McQuay MPS015AYCL Installation Manual

Page 1
1
Maverick I™ Commercial Packaged Rooftop System Cooling Only or Heating & Cooling
Electric/Electric
Models MPS015AY – 020AY 15 to 20 Tons
Installat
IM 867
Group: Applied Systems
Part Number: 92-102421-06-00
Date: March 2007
© 2007 McQuay International
ARI Standard 210/240 UAC
Page 2
2 IM 867
Table of Contents
Table of Contents. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Checking Product Received . . . . . . . . . . . . . . . . . . . . 3
Equipment Protection . . . . . . . . . . . . . . . . . . . . . . . . . 3
Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6
General Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-9
Electrical & Physical Data Tables. . . . . . . . . . . . . . . . . . . . . . . . 10
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Outside Slab Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Rooftop Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Ductwork. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Horizontal Conversion Procedure . . . . . . . . . . . . . . . 13
Downflow to Horizontal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Electrical Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Control Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Internal Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Grounding. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Indoor Air Flow Data . . . . . . . . . . . . . . . . . . . . . . . . . 15
Airflow Performance Tables . . . . . . . . . . . . . . . . . . . 16
Pre-Start Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Cooling Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Heating Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Auxiliary Heat. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Heater Kit Characteristics. . . . . . . . . . . . . . . . . . . . . 20
Trouble Shooting Chart. . . . . . . . . . . . . . . . . . . . . . . 21
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . 22-23
Charging Charts . . . . . . . . . . . . . . . . . . . . . . . . . . 24-25
Page 3
IM 867
3
Introduction
This manual contains the installation and operating instruc­tions for your packaged rooftop system. There are a few pre­cautions that should be taken to derive maximum satisfaction from it. Improper installation can result in unsatisfactory operation or dangerous conditions.
Read this manual and any instructions packaged with separate equipment required to make up the system prior to installa­tion. Give this manual to the owner and explain its provisions. The owner should retain this manual for future reference.
Checking Product Received
Upon receiving unit, inspect it for any shipping damage. Claims for damage, either apparent or concealed should be filed immediately with the shipping company. Check con-
densing unit model number, electrical characteristics and accessories to determine if they are correct. Check system components (evaporator coil, condensing unit, evaporator blower, etc.) to make sure they are properly matched.
Equipment Protection From The Environment
The metal parts of this unit may be subject to rust or deterio­ration in adverse environmental conditions. This oxidation could shorten the equipment’s useful life. Salt spray, fog or mist in seacoast areas, sulphur or chlorine from lawn watering systems, and various chemical contaminants from industries such as paper mills and petroleum refineries are especially corrosive.
If the unit is to be installed in an area where contaminants are likely to be a problem, special attention should be given to the equipment location and exposure.
1 Avoid having lawn sprinkler heads spray directly on the
unit cabinet.
2 In coastal areas, locate the unit on the side of the build-
ing away from the waterfront.
3 Shielding provided by a fence or shrubs may give some
protection.
Regular maintenance will reduce the buildup of contami­nents and help to protect the unit’s finish.
1 Frequent washing of the cabinet, fan blade and coil with
fresh water will remove most of the salt or other contam­inants that build up on the unit.
2 Regular cleaning and waxing of the cabinet with a good
automobile polish will provide some protection.
3 A good liquid cleaner may be used several times a year
to remove matter that will not wash off with water.
Several different types of protective coatings are offered in some areas. These coatings may provide some benefit, but the effectiveness of such coating materials cannot be verified by the equipment manufacturer.
The best protection is frequent cleaning, maintenance and minimal exposure to contaminant.
Proposition 65: This unit contains fiberglass insulation. Respirable particles of fiberglass are known to the state of California to cause cancer.
WARNING
!
The manufacturer’s warranty does not cover any damage or defect to the air conditioner caused by the attachment or use of any components, accessories or devices (other than those authorized by the manufacturer) into, onto or in conjunction with the air conditioner. You should be aware that the use of unauthorized components, accessories or devices may adversely affect the operation of the air conditioner and may also endanger life and property. The manufacturer disclaims any responsibility for such loss or injury resulting from the use of such unauthorized components, accessories or devices.
DANGER
!
Disconnect all power to the unit before starting maintenance. Failure to do so can result in severe electrical shock or death.
