Heat medium
Y = None (cooling only)
G = Natural gas
E = Electric heat
W = Hot water heat
Design vintage
Nominal capacity (tons)
General Information
Introduction
This manual provides general information about the “F”
vintage McQuay Commercial Packaged Rooftop Unit model
MPS. In addition to an overall description of the unit, it
includes mechanical and electrical installation procedures,
commissioning procedures, sequence of operation information,
and maintenance instructions.
The MicroTech
®
III rooftop unit controller is available on “F”
vintage rooftop units. For a detailed description of the
MicroTech III components, input/output configurations, field
wiring options and requirements, and service procedures, see
OM 920. For operation and information on using and
programming the MicroTech III unit controller, refer to the
appropriate operation manual (see Table 1).
For a description of operation and information on using the
keypad to view data and set parameters, refer to the
appropriate program-specific operation manual (see Table 1)
Table 1: Program Specific Unit Operation Literature
Rooftop unit control configurationManual bulletin number
VFDsOM 844 - MD2
MPS Unit Controller
Discharge Air Control (VAV or CAV)
Space Comfort Control (SCC)
LonWorks IntegrationIM 918
BACnet IntegrationIM 917
BACnet IP Comm ModuleIM 916
OM 895 - MD3
OM 847 - MD6
OM 920
.
Unit Nameplate
The unit nameplate is located on the outside of the main
control box door. It includes the unit model number, serial
number, electrical characteristics, and refrigerant charge.
Hazard Identification Information
DANGER
Dangers indicate a hazardous situation which will result in
death or serious injury if not avoided.
WARNING
Warnings indicate potentially hazardous situations, which can
result in property damage, severe personal injury, or death if
not avoided.
CAUTION
Cautions indicate potentially hazardous situations, which can
result in personal injury or equipment damage if not avoided.
Nomenclature (MPS 015–050)
McQuay IM 10583
Mechanical Installation
Mechanical Installation
Installer Responsibilities
The installation of this equipment shall be in accordance with
the regulations of authorities having jurisdiction and all
applicable codes. It is the responsibility of the installer to
determine and follow the applicable codes.
CAUTION
Sharp edges on sheet metal and fasteners can cause
personal injury. This equipment must be installed, operated,
and serviced only by an experienced installation company and
fully trained personnel.
Receiving Inspection
When the equipment is received, all items should be carefully
checked against the bill of lading to be sure all crates and
cartons have been received. If the unit has become dirty
during shipment (winter road chemicals are of particular
concern), clean it when received.
Figure 1: Service Clearances
All units should be carefully inspected for damage when
received. Report all shipping damage to the carrier and file a
claim. In most cases, equipment is shipped F.O.B. factory and
claims for freight damage should be filed by the consignee.
Before unloading the unit, check the unit nameplate to make
sure the voltage complies with the power supply available.
Service Clearance
Allow service clearances as approximately indicated in
Figure 1. Also, McQuay recommends providing a roof
walkway to the rooftop unit as well as along each side of the
unit that provides access to most controls and serviceable
components.
4McQuay IM 1058
Mechanical Installation
Ventilation Clearance
Below are minimum ventilation clearance recommendations.
The system designer must consider each application and
provide adequate ventilation. If this is not done, the unit may
not perform properly.
Unit(s) Surrounded by a Screen or a Fence:
1 The bottom of the screen or fence should be at least 1 ft.
(305 mm) above the roof surface.
2 The distance between the unit and a screen or fence should
be as described in Figure 1 on page 4.
3 The distance between any two units within a screen or
fence should be at least 120" (3048 mm).
Unit(s) Surrounded by Solid Walls:
1 If there are walls on one or two adjacent sides of the unit,
the walls may be any height. If there are walls on more than
two adjacent sides of the unit, the walls should not be
higher than the unit.
2 The distance between the unit and the wall should be at
least 96" (2438 mm) on all sides of the unit.
3 The distance between any two units within the walls should
be at least 120" (3048 mm).
Do not locate outside air intakes near sources of contaminated
air.
