seat into the mating gas­ket to provide an air seal. If the Splice Joint was bent during shipping or rigging, verify it is restored to its origin al posi­tion. Figure 6 on page 5.
2. Pull sections together to fasten. Use straps and a ratchet to help pull the sections together securely. Apply sealant to any gaps that may admit moisture.
3a.Fasten base rails together first using the 3/8"-16 by 5"
bolts found in the splice kit provided with the unit See Figure 6. To fasten 2 shipping sections together, 4 bolts are needed (two on each side of the unit). The bolts are run from one base rail into the other and fastened with a nut. Complete each section bottom and top before attaching additional sections.
Figure 6. Fasten bottom of section
Use the following procedure to assemble shipping sections:
1. Caulk all assembly joints of the unit. The mating faces of the cabinet must have at least a 1/4 inch diameter bead of sealant applied before the sections are joined. Use the splice joint as a guide for application of the sealant. See
Figure 5.
IM777 Page 5
3 / 8 x 1 " B o l t a n d N u t
3b.If desired, shipping sections for non curb-ready units can
be fastened together internally. Internal fastening is achieved by running field provided #10 sheet metal screws or drill screws (4" long maximum) through the interior frame channel of one unit into the splice joint of the neighboring section.
Page 6
Figure 7. Internal fastening
flanges. Bend the ends of the splice cap down to secure in place. Assemble the small splice plate at the top rail to secure the sections together at the top. Use 5/16" bolts.
See Figure 9.
Figure 9. Splice cap & splice plate
S l i d e S p l i c e C a p o n a n d b e n d e n d s d o w n
Splice Collar must be aligned to seal to gasket.
A
View A
3c.Units with curb-ready ba ses and vesti bules must be han-
dled so that the lifting bracket can be removed after the unit is placed on the curbing. Remove the lifting bracket that projects inward over the curbing. Save the self tap­ping screws. When the adjacent section is placed in posi­tion, use self tapping screw to secure the bases together.
Figure 8. Remove vestibule lifting bracket
5 / 1 6 - 1 8 B o l t
5 / 1 6 - 1 8 N u t
S p l i c e P l a t e
Access Doors and Panels
For routine maintenance, access is normally obtained through access doors or by removing side panels. Removing all flat head fasteners along the sides of a panel will allow it to be removed.
Fan and filter sections are always provided with a service door on one side of the unit. If requested on order, doors can be provided on both sides of the unit. Optional service doors are available for most section types, and are provided based on customer request.
NOTE: Opening fan section doors requires the use of a 1/2" socket wrench. This satisfies ANSI standards and other codes that require the "use of tools" to access compartments con­taining moving parts or electrical wiring. See Figure 10.
1. Remove padlock if one is present.
CAUTION: DO NOT attempt to rotate the cup. Damage to the unit will occur.
R e m o v a b l e L i f t i n g B r a c k e t
4. Check that the sealant is compressed between the mating channels when the unit sections are joined. Touch up any places where gaps are noted. After sections are seated tightly together, slip the splice cap over the top panel
Page 6 IM777
2. Insert 1/2" socket into cup and rotate 1/4 turn clockwise as shown in Figure 10. If the cup and handle are on the left side of the door, rotate 1/4 turn counter-clockwise.
3. Rotate door handle 1/4 turn clockwise, then 1/4 turn counter-clockwise to release any internal pressure or vac­uum and open the door. If the cup and handle are on the left side of the door, rotate door handle 1/4 turn counter­clockwise, then 1/4 turn clockwise.
4. To prevent air leakage, tighten the door panels by adjust­ing the jam nuts.
Page 7
Figure 10. Opening fan section door
Figure 12. Flashing over top panels and sides of units
Do Not Rotate Cup
Jam Nuts
View from inside door
OPEN
Duct Connections
Flexible connectors should be used on the outlet and inlet duct connections of all units. Do not position down flow fans over air ducts that are routed down into the building. A dis­charge plenum is recommended when bottom connections are necessary. See Figure 11.
F l a s h i n g
D u c t
F l a s h i n g
D u c t
F l a s h i n g
U n i t t o p p a n e l
F l a s h i n g
Dampers and Hoods
Side dampers may be provided in the mixing box and econo­mizer sections of units. When dampers are provided, a removable panel is located above the weather hood to pro­vide access to the damper drive shaft. Other access may be available depending on the specific construction of the unit. See Figure 13.
Figure 13. Filler panel over the weather hood
Figure 11. Discharge plenum
D i s c h a r g e
P l e n u m
If the unit has a top mixing box or econo mi zer damper, or a top duct connection, flashing mu st be field fabricated and installed to divert moisture from the connection. The flashing must lap over the standing seams of the top panels. The flashing must also lap over the side edges of th e unit. See
Figure 12.
Remove screws and panel to access damper control shaft.
Hood
When units are ordered with exhaust hoods and intake hoods adjacent to each other, a field supplied barrier is recom­mended to prevent re-circulation of exhaust air into the intake openings. See Figure 14.
IM777 Page 7
Page 8
Figure 14. Field installed barrier between hoods
I n t a k e
B a r r i e r
E x h a u s t
Mounting Actuators
The installing contractor is responsible for the mounting of all field installed actuators. No provisions are made for the loca­tion of these actuators due to the number of options and arrangements available and the variety of specific applications. Ty pically, actu ators are mounted insi de the cabinet . Provide proper support for the actuator to avoid excessive stress in the cabinet, linkage, or damper shafts.
Piping Vestibules
The openings for routing the field piping must be cut as required in the field for units that include a piping vestibule. Carefully seal passages cut through the panels to prevent air leakage. A single metal thickness pan is provided in the bottom of the curb mounted vestibule. The pan can be removed if necessary. If holes are cut into the pan for a piping passage, seal the holes to prevent moisture leakage.
See Figure 15.
Figure 15. Seal holes for piping - curb mounted units
Seal Holes Cut for Piping
Note: Damper blades are at full flow when open to 70
degrees. Do not open blades further than 70 degrees.
Fresh air and return air dampers can be linked together and driven from the same actuator if the dampers are the same size. If the dampers are different sizes, they must be driven by separate actuators and controlled appropriately. Exhaust dampers are always driven by a separate actuator.
A typical rotary electric actuator can handle up to 40 sq. ft. of damper. For pneumatic actuators, allow 5 in-lb. per square foot of damper area.
Face and Bypass Section Mounting
Internal and external face and bypass sections are mounted together using the instructions for horizontal components and do not require additional instruction. Skyline air handlers are provided with a bypass duct that is integral to the unit con­struction and requires no field assembly.
