McQuay MPS040A Installation Manual

Installation and Maintenance Manual IM 842-1
Maverick II™ Commercial Packaged Rooftop Systems Heating & Cooling
Models MPS030A – 050A 30 to 50 Tons R–410A Refrigerant
Part Number: IM 842-1
Date: January 2008
© 2008 McQuay International
Contents
Introduction .............................................................. 3
General Information................................................ 3
Unit Nameplate ................................................... 3
Hazard Identification Information ........................ 3
Mechanical Installation ............................................ 4
Installer Responsibilities ......................................... 4
Receiving Inspection........................................... 4
Service Clearance .............................................. 4
Ventilation Clearance.......................................... 5
Overhead Clearance........................................... 5
Roof Curb Assembly and Installation.................. 5
Rigging and Handling ......................................... 9
Unit Piping for Condensate Drain Connection.. 10
Damper Assemblies.......................................... 10
Cabinet Weather Protection.............................. 10
Installing Ductwork............................................ 11
Installing Duct Static Pressure Sensor Taps .... 11
Installing Building Static Pressure Sensor Taps 12
Electrical Installation ............................................. 13
Field Power Wiring............................................ 13
Field Control Wiring .......................................... 14
Preparing Unit for Operation ................................. 15
Spring Isolated Fans......................................... 15
Optional Gas Heat .................................................. 16
Gas Furnace Design............................................. 16
Gas Heating Capacity Data .............................. 16
Installation ........................................................ 18
Gas Piping Routing Into Unit ............................ 20
Sequence of Operation..................................... 21
Start-Up Procedures ......................................... 21
Operating Procedures....................................... 22
Service.............................................................. 22
Maintenance ..................................................... 22
Ignition Control Module Information.................. 23
Optional Electric Heat ............................................ 24
Electric Heater Design.......................................... 24
Electric Heating Capacity Data ......................... 25
Electric Heater Data.......................................... 25
Wiring Diagrams ..................................................... 26
Unit Options ............................................................ 42
Economizer Enthalpy Control ........................... 42
External Time Clock.......................................... 42
Duct High Pressure Limit .................................. 42
Convenience Receptacle/Section Lights.......... 42
Exhaust Fan Option ......................................... 42
Sequence of Operation.......................................... 43
Operating States .................................................. 43
Start Up ............................................................ 43
Recirculation .................................................... 43
Fan Only........................................................... 43
Heating............................................................. 43
Minimum DAT .................................................. 43
Mechanical Cooling.......................................... 44
Economizer ...................................................... 44
Check, Test, and Start Procedures ...................... 45
Pre-Start of Unit ................................................... 45
Servicing Control Panel Components .............. 45
Before Start-Up ................................................ 45
Power-Up ......................................................... 45
Fan Start-Up..................................................... 45
Economizer Start-Up........................................ 45
Compressor Start-Up ....................................... 46
Sheave Alignment ............................................ 47
Drive Belt Tension Adjustment......................... 47
Air Balancing .................................................... 47
Final Control Settings............................................ 48
Controller Settings for Normal Operation ............. 48
Maintenance ........................................................... 49
Performing Service Maintenance ......................... 49
Servicing Control Panel Components .............. 49
Planned Maintenance ...................................... 49
All-Aluminum Condenser Coils ........................ 49
Unit Storage ..................................................... 50
Bearing Lubrication .......................................... 51
Setscrews......................................................... 52
Supply Fan Wheel-to-Funnel Alignment .......... 52
Refrigerant Charge........................................... 52
Servicing Refrigerant Sensors or Switches...... 52
Servicing Optional Electric Heater ................... 52
Service and Warranty Procedure ......................... 53
Replacement Parts........................................... 53
Scroll Compressor............................................ 53
All Compressors............................................... 53
In-Warranty Return Material Procedure ........... 53
Commercial Rooftop Equipment Warranty
Registration Form............................................. 54

Introduction

General Information

Introduction
This manual provides general information about the “A” vintage McQuay Commercial Packaged Rooftop Unit model MPS. In addition to an overall description of the unit, it includes mechanical and electrical installation procedures, commissioning procedures, sequence of operation information, and maintenance instructions.
The MicroTech II
®
rooftop unit controller is available on “A” vintage rooftop units. For a detailed description of the MicroTech II components, input/output configurations, field wiring options and requirements, and service procedures, see OM 843. For operation and information on using and programming the MicroTech II unit controller, refer to the appropriate operation manual (see Table 1).
For a description of operation and information on using the keypad to view data and set parameters, refer to the
appropriate program-specific operation manual (see Table 1)
Table 1: Program Specific Rooftop Unit Operation Literature
Rooftop unit control configuration
VFDs OM 844 - MD2
MPS Unit Controller
Discharge Air Control (VAV or CAV)
Space Comfort Control (SCC)
Operation manual bulletin
number
OM895 - MD3 OM847 - MD6
OM 843
.