DANGER
!
Page 4
4 IM 867
Figure 1: Unit Dimensions (Bottom View)
Figure 2: Unit Dimensions (Bottom View)
A0886-16
A0886-20
RETURN
AIR
SUPPLY
AIR
Page 5
IM 867
5
Figure 3: Unit Dimensions
Figure 4: Unit Dimensions – Back View
A0886-17
A0886-21
Figure 5: Component Location
A0886-33
OUTDOOR FAN #4
OUTDOOR FAN #3
OUTDOOR COIL
COMPRESSOR #4
[NOT USED ON RKNB-A180]
COMPRESSOR #3
[COMPRESSOR #2 ON RKNB-A180 MODELS]
FILTER RACK
RETURN COMPARTMENT
OUTDOOR FAN #1
OUTDOOR FAN #2
146.094
42.750
18.443
5.876
20.000
4.483
7.220
47.221
50.000
13.344
SUPPLY COVER
RETURN COVER
COMPRESSOR ACCESS
146.094
58.836
4.610
19.594
24.319
25.869
6.230
46.185
OUTDOOR FANS
3.815
REMOVE COVER PLATE WHEN CONVERTING FROM DOWN FLOW TO HORIZONTAL CONFIGURATION.
13.719
6.843
3.730
OPTIONAL OUTDOOR AIR HOOD LOCATION
OPTIONAL EXHAUST
HOOD LOCATION
Page 6
6 IM 867
Figure 6: Unit Dimensions & Component Access – Front View
A0886-18
Figure 7: Unit Dimensions & Component Access
A0886-19
Figure 8: Internal Component Locations
A0886-32
HIGH/LOW CIRCUIT #3
HIGH/LOW CIRCUIT #1
50.000
8.018
5.625
33.250
46.904
146.094
SINGLE POWER ENTRY
CONDENSATE DRAIN
HIGH/LOW CIRCUIT #2
HIGH/LOW CIRCUIT #4
HIGH PRESSURE SWITCH
CRKT #3
HIGH PRESSURE SWITCH
CRKT #4
HIGH PRESSURE SWITCH
CRKT #1
HIGH PRESSURE SWITCH
CRKT #2
144.750
57.438
50.000
5.625
33.250
CONTROL POWER ENTRY
SINGLE POWER ENTRY
ELECTRIC HEAT ACCESS
BLOWER ACCESS
COMPRESSOR ACCESS
CONDENSATE DRAIN 1” FNPT
CONTROL/FILTER ACCESS
OUTDOOR FANS
OUTDOOR FAN #4
OUTDOOR FAN #3
OUTDOOR FAN #2
OUTDOOR FAN #1
INDOOR COIL
OUTDOOR COIL
COMPRESSOR #2 [NOT ON RLNB-A180 MODELS
COMPRESSOR #1
INDOOR MOTOR
BLOWERS
FILTER OPENING
CONTROL COMPARTMENT
OPTIONAL ELECTRIC HEAT COMPARTMENT
Page 7
IM 867
7
NOTES:
1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner Equipment certification program, which is based on ARI Standard 210/240 or 360.
2. EER and/or SEER are rated at ARI conditions a
nd in accordance with DOE test procedures.
3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80° F ambient, 80° F entering dry bulb, and 67° F entering wet bulb at ARI rated cfm.
4. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270.