Face and bypass dampers may or may not be linked together. When dampers are placed before a single bank of coils, they are always linked together and require a single actuator. When dampers are bypassing a stacked or staggered coil, the dampers are not linked and will require multiple actuators.
Face and bypass dampers have a torque requirement of 10 in­lbs. per square foot of damper face area.
For units with standard base rails, the vestibule is open to the coil section so all holes must be sealed to prevent air leakage.
Figure 16. Seal holes for piping - standard base rail units
Seal Holes Cut for Piping
Piping and Coils
Follow applicable piping design, sizing, and installation information presented in ASHRAE Handbooks in the design and installation of piping. Observe all local codes and indus­try standards. Undue stress should not be applied at the con­nection to coil headers. Pipework should be supported independently of the coils.
Page 8 IM777
Page 9
Water Cooling Coils
Note:It is recommended that Glycol be used in water coils for
outdoor air handlers. Power failures and other mechani­cal issues can expose coil s to freezing temperatures.
1. Water supply, water return, drain, and vent connections extend through the end panel of the coil section. All con­nections are labeled on the end panel.
2. Water supply and water return connections are typically male N.P.T. iron pipe.
3. When installing couplings, do not apply undue stress to the connection extending through unit panel. Use a
backup pipe wrench to avoid breaking the weld between coil connection and header.
4. Follow recommendations of the control manufacturer regarding types, sizing, and installation of controls.
Direct Expansion Coils
1. The coil distributor and suction connection extend through the end panel of the coil section.
2. Check nozzle in distributor for proper tonnage.
3. When a thermostatic expansion valve is supplied with the unit, it will be located outside the unit and connected directly to the distributor (except on units with piping vesti­bules). Do not apply heat to the body of the expansion valve.
4. The thermostatic expansion valve must be of the external equalizer tube type. Connect the 1/4-inch diameter exter­nal equalizer tube provided on the coil to connection on expansion valve.
5. Use care when piping up the system to see that all joints are tight and all lines are dry and free of foreign mate­rial. For typical refrigerant piping, see condensing unit product manual.
Steam coils (refer to Figure 17 on page 10)
Note: Steam traps should not be placed outdoors.
1. All steam coils in units are pitched toward return connection.
2. Steam supply and steam return connections are typically male N.P.T. iron pipe and are labeled o n the en d panel of coil section. Connections extend through coil section end panel.
3. When installing couplings, do not apply undue stress to the connection extending through unit panel. Use a
backup pipe wrench to avoid breaking the weld between coil connection and header.
4. Support piping independently of coils and provide ade­quate piping flexibility. Stresses resulting from expansion of closely coupled piping can cause serious damage.
5. Do not reduce pipe size at the coil return connection. Carry return connection size through the dirt pocket, mak­ing the reduction at the branch leading to the trap.
6. Install vacuum breakers on all applications to prevent retaining condensate in the coil. Generally, the vacuum breaker is to be connected between the coil inlet and the return main, the vacuum breaker should be open to the
atmosphere, and the trap design should allow venting of large quantities of air.
7. Do not drip supply mains through the coil.
8. Do not attempt to lift condensate when using modulating or on/off control.
9. Size traps in accordance with manufacturers' recommen­dations. Be certain that the required pressure differential will always be available. Do not under-size.
10.Float and thermostatic or bucket traps are recommended for low pressure steam. On high pressure steam, bucket traps are normally recommended. Thermostatic traps should be used only for air venting.
11.Bucket traps are recommended for use with on/off control only.
12.Locate traps at least 12 inches below the coil return connection.
13.Multiple coil installation.
a. Each coil or group of coils that is individually con-
trolled must be individually trapped.
b. Coils in series: Separate traps are required for each
coil, or bank of coils, in series.
c. Coils in parallel: A single trap may generally be used
but an individual trap for each coil is preferred.
d. Do not attempt to lift condensate when using modu lat-
ing or on/off control.
14.With coils arranged for series airflow a separate control is required on each bank or coil in the direction of airflow.
15.Modulating steam valves are not recommended on high pressure systems.
16.Modulating valves must be sized properly. Do not under-size.
17.Freezing conditions (entering air temperatures below 35°F).
a. 5JA, 8JA, 5RA and 8RA coils are strongly recommended. b. 5 psi steam must be supplied to coils at all times. c. Modulating valves are not recommended. Control
should be provided by face and bypass dampers.
d. Consideration should be given to the use of two or three
coils in series with two position steam control valves on that coil or coils which will be handling 35°F or colder air. The desired degree of control can be at tain ed wit h a modulating valve on the downstream coil.
e. Thoroughly mix fresh air and return air before it enters
the coil. Also, temperature control elements must be properly located to obtain true air mixture temperatures.
f. As additional protection against freeze-up, the trap
should be installed sufficiently below coil to provide an adequate hydrostatic head to provide removal of condensate during an interruption in the steam pres­sure. Estimate three feet for each 1 psi of trap differ­ential required.
g. On startup, admit steam to coil ten minutes before
admitting outdoor air.
h. Close fresh air dampers if steam supply pressure falls
below minimum specified.
IM777 Page 9
Page 10
Figure 17. Piping arrangements
Steam main
Float and
thermostatic trap
Vacuum breaker 1/2" check valve
1/4" petcock for continuous air venting
1" min.
12" min.
5GA or 8GA coils. Note the addition of a vacuum breaker to permit the coil to drain during shutdown.
Vacuum breaker 1/2" check valve
Chec k Valve Strainer Gate V alve
High pressure (over 25 psi)
Steam main
Return main
1/4" petcock for continuous
High pressure float or bucket trap
Return main
air venting
High pressure bucket trap
5TA, 8TA, or 5HA coils. Condensate is lifted to overhead return main
Low pressure (to 25 psi)
Vacuum breaker 1/2" check valve
1" min.
Steam main
Control valve
modulating
two position
12" min.
Full size of return conn.
Steam main
12" min.
5J, 5G, 8J or 8G coils.
Steam main
Vacuum breaker 1/2" check valve
Return main
5RA, 8RA, or 5SA coils. Installed
Return main
Vacuum breaker 1/2" check valve
12" min.
Full size of return conn.
Steam main
12" min.
5JA or 8JA coil. Installed in series. Note that each coil must have a separate control valve and trap.
Return main
Vacuum breaker 1/2" check valve
Return main
5RA, 8RA, or 5SA coils. Banked two high, individual trapping of each coil as shown is preferred.
Page 10 IM777
Page 11
Water heating coils
1. W ater supply and water return connections extend through the end panel of the coil section. All connections are labeled on the end panel.
2. Water supply and water return connections are male N.P.T. iron pipe.
3. When installing couplings, do not apply undue stress to the connection extending through unit panel. Use a backup pipe wrench to avoid breaking the weld between coil connection and header.