Unit Nameplate

The unit nameplate is located on the outside of the main control box door. It includes the unit model number, serial number, electrical characteristics, and refrigerant charge.

Hazard Identification Information

DANGER
Dangers indicate a hazardous situation which will result in death or serious injury if not avoided.
WARNING
Warnings indicate potentially hazardous situations, which can result in property damage, severe personal injury, or death if not avoided.
CAUTION
Cautions indicate potentially hazardous situations, which can result in personal injury or equipment damage if not avoided.
Figure 1: Nomenclature
McQuay Packaged System
(030, 035, 040, 050 tons)
Nominal capacity
M P S – 030 – A G
Heat medium Y = None (cooling only) G = Natural gas E = Electric
Design vintage
McQuay IM 842-1 3

Mechanical Installation

Mechanical Installation

Installer Responsibilities

The installation of this equipment shall be in accordance with the regulations of authorities having jurisdiction and all applicable codes. It is the responsibility of the installer to determine and follow the applicable codes.
CAUTION
Sharp edges on sheet metal and fasteners can cause personal injury. This equipment must be installed, operated,
and serviced only by an experienced installation company and fully trained personnel.

Receiving Inspection

When the equipment is received, all items should be carefully checked against the bill of lading to be sure all crates and cartons have been received. If the unit has become dirty
during shipment (winter road chemicals are of particular concern), clean it when received.
Figure 2: Service Clearances
All units should be carefully inspected for damage when received. Report all shipping damage to the carrier and file a claim. In most cases, equipment is shipped F.O.B. factory and claims for freight damage should be filed by the consignee.
Before unloading the unit, check the unit nameplate to make sure the voltage complies with the power supply available.

Service Clearance

Allow service clearances as approximately indicated in Figure 2. Also, McQuay recommends providing a roof walkway to the rooftop unit as well as along each side of the unit that provides access to most controls and serviceable components.
4 McQuay IM 842-1
Mechanical Installation

Ventilation Clearance

Below are minimum ventilation clearance recommendations. The system designer must consider each application and provide adequate ventilation. If this is not done, the unit may not perform properly.
Unit(s) Surrounded by a Screen or a Fence:
1 The bottom of the screen or fence should be at least 1 ft.
(305 mm) above the roof surface.
2 The distance between the unit and a screen or fence should
be as described in Figure 2 on page 4.
3 The distance between any two units within a screen or
fence should be at least 120" (3048 mm).
Unit(s) Surrounded by Solid Walls:
1 If there are walls on one or two adjacent sides of the unit,
the walls may be any height. If there are walls on more than two adjacent sides of the unit, the walls should not be higher than the unit.
2 The distance between the unit and the wall should be at
least 96" (2438 mm) on all sides of the unit.
3 The distance between any two units within the walls should
be at least 120" (3048 mm).
Do not locate outside air intakes near sources of contaminated air.
If the unit is installed where windy conditions are common, install wind screens around the unit, maintaining the clearances specified (see Figure 2). This is particularly important to maintain adequate head pressure control when mechanical cooling is required at low outdoor air temperatures.
Note: Low head pressure may lead to poor and erratic
refrigerant feed control at the thermostatic expansion valve. The unit has automatic control of the condenser fans which should provide adequate head pressure control down to 20°F provided the unit is not exposed to windy conditions. The system designer is responsible for assuring the condensing section is not exposed to excessive wind or air recirculation.