If the unit is installed where windy conditions are common,
install wind screens around the unit, maintaining the
clearances specified (see Figure 1). This is particularly
important to maintain adequate head pressure control when
mechanical cooling is required at low outdoor air
temperatures.
Note: Low head pressure may lead to poor and erratic
refrigerant feed control at the thermostatic expansion
valve. The unit has automatic control of the condenser
fans which should provide adequate head pressure
control down to 20°F provided the unit is not exposed to
windy conditions. The system designer is responsible
for assuring the condensing section is not exposed to
excessive wind or air recirculation.
Overhead Clearance
1 Unit(s) surrounded by screens or solid walls must have no
overhead obstructions over any part of the unit.
2 The area above the condenser must be unobstructed in all
installations to allow vertical air discharge.
3 The following restrictions must be observed for overhead
obstructions above the air handler section:
a There must be no overhead obstructions above the
furnace flue, or within 9" (229 mm) of the flue box.
b Overhead obstructions must be no less than 96"
(2438 mm) above the top of the unit.
c There must be no overhead obstructions in the areas
above the outside air and exhaust dampers that are
farther than 24" (610 mm) from the side of the unit.
Roof Curb Assembly and Installation
Locate the roof curb and unit on a portion of the roof that can
support the weight of the unit. The unit must be supported to
prevent bending or twisting of the machine.
If building construction allows sound and vibration into
the occupied space, locate the unit over a non-critical area.
It is the responsibility of the system designer to make
adequate provisions for noise and vibration in the occupied
space.
WARNING
Mold can cause personal injury. Some materials such as
gypsum wall board can promote mold growth when damp.
Such materials must be protected from moisture that can enter
units during maintenance or normal operation.
Install the curb and unit level to allow the condensate drain to
flow properly and allow service access doors to open and close
without binding.
The gasketed top surface of the curb seals against the unit
when it is set on the curb. These flanges must not support the
total weight of the duct work. See “Installing Ductwork” on
page 12 for details on duct connections. It is critical that the
condensate drain side of the unit be no higher than the opposite
side.
Assembly Instructions
Assembly of a typical roof curb is shown in Figure 2.
1 Set curbing parts A thru G per dimensions shown over roof
opening or on a level surface. Note location of supply air
opening. Check alignment of all mating screw holes.
2 Screw curbing parts together using fasteners provided.
Leave all screws loose until curb is checked to be square.
3 Square entire curbing assembly and securely tighten all
screws.
4 Position curb assembly over roof openings. Curb must be
level within .25 inches from side to side and 1.50 inches
over its length. Check that top surface of curb is flat with
no bowing or sagging.
5 Weld curb assembly in place. Caulk all seams watertight.
Remove backing from .25 x 1.50 wide gasket and apply to
surfaces shown by crosshatching.
6 Check that electrical connections are coordinated.
Only trained and qualified personnel should be allowed to
rig loads or operate load rated cranes and/or hoist
assemblies. Do not use a forklift to lift or maneuver the
unit. Failure to use a load rated crane or hoist assembly to
lift or maneuver the unit can cause severe personal injury
and property damage.
WARNING
Use all lifting points. Improper lifting can cause property
damage, severe personal injury, or death.
CAUTION
Lifting points may not be symmetrical to the center of
gravity of the unit. Ballast or unequal cable lengths may be
required.
Rigging holes for shackles are integral on the unit base. All six
lifting points must be used for rigging the equipment. Use
four independent lines, securing one end of a line to a unit
base lifting point and the other end of the line to an
associated spreader bar lifting point (see Figure 7).Figure 6
is an example of an instruction label shipped with each unit.
Figure 6: Rigging Label
Use spreader bars, 96" to 100" (2438 to 2540 mm) wide to
prevent damage to the unit cabinet. Avoid twisting or uneven
lifting of the unit. The cable length from the bracket to the
hook should always be longer than the distance between the
outer lifting points.
If the unit is stored at the construction site for an intermediate
period, take these additional precautions:
1 Support the unit well along the length of the base rail.
2 Level the unit (no twists or uneven ground surface).
3 Provide proper drainage around the unit to prevent flooding
of the equipment.
4 Provide adequate protection from vandalism, mechanical
contact, etc.
