McQuay Skyline OAH 003, Skyline OAC 004, Skyline OAC 003, Skyline OAH 004, Skyline OAH 006 Installation And Maintenance Manual

...
Installation and Maintenance Manual IM777
Skyline Outdoor Air Handler
Sizes 003 - 055
Group: Applied AIr Part Number: IM777 Date: April 2003
© 2003 McQuay International
IM777 Page 1
Table of Contents
Nomenclature ...................................................................... 2
General Information .................................. .......................... 3
Receiving and Handling .................................................. 3
Unit Storage .....................................................................3
Installation Guidelines ........................................................ 4
Service Clearances .......................................................... 4
Rigging ............................................................................ 4
Curb Mounting and Leveling .......................................... 5
Section Assembly ............................................................5
Access Doors and Panels ................................................. 6
Duct Connections ............................................................ 7
Dampers and Hoods ........................................................ 7
Mounting Actuators ......................................................... 8
Face and Bypass Section Mounting ................................ 8
Piping Vestibules ................................ ............................. 8
Piping and Coils ....................................... ....................... 8
Drain Pan Traps ............................................................. 11
Internal Isolation Assembly Adjustment .......................11
Nomenclature
OAH 003 F D A C
Electrical Installation .....................................................12
Operation Guidelines .........................................................13
Startup Checks ...............................................................13
Fan Wheel Alignment ....................................................14
Fan Operating Limits .....................................................16
Fan Vibration Levels ......................................................17
Service and Maintenance ..................................... ..............18
Periodic Service and Maintenance .................................18
Ball Bearing Lubrication ................................................18
Fan Drive Adjustments ..................................................18
Drive Belt Adjustment ...................................................21
Front Load Filter Option ................................................22
Winterizing Water Coils ................................................23
Coil Maintenance ...........................................................23
Component Removal & Replacement ...........................24
Warranty ............................................................................26
Warranty Return Material Procedure .............................26
Replacement Parts ..........................................................26
Model
OAH = Outdoor air handler OAC = Outdoor component
Nominal Unit Size (nominal square foot of coil)
003, 004, 006, 008, 010, 012, 014, 017, 021, 025, 030, 035, 045, 055
Vintage of McQuay Air Handling Unit
Unit Cross Section
C = Standard unit cross section M = Custom size cross section
Motor Location
A = Motor along side of fan housing D = Motor downstream of belt drive plenum fan F = Motor on inline fan G = Motor downstream of direct drive plenum fan T = Motor behind twin housed fans
Unit T y pe/Co il Positi on
B = Blow-thru cooling coil location D = Draw-thru cooling coil location H = Heating only V = Vent only
Page 2 IM777
General Information
The system design and installation must follow accepted industry practice, such as described in the ASHRAE Hand­book, the National Electric Code, and other applicable stan­dards. The installation of this equipment must be in accordance with regulations of authorities having juris­diction and all applicable codes. It is the responsibility of the installer to determine and follow the applicable codes.
Installation and maintenance must be performed by qual­ified personnel familiar with applicable codes and regula­tions, and experienced with this type of equipment. Sheet metal parts, self-tapping screws, clips, and such items inherently have sharp edges, and it is necessary that the
installer exercise caution.
CAUTION
SHARP EDGES AND COIL SURFACES are a potential injury hazard. Avoid contact with them.
ATTENTION
Les bords tranchants et les surfaces des bobines sont un risque de blessure. Ne les touchez pas.
Receiving and Handling
1. Carefully check items against the bills of lading to verify all crates and cartons have been received. Carefully inspect all units for shipping damage when received. Report damage immediately and file a claim for damage with the carrier.
2. Skyline air handler units are constructed of heavy-gauge galvanized steel and are thoroughly inspected before leav­ing the factory. Care must be taken during installati on to prevent damage to units.
3. Take special care when handling the blower section. All fans are dynamically balanced before leaving the factory. Rough handling can cause misalignment or a damaged bearings or shaft. Carefully inspect fans and shaft before unit installation to verify this has not happened.
4. If necessary, screws, bolts, etc., for assembly of sections are supplied in a bag attached to each section. All neces­sary gasketing is applied in the factory for section to sec­tion mounting. Units require caulk sealant between sections.
Unit Storage
Store unit on a level surface. If air handling units are to be stored for any period of time, it is important to periodically rotate the fan wheel. The fan wheel should be periodically rotated to prevent permanent distortion of drive components. In addition, grease may settle in the lower part of the bearing, which may lead to oxidation on the upper portion of the bearing surface. It is also important to keep the fan bearings lubricated.