4. Follow recommendations of the control manufacturer regarding types, sizes, and installation of controls.
Figure 19. Extend drain fitting for door clearance
C l e a r a n c e
5. Hot water coils are not recommended for use with enter­ing air below 40°F.
6. If fresh air and return air are to be heated by a hot water coil, care should be used in the design of the system to provide thorough mixing before air enters the coil.
7. For preparation of coils for winter operation, see “Winter- izing Water Coils” on page 23.
Drain Pan Traps
Drain lines and traps should be run full size from the drain pan connection. Drain pans should have traps to permit the condensate from the coils to drain freely. On both blow­through and draw-through units, the trap depth and the dis­tance between the trap outlet and the drain pan outlet should be twice the static pressure in the drain pan section under normal operation for the trap to remain sealed. See Figure 18.
Figure 18. Allow adequate distance between tra p o utlet
and drain pan
P r e s s u r e ( P )
a t t h e d r a i n p a n
2 P
2 P
D r a i n
Internal Isolation Assembly Adjustment
On units with internally isolated fan and motor assemblies, the assemblies have been secured for shipment with a tie­down at each point of isolation.
Before operating the unit:
Remove the shipping brackets and tie-down bolts and dis­card. The shipping brackets located on the opposite drive side of the unit are difficult to access from the drive side of the unit. Either remove them before the unit is assembled, or remove the panel on the opposite drive side to gain access. See Figure 20.
The spring isolators under the four corners of the fan and motor assembly have been factory adjusted while the fan was not running. See Table 1. With the unit operating at normal cfm and static pressure, the isolators should all be at the same height opening. If adjustments are required, loosen the 1/2" capscrew on top of the isolator and turn the adjusting bolt to lower or raise the fan and motor base. Retighten the capscrew when adjustments are completed.
Note: The door panels on some applications have a close clearance over the drain pipes. Extend the drain fitting with a coupling if necessary for door clearance. See Figure 19.
Note: Outdoor drain traps should be made of a material that can withstand freezing temperatures.
Note: Drain traps that dry out can allow cold air to seep into the equipment.
IM777 Page 11
Table 1: Factory spring mount adjustments
SPRING MOUNT ADJUSTMENT AT REST
Fan Discharge
Position
1 3.75 3.75 4.25 2 4.25 3.75 4.25 3 4.25 3.75 4.25 4 3.75 3.75 4.25
Top or Bottom Horz. HDownblast
H
Upblast H
Page 12
Figure 20. Removing shipping brackets
S h i p p i n g h o l d d o w n r e m o v e a n d d i s c a r d
S h i p p i n g b r a c k e t r e m o v e a n d d i s c a r d ( T y p i c a l 4 p l a c e s )
( T y p i c a l 4 p l a c e s )
S e e d e t a i l " A "
S p r i n g h e i g h t a d j u s t m e n t s c r e w
Electrical Installation
1. Electrical service to the fan must correspond to the rated voltage on the motor nameplate and be in conformance with the National Electric Code and local restrictions.
2. The fan section metal frame must be connected to the building electrical ground.
3. A door electrical interlock is not provided as standard.
4. Thermal motor protection is external to the unit.
Electrical conduit entrances for units should be located above the bottom of the unit enough to clear components inside, but MUST be located below the bottom of the fan motor junction box. See Figure 21.
Figure 21. Electrical conduit location
D i m " H "
P O S 3
P O S 4
S p r i n g h e i g h t a d j u s t m e n t s c r e w
S h i p p i n g b r a c k e t
M o t o r
F a n
F a n i s o l a t o r p o s i t i o n n u m b e r s
P O S 2
A i r f l o w
P O S 1
S h i p p i n g h o l d d o w n s c r e w
Fan Motor Junction Box
Conduit Entrance (typical)
NOTICE
The base section of each cabinet has a drip pan installed below every panel that drains to the outside frame trough. Any holes cut through the bottom of the unit must also penetrate the drip pan. If holes are cut in the drip pan, they must be sealed to prevent moisture leakage.
Page 12 IM777
Page 13
Operation Guidelines
Startup Checks
When performing startup and service, thorough safety precautions must always be taken. These functions must
be performed by trained, experienced personnel.
WARNING
ROTATING FAN
Can cause severe injury or death. Before servicing fans,
lockout and tag out power.
ATTENTION
Risques de dommages dans le moteur du ventilateur électrique. Si Ia température de l'air a proximité du ventilateurest élevée, le moteurdu ventilateur électrique peut chauffer et brûler. Sur les transmetteurs d'air à circulation transversale ou les transmetteurs dont le ventilateur est en aval de l'unité de chauffage, régler la température de l'air sortant de l'unité de chauffage à 40°C (104°F).
AVERTISSEMENT
PIÈCES MOBILES DANGEREUSES.
Avant de réparer ou entretenir les ventilateurs, coupez l'alimentation èlectrique de cet appareil et bloquez le commutateur à OFF.
WARNING
FIRE/ELECTRIC SHOCK HAZARD.
Can cause property damage, personal injury or death. Fan power supply must be wired and motor frame grounded in accordance with local electric codes.
AVERTISSEMENT
Risques d´incendie et d' électrocution pouvant causer des dommages matériels, des blessures et même la mort. L'alimentation électrique du moteur du ventilateur de même que la mise à la terre du chàssis du moteur doivent être faits conformément aux codes d'installations électriques en vigueur.
WARNING
FAN MOTOR REQUIRES
OVERLOAD PROTECTION.
Failure to provide motor overload protection can result
in fire, property damage, electric shock, personal injury
or death. Connect motor to an overload protective
device rated in compliance with local electric codes.
AVERTISSEMENT
Risques d´incendie et d' électrocution pouvant causer des dommages matériels, des blessures et même la mort. Connecter au moteur du ventilateur électrique un dispositif de protection contre les surcharges conforme aux codes d'installations électriques en vigueur.
CAUTION
DO NOT OVERHEAT FAN MOTOR
High air temperatures in the fan section can cause the fan motor to burnout. On draw-through air handlers or air handlers with the fan section down the air stream from the heating section, the discharge air temperature of the heating section must not exceed 104°F (40°C).
Before starting up the unit
Before entering fan section, make sure that fan electrical power source is disconnected and locked in the "OFF" position.
1. Check that the unit is completely and properly installed with ductwork connected. Check that all construction debris is removed and filters are clean.
2. Check that all electrical work is complete and properly terminated. Check that all electrical connections are tight and that the proper voltage is connected. Phase imbalance must not exceed 2%.