5 Securely close the doors.
6 Cover the supply and return air openings.
Table 2 lists the weight distribution at each of the six lifting
points on the unit (refer to Figure 7 on page 11). Table 3 details
lifting point locations.
Table 2: Percentage of Load and Weight Points
Unit (tons)
015 Cooling 2655292 292 531 637 425 478
015 Gas Heating2855315 315 571 685 457 514
015 Electric Heating2775305 304 555 666 444 500
015 Hot Water Heating2850314 314 570 684 456 513
017 Cooling 2705298 298 541 649 433 487
017 Gas Heating2905320 320 581 697 465 523
017 Electric Heating2825311 311 565 678 452 509
017 Hot Water Heating2900319 319 580 696 464 522
020 Cooling
020 Gas Heating
020 Electric Heating
020 Hot Water Heating
025 Cooling
025 Gas Heating
025 Electric Heating
025 Hot Water Heating
030 Cooling 3610397 397 722 866 578 650
030 Gas Heating3880427 427 776 931 621 698
030 Electric Heating3880427 427 776 931 621 698
030 Hot Water Heating3901429 429 780 936 624 702
035 Cooling3660403 403 732 878 586 659
035 Gas Heating3930432 432 786 943 629 707
035 Electric Heating3930432 432 786 943 629 707
035 Hot Water Heating3961435 435 790 948 632 711
040 Cooling4685515 515 937 1124 750 843
040 Gas Heating5035554 554 1007 1208 806 906
040 Electric Heating5035554 554 1007 1208 806 906
040 Hot Water Heating4992549 549 998 1198 799 899
050 Cooling4985548 548 997 1196 798 897
050 Gas Heating5335587 587 1067 1280 854 960
050 Electric Heating5335587 587 1067 1280 854 960
050 Hot Water Heating5292582 582 1058 1270 847 953
*
Base unit weight includes Economizer, VFDs, and the smallest supply fan
available (see Table 5 and Table 6 on page 11 for additional fan/motor
weights).
Table 3: Weight Distribution Locations (see Figure 7)
Unit (Tons)
015–035 Ton Unit35.562.052.0
040–050 Ton Unit40.069.089.0
The unit is provided with a 1" female NPT condensate drain
connection. For proper drainage, level the unit and drain pan
side to side and install a P-trap.
Figure 8 shows the layout of the condensate drain connection.
The distance from the drain pan outlet to the horizontal run of
the P-trap should be a distance of twice the static pressure in
the drain pan.
Example: If the static pressure as measured in the drain pan is
1.5", then the distance between the drain outlet and the
horizontal run should be 3".
Draining condensate directly onto the roof may be acceptable;
refer to local codes. Provide a small drip pad of stone, mortar,
wood, or metal to protect the roof against possible damage.
If condensate is piped into the building drainage system, pitch the
drain line away from the unit a minimum of 1/8" per foot. The
drain line must penetrate the roof external to the unit. Refer to
local codes for additional requirements. Sealed drain lines require
venting to provide proper condensate flow.
Where the cooling coils have intermediate condensate pans on
the face of the evaporator coil, copper tubes near both ends of
the coil supply drainage to the main drain pan. Verify the tubes
are in place and open before putting the unit into operation.
Periodically clean to prevent microbial growth/algae buildup
from plugging the drain and causing the drain pan to overflow.
Clean drain pans to prevent the spread of disease. Cleaning
should be performed by qualified personnel
WARNING
Drain pans must be cleaned periodically. Material in
uncleaned drain pans can cause disease.
Cleaning should be performed by qualified personnel.
Figure 8: Condensate Drain Connection
Static Pressure (P)
at the Drain Pan
.
Additional Weights for 6-Row DX Coil and
HGRH Coil
Table 7: Coil Weights
Unit
15–2511870
30–3516482
4018792
5023192
McQuay IM 105811
Weight (lbs)
6 Row DXHGRH
Mechanical Installation
Damper Assemblies
The optional damper assemblies described in this section are
ordered with factory-installed actuators and linkages. The
following sections describe the operation and linkage
adjustment of the factory option.