Overhead Clearance

1 Unit(s) surrounded by screens or solid walls must have no
overhead obstructions over any part of the unit.
2 The area above the condenser must be unobstructed in all
installations to allow vertical air discharge.
3 The following restrictions must be observed for overhead
obstructions above the air handler section:
a There must be no overhead obstructions above the
furnace flue, or within 9" (229 mm) of the flue box.
b Overhead obstructions must be no less than 96"
(2438 mm) above the top of the unit.
c There must be no overhead obstructions in the areas
above the outside air and exhaust dampers that are farther than 24" (610 mm) from the side of the unit.

Roof Curb Assembly and Installation

Locate the roof curb and unit on a portion of the roof that can support the weight of the unit. The unit must be supported to prevent bending or twisting of the machine.
If building construction allows sound and vibration into the occupied space, locate the unit over a non-critical area. It is the responsibility of the system designer to make adequate provisions for noise and vibration in the occupied
space.
WARNING
Mold can cause personal injury. Some materials such as
gypsum wall board can promote mold growth when damp. Such materials must be protected from moisture that can enter units during maintenance or normal operation.
Install the curb and unit level to allow the condensate drain to flow properly and allow service access doors to open and close without binding.
The gasketed top surface of the curb seals against the unit when it is set on the curb. These flanges must not support the total weight of the duct work. See “Installing Ductwork” on page 11 for details on duct connections. It is critical that the condensate drain side of the unit be no higher than the opposite side.
Assembly Instructions
Assembly of a typical roof curb is shown in Figure 3.
1 Set curbing parts A thru G per dimensions shown over roof
opening or on a level surface. Note location of supply air opening. Check alignment of all mating screw holes.
2 Screw curbing parts together using fasteners provided.
Leave all screws loose until curb is checked to be square.
3 Square entire curbing assembly and securely tighten all
screws.
4 Position curb assembly over roof openings. Curb must be
level within .25 inches from side to side and 1.50 inches over its length. Check that top surface of curb is flat with no bowing or sagging.
5 Weld curb assembly in place. Caulk all seams watertight.
Remove backing from .25 x 1.50 wide gasket and apply to surfaces shown by crosshatching.
6 Check that electrical connections are coordinated.
McQuay IM 842-1 5
Mechanical Installation
Figure 3: Roof Curb Assembly—MPS 030A – 035A
6 McQuay IM 842-1
Figure 4: Roof Curb Layout—MPS 030A – 035A
2.00
[51 mm]
2.00
[51 mm]
23.50
[597 mm]
Mechanical Installation
21.25
[540 mm]
87.25
[2216 mm]
(INSIDE CURB)
2.00
[51 mm]
1.25
[32 mm] TYP
63.69
[1610 mm]
71.38
[1813 mm]
15.87
[403 mm]
1.63
[41 mm]
93.70
[2380 mm]
171.18 (INSIDE CURB) [4348 mm]
PLAN VIEW
2.00
[51 mm]
1.00
[26 mm]
1.00
[26 mm]
2.00
[51 mm]
23.86
[606 mm]
3.75
[95 mm]
2.38
[58 mm]
F
KNOCKOUT DETAIL
CURB CROSS SECTION
McQuay IM 842-1 7
Mechanical Installation
Figure 5: Roof Curb Layout—MPS 040A – 050A
2.00
[51 mm]
2.00
[51 mm]
87.25
[2216 mm]
(INSIDE CURB)
2.00
[51 mm]
30.63
[778 mm]
1.25 TYP [32 mm]
69.39
[1763 mm]
1.63
[41 mm]
105.45
[2678 mm]
28.25
[718 mm]
71.38
[1813 mm]
15.87
[403 mm]
208.57 (INSIDE CURB) [5298 mm]
1.00
[25 mm]
2.00
[51 mm]
2.00
[51 mm]
28.92
[735 mm]
3.75
[95 mm]
PLAN VIEW
2.28
[58 mm]
F
CURB CROSS SECTION
8 McQuay IM 842-1
Mechanical Installation