3. Ball bearings on fan shaft and motor are prelubricated and do not need grease before startup.
4. Check tightness of setscrews in bearings and fan wheel(s). If retightening is needed, make certain the fan wheel(s) are positioned per Table 2 or Table 3 on page 14 and set- screws are torqued per Table 6 on page 15.
CAUTION: Equipment damage due to loose fasteners
represents improper start-up and equipment abuse. It is not covered by the warranty.
5. Check alignment of fan and motor sheaves and belt ten­sion. Adjust if necessary. Check tightness of sheave set­screws and/or capscrews. See Figure 28 and Figure 29 on page 21.
6. Leak test thermal system to verify that connections are tight.
7. Check that condensate drain is trapped.
8. Rotate shaft by hand to be sure it is free.
9. Fan startup: Fan should start and run. Observe the rota­tion. If the fan is operating backward, reverse two legs of the 3-phase supply power.
Note: Variable pitch fan drives are usually provided for oper­ation in the mid-speed adjustment range. However, the drives are usually shipped with the adjustment opened up for mini­mum fan speed. The drives should be adjusted for the proper airflow. See “Fan Drive Adjustments” on page 18.
After first 48 hours of operation
1. Disconnect and lock electrical power source. Check tight­ness of all bearing, wheel, and sheave setscrews (or cap­screws). See Table 6
2. Recheck belt tension and adjust if necessary. Belts ten­sioned sufficiently to slip one to two seconds at startup will perform satisfactorily, extending life and reducing vibration. If retensioning is necessary, be certain sheave alignment is retained.
IM777 Page 13
Page 14
Fan Wheel Alignment
Table 2: Wheel-to-inlet funnel relationship —
airfoil type fan wheels (housed)
Table 3: Wheel-to-inlet funnel relationship —
forward curved type fan wheels (housed)
Equal spacing
B
all around
A
AIRFOIL
Unit Sizes 003-055
Diameter A (inches) A (mm) B (inches) B (mm)
13.22 4.56 116 0.21 5.33
14.56 5.06 129 0.21 5.33
16.18 5.62 143 0.21 5.33
17.69 6.90 175 0.22 5.59
21.56 7.59 193 0.24 6.10
24.00 8.45 215 0.23 5.84
Notes:
1. Dimensional relationship must be held to obtain rated air performance.
2. Dimension A is achieved by loosening setscrews in wheel hub(s), shifting wheel(s) axially as needed, and retightening setscr ews.
3. Dimension B is obtained by loosening screw and washer fasteners around periphery of funnel(s), shifting funnel radially as required, and re-torquing fasteners.
A
CC
Inlet
Funnel
Diameter (Inches) C (inches) C (mm)
9 x 4 0.25 6.35 9 x 7 0.13 3.30 9 x 9 0.25 6.35
10 0.22 5.59 12 0.35 8.89 15 0.44 11.18 18 0.25 6.35
20 (class 1 & 2) 0.73 18.54 22-1/2 (class 1 & 2) 0.59 14.99 24-1/2 (class 1 & 2) 0.56 14.22
Notes:
1. Dimensional relationship must be held to obtain rated air performance.
2. Adjust dimension C by loosening wheel hub setscrews, shifting wheel(s) axi­ally as needed, and retightening setscrews.
Wheel
Inlet
Funnel
FORWARD CURVED
Unit Sizes 003-055
Page 14 IM777
Page 15
Table 4: Wheel-to-inlet funnel relationsh ip - plenum fans Table 5: Wheel-to-inlet funnel relationship - inline fa ns
OVERLAP
OVERLAP
WHEEL — FUNNEL OVERLAP
SIZE OVERLAP
13 .120 15 .190
16.5 .250
18.25 .310 20 .380
22.25 .440
24.5 .500 27 .560 30 .620 33 .750
36.5 .810
40.25 .880
WHEEL — FUNNEL OVERLAP
SIZE OVERLAP
150 .375 165 .438 182 .562 200 .625 222 .688 245 .750 270 .812 300 .875
Table 6: Bearing collar and wheel hub setscrew torque
SETSCREW MINIMUM TORQUE
Diameter (inches) ft. / lbs. kg. / M.
1/4 5.5 .76
1/16 10.5 1.45
3/8 19.0 2.63
7/16 29.0 4.01
1/2 42.0 5.81 5/8 92.0 12.72
IM777 Page 15
Page 16
Fan Operating Limits
)
Do not exceed the operating limits in Table 7. A fan wheel that is operated beyond the rpm limits shown may suffer permanent
Table 7: Operating limits - housed fans
FAN OPERATING LIMITS
Forward curved — Housed
Diameter 9 x 4 9 x 7 9 x 9 10.62 12.62 15 18 20 22.25 24.50 Maximum RPM Class I N/A 2189 2223 1934 1614 1328 1155 1050 944 858 Maximum RPM Class II 2244 2854 2896 2518 2091 1725 1450 1200 1030 910
Airfoil — Housed
Diameter 13.22 14.56 16.19 19.69 21.56 24.00 Maximum RPM Class I 3000 3000 2300 2000 1700 1500 Maximum RPM Class Il 4335 3918 3457 2858 2547 2255
Figure 22. Torque for FC variable inlet vanes (in. - lb.) Figure 23. Torque for AF variable inlet vanes (in. - lb.)
distortion or fracture. The resulting unbalance may cause severe unit vibration.
300 250
200
150
100
90
Torque (in.-lb.)
80 70
60
50
350
400
450
500
550
600
650
FC24.50
FC22.25
800
900
700
750
850
Fan Speed (rpm)
1000
FC20.00
FC18.00
FC15.00
1500
FC12.62
2000
4 5 0 4 0 0
3 5 0 3 0 0 2 5 0
2 0 0
1 5 0
1 0 0
9 0 8 0 7 0
T o r q u e ( i n . - l b . )
6 0 5 0 4 0 3 5
3 0
7 5 0
9 0 0
8 0 0
8 5 0
1 0 0 0
A F 2 4 . 0 0
A F 2 1 . 5 6
1 5 0 0
F a n Spe e d (rpm
2 0 0 0
A F 1 9 . 6 9
2 5 0 0
A F 1 6 . 1 9
A F 1 4 . 5 6
3 0 0 0
A F 1 3 . 2 2
3 5 0 0
4 0 0 0
Table 8: Operating limits — plenum fans
FAN OPERATING LIMITS
Diameter 13.5 15 16.5 18.25 20 22.25 24.5 27 30 33 36.5 40.25 Maximum RPM Class I 2895 2589 2376 2256 2077 1875 1691 1479 1328 1209 1073 972 Maximum RPM Class II 3786 3384 3100 2959 2703 2413 2199 1928 1730 1579 1401 1264 Maximum RPM Class III 4000 4000 3887 3735 3409 3065 2780 2423 2182 1984 1756 1598
4 5 0 0
Page 16 IM777
Page 17
Figure 24. Torque requirements at 100% WOV for SWSI plenum fa ns with NESTED inlet vane
5000
4000
3000
2000
1000
Torque (lb./in.)