Figure 9: Damper Assembly
Economizer Dampers
As the single actuator modulates, the outside air dampers open,
the return air dampers close, and the exhaust air exits the unit
through the gravity relief dampers.
The economizer comes with manually adjustable linkage
(Figure 9). The damper is set so that the crankarm moves
through a 90-degree angle to bring the economizer dampers
from full open to full close. Mechanical stops are placed in the
crankarm mounting bracket. Do not remove stops. Driving the
crankarm past the stops results in damage to the linkage or
damper.
Outdoor Air Dampers (0% to 30%)
These dampers are intended to remain at a fixed position
during unit operation, providing fresh air quantities from 0 to
30% of the total system airflow, depending on the damper
setting.
The damper position may be set at the unit controller keypad
(refer to OM 920 for further detail). During unit operation, the
damper is driven to the position set at the unit controller.
During the off cycle, the damper is automatically closed.
Cabinet Weather Protection
This unit ships from the factory with fully gasketed access
doors and cabinet caulking to provide weather resistant
operation. After the unit is set in place, inspect all door gaskets
for shipping damage and replace if necessary.
Protect the unit from overhead runoff from overhangs or other
such structures.
CAUTION
Transportation, rigging, or maintenance can damage the
unit’s weather seal. Periodically inspect the unit for leakage.
Standing moisture can promote microbial growth, disease, or
damage to the equipment and building.
Installing Ductwork
On vertical-supply/vertical-return units, if a McQuay roof curb
is not used, the installing contractor should make an airtight
connection by attaching field fabricated duct collars to the
bottom surface of the unit’s duct opening. Do not support the
total weight of the duct work from the unit. See Figure 4 on
page 8 or Figure 5 on page 9.
Use flexible connections between the unit and ductwork to
avoid transmission of vibration from the unit to the structure.
To minimize losses and sound transmission, design duct work
per ASHRAE and SMACNA recommendations.
Where return air ducts are not required, connect a sound
absorbing T or L section to the unit return to reduce noise
transmission to the occupied space.
WARNING
Mold can cause personal injury. Materials such as gypsum
wall board can promote mold growth when damp. Such
materials must be protected from moisture that can enter units
during maintenance or normal operation.
Ductwork exposed to outdoor conditions must be built in
accordance with ASHRAE and SMACNA recommendations
and local building codes
.
Installing Duct Static Pressure Sensor Taps
For all VAV units, duct static pressure taps must be field
installed and connected to the static pressure sensor 1 (SPS1)
in the unit. Sensor SPS1 is standard on VAV units and is
located in the main control panel.
Carefully locate and install the duct static pressure sensing tap.
Improperly locating or installing the sensing tap causes
unsatisfactory operation of the entire variable air volume
system. Below are pressure tap location and installation
recommendations. The installation must comply with local
code requirements.
12McQuay IM 1058
Mechanical Installation
Roof
SPS1
Main Control Panel
Condenser Section
HI Line
LO Line
Remote Sense Point
To Sensor
HI Input
Pressure Sensing
Tubing
Tubing Extends
Through Approx. 1/8”
Rubber
Grommet
Ductwork
(Remote Location)
To Sensor
LO Input
1 Install a tee fitting with a leak-tight removable cap in each
tube near the sensor fitting. This facilitates connecting a
manometer or pressure gauge if testing is required.
2 Use different colored tubing for the duct pressure (HI) and
reference pressure (LO) taps, or tag the tubes. McQuay
recommends 1/8" ID tubing.
3 Locate the duct pressure (HI) tap near the end of a long
duct to ensure that all terminal box take-offs along the run
have adequate static pressure.
4 Locate the duct tap in a nonturbulent flow area of the duct.
Keep it several duct diameters away from take-off points,
bends, neckdowns, attenuators, vanes, or other
irregularities.
5 Use a static pressure tip (Dwyer A302 or equivalent) or the
bare end of the plastic tubing for the duct tap. (If the duct is
lined inside, use a static pressure tip device.)
6 Install the duct tap so that it senses only static pressure (not
velocity pressure). If a bare tube end is used, it must be
smooth, square (not cut at an angle) and perpendicular to
the airstream (see Figure 11).