Rigging and Handling

WARNING
Only trained and qualified personnel should be allowed to rig loads or operate load rated cranes and/or hoist assemblies. Do not use a forklift to lift or maneuver the unit. Failure to use a load rated crane or hoist assembly to lift or maneuver the unit can cause severe personal injury and property damage.
WARNING
Use all lifting points. Improper lifting can cause property damage, severe personal injury, or death.
CAUTION
Lifting points may not be symmetrical to the center of gravity of the unit. Ballast or unequal cable lengths may be
required.
Rigging holes for shackles are integral on the unit base. All six lifting points must be used for rigging the equipment. Use four independent lines, securing one end of a line to a unit base lifting point and the other end of the line to an associated spreader bar lifting point (see Figure 7). Figure 6
is an example of an instruction label shipped with each unit.
Figure 6: Rigging Label
LIFT UNIT ONLY AS SHOWN
Table 2 lists the weight distribution at each of the six lifting points on the unit (also refer to Figure 7). Table 3 details lifting
point locations (also refer to Figure 7).
Table 4 lists the
weights of accompanying curbs.
Table 2: Percentage of Load and Weight Points
Tot al
Unit (Tons)
030A Cooling 3525 388 388 705 846 564 635 030A Heating 3625 399 399 725 870 580 653 035A Cooling 3680 405 405 736 883 589 662 035A Heating 3780 416 416 756 907 605 680 040A Cooling 4160 458 458 832 998 666 749 040A Heating 4410 485 485 882 1058 706 794 050A Cooling 4560 502 502 912 1094 730 821 050A Heating 4870 536 536 974 1169 779 877
Weight
(lbs)
A
11%B11%C20%D24%E16%F18%
Table 3: Location of Lifting Points
Unit (tons)
030A – 035A 35.5 62.0 52.0
050A 40.0 69.0 89.0
040A
L1 L2 L3
Table 4: Curb Weights
Unit (Tons) / Curb Height Weight (lbs)
030A – 035A / 14" Curb 341 030A
035A / 24" Curb 501
050A / 14" Curb 481
040A 040A
050A / 24" Curb 708
Point
% of Total Load
Distance (inches)
SPREADER BARS REQUIRED
MUST USE ALL OF THESE
LIFTING LUGS FOR LIFTING UNIT.
Use spreader bars, 96" to 100" (2438 to 2540 mm) wide to prevent damage to the unit cabinet. Avoid twisting or uneven lifting of the unit. The cable length from the bracket to the hook should always be longer than the distance between the outer lifting points.
If the unit is stored at the construction site for an intermediate period, take these additional precautions:
1 Support the unit well along the length of the base rail.
2 Level the unit (no twists or uneven ground surface).
3 Provide proper drainage around the unit to prevent flooding
of the equipment.
4 Provide adequate protection from vandalism, mechanical
contact, etc.
5 Securely close the doors.
6 Cover the supply and return air openings.
Figure 7: Rigging the Unit (MPS 030A – 035A Example)
McQuay IM 842-1 9
Mechanical Installation
Unit Piping for Condensate Drain Connec­tion
The unit is provided with a 1" female NPT condensate drain connection. For proper drainage, level the unit and drain pan side to side and install a P-trap.
Figure 8 shows the layout of the condensate drain connection. The distance from the drain pan outlet to the horizontal run of the P-trap should be a distance of twice the static pressure in the drain pan.
Example: If the static pressure as measured in the drain pan is
1.5", then the distance between the drain outlet and the horizontal run should be 3".
Draining condensate directly onto the roof may be acceptable; refer to local codes. Provide a small drip pad of stone, mortar, wood, or metal to protect the roof against possible damage.
If condensate is piped into the building drainage system, pitch the drain line away from the unit a minimum of 1/8" per foot. The drain line must penetrate the roof external to the unit. Refer to local codes for additional requirements. Sealed drain lines require venting to provide proper condensate flow.
Where the cooling coils have intermediate condensate pans on the face of the evaporator coil, copper tubes near both ends of the coil provide drainage to the main drain pan. Verify that the copper tubes are in place and open before the unit is put into operation.
Periodically clean to prevent microbial growth/algae buildup from plugging the drain and causing the drain pan to overflow. Clean drain pans to prevent the spread of disease. Cleaning
should be performed by qualified personnel
WARNING
Drain pans must be cleaned periodically. Material in uncleaned drain pans can cause disease.
Cleaning should be performed by qualified personnel.
.
Figure 9: Damper Assembly
Economizer Dampers
As the single actuator modulates, the outside air dampers open, the return air dampers close, and the exhaust air exits the unit through the gravity relief dampers.
The economizer comes with manually adjustable linkage (Figure 9). The damper is set so that the crankarm moves through a 90-degree angle to bring the economizer dampers from full open to full close. Mechanical stops are placed in the crankarm mounting bracket. Do not remove stops. Driving the crankarm past the stops results in damage to the linkage or damper.
Outdoor Air Dampers (0% to 30%)
These dampers are intended to remain at a fixed position during unit operation, providing fresh air quantities from 0 to 30% of the total system airflow, depending on the damper setting.
The damper position may be set at the unit controller keypad (refer to OM 843 for further detail). During unit operation, the damper is driven to the position set at the unit controller. During the off cycle, the damper is automatically closed.
Figure 8: Condensate Drain Connection
Static Pressure (P) at the Drain Pan