IM777 Page 3
Installation Guidelines
Service Clearances
In addition to providing adequate space around the unit for piping coils and drains, access is always required on at least one side of the unit to allow for regular service and mainte­nance. Filter replacement, drain pan inspection and cleaning, fan bearing lubrication and belt adjustment are examples of routine maintenance that must be performed. Sufficient space must also be provided on the side of the unit for shaft removal and coil removal if necessary . Space at least equal to the length of the coil is required for coil removal. Refer to the
"Coil data" section in Catalog 570 for information about coil sizes. See Figure 1 for servicing space requirements.
At least 54" of clearance must be maintained in front of elec­trical power devices. Electrical power devices that are mounted on the side of the unit are typically up to 12" deep. See Figure 2.
Figure 1. Servicing space requirements
4.00" Lifting Bracket
Width
30.00"
4.00"
Width of coil section
30.00"
Width of
fan section
Figure 2. Service clearance for electrical power devices
1 2 "
5 4 "
Rigging
Skyline air handlers ship completely assembled, or in sec­tions. The unit must be rigged as it ships from the factory. Do not rig units after assembly. Unit s ar e p rovide d wit h a factory installed base rail and can be lifted using the 2" diame­ter lifting holes located in the corners of each shipping section.
To prevent damage to the unit cabinetry, use spreader bars. Spreader bars must be in position to stop cables from rub­bing the frame or panels. Before hoisting into position, test lift for stability and balance. Avoid twisting or uneven lift­ing of the unit.
Figure 3. Unit and section rigging
3
0
.
0
0
"
Page 4 IM777
Height
Curb Mounting and Leveling
Do not place a Skyline unit over an open curb unless it is equipped with a curb-ready base. Installation instructions for mounting units on a roof curb are provided in IM770. For a copy , contact your local McQuay Representative or visit www.mcquay.com. Make provisions under the unit to divert any moisture from entering the building below.
For units without roof curb mounting, place the equip­ment on a flat and level surface. Where surface irregular­ities exist, shim the base of the unit at one or more points along the length of the rails to prevent distortion or sag­ging. Uneven or distorted sections will cause misfit or binding of the doors and panels and improper draining of drain pans. See Figure 4.
Figure 5. Apply sealant to mating faces
1 / 4 " d i a m e t e r b e a d c e n t e r e d i n f a c e o f c l e a r a n c e
U s e S p l i c e J o i n t a s a g u i d e
Figure 4. Leveling the unit
Shim sections until they are straight and level
Shim to prevent distortion if width is over 108"
Section Assembly
If the unit is shipped in more than one shipping section, rig each section into position separately. Shipping sections are provided with a connection splice joint attached on the leav­ing air side of the shipping section that seals against the frame channel on the entering-air side of the adjoining sec­tion. The splice joint is insulated, and provides an air-tight seal between two sections once they are assembled together. The Splice Joint must be aligned to seat into the mating gas­ket to provide an air seal. If the Splice Joint was bent during shipping or rigging, verify it is restored to its origin al posi­tion. Figure 6 on page 5.
2. Pull sections together to fasten. Use straps and a ratchet to help pull the sections together securely. Apply sealant to any gaps that may admit moisture.
3a.Fasten base rails together first using the 3/8"-16 by 5"
bolts found in the splice kit provided with the unit See Figure 6. To fasten 2 shipping sections together, 4 bolts are needed (two on each side of the unit). The bolts are run from one base rail into the other and fastened with a nut. Complete each section bottom and top before attaching additional sections.
Figure 6. Fasten bottom of section
Use the following procedure to assemble shipping sections:
1. Caulk all assembly joints of the unit. The mating faces of the cabinet must have at least a 1/4 inch diameter bead of sealant applied before the sections are joined. Use the splice joint as a guide for application of the sealant. See
Figure 5.
IM777 Page 5
3 / 8 x 1 " B o l t a n d N u t
3b.If desired, shipping sections for non curb-ready units can
be fastened together internally. Internal fastening is achieved by running field provided #10 sheet metal screws or drill screws (4" long maximum) through the interior frame channel of one unit into the splice joint of the neighboring section.
Figure 7. Internal fastening
flanges. Bend the ends of the splice cap down to secure in place. Assemble the small splice plate at the top rail to secure the sections together at the top. Use 5/16" bolts.
See Figure 9.
Figure 9. Splice cap & splice plate
S l i d e S p l i c e C a p o n a n d b e n d e n d s d o w n
Splice Collar must be aligned to seal to gasket.
A
View A
3c.Units with curb-ready ba ses and vesti bules must be han-
dled so that the lifting bracket can be removed after the unit is placed on the curbing. Remove the lifting bracket that projects inward over the curbing. Save the self tap­ping screws. When the adjacent section is placed in posi­tion, use self tapping screw to secure the bases together.
Figure 8. Remove vestibule lifting bracket
5 / 1 6 - 1 8 B o l t
5 / 1 6 - 1 8 N u t
S p l i c e P l a t e
Access Doors and Panels
For routine maintenance, access is normally obtained through access doors or by removing side panels. Removing all flat head fasteners along the sides of a panel will allow it to be removed.