7 Locate the reference pressure (LO) tap near the duct
pressure tap within the building. If the tap is not connected
to the sensor, unsatisfactory operation will result.
8 Route the tubes through the curb and feed them into the
unit through the knockout in the bottom of the control panel
(see Figure 10). Connect the tubes to appropriate barbed
fittings (on SPS1) in the control panel. (Fittings are sized to
accept 1/8" ID tubing.)
If a unit has building static pressure control capability, you
must field install and connect static pressure taps to the static
pressure sensor SPS2 in the unit. This sensor is located at the
bottom of the main control panel next to SPS1.
Carefully locate and install the two static pressure sensing
taps. Improper location or installation of the sensor taps causes
unsatisfactory operation. Below are pressure tap location and
installation recommendations for both building envelope and
lab, or “space within a space” pressure control applications.
The installation must comply with local code requirements.
CAUTION
Fragile sensor fittings. If you must remove tubing from a
pressure sensor fitting, use care. Do not use excessive force or
wrench the tubing back and forth to remove or the fitting can
break off and damage sensor.
McQuay IM 105813
Mechanical Installation
Building Pressurization Applications
1 Install a tee fitting with a leak-tight removable cap in each
tube near the sensor fitting. This facilitates connecting a
manometer or pressure gauge if testing is required.
2 Locate the building pressure (high) tap in the area that
requires the closest control. Typically, this is a ground level
floor that has doors to the outside.
3 Locate the building tap so it is not influenced by any source
of moving air (velocity pressure). These sources may
include air diffusers or outside doors.
4 Route the building tap tube through the curb and feed it into
the unit through the knockout in the bottom of the control
panel (refer to Figure 10). Connect the 1/8" ID tube to the
(high) fitting for sensor SPS2.
5 Locate the reference pressure (low) tap on the roof. Keep it
away from the condenser fans, walls, or anything else that
may cause air turbulence. Mount it high enough above the
roof so it is not affected by snow. Not connecting the
reference tap to the sensor results in unsatisfactory
operation.
6 Use an outdoor static pressure tip (Dwyer A306 or
equivalent) to minimize the adverse effects of wind. Place
some type of screen over the sensor to keep out insects.
Loosely packed cotton works well.
7 Route the outdoor tap tube out of the main control panel
through a small field-cut opening in the upright. Seal the
penetration to prevent water from entering. Connect the
1/8" ID tube to the (low) fitting for sensor SPS2.
Lab Pressurization Applications
1 Install a “T” fitting with a leak-tight removable cap in each
tube near the sensor fitting. This facilitates connecting a
manometer or pressure gauge if testing is required.
2 Use different colored tubing for the controlled space
pressure (high) and reference pressure (low) taps, or tag the
tubes.
3 Regardless whether the controlled space is positive or
negative with respect to its reference, locate the high
pressure tap in the controlled space (the setpoint can be set
between -0.2" and 0.2" wc).
4 Locate the reference pressure (low) tap in the area
surrounding the controlled space. Not locating the
reference tap to the sensor results in unsatisfactory
operation.
5 Locate both taps so they are not influenced by any source
of moving air (velocity pressure). These sources may
include air diffusers or doors between the high and low
pressure areas.
6 Route the building tap tube between the curb and the
supply duct and feed it into the unit through the knockout in
the bottom of the control panel.
7 Connect the tube to the (high) fitting for sensor SPS2.
Wiring must comply with all applicable codes and ordinances.
The warranty is voided if wiring is not in accordance with
these specifications.
According to the National Electrical Code, a disconnecting
means shall be located within sight of and readily accessible
from the air conditioning equipment. The unit can be ordered
with an optional factory mounted disconnect switch. This
switch is not fused. Power leads must be over-current
protected at the point of distribution. The maximum rated
overcurrent protection device (MROPD) value appears on the
unit nameplate.
All Units
All units are provided with internal power wiring for single
point power connection. The power block or an optional
disconnect switch is located within the main control panel.
Field power leads are brought into the unit through knockouts
in the bottom of the main control panel (see Figure 13 and also
Table 8). Refer to the unit nameplate to determine the number
of power connections.
