McQuay MQFCI6 User Manual

Generic I/O Control Panel Technical Specifications
Group: Controls
Part Number: ASP 31-333
Date: August 2011
McQuay International certifies that its equipment will conform to this drawing and McQuay's published specifications, subject to its published warranty. Purchaser must determine that the equipment is fit and sufficient for the job specifications. No change to this drawing may be made unless approved in writing by McQuay. www.mcquay.com
ASP 31-333
MicroTech® III Control Panel
Description
The MicroTech III Generic I/O Panel provides configurable inputs and outputs for use in conjunction with the McQuay Delivered VAV System. This panel communicates via BACnet® MS/TP and can be set up and monitored through the VAV System’s touch screen controller. With the MicroTech III Generic I/O Panel, the Delivered VAV System can be configured to provide hardwired signals to, and/or monitor inputs from, third part devices and sensors.
Use the MicroTech III Generic I/O Panel along with ancillary control features in the Delivered VAV System to create custom control sequences unique to your building.
Features
Power supply AC 24 V or DC 24 V 8 configurable analog I/Os
o 4 analog outputs 10V or 25mA o 1 analog output 10V o 3 analog inputs 10V, 25mA, NI1000, PT1000,
I-R2500, NTC10K, or NTC100K 3 analog inputs NTC 10k or NTC 100k DC 24 V and DC 5 V power supply for active sensors
on board 2 digital inputs for potential-free contacts 2 digital inputs galvanically isolated AC 24 V 2 digital inputs galvanically isolated AC 115V 8 relay outputs (6 NO contacts, 2 relays switching type) 2 triac outputs (AC 24 V) SD card interface for application and operating system
upgrade Operating temperature: -4°F to 140°F (-20°C to 60°C)
Specifications
Controller
Inbuilt HMI:
LCD with white backlight (144 x 64 dots) 5 line by 22 characters display Roll-and-push knob navigation, 3 function buttons
Main Controller:
Dimensions: 207 x 110 x 79 mm Housing: Plastic, light-grey RAL 7035
I/O Connectors:
Plug- in terminals: clamp Grid: 5mm AWG min/max: 26/14
Power Requirements:
15VA plus loads
BACnet MS/TP Communication Card - RS-485 (EIA-485):
Bus connection/electronics: galvanically isolated Bus connection: A+, B- REF (3 wires)
Control Panel
Panel:
IP65, NEMA 4 rugged plastic
Network Connection:
Shielded twisted pair wire for BACnet connection
Power:
120V AC wall source Phase: 1 Frequency: 60Hz Terminal type: strip wire spring terminal AWG min/max: 22/12
Transformer:
120/24VAC, 75VA
Dimensions:
15.3 in. (389 mm) Wide x 17.36 in. (441 mm)
High x 6.25 in. (159 mm) Deep