Fan and filter sections are always provided with a service door on one side of the unit. If requested on order, doors can be provided on both sides of the unit. Optional service doors are available for most section types, and are provided based on customer request.
NOTE: Opening fan section doors requires the use of a 1/2" socket wrench. This satisfies ANSI standards and other codes that require the "use of tools" to access compartments con­taining moving parts or electrical wiring. See Figure 10.
1. Remove padlock if one is present.
CAUTION: DO NOT attempt to rotate the cup. Damage to the unit will occur.
R e m o v a b l e L i f t i n g B r a c k e t
4. Check that the sealant is compressed between the mating channels when the unit sections are joined. Touch up any places where gaps are noted. After sections are seated tightly together, slip the splice cap over the top panel
Page 6 IM777
2. Insert 1/2" socket into cup and rotate 1/4 turn clockwise as shown in Figure 10. If the cup and handle are on the left side of the door, rotate 1/4 turn counter-clockwise.
3. Rotate door handle 1/4 turn clockwise, then 1/4 turn counter-clockwise to release any internal pressure or vac­uum and open the door. If the cup and handle are on the left side of the door, rotate door handle 1/4 turn counter­clockwise, then 1/4 turn clockwise.
4. To prevent air leakage, tighten the door panels by adjust­ing the jam nuts.
Figure 10. Opening fan section door
Figure 12. Flashing over top panels and sides of units
Do Not Rotate Cup
Jam Nuts
View from inside door
OPEN
Duct Connections
Flexible connectors should be used on the outlet and inlet duct connections of all units. Do not position down flow fans over air ducts that are routed down into the building. A dis­charge plenum is recommended when bottom connections are necessary. See Figure 11.
F l a s h i n g
D u c t
F l a s h i n g
D u c t
F l a s h i n g
U n i t t o p p a n e l
F l a s h i n g
Dampers and Hoods
Side dampers may be provided in the mixing box and econo­mizer sections of units. When dampers are provided, a removable panel is located above the weather hood to pro­vide access to the damper drive shaft. Other access may be available depending on the specific construction of the unit. See Figure 13.
Figure 13. Filler panel over the weather hood
Figure 11. Discharge plenum
D i s c h a r g e
P l e n u m
If the unit has a top mixing box or econo mi zer damper, or a top duct connection, flashing mu st be field fabricated and installed to divert moisture from the connection. The flashing must lap over the standing seams of the top panels. The flashing must also lap over the side edges of th e unit. See
Figure 12.
Remove screws and panel to access damper control shaft.
Hood
When units are ordered with exhaust hoods and intake hoods adjacent to each other, a field supplied barrier is recom­mended to prevent re-circulation of exhaust air into the intake openings. See Figure 14.
IM777 Page 7
Figure 14. Field installed barrier between hoods
I n t a k e
B a r r i e r
E x h a u s t
Mounting Actuators
The installing contractor is responsible for the mounting of all field installed actuators. No provisions are made for the loca­tion of these actuators due to the number of options and arrangements available and the variety of specific applications. Ty pically, actu ators are mounted insi de the cabinet . Provide proper support for the actuator to avoid excessive stress in the cabinet, linkage, or damper shafts.
Piping Vestibules
The openings for routing the field piping must be cut as required in the field for units that include a piping vestibule. Carefully seal passages cut through the panels to prevent air leakage. A single metal thickness pan is provided in the bottom of the curb mounted vestibule. The pan can be removed if necessary. If holes are cut into the pan for a piping passage, seal the holes to prevent moisture leakage.
See Figure 15.
Figure 15. Seal holes for piping - curb mounted units
Seal Holes Cut for Piping
Note: Damper blades are at full flow when open to 70
degrees. Do not open blades further than 70 degrees.
Fresh air and return air dampers can be linked together and driven from the same actuator if the dampers are the same size. If the dampers are different sizes, they must be driven by separate actuators and controlled appropriately. Exhaust dampers are always driven by a separate actuator.
A typical rotary electric actuator can handle up to 40 sq. ft. of damper. For pneumatic actuators, allow 5 in-lb. per square foot of damper area.
Face and Bypass Section Mounting
Internal and external face and bypass sections are mounted together using the instructions for horizontal components and do not require additional instruction. Skyline air handlers are provided with a bypass duct that is integral to the unit con­struction and requires no field assembly.
Face and bypass dampers may or may not be linked together. When dampers are placed before a single bank of coils, they are always linked together and require a single actuator. When dampers are bypassing a stacked or staggered coil, the dampers are not linked and will require multiple actuators.
Face and bypass dampers have a torque requirement of 10 in­lbs. per square foot of damper face area.