WARNING
Hazardous voltage. Can cause severe injury or death.
Disconnect electric power before servicing equipment. More
than one disconnect may be required to de-energize the unit.
Note: To wire entry points, refer to certified drawings for
dimensions.
Figure 13: MPS Power Wiring Knockout Locations
The preferred entrance for power cables is through the bottom
knockouts provided on the unit. If a side entrance is the only
option, a hole may be drilled in the stationary upright.
The minimum circuit ampacity (MCA) is shown on the unit
nameplate. Refer to Table 8 for the recommended number of
power wires.
Copper wire is required for all conductors. Size wires in
accordance with the ampacity tables in Article 310 of the
National Electrical Code. If long wires are required, it may be
necessary to increase the wire size to prevent excessive voltage
drop. Wires should be sized for a maximum of 3% voltage
drop. Supply voltage must not vary by more than 10% of
nameplate. Phase voltage imbalance must not exceed 2%.
(Calculate the average voltage of the three legs. The leg with
voltage deviating the farthest from the average value must not
be more than 2% away.) Contact the local power company for
correction of improper voltage or phase imbalance.
CAUTION
Provide proper line voltage and phase balance.
Improper line voltage or excessive phase imbalance constitutes
product abuse. It can cause severe damage to the unit's
electrical components.
A ground lug is provided in the control panel. Size the
grounding conductor in accordance with Table 250-95 of the
National Electrical Code.
In compliance with the National Electrical Code, a 115 V
factory mounted service receptacle outlet is provided. This
outlet must be powered by a field connected 15 A, 115 V
power supply. Leads are brought into the unit through a 7/8"
knockout in the bottom of the main control panel.
1. All wire sizes assume separate conduit for each set of parallel conductors.
2. All wire sizes based on NEC Table 310-16 for 75°C THW wire (copper).
Canadian electrical code wire ampacities may vary.
3. All wire sizes assume no voltage drop for short power leads.
# of Power
Wires Per
Phase
Wire Gauge
Insulation
Temperature
Rating (°C)
McQuay IM 105815
Electrical Installation
Field Control Wiring
The Maverick rooftop units are available with the following
field control connections:
• Space sensor.
• Space sensor with setpoint adjustment.
• Fan operation output.
• VAV box output.
• Remote alarm output.
• External discharge air temperature reset.
• Outdoor air damper minimum position adjustment.
Descriptions of these field connections are included in the
MicroTech III Unit Controller manual (OM 920).
WARNING
Electrical shock hazard. Can cause severe injury or death.
Connect only low voltage NEC Class II circuits to terminal block
TB2.
16McQuay IM 1058
Preparing Unit for Operation
Preparing Unit for Operation
Spring Isolated Fans
WARNING
Moving machinery hazard. Can cause severe injury or
death. Before servicing equipment, disconnect power and lock
off. More than one disconnect may be required to de-energize
unit. Prior to operating the fans for the first time, refer to “Check,
Test, and Start Procedures” on page 52.
Releasing Spring Mounts
The spring-mounted supply fan is locked down with four
shipping bolts for shipment. Remove each shipping bolt before
operating the fans. Figure 14 shows a typical spring mount
with a height adjustment nut and a shipping bolt.
After removing the shipping bolts, rock the fan assembly by
hand to check for freedom of movement.
Figure 14: Spring Mounts
Adjusting Spring Mounts
During operation all fans should ride level. Level the fan
assembly by performing the following:
1 Loosen the 3/8" cap screw (do not remove).
2 Loosen the spring cap nut.
3 Rotate the 5/8" adjustment nut counter-clockwise to raise
the fan assembly, or clockwise to lower the fan assembly.
4 Tighten the 3/8" cap screw.
5 Tighten the spring cap nut.
McQuay IM 105817
Optional Gas Heat
Optional Gas Heat
Gas Furnace Design
If the 8th digit in the model number is a “G”, the rooftop unit
was furnished with a factory installed furnace (Example,
MPS035FG). The Maverick commercial rooftop units are
available with either the low heat input or the high heat input
furnace (see capacities in Table 9). This packaged gas heat
rooftop unit is designed for outdoor non-residential
installations only.