Damper Assemblies

The optional damper assemblies described in this section are ordered with factory-installed actuators and linkages. The following sections describe the operation and linkage adjustment of the factory option.
10 McQuay IM 842-1

Cabinet Weather Protection

This unit ships from the factory with fully gasketed access doors and cabinet caulking to provide weather resistant operation. After the unit is set in place, inspect all door gaskets for shipping damage and replace if necessary.
Protect the unit from overhead runoff from overhangs or other such structures.
CAUTION
Transportation, rigging, or maintenance can damage the unit’s weather seal. Periodically inspect the unit for leakage.
Standing moisture can promote microbial growth, disease, or damage to the equipment and building.
Mechanical Installation

Installing Ductwork

On vertical-supply/vertical-return units, if a McQuay roof curb is not used, the installing contractor should make an airtight connection by attaching field fabricated duct collars to the bottom surface of the unit’s duct opening. Do not support the total weight of the duct work from the unit. See Figure 4 on page 7 or Figure 5 on page 8.
Use flexible connections between the unit and ductwork to avoid transmission of vibration from the unit to the structure.
To minimize losses and sound transmission, design duct work per ASHRAE and SMACNA recommendations.
Where return air ducts are not required, connect a sound absorbing T or L section to the unit return to reduce noise
transmission to the occupied space.
WARNING
Mold can cause personal injury. Materials such as gypsum
wall board can promote mold growth when damp. Such materials must be protected from moisture that can enter units during maintenance or normal operation.
Ductwork exposed to outdoor conditions must be built in accordance with ASHRAE and SMACNA recommendations
and local building codes
.
6 Install the duct tap so that it senses only static pressure (not
velocity pressure). If a bare tube end is used, it must be smooth, square (not cut at an angle) and perpendicular to the airstream (see Figure 11).
7 Locate the reference pressure (LO) tap near the duct
pressure tap within the building. If the tap is not connected to the sensor, unsatisfactory operation will result.
8 Route the tubes through the curb and feed them into the
unit through the knockout in the bottom of the control panel (see Figure 10). Connect the tubes to appropriate barbed fittings (on SPS1) in the control panel. (Fittings are sized to accept 1/8" ID tubing.)
Figure 10: Static Pressure Tubing Knockout Location

Installing Duct Static Pressure Sensor Taps

For all VAV units, duct static pressure taps must be field installed and connected to the static pressure sensor 1 (SPS1) in the unit. Sensor SPS1 is standard on VAV units and is located in the main control panel.
Carefully locate and install the duct static pressure sensing tap. Improperly locating or installing the sensing tap causes unsatisfactory operation of the entire variable air volume system. Below are pressure tap location and installation recommendations.The installation must comply with local code requirements.
1 Install a tee fitting with a leak-tight removable cap in each
tube near the sensor fitting. This facilitates connecting a manometer or pressure gauge if testing is required.
2 Use different colored tubing for the duct pressure (HI) and
reference pressure (LO) taps, or tag the tubes. McQuay recommends 1/8" ID tubing.
3 Locate the duct pressure (HI) tap near the end of a long
duct to ensure that all terminal box take-offs along the run have adequate static pressure.
4 Locate the duct tap in a nonturbulent flow area of the duct.
Keep it several duct diameters away from take-off points, bends, neckdowns, attenuators, vanes, or other irregularities.
5 Use a static pressure tip (Dwyer A302 or equivalent) or the
bare end of the plastic tubing for the duct tap. (If the duct is lined inside, use a static pressure tip device.)
Figure 11: Duct Static Pressure Sensing Tubing Installation
Condenser Section
Roof
Ductwork (Remote Location)
Tubing Extends Through Approx. 1/8”
HI Line
LO Line
Remote Sense Point
To Sensor LO Input
Main Control Panel
SPS1
To Sensor HI Input
Rubber Grommet
Pressure Sensing Tubing
McQuay IM 842-1 11
Mechanical Installation