900 800
Torque (in.-lb.)
700
600
500
400
300
200
100
600
400
300
200
700
500
Fan Speed (rpm)
0
0
6
2
4
5
0
9
4
5
4
4
2
0
4
5
6
3
0
3
3
300
270
45
2
800
900
1000
2000
1500
3000
Table 9: Operating limits — inline fans, twin fans
FAN OPERATING LIMITS
Inline Fans
Diameter 150 165 182 200 222 245 270 300 Maximum RPM Class I 2727 2488 2236 2041 1835 1665 1476 1330 Maximum RPM Class II 3409 3111 2796 2551 2294 2082 1846 1662
Twin Fans
Diameter 9.5 10.62 12.62 15 18.12 20 Maximum RPM 2400 2000 1600 1400 1200 1000 Maximum HP 10 15 15 30 40 40
Fan Vibration Levels
Each unit as shipped has been trim-balanced to operate smoothly. If excessive vibration occurs after installation, use the accepted industry guidelines for field balancing fans. See
Table 10.
Table 10: Vibration levels
FAN SPEED (RPM) VIBRATION
800 or less 5 mils maximum displacement
801 or greater 0.20 in/sec. maximum velocity
Note:Excessive vibration from any cause contributes to premature fan and motor bearing failure. Overall vibration levels should be monitored every six months of operation. An increase in levels is an indication of potential trouble.
Vibration causes
1. Wheel imbalance. a. Dirt or debris on wheel blades.
IM777 Page 17
b. Loose setscrews in wheel hub or bearing-to-shaft. c. Wheel distorted from overspeed.
2. Bent shaft.
3. Drive faulty. a. Variable pitch sheaves - Axial and radial runout of
flanges; uneven groove spacing; out of balance. Also similar faults in driven sheave.
b. Bad V-belts; lumpy, or mismatched; belt tension too
tight or too loose.
4. Bad bearings, loose bearing hold-down bolts.
5. Motor imbalance.
6. Fan section not supported evenly on foundation.
Page 18
Service and Maintenance
Periodic Service and Maintenance
1. Check all moving parts for wear every six months.
2. Check bearing collar, sheave, and wheel hub setscrews, sheave capscrews, and bearing hold-down bolts for tight­ness every six months.
Ball Bearing Lubrication
1. Motor bearings - All ball bearings are prelubricated and do not require addition of grease at time of installation. However, periodic cleaning out and renewal of grease is necessary . Please note that extreme care must be exercised to prevent foreign matter from entering the bearing. It is also important to avoid over-greasing. Only a high grade, clean mineral grease having the following characteristics should be used.
a. Melting point preferably over 302°F (150°C), freedom
from separation of oil and soap under operating and storage conditions; and freedom from abrasive matter, acid, alkali and moisture.
b. Specific greasing instructions are located on a label
attached to the fan section door.
2. Fan shaft bearings - All ball bearings are prelubricated and do not require addition of grease at time of installa­tion. However, periodic renewal of grease is necessary. Bearings are accessible through access door in fan sec­tion. Grease fittings are located in front of door opening on drive end of blower section. Apply grease slowly until a very slight bleeding of grease from the seals is noted. Tie hinged door(s) open. Do not over-lubricate. W ipe of f any excess grease to prevent overheating.
The lubrication interval varies with the period of opera­tion and temperature of the ambient air. Follow instruc­tions listed below:
Bearing Operating Temp Range
to 130°F
(54°C) Cont. Operation: 6 months 4 months 2 months 12-Hr. Day Operation: 12 months 12 months 6 months
Table 11: Lubricants recommended for
fan shaft ball bearings
MANUFACTURER PRODUCT NAME
Texaco Lubricants Company Premium RB -30 to 300 -34 to 149 Keystone Ind. Lubricants 81EP-2 0 to 250 -18 to 121 Mobil Oil Corporation Mobilith SCH100 -40 to 350 -40 to 177 Chevron U.S.A. Inc. SRI-2 -20 to 325 -29 to 163 Exxon Company, U.S.A. Ronex MP -40 to 300 -40 to 149 Shell Oil Company Alvania No. 2 -20 to 240 -29 to 116
Note:Temperature ranges over 225°F are shown for lubricants only. High temperature applications are not suitable for standard air handler components.
to 150°F
(66°C)
over 150°F
(66°C)
TEMP. RANGE
°F °C
Fan Drive Adjustments
WARNING
ROTATING FAN
Can cause severe injury or death. Before servicing fans,
lockout and tag out power.
AVERTISSEMENT
PIÈCES MOBILES DANGEREUSES.
Avant de réparer ou entretenir les ventilateurs, coupez l'alimentation èlectrique de cet appareil et bloquez le commutateur à OFF.
WARNING
MOVING PARTS
Do not open the hinged access door and screw-fastened
access panels while the unit is operating. Moving parts
and strong suction forces can cause severe personal
injury or death.
BEFORE ENTERING ANY FAN SECTION, MAKE SURE THE ELECTRICAL POWER SOURCE TO THE FAN MOTOR IS DISCONNECTED, LOCKED OUT AND TAGGED OUT.
Do not enter the fan section while the unit is operating to determine fan speed.
Upon completion of the air balance, it is recommended that the variable pitched motor sheave be replaced with a properly sized fixed sheave. Initially, it is best to have a variable pitched motor sheave for the purpose of air balancing, but fixed sheaves maintain balancing and alignment more effec­tively and provide longer belt and bearing life and vibration free operation.
With the electrical power disconnected, locked and tagged out, measure the diameter of the V-belt outer surface where it passes around the sheave (pitch diameter). Calculate fan speed from the motor nameplate rpm.
Fan rpm = Motor rpm x
"VM" and "VP" Variable Pitch Key Type Sheaves
Mounting:
1. All sheaves should be mounted on the motor or driving shaft with the setscrews "A" toward the motor.
2. Verify that both driving and driven sheaves are in align­ment and that shafts are parallel.
3. Fit internal key "D" between sheave and shaft, and lock setscrew "A" securely in place.
Measured Diameter at Motor Sheave Measured Diameter at Fan Sheave
Page 18 IM777
Page 19
Adjusting:
1. Loosen setscrews "B" and "C" in moving parts of sheave and pull out external key "E". (This key projects a small amount to provide a grip for removing.)