For units with standard base rails, the vestibule is open to the coil section so all holes must be sealed to prevent air leakage.
Figure 16. Seal holes for piping - standard base rail units
Seal Holes Cut for Piping
Piping and Coils
Follow applicable piping design, sizing, and installation information presented in ASHRAE Handbooks in the design and installation of piping. Observe all local codes and indus­try standards. Undue stress should not be applied at the con­nection to coil headers. Pipework should be supported independently of the coils.
Page 8 IM777
Water Cooling Coils
Note:It is recommended that Glycol be used in water coils for
outdoor air handlers. Power failures and other mechani­cal issues can expose coil s to freezing temperatures.
1. Water supply, water return, drain, and vent connections extend through the end panel of the coil section. All con­nections are labeled on the end panel.
2. Water supply and water return connections are typically male N.P.T. iron pipe.
3. When installing couplings, do not apply undue stress to the connection extending through unit panel. Use a
backup pipe wrench to avoid breaking the weld between coil connection and header.
4. Follow recommendations of the control manufacturer regarding types, sizing, and installation of controls.
Direct Expansion Coils
1. The coil distributor and suction connection extend through the end panel of the coil section.
2. Check nozzle in distributor for proper tonnage.
3. When a thermostatic expansion valve is supplied with the unit, it will be located outside the unit and connected directly to the distributor (except on units with piping vesti­bules). Do not apply heat to the body of the expansion valve.
4. The thermostatic expansion valve must be of the external equalizer tube type. Connect the 1/4-inch diameter exter­nal equalizer tube provided on the coil to connection on expansion valve.
5. Use care when piping up the system to see that all joints are tight and all lines are dry and free of foreign mate­rial. For typical refrigerant piping, see condensing unit product manual.
Steam coils (refer to Figure 17 on page 10)
Note: Steam traps should not be placed outdoors.
1. All steam coils in units are pitched toward return connection.
2. Steam supply and steam return connections are typically male N.P.T. iron pipe and are labeled o n the en d panel of coil section. Connections extend through coil section end panel.
3. When installing couplings, do not apply undue stress to the connection extending through unit panel. Use a
backup pipe wrench to avoid breaking the weld between coil connection and header.
4. Support piping independently of coils and provide ade­quate piping flexibility. Stresses resulting from expansion of closely coupled piping can cause serious damage.
5. Do not reduce pipe size at the coil return connection. Carry return connection size through the dirt pocket, mak­ing the reduction at the branch leading to the trap.
6. Install vacuum breakers on all applications to prevent retaining condensate in the coil. Generally, the vacuum breaker is to be connected between the coil inlet and the return main, the vacuum breaker should be open to the
atmosphere, and the trap design should allow venting of large quantities of air.
7. Do not drip supply mains through the coil.
8. Do not attempt to lift condensate when using modulating or on/off control.
9. Size traps in accordance with manufacturers' recommen­dations. Be certain that the required pressure differential will always be available. Do not under-size.
10.Float and thermostatic or bucket traps are recommended for low pressure steam. On high pressure steam, bucket traps are normally recommended. Thermostatic traps should be used only for air venting.
11.Bucket traps are recommended for use with on/off control only.
12.Locate traps at least 12 inches below the coil return connection.
13.Multiple coil installation.
a. Each coil or group of coils that is individually con-
trolled must be individually trapped.
b. Coils in series: Separate traps are required for each
coil, or bank of coils, in series.
c. Coils in parallel: A single trap may generally be used
but an individual trap for each coil is preferred.
d. Do not attempt to lift condensate when using modu lat-
ing or on/off control.
14.With coils arranged for series airflow a separate control is required on each bank or coil in the direction of airflow.
15.Modulating steam valves are not recommended on high pressure systems.
16.Modulating valves must be sized properly. Do not under-size.
17.Freezing conditions (entering air temperatures below 35°F).
a. 5JA, 8JA, 5RA and 8RA coils are strongly recommended. b. 5 psi steam must be supplied to coils at all times. c. Modulating valves are not recommended. Control
should be provided by face and bypass dampers.
d. Consideration should be given to the use of two or three
coils in series with two position steam control valves on that coil or coils which will be handling 35°F or colder air. The desired degree of control can be at tain ed wit h a modulating valve on the downstream coil.
e. Thoroughly mix fresh air and return air before it enters
the coil. Also, temperature control elements must be properly located to obtain true air mixture temperatures.
f. As additional protection against freeze-up, the trap
should be installed sufficiently below coil to provide an adequate hydrostatic head to provide removal of condensate during an interruption in the steam pres­sure. Estimate three feet for each 1 psi of trap differ­ential required.
g. On startup, admit steam to coil ten minutes before
admitting outdoor air.
h. Close fresh air dampers if steam supply pressure falls
below minimum specified.
IM777 Page 9
Loading...
+ 19 hidden pages