Installing Building Static Pressure Sensor Taps

If a unit has building static pressure control capability, you must field install and connect static pressure taps to the static pressure sensor SPS2 in the unit. This sensor is located at the bottom of the main control panel next to SPS1.
Carefully locate and install the two static pressure sensing taps. Improper location or installation of the sensor taps causes unsatisfactory operation. Below are pressure tap location and installation recommendations for both building envelope and lab, or “space within a space” pressure control applications.
The installation must comply with local code requirements.
CAUTION
Fragile sensor fittings. If you must remove tubing from a
pressure sensor fitting, use care. Do not use excessive force or wrench the tubing back and forth to remove or the fitting can break off and damage sensor.
Building Pressurization Applications
1 Install a tee fitting with a leak-tight removable cap in each
tube near the sensor fitting. This facilitates connecting a manometer or pressure gauge if testing is required.
2 Locate the building pressure (HI) tap in the area that
requires the closest control. Typically, this is a ground level floor that has doors to the outside.
3 Locate the building tap so it is not influenced by any source
of moving air (velocity pressure). These sources may include air diffusers or outside doors.
4 Route the building tap tube through the curb and feed it into
the unit through the knockout in the bottom of the control panel (refer to Figure 10). Connect the 1/8" ID tube to the HI fitting for sensor SPS2.
5 Locate the reference pressure (LO) tap on the roof. Keep it
away from the condenser fans, walls, or anything else that may cause air turbulence. Mount it high enough above the roof so it is not affected by snow. Not connecting the reference tap to the sensor results in unsatisfactory operation.
6 Use an outdoor static pressure tip (Dwyer A306 or
equivalent) to minimize the adverse effects of wind. Place some type of screen over the sensor to keep out insects. Loosely packed cotton works well.
7 Route the outdoor tap tube out of the main control panel
through a small field-cut opening in the upright. Seal the penetration to prevent water from entering. Connect the 1/8" ID tube to the LO fitting for sensor SPS2.
Figure 12: Outdoor Static Pressure Tubing Installation
Lab Pressurization Applications
1 Install a “T” fitting with a leak-tight removable cap in each
tube near the sensor fitting. This facilitates connecting a manometer or pressure gauge if testing is required.
2 Use different colored tubing for the controlled space
pressure (HI) and reference pressure (LO) taps, or tag the tubes.
3 Regardless whether the controlled space is positive or
negative with respect to its reference, locate the HI pressure tap in the controlled space. (The setpoint can be set between -0.2" and 0.2" wc)
4 Locate the reference pressure (LO) tap in the area
surrounding the controlled space. Not locating the reference tap to the sensor results in unsatisfactory operation.
5 Locate both taps so they are not influenced by any source
of moving air (velocity pressure). These sources may include air diffusers or doors between the high and low pressure areas.
6 Route the building tap tube between the curb and the
supply duct and feed it into the unit through the knockout in the bottom of the control panel.
7 Connect the tube to the HI fitting for sensor SPS2.
12 McQuay IM 842-1

Electrical Installation

Electrical Installation

Field Power Wiring

Wiring must comply with all applicable codes and ordinances. The warranty is voided if wiring is not in accordance with these specifications.
According to the National Electrical Code, a disconnecting means shall be located within sight of and readily accessible from the air conditioning equipment. The unit can be ordered with an optional factory mounted disconnect switch. This switch is not fused. Power leads must be over-current protected at the point of distribution. The maximum rated overcurrent protection device (MROPD) value appears on the unit nameplate.