The gas heat furnace design consists of a tubular heat
exchanger, in-shot burner manifold with gas valve, induced
combustion blower, gas heat DDC control module and all
operational safeties. The tubular heat exchanger can come with
the standard aluminized steel construction or the optional
stainless steel construction. The safety switches include a highlimit temperature switch (Figure 15), an auxiliary high-limit
switch (Figure 15), a combustion blower proof of airflow (see
Figure 16), and the flame roll-out switch (see Figure 16).
The high limit switch is an automatic reset switch and it opens
up at 160°F to shut the furnace down and closes at 130°F. The
auxiliary limit switch is a manual reset and opens up at 180°F
to shut the furnace down.
Warranty is void if the furnace is operated in the presence of
chlorinated vapors, if the airflow through the furnace is not in
accordance with rating plate, or if the wiring or controls have
been modified or tampered with.
WARNING
Hot surface hazard. Can cause severe equipment damage,
personal injury, or death. Allow burner assembly to cool
before servicing equipment.
WARNING
Units equipped with gas heating must not be operated in
an atmosphere contaminated with chemicals which will
corrode the unit such as halogenated hydrocarbons,
chlorine, cleaning solvents, refrigerants, swimming pool
exhaust, etc. Exposure to these compounds may cause
severe damage to the gas furnace and result in improper
or dangerous operation. Operation of the gas furnace in such
a contaminated atmosphere constitutes product abuse and will
void all warranty coverage by the manufacturer. Questions
regarding specific contaminants should be referred to your
local gas utility.
Ventilation & Flue Pipe Requirements
The McQuay rooftop unit is equipped with an outdoor air hood
to supply adequate combustion air. The unit also has a flue
outlet assembly and requires no additional chimney, flue pipe,
Breidert cap, draft inducer, etc.
Factory Checkout
This complete furnace was fired and tested at the factory. The
unit was fired through several complete sequences of start-up
through shutoff to check operation. A check was made of the
air switch, gas pressure switch, high limit operation.
This checkout normally eliminates on-the-job start-up
problems; however, the equipment is subject to variable job
conditions and shipping shocks can change adjustments, cause
damage, and loosen connections and fasteners. Therefore, it is
necessary to go through the complete start-up procedure even
though the unit may appear to be operating properly.
McQuay IM 105819
Optional Gas Heat
Installation
IMPORTANT
This furnace must be installed by an experienced
professional installation company that employs fully
trained and experienced technicians. Install the furnace in
accordance with the manufacturer's instructions and local
codes. In the absence of local codes, follow the National
Fuel Gas Code, ANSI Z223.1/NFPA 54, or the CSA B149.1,
Natural Gas and Propane Installation Code.
WARNING
Sharp edges hazard. Can cause personal injury or death.
Sheet metal parts, self-tapping screws, clips, and similar items
inherently have sharp edges, and it is necessary that the
installer exercise caution when handling these items.
Flue Box
The flue box (Figure 17) is not installed at the factory because
it would increase the width of the unit beyond the allowable
shipping width.
Figure 17: Flue Box Installation
3 Line assembly holes up.
4 Install screws to fasten the flue box to the side of the unit.
Outdoor Air (OA) Hood
The OA hood (Figure 18) is not installed at the factory because
it would increase the width of the unit beyond the allowable
shipping width. The hood is shipped in a box in the fan
section.
Figure 18: Outdoor Air (OA) Hood Installation
The OA hoods must be installed over the outdoor air openings
as shown in Figure 18.
1 Remove and discard the shipping covers.
2 Position the hood over the OA openings.
3 Line assembly holes up.
4 Install screws to fasten the OA hood.
The OA hoods must be installed before the furnace is operated.
The flue box must be installed over the combustion exhaust
openings shown in Figure 17. All holes are prepunched, the
fasteners are furnished and everything is shipped inside the fan
section.
1 Remove and discard the shipping covers.
2 Position the flue box over the exhaust openings.
20McQuay IM 1058
Loading...
+ 44 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.