McQuay MT 155 Maintenance Manual

Installation and Maintenance Manual IM 1014
MT 155 Thermostat
Installation
DANGER
READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS THERMOSTAT.
Failure to observe safety information and comply with instructions could result in PERSONAL INJURY, DEATH AND/ OR PROPERTY DAMAGE.
To avoid electrical shock or damage to equipment, disconnect power before installing or servicing. Use only wiring with insulation rated for full thermostat operating voltage. Use copper wire only. Insulate or wirenut all un-used leads. Any wiring, including the remote probe,may carry the full operating voltage of the thermostat.
To avoid potential fire and/ or explosion do not use in potentially flammable or explosive atmospheres.
Retain these instructions for future reference. You must review your application and national and local codes to ensure that your installation will be functional and safe.
1 Install the thermostat with the two furnished mounting
screws to a standard 2" x 4" electrical box, 4-11/16" x 2­1/8" square device box with a 2" x 4" adapter ring or to a 4" x 4" box with accessory adapter plate.
2 For wall installations, mount the thermostat on an inside
wall approximately 5 feet above the floor. The location should provide circulation at average room temperature. Avoid direct sunlight or sources of hot or cold air in the room or wall.
3 Remove the knob and then the cover. Mount thermostat
base assembly to the outlet box using the screws provided, tighten the screws evenly but do not over tighten. Make wiring connections as noted.
4 To use a remote sensor, remove jumper JP-1 to disable
local sensing. See Figure 1. Failure to remove JP-1 when using a remote sensor will cause improper operation of the thermostat. Some units do not have remote sensing capability . See Application Notes.
Group: Applied Air Systems Part Number: 910102989 Date: August 2009
Figure 1: Removing Jumper JP-1
INSTALL COVER
LOCKING SCREW
REMOVE JP1
WHEN USING A
REMOTE SENSOR
5 Reinstall the cover assembly. Install cover locking screw
JP1
provided. Reinstall the knob.
6 Checkout: After wiring and installation are complete,
energize the system and check the operation. Adjust the thermostat as necessary to complete at least one cycle. Be sure the thermostat and all other equipment are functioning correctly.
Thermostat Operation
Temperature Range: 50°F - 90°F (10°C - 32°C) TA155: A HEAT-OFF-COOL system switch manually selects
heating or cooling mode. In the HEAT position, only the heat output cycles with demand. In the COOL position, only the cool output cycles with demand. In the OFF position, heating and cooling outputs are off. Units with a two position system switch or without a system switch must use a load transfer switch when both heating and cooling outputs are used. This prevents control failure and equipment damage caused by direct cycling between loads.
TB155: An ON-OFF system switch enables auto-changeover of heating and cooling modes. In the ON position the thermostat activates heating or cooling outputs dependant upon the relationship between set point and ambient temperature. Heat on to cool on dead band is 4°F. In the OFF position, heating and cooling outputs are off. Units without a system switch cycle between heating and cooling with a 4°F dead band.
IM 1014 / Page 1 of 2 © 2009 McQuay International 800-432-1342 www.mcquay.com
FAN: Some units have a switch for manual selection of fan speed. On these units fan operation is either internally wired
for fan continuous operation or is dependant upon connection
1
2
3
1
2
5
1
2
3
4
TB1
TB2
TB3
NO CONNECTION
L2 or NEUTRAL
TB1-3
TB1-4
FAN
COOL
OUTPUT
HEAT
OUTPUT
TB2-3
FAN HIGH
FAN LOW
FAN MED
L1
FAN SUPPLY
TB2-2
TB2-1
TB2-4
TB2-5
TB3-3
CONNECT FOR FAN CONTINUOUS
TB3-2
TB3-1
SWITCHED POWER
COOL
OUTPUT
HEAT
OUTPUT
1
2
3
1
2
TB1
TB3
L1
TB3-3
TB3-2
TB3-1
NO CONNECTION
L2 or NEUTRAL
TB1-3
TB1-4
to the fan supply input . When internally wired for fan continuous operation, the fan will be off when the system switch is off. When dependant upon external connections the fan may not be off with the system switch in the off position. The fan supply input is switched to fan speed outputs (HI ­MED - LO).
SWITCHED POWER: L1 power is switched to this output any time the system switch is out of the OFF position.
Ratings
Table 1: Fan and system switches
Voltage Rating
Inductive FLA LRA
24 VAC N.A. N.A. N.A. 24 VA 10 VA 120 5.8 34.8 6.0 125 VA 20 VA 240 2.9 17.4 5.0 125 VA 20 VA 277
2.4 14.4 4.2 125 VA 20 VA
Resistive Amps
Pilot Duty
Wire Lead Colors (if applicable)
White with Orange Stripe Fan High White with Red Stripe Fan Med. White with Brown Stripe Fan Low Red Heat Blue Cool Black L1 Yellow L2 or Neutral Orange Switched Power Violet Fan Supply Brown Remote Probe Brown Remote Probe
Application Notes
1 To use a remote sensor, remove jumper JP-1 to disable
local sensing. See Figure 1. Failure to remove JP-1 when using a remote sensor will cause improper operation of the thermostat. Some units do not have remote sensing capability.
2 Units with remote sensing capability have a four-position
terminal block at TB1. If TB1 is two position the unit is local sensing only.
3 Remote probe wiring should be located away from any
electrical motors or power wiring
4 Some units are internally wired for permanent fan
continuous operation.
5 On units with a Fan Supply input, the operation of the
fan is determined by wiring connection. For fan continuous, jumper the Fan Supply input (TB2-5) to the Switched Power output (TB3-3).
6 For fan cycling operation with a call for heat or cool, a
fan relay must be used.
© 2009 McQuay International 800-432-1342 www.mcquay.com IM 1014 / Page 2 of 2
Thermostatic Switching
7 Observe electrical ratings. Thermostatic outputs are pilot
duty only.
Wiring Diagrams
Figure 2: Units with remote sensing capability
TB3-1
HEAT
OUTPUT
TB3-2
TB3
1
2
TB3-3
3
TB2-1
TB2
1
L2 or NEUTRAL
NO CONNECTION
REMOTE PROBE 1
REMOTE PROBE 2
TB1-4
TB1-3
TB1-2
TB1-1
4
3
2
1
TB1
TB2-2
2
TB2-3
3
4
TB2-4
5
TB2-5
Figure 3: Units with switches used for local sensing only
Figure 4: Units with no switches with local/remote sensing capability
TB3
1
2
3
L2 or NEUTRAL
NO CONNECTION
REMOTE PROBE 1
REMOTE PROBE 2
TB1-4
TB1-3
TB1-2
TB1-1
4
3
2
1
TB1
Figure 5: Units with no switches used for local sensing only
COOL
OUTPUT
SWITCHED POWER
L1
FAN H IGH
FAN MED
FAN L OW
FAN SUPPLY
TB3-1
TB3-2
TB3-3
FAN
HEAT
OUTPUT
COOL
OUTPUT
CONNECT FOR FAN CONTINUOUS
L1
5
Loading...