All Units

All units are provided with internal power wiring for single point power connection. The power block or an optional disconnect switch is located within the main control panel. Field power leads are brought into the unit through knockouts in the bottom of the main control panel (see Figure 13 and also Table 5). Refer to the unit nameplate to determine the number of power connections.
WARNING
Hazardous voltage. Can cause severe injury or death.
Disconnect electric power before servicing equipment. More than one disconnect may be required to de-energize the unit.
Note: To wire entry points, refer to certified drawings for
dimensions.
Figure 13: MPS Power Wiring Knockout Locations
The preferred entrance for power cables is through the bottom knockouts provided on the unit. If a side entrance is the only option, a hole may be drilled in the stationary upright.
The minimum circuit ampacity (MCA) is shown on the unit nameplate. Refer to Table 5 for the recommended number of power wires.
Copper wire is required for all conductors. Size wires in accordance with the ampacity tables in Article 310 of the National Electrical Code. If long wires are required, it may be necessary to increase the wire size to prevent excessive voltage drop. Wires should be sized for a maximum of 3% voltage drop. Supply voltage must not vary by more than 10% of nameplate. Phase voltage imbalance must not exceed 2%. (Calculate the average voltage of the three legs. The leg with voltage deviating the farthest from the average value must not be more than 2% away.) Contact the local power company for correction of improper voltage or phase imbalance.
CAUTION
Provide proper line voltage and phase balance.
Improper line voltage or excessive phase imbalance constitutes product abuse. It can cause severe damage to the unit's electrical components.
A ground lug is provided in the control panel. Size the grounding conductor in accordance with Table 250-95 of the National Electrical Code.
In compliance with the National Electrical Code, a 115 V factory mounted service receptacle outlet is provided. This outlet must be powered by a field connected 15 A, 115 V power supply. Leads are brought into the unit through a 7/8" knockout in the bottom of the main control panel.
Table 5: Recommended Field Power Wiring
Ampacity
(MCA)
30 1 10 75 40 1 8 75 55 1 6 75 70 1 4 75 85 1 3 75
95 1 2 75 130 1 1 75 150 1 1/0 75 175 1 2/0 75 200 1 3/0 75 230 1 4/0 75 255 1 250 75 300 2 1/0 75 350 2 2/0 75 400 2 3/0 75 460 2 4/0 75 510 2 250 75 600 3 3/0 75 690 3 4/0 75 765 3 250 75
Notes:
1. All wire sizes assume separate conduit for each set of parallel conductors.
2. All wire sizes based on NEC Table 310-16 for 75°C THW wire (copper). Canadian electrical code wire ampacities may vary.
3. All wire sizes assume no voltage drop for short power leads.
# of Power
Wires Per
Phase
Wire Gauge
Insulation
Temperature
Rating (°C)
McQuay IM 842-1 13
Electrical Installation

Field Control Wiring

The Maverick rooftop units are available with the following field control connections:
Space sensor.
Space sensor with setpoint adjustment.
Fan operation output.
VAV box output.
Remote alarm output.
External discharge air temperature reset.
Outdoor air damper minimum position adjustment.
Descriptions of these field connections are included in the MicroTech II Unit Controls manual (OM 843).
WARNING
Electrical shock hazard. Can cause severe injury or death.
Connect only low voltage NEC Class II circuits to terminal block TB2.
14 McQuay IM 842-1

Preparing Unit for Operation

Preparing Unit for Operation

Spring Isolated Fans

WARNING
Moving machinery hazard. Can cause severe injury or death. Before servicing equipment, disconnect power and lock
off. More than one disconnect may be required to de-energize unit. Prior to operating the fans for the first time, refer to “Check, Test, and Start Procedures” on page 45.

Releasing Spring Mounts

The spring-mounted supply fan is locked down with four shipping bolts for shipment. Remove each shipping bolt before operating the fans. Figure 14 shows a typical spring mount with a height adjustment nut and a shipping bolt.
After removing the shipping bolts, rock the fan assembly by hand to check for freedom of movement.
Figure 14: Spring Mounts

Adjusting Spring Mounts

During operation all fans should ride level. Level the fan assembly by performing the following:
1 Loosen the 3/8" cap screw (do not remove).
2 Loosen the spring cap nut.
3 Rotate the 5/8" adjustment nut counter-clockwise to raise
the fan assembly, or clockwise to lower the fan assembly.
4 Tighten the 3/8" cap screw.
5 Tighten the spring cap nut.
McQuay IM 842-1 15

