McQuay MT 168 0-10 VDC/4-20mA, MT 168 0-10 VDC Maintenance Manual

Installation and Maintenance Manual IM 1017
LOW VOLTAGE
CONNECTIONS
LINE V
OL
TAGE
CONNECTIONS
FAN
L2 OR NEUTRAL
OPTIONAL REMOTE PROBE
OPTIONAL PIPE SENSOR
L1 (HOT)
LO FAN
MED FAN
HIGH FAN
OR SINGLE SPEED
24 VAC 1
24 VAC 2
SETBACK
24 VAC XFMR
MAIN 1
0-10 VDC
OUTPUT
SECONDARY
0-10 VDC
1 OUTPUT
FAN
OUTPUT
AUXILIARY
HEAT
OUTPUT
DAMPER OUTPUT
10
11
12
13
14
15
16
17
1
2
3
4
5
6
7
MT 168 0-10 VDC/4-20mA Thermostat
Installation
DANGER
READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS THERMOSTAT.
Failure to observe safety information and comply with instructions could result in PERSONAL INJURY, DEATH AND/ OR PROPERTY DAMAGE.
To avoid electrical shock or damage to equipment, disconnect power before installing or servicing. Use only wiring with insulation rated for full thermostat operating voltage. Use copper wire only. Insulate or wire-nut all un-used leads. Any wiring, including the remote probe, may carry the full operating voltage of the thermostat.
To avoid potential fire and/ or explosion do not use in potentially flammable or explosive atmospheres.
Retain these instructions for future reference. You must review your application and national and local codes to ensure that your installation will be functional and safe.
Figure 1: Mounting
Figure 2: Typical Wi ring *
Group: Applied Air Systems Part Number: 910102992 Date: August 2009
CAUTION
Care should be used to avoid electrostatic discharge to the microprocessor.
This unit has configuration dip switches and jumpers. You may need to reconfigure the thermostat for your application.
1 Install the thermostat with the two furnished mounting
screws to a standard 4-1/16" x 2-1/8" square device box with a 2" x 4" adapter ring.
2 For wall installations, mount the thermostat on an inside
wall approximately 5 feet above the floor. The location
should provide circulation at average room temperature. Avoid direct sunlight or sources of hot or cold air in the room or wall.
IM 1017 / Page 1 of 3 © 2009 McQuay International 800-432-1342 www.mcquay.com
Note: * Specific models may have fewer connections.
3 Remove the cover. Mount thermostat base assembly to
the outlet box using screws provided. Tighten the screws evenly but do not overtighten. Connect wires per wiring diagram.
4 To use a remote sensor on units with local sensing
capability, remove jumper JP-1 to disable local sensing. Failure to remove JP-1 will cause improper operation of thermostat.
5 Connecting a jumper between terminals 16 and 17 will
disable the secondary output and change the main output to heat mode.
6 Connection of a 24 VAC set-back signal will force the
control into unoccupied mode (see diagram). Pressing an arrow key or the mode buttons on the thermostat cover will disable the setback input for one hour.
7 Remove the LCD plastic protective film to complete the
installation. Reinstall the cover assembly. Install cover locking screw provided.
8 Checkout: After wiring and installation are complete,
energize the system and check the operation. Adjust the thermostat as necessary to complete at least one cycle. Be sure the thermostat and all other equipment are functioning correctly.
Electrical Ratings
Table 1: Fan switch (terminals 1-4) line voltage connections
Voltage
Rating
24 VAC N.A. N.A. N.A. 24 VA 10 VA 120 VAC 5.8 34.8 6.0 125 VA NA 240 VAC 2.9 17.4 5.0 125 VA NA 277 VAC 2.4 14.4 4.2 125 VA NA
Inductive Resistive
FLA LRA
Amps
Pilot Duty
Thermostatic
Switching
Application Notes
1 When no changeover pipe sensor is used, the main
output controls cooling and the secondary output controls heating.
2 The fan output, terminal 12, is energized whenever there
is a demand for heating or cooling. This output can be connected to a relay that can be used to provide fan cycling to terminal 1.
3 The changeover pipe sensor should be mounted on the
main coil input for water system operation and in the main duct system for forced air operation.
4 The set point and operating mode will be retained on a
loss of power.
5 When using either a remote probe or pipe sensor, run
wiring away from any electrical motors or power wiring.
6 The auxiliary heat output supplies a 24 VAC signal with
call for heat. This output is shipped configured for staged heat.
7 The thermostat is shipped with all dip switches in the
"ON" (closed) position.
8 The damper output is ON when mode is AUTO, HEAT
or COOL. Damper is OFF in set back.
Thermostat Operation
These thermostats are designed to control 0-10 VDC/4-0 mA valves. These units may include a fan switch with one or more fan speed selections.
Mode Button Operation
OFF: All thermostat outputs are off, fan is still operational if connected to a manual fan switch.
AUTO: The thermostat automatically selects heating or cooling mode depending upon the relationship of the setpoint and the room temperature. The appropriate HEAT or COOL indicator is enabled in addition to AUTO. A 3°F dead band is provided to prevent short cycling between heating and cooling modes. After changeover, the control points automatically shift so that the heating off-point equals the set point temperature or the cooling off-point equals the set point temperature.
COOL: The thermostat operates as a cooling only thermostat. The heating outputs are disabled.
HEAT: The thermostat operates as a heatin- only thermostat. The cooling outputs are disabled.
Fan Speed Switch Operation
Fan speed is determined by manual selection from fan switch OFF to HIGH, MEDIUM and/or LOW. In the OFF position, all outputs are off and the display is blank.
Up/Down Arrow Operation
A first touch of either arrow will display the setpoint (a single set point is employed for both heating and cooling). Continued pressure on either arrow will scroll the setpoint to new values. After three consecutive seconds on either arrow, the selected setpoint becomes effective and the display of the room temperature resumes.
Configuration
Table 2: Circuit Board Jumpe r Configuration
Jumper Closed On* Open Off
JP1 Local Sensing Remote Sensing JP2 2 Pipe System 4 Pipe System JP3 Factory Use Only JP4 0-10 VOC Main Output 4-20 mA Main Output
JP5
0-10 VOC Secondary
Output
4-20 mA Secondary
Output
© 2009 McQuay International 800-432-1342 www.mcquay.com IM 1017 / Page 2 of 3
Loading...
+ 1 hidden pages