2. Adjust sheave pitch diameter for desired speed by opening moving parts by half or full turns from closed position. Do
not open more than five full turns for "A" belts or six full turns for "B" belts.
3. Replace external key "E" and securely tighten setscrews "B" over key and setscrews "C" into keyway in fixed half of the sheave.
4. Put on belts and adjust belt tension. Do not force belts over grooves (see “Drive Belt Adjustment” on page 21).
5. Future adjustments should be made by loosening the belt tension and increasing or decreasing the pitch diameter of the sheave by half or full turns as required. Readjust belt tension before starting drive.
6. Two-groove sheaves must have both halves adjusted by the same number of turns from closed position to provide the same pitch diameter.
c. Remove key "F". Note: This key projects a small
amount to provide a grip for removing.
d. Rotate the flange counterclockwise until it disengages
the threads on the sheave barrel.
4. V erify that the driving and driven sheaves are in alignment and the shafts are parallel. When aligning two-groove sheaves, allow room between the sheave and motor to get to capscrews "E".
5. Insert key "C" between the sheave and the shaft and tighten setscrew "A" securely.
6. If flange and locking ring have been removed, when replacing them make sure that the inner and outer flanges are open from the closed position by the same amount as the other flange. This can be determined by accurately measuring the top width of the grooves.
7. Insert key "F".
8. Tighten setscrews "D" and capscrews "E".
9. Put on belts and adjust belt tension. Do not force belts over grooves (see “Drive Belt Adjustment” on page 21).
7. Verify that all keys are in place and that all setscrews are tight before starting drive. Check setscrews and belt ten­sion after 24 hours service.
Figure 25. "VP" type sheave adjustment
A
S i n g l e G r o o v e
N O T E : D o n o t o p e r a t e s h e a v e w i t h f l a n g e p r o j e c t i n g b e y o n d t h e h u b e n d .
B
E
A
D
C
T w o G r o o v e
K e y " E " p r o j e c t s t o p r o v i d e a g r i p f o r r e m o v i n g
B
E
D
C
"LVP" Variable Speed Sheaves
Mounting:
1. Slide sheave on motor shaft so that the side of the sheave with setscrew "A" is next to the motor, when setscrew "A" is in the hub or barrel of the sheave.
2. When setscrew "A" is at an angle in the center flange "B", it should be mounted away from the motor so that the outer locking ring and flange can be removed to get to the setscrew.
3. To remove the flange and locking ring: a. Loosen setscrews "D".
10.Be sure that all keys are in place and all setscrews and all capscrews are tight before starting the drive. Check and retighten all screws and retension belts after approxi­mately 24 hours of service.
Adjusting:
1. Slack off belt tension if belts have been installed.
2. Loosen setscrews "D".
3. Loosen but do not remove capscrews "E".
4. Remove key "F". Note: This key projects a small amount to provide a grip for removing.
5. Adjust pitch diameter by opening or closing the movable flanges by half or full turns. Note: Two-groove sheaves are supplied with both grooves set at the same pitch diam­eter. Both movable flanges must be moved the same
number of turns to provide the same pitch diameter for satisfactory operation. Do not open sheaves more than five turns for "A" belts or six turns for "B" belts.
6. Replace key "F".
7. Tighten setscrews "D" and capscrews "E".
8. If belts have been installed, readjust belt tension. If belts have not been installed, install them and adjust belt ten­sion. Do not force belts over grooves (see “Drive Belt Adjustment” on page 21).
9. Verify that all keys are in place and all setscrews and all capscrews are tight before starting the drive. Check and retighten all screws and retension belts after approxi­mately 24 hours of operation.
b. Loosen but do not remove capscrews "E".
IM777 Page 19
Page 20
Figure 26. "LVP" type sheave adjustment
"MVP" Variable Speed Sheaves
Mounting:
1. Verify both driving and driven sheaves are in alignment and the shafts are parallel. The centerline of the driving sheave must be in line with the centerline of the driven sheave. See Figure 27.
2. Verify that all setscrews are torqued to the values shown in Table 12 before starting drive. Check setscrew torque and belt tension after 24 hours of service.
Adjusting:
1. Adjust motor base forward to release belt tension. Remove the belts for easier adjustment.
2. Loosen, but do not remove both of the locking setscrews "A" in the outer locking ring by using a hex key or torque wrench with a hex bit.
3. Adjust sheave to desired pitch diameter by turning the outer locking ring. Use a spanner wrench or drift inserted into the 3 holes that are located 120° apart on the ring.
4. Any pitch diameter can be obtained within the sheave range. One complete turn of the outer locking ring will change the pitch diameter 0.233".
5. Do not open sheaves more than the following
• Do not open "B" sheaves more than 4-3/4 turns for the "A" belts or 6 turns for the "B" belts.
• Do not open "C" sheaves more than 9-1/2 turns.
• Do not open "5V" sheaves more than 6 turns.
• Do not open "8V" sheaves more than 8 turns.
sheave pitch. Do not operate the drive until the locking screws have been set to the torque specifications.
Table 12: Screw torque values
Nominal
Screw
Size
(Dia-Thds/
In.)
1/4-20NC 150 12.5 100 87 7.3 3/16 50
5/16-11NC 305 25.4 200 165 13.8 1/4 90
3/8-16NC 545 45.4 350 290 24.2 1/4,5/16 150,250 1/2-13NC 1300 108.3 N/A 620 51.7 N/A N/A 5/8-11NC N/A N/A N/A 1225 102.1 N/A N/A
Socket Head
Cap Screws
Seating Torque
(in.-lbs.) (ft.-lbs.) (in.-lbs.) (in.-lbs.) (ft.-lbs.) (in.) (in.-lbs.)
Flat
Head
Socket
Screws Seating
Torque
Hollow Head Set Screws Only
Lengths equal or greater than Dia.
Seating
Torque
Seating
Torque
For Lengths (L)
less than Dia.
Length
(L)
Seating
Torque
Figure 27. Sheave adjustment
Must be parallel
Bearing
Motor
Center lines must coincide
6. Tighten BOTH locking screws "A" in the outer locking ring before operating the drive. Use a torque wrench and tighten to the value shown in Table 12.
7. Replace belts and adjust the motor base to tension the belts properly. See Figure 29.
8. Do not loosen any screws other than the two locking screws "A" in the outer locking ring when adjusting the
Page 20 IM777
Must be parallel
Adjustable Sheave
Page 21
Figure 28. Sheave adjustment
Adjustable Center-Flange
Split Taper Bushing
Fixed Center-Flange
(2) Locking Setscrews "A"
Flathead Socket Screws (Do Not Remove)
Capscrews (Do Not Remove)
Drive Belt Adjustment
General Rules of Tensioning
1. The ideal tension is the lowest tension at which the belt will not slip under peak load conditions.
2. Check tension frequently during the first 24-48 hours of operation.
3. Over tensioning shortens belt and bearing life.
4. Keep belts free from foreign material which may cause slippage.
5. Make V-drive inspection on a periodic basis. Adjust ten­sion if the belt is slipping. Do not apply belt dressing. This may damage the belt and cause early failure.