Optional Gas Heat

Optional Gas Heat

Gas Furnace Design

This section of the manual covers the optional furnace (Figure 15). If the 8th digit in the model number is a “G”, the rooftop unit was furnished with a factory installed furnace (Example, MPS035AG). The Maverick commercial rooftop units are available with either the low heat input or the high heat input furnace (see capacities in Table 6). This packaged gas heat rooftop unit is designed for outdoor non-residential installations only.
The gas heat furnace design consists of a tubular heat exchanger, in-shot burner manifold with gas valve, induced combustion blower, gas heat DDC control module and all operational safeties. The tubular heat exchanger can come with the standard aluminized steel construction or the optional stainless steel construction. The safety switches include a high­limit temperature switch (Figure 15), an auxiliary high-limit switch (Figure 15), a combustion blower proof of airflow (see Figure 16), and the flame roll-out switch (see Figure 16).
The high limit switch is an automatic reset switch and it opens up at 160°F to shut the furnace down and closes at 130°F. The auxiliary limit switch is a manual reset and opens up at 180°F to shut the furnace down.
Figure 15: Gas Heat Section

Gas Heating Capacity Data

Table 6: MPS 030A – 050A Gas Heating Capacities
Unit Size
Data
Heating Input (MBh) 300 600 Heating Output (MBh) Steady State Efficiency Number of Stages Minimum Airflow 3800 7400 Maximum Temperature Rise Gas Main Pressure Natural Gas (in. wc) 7-147-147-147-147-147-147-147-14 Liquid Propane (in. wc) 12-14 12-14 12-14 12-14 12-14 12-14 12-14 12-14 Manifold Pressure Natural Gas (per gas valve) Stage 1 (in. wc) 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 Stage 2 (in. wc) 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 Propane Stage 1 (in. wc) 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 Stage 2 (in. wc) 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 Connection Size 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" Quantity 12121212
030A
(Lo Heat)
240 480
80% 80% 80% 80% 80% 80% 80% 80%
24
60°F 60°F 60°F 60°F 60°F 60°F 60°F 60°F
030A
(High Heat)
035A
(Lo Heat)
300 600 400 800 400 800 240 480 320 640 320 640
242424
3800 7400 4900 9800 4900 9800
035A
(High Heat)
040A
(Lo Heat)
040A
(High Heat)
050A
(Lo Heat)
(High Heat)
050A
16 McQuay IM 842-1
Figure 16: Burner Assembly
4
5
6
7
Optional Gas Heat
1
2
3
Item # D escr ip ti on
1Furnace 2 I nduced Co mbus tion Bl ower 3 P late-Induc er Orifice 4 T rans forme r-40VA 5 S park I gnito r
12
11
10
9
8
6IgnitionControl 7 G as Val ve-2 S tage 8 M anifold A ss embly Test Port
9 B urner Ins hot 10 Fl ame R ollout Switc h 11 Fl ame S ensor 12 Pr oof of A irflow S witch
Warranty Exclusion
Warranty is void if the furnace is operated in the presence of chlorinated vapors, if the airflow through the furnace is not in accordance with rating plate, or if the wiring or controls have
been modified or tampered with.
WARNING
Hot surface hazard. Can cause severe equipment damage, personal injury, or death. Allow burner assembly to cool
before servicing equipment.
WARNING
Units equipped with gas heating must not be operated in an atmosphere contaminated with chemicals which will corrode the unit such as halogenated hydrocarbons, chlorine, cleaning solvents, refrigerants, swimming pool exhaust, etc. Exposure to these compounds may cause severe damage to the gas furnace and result in improper or dangerous operation. Operation of the gas furnace in such
a contaminated atmosphere constitutes product abuse and will void all warranty coverage by the manufacturer. Questions regarding specific contaminants should be referred to your local gas utility.
Ventilation & Flue Pipe Requirements
The McQuay rooftop unit is equipped with an outdoor air hood to supply adequate combustion air. The unit also has a flue outlet assembly and requires no additional chimney, flue pipe, Breidert cap, draft inducer, etc.
Factory Checkout
This complete furnace was fired and tested at the factory. The unit was fired through several complete sequences of start-up through shutoff to check operation. A check was made of the air switch, gas pressure switch, high limit operation.
This checkout normally eliminates on-the-job start-up problems; however, the equipment is subject to variable job conditions and shipping shocks can change adjustments, cause damage, and loosen connections and fasteners. Therefore, it is necessary to go through the complete start-up procedure even though the unit may appear to be operating properly.
McQuay IM 842-1 17
Loading...
+ 39 hidden pages