Stationary End-Flange
Outer
Locking-Ring
Inner Locking-Ring
(3) Holes for Spanner Wrench or Drift
Tension Measurement Procedure
1. Measure the belt span. See Figure 29.
2. Place belt tension checker squarely on one belt at the cen­ter of the belt span. Apply force to the checker, perpendic­ular to the belt span, until the belt deflection equals belt span distance divided by 64. Determine force applied while in this position.
3. Compare this force to the values in Table 13.
Figure 29. Drive belt adjustment
Deflection =
B
e
Belt Span
64
l
t
S
p
a
n
IM777 Page 21
Page 22
Table 13: Belt deflection force
SHEAVE DIAMETER (INCHES) DEFLECTION FORCE (LBS.)
CROSS SECTION
A, AX
B, BX
5V, 5VX
SMALLEST SHEAVE
DIAMETER RANGE
3.0-3.6
3.8-4.8
5.0-7.0
3.4-4.2
4.4-5.6
5.8-8.6
4.4-6.7
7.1-10.9
11.8-16.0
BELT DEFLECTION FORCE
RPM RANGE
1000-2500 3.7 5.5 4.1 6.1 2501-4000 2.8 4.2 3.4 5.0 1000-2500 4.5 6.8 5.0 7.4 2501-4000 3.8 5.7 4.3 6.4 1000-2500 5.4 8.0 5.7 9.4 2501-4000 4.7 7.0 5.1 7.6
850-2500 4.9 7.2
2501-4000 4.2 6.2
860-2500 5.3 7.9 7.1 10.5
2501-4000 4.5 6.7 7.1 9.1
860-2500 6.3 9.4 8.5 12.6
2501-4000 6.0 8.9 7.3 10.9
500-1749 10.2 15.2 1750-3000 8.8 13.2 3001-4000 5.6 8.5
500-1740 12.7 18.9 14.8 22.1 1741-3000 11.2 16.7 13.7 20.1
500-1740 15.5 23.4 17.1 25.5 1741-3000 14.6 21.8 16.8 25.0
CROSS SECTION A, B, 5V CROSS SECTION AX, BX, 5VX
USED BELT NEW BELT USED BELT NEW BELT
Front Load Filter Option
Front loaded filter options require that the filters be removed and replaced from inside the unit.
Moving belt and fan can cause severe personal injury or death. During installation and filter maintenance:
1. Verify that the belt and fan guards on plenum fan units are always in place.
2. Lock and tag out fans to prevent accidental start up.
3. Do not enter the filter compartment until the fan is completely
stopped.
4. Use approved equipment for reaching filters located above nor­mal reach. Do not step on filter frames or unit components.
5. Floor surfaces must be dry and free of oil or grease.
AVERTISSEMENT
Pendant l'installation et où l'entretien des filtres, une cour­roie en mouvement ou un ventilateur en opération peuvent causer des blessures graves où même causer la mort.
1. S' assurer que les gardes de courroie et de ventilateur sont tou-
jours en place.
2. Verouiller les démarreurs des ventilateurs et afficher un avis de
mise-en-garde afin de prévenir tout accident ou démarrage.
3. Attendre que le ventilateur soit complètement arrêté avant d'
entrer dans l' unité.
4. Utiliser seulement des équipements approuvé pour joindre les
bancs de filtres; ne pas mettre soit sur les cadres des filtres ou même sur toutes composantes de l'unité.
5. La surface des planchers doit être sec et libre de toute trace
d'huile et où de graisse.
WARNING
T o remove filters, rotate the wire clips. This will release both the pre-filter and the final filter. When installing clean fil­ters, check to verify the filters are fully seated in the frame.
See Figure 30.
Figure 30. Frame and filters with holding clips
Final Filter
Filter Frame
Rotate Wire Clips
Prefilter
Page 22 IM777
Page 23
Table 14 shows the typical filter pressure drop for clean filters at rated air flow and a final pressure drop for front loaded filters.
Table 14: Filter pressure drops Bag filters - DriPak 2000
Efficiency 45% 65% 85% 95% Rated Velocity (FPM) 625 500 500 500 Initial Pressure Drop .20 -.26 .21 -.30 .34 -.48 .50 -.70
Final Pressure Drop 1.0 1.0 1.0 1.0
Cartridge filters - Varicel II MH - 4.25" deep
Efficiency 65% 85% 95% Rated Velocity (FPM) 500 500 500 Initial Pressure Drop .43 .61 .70
Final Pressure Drop 1.5 1.5 1.5
Cartridge filters - Varicel SH - 12" deep
Efficiency 70% 80% 95% Rated Velocity (FPM) 500 500 500 Initial Pressure Drop .39 .56 .58
Final Pressure Drop 1.2 1.2 1.2
Pleated flat panel filters
Type Perfect Pleat AMAir 300 4"
Efficiency 30% 30%
Rated Velocity (FPM) 500 625 Initial Pressure Drop .36 .36
Final Pressure Drop 1.0 1.0
5700 filters
Efficiency N/A
Rated Velocity (FPM) 500
Initial Pressure Drop .25
Final Pressure Drop 1.0
Pleated 62-Plus filters
Size 2" 4"
Efficiency 70% 70%
Initial Pressure Drop .42 .37
Final Pressure Drop 1.0 1.0
Winterizing Water Coils
Coil freeze-up can be caused by such things as air stratifica­tion and failure of outdoor dampers and/or preheat coils. Routine draining of water cooling coils for winter shutdown cannot be depended upon as insurance against freeze-up. Severe coil damage may result. It is recommended that all coils be drained as thoroughly as possible and then treated in the following manner.
Fill each coil independently with an antifreeze solution using a small circulating pump and again thoroughly drain.
Check freezing point of antifreeze before proceeding to next coil. Due to a small amount of water always remaining in each coil, there will be a diluting effect. The small amount of antifreeze solution remaining in the coil must always be con­centrated enough to prevent freeze-up.
Note: Carefully read instructions for mixing antifreeze
solution used. Some products will have a higher freezing point in their natural state than when mixed with water.
Coil Maintenance
1. The coil must be clean to obtain maximum performance. Check once a year under normal operating conditions and, if dirty, brush or vacuum clean. Use a chemical coil cleaner on multiple row coils. Read and follow the chemi­cal cleaner’s instructions as some cleaners may contain harsh chemicals. Take care not to damage fins while cleaning. Caution: Fin edges are sharp.
2. Drain pans in any air conditioning unit may have some moisture. Algae, etc., will grow due to airborne spores and bacteria. Periodic cleaning is necessary to prevent this build-up from plugging the drain and causing the drain pan to overflow. Also, the drain pans should be kept clean to prevent the spread of disease. Cleaning should be per-
formed by qualified personnel.
IM777 Page 23
WARNING
CLEAN DRAIN PAN REGULARLY SO MOLD
DOES NOT DEVELOP.
AVERTISSEMENT
Pour eviter la moisissure Nettoyer regulierement le
bassin de recuperage.
3. Dirt and lint can clog the condensate drain, especially with dirty filters. Inspect the drain twice a year to help avoid overflow.
Page 24
Component Removal & Replacement
See “Access Doors and Panels” on page 6 for instructions on removing panels and opening fan access doors to remove or replace components.
Fan Section
The fan shaft, motor, and any drive components can be removed and replaced through the access door opening. If required, the side panel can be removed for additional access.
If fan replacement is required, the entire fan assembly can be pulled out the side of the cabinet. The fan assembly includes the fan housing, the bearing support, and the fan base.
To remove the fan assembly, remove the side panels and any intermediate supports (follow instructions for side panel removal). Once the panels and any intermediate supports are removed, disconnect the neoprene bulk head seal that is attached to the fan discharge. Remove the four discharge angles that hold the neoprene canvas in place around the dis­charge opening. Then disconnect the fan sled from each of the corner mounts and pull the entire assembly out the side of the unit. After the fan sled is out, loosen the fan bearings and pull out the shaft. Disconnect the fan housing from the fan sled, and bearing support by removing the attaching bolts.
Replace the new fan, re-connect the shaft and bearings and put the fan assembly in the cabinet. Replace panels and fasteners.
Coil Removal and Replacement
Removing Single coils
Note: Single coils are bolted to the unit on the connection end. The connection end is held in place with a clamp. See Figure 31.
1. Disconnect all piping and remove the brass plugs for the vents and drains located in the connections. Remove all screws and remove the access panel.
2. Remove the screws holding the coil in place then lift and pull the coil out the side.
Installing Single Coils
1. Slide the coil through the opening in th e coil section onto
the bottom coil rests. Coils must be placed up against the coil bulkheads to prevent any air bypass around the coil. Once the coil is in place, fasten coil to the section. Caulk the seams between the coil casings and bulkheads.
See Figure 31.
2. If this is an additional co il being installed and not a
replacement, you must locate the coil supply and return connections dimensionally. Carefully drill holes in the end panels of the unit.
3. Remove the brass plugs for the vents and drains on the
connections. Slip the panel over the connections. Replace the brass plugs and panel fasteners.
Figure 31. Single coil installation / removal
Opposite connection end
Coil
Coil Bulkhead
Connection end
Coil
Coil Rests
Removing Stacked Coils
Note: Top and bottom stacked coils are held together with steel plate and screws on one side and drain trough and screws on the other side. Remove the plate and trough before removing the coils. The coils cannot be removed attached together. See Figure 32.
1. Disconnect all piping and remove the brass plugs for the vents and drains located in the connections. Remove all screws and remove the access panel.
2. Remove the bolts holding the coil in place then lift and pull the coil out the side.
3. Remove the steel plate and the drai n trough that hold the coils together.
4. Remove the bolts on both ends of the top coil holding it in place, then lift and slide the coil out.
5. Remove the bolts o n both ends of t he bottom co il holding it in place, then lift and slide the coil out.
Installing Stacked Coils
1. Slide the bottom coil through the opening in the coil sec­tion onto the bottom coil rests. The coil must be placed up against the coil bulkheads to prevent any air bypass around the coil. Once the coil is in place, bolt the coil to the section.
2. Slide the bottom coil through the opening. The coil must be placed up against the coil bulkheads to prevent any air bypass around the coil. Once the coil is in place, bolt the coil to the section.
3. Caulk the mounting surface of the steel plate and install the plate on the coils.
4. Caulk the mounting surface of the drain tro ugh and install the drain trough on the coils.
Page 24 IM777
Page 25
5. Caulk the seams between the coil casings and blockoffs.
6. Connect all pip ing and install the brass plugs for the vents and drains located in the connections. Install the access panel.
Figure 32. Locations of plate and trough - stacked coils
Trough
Apply Caulk to Mounting Surface Before Installing
Plate
Removing and Installing Staggered Coils
Staggered coils have two banks of coils positioned a few inches apart in the direction of airflow. Both coils are secured to the unit on the connection and opposite connection end of the unit.
1. Disconnect all piping and remove the brass plugs for the vents and drains located in the connections.
2. Panels on both the connection and opposite connection end of the coil section need to be removed to access bolts holding the coils in place. Each coil is held in place with bolts located in the corners of the coil side plates. Remove the bolts then lift and pull the coil out the side.
3. The bottom coil is fastened to the air block off plate. The
screws attaching this plate to the coil must also be removed. Once fasteners holding the coil in place are removed, the coil can be pulled out either side of the unit.
4. Install coils in reverse order of removal.
IM777 Page 25
Page 26
Warranty
Consult your local McQuay Representative for warranty details. Refer to Form 933-43285Y. To find your local McQuay Representative, go to www.mcquay.com.
Warranty Return Material Procedure
Defective material may not be returned without permission of authorized factory service personnel of McQuay Interna­tional in Minneapolis, Minnesota, (763) 553-5330. A "Return Goods" tag must be included with the returned material. Enter the required information to expedite handling and prompt issuance of credits. All parts must be returned to the appropriate McQuay facility, designated on the "Return Goods" tag. Transportation charges must be prepaid.
The return of the part does not constitute an order for replacement. Therefore, a purchase order must be entered through the nearest McQuay representative. The order should include part number, model number, and serial number of the unit involved.
Credit will be issued on customer's purch ase order fol lo wing an inspection of the return part and upon determination that the failure is due to faulty material or workmanship during the warranty period.
Replacement Parts
When writing to McQuay for service or replacement parts, refer to the model number and serial number of the unit as stamped on the serial plate attached to the unit. If replacement parts are required, mention the date of installation of the unit and date of failure, along with an explanation of the malfunc­tions and a description of the replacement parts required.
Page 26 IM777
Page 27
Notes:
IM777 Page 27
Page 28
This document contains the most current product information as of this printing. For the most up-to-date product information, please go to www.mcquay.com.
© 2003 McQuay International • www.mcquay.com • 800-432-1342
Page 28 IM777
Loading...