[ ] Designates Metric Conversions
General Data
NOM. SIZES 15 & 20 TONS [52.8-70.3 kW] ASHRAE 90.1-2004 COMPLIANT MODELS
McQuay MPS Series 015AYCL 015AYCM 015AYDL 015AYDM Cooling Performance
Gross Cooling Capacity Btu [kW] 188,000 [55.08] 188,000 [55.08] 188,000 [55.08] 188,000 [55.08] EER/SEER Nominal CFM/ARI Rated CFM [L/s] 6000/6000 [2831/2831] 6000/6000 [2831/2831] 6000/6000 [2831/2831] 6000/6000 [2831/2831] ARI Net Cooling Capacity Btu [kW] 180,000 [52.74] 180,000 [52.74] 180,000 [52.74] 180,000 [52.74] Net Sensible Capacity Btu [kW] 134,000 [39.26] 134,000 [39.26] 134,000 [39.26] 134,000 [39.26] Net Latent Capacity Btu [kW] 46,000 [13.48] 46,000 [13.48] 46,000 [13.48] 46,000 [13.48] Integrated Part Load Value Net System Power kW 17.65 17.65 17.65 17.65
Compressor
No./Type 4/Scroll 4/Scroll 4/Scroll 4/Scroll
Outdoor Sound Rating (dB) Outdoor Coil—Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled Tube Size in. [mm] OD 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 36 [3.34] 36 [3.34] 36 [3.34] 36 [3.34] Rows / FPI [FPcm] 1 / 22 [9] 1 / 22 [9] 1 / 22 [9] 1 / 22 [9]
Indoor Coil—Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 15.75 [1.46] 15.75 [1.46] 15.75 [1.46] 15.75 [1.46] Rows / FPI [FPcm] 4 / 13 [5] 4 / 13 [5] 4 / 13 [5] 4 / 13 [5] Refrigerant Control Capillary Tubes Capillary Tubes Capillary Tubes Capillary Tubes Drain Connection No./Size in. [mm] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4]
Outdoor Fan—Type Propeller Propeller Propeller Propeller
No. Used/Diameter in. [mm] 4/24 [609.6] 4/24 [609.6] 4/24 [609.6] 4/24 [609.6] Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1 CFM [L/s] 16000 [7550] 16000 [7550] 16000 [7550] 16000 [7550] No. Motors/HP 4 at 1/3 HP 4 at 1/3 HP 4 at 1/3 HP 4 at 1/3 HP Motor RPM 1075 1075 1075 1075
Indoor Fan—Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal
No. Used/Diameter in. [mm] 2/15x15 [381x381] 2/15x15 [381x381] 2/15x15 [381x381] 2/15x15 [381x381] Drive Type/No. Speeds Belt/Variable Belt/Variable Belt/Variable Belt/Variable No. Motors 1 1 1 1 Motor HP 3 5 3 5 Motor RPM 1725 1725 1725 1725 Motor Frame Size 56 184 56 184
Filter—Type Disposable Disposable Disposable Disposable
Furnished Yes Yes Yes Yes (No.) Size Recommended in. [mm] (3)2x18x18 [51x457x457] (3)2x18x18 [51x457x457] (3)2x18x18 [51x457x457] (3)2x18x18 [51x457x457]
Refrigerant Charge Oz. (Sys. 1/Sys. 2) [g] 82/72 [2325/2041] 82/72 [2325/2041] 82/72 [2325/2041] 82/72 [2325/2041] Weights
Net Weight lbs. [kg] 1677 [761] 1707 [774] 1677 [761] 1707 [774] Ship Weight lbs. [kg] 1897 [860] 1927 [874] 1897 [860] 1927 [874]
1
2
3
4
10.2/NA 10.2/NA 10.2/NA
10.4 10.4 10.4 10.4
91 91 91 91
(3)2x18x24 [51x457x610] (3)2x18x24 [51x457x610] (3)2x18x24 [51x457x610] (3)2x18x24 [51x457x610]
CONTINUED
10.2/NA
Page 8
8 IM 867
NOTES:
1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner Equipment certification program, which is based on ARI Standard 210/240 or 360.
2. EER and/or SEER are rated at ARI conditions a
nd in accordance with DOE test procedures.
3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80° F ambient, 80° F entering dry bulb, and 67° F entering wet bulb at ARI rated cfm.
4. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270.
McQuay MPS Series 015AYYL 015AYYM 020AYCL 020AYCM Cooling Performance
1
Gross Cooling Capacity Btu [kW] 188,000 [55.08] 246,000 [72.08] 246,000 [72.08] 246,000 [72.08] EER/SEER
2
10.2/NA 10.2/NA 9.7/NA Nominal CFM/ARI Rated CFM [L/s] 6000/6000 [2831/2831] 6000/6000 [2831/2831] 8000/7400 [3775/3492] 8000/7400 [3775/3492] ARI Net Cooling Capacity Btu [kW] 180,000 [52.74] 180,000 [52.74] 232,000 [67.98] 232,000 [67.98] Net Sensible Capacity Btu [kW] 134,000 [39.26] 134,000 [39.26] 168,000 [49.22] 168,000 [49.22]
Net System Power kW 17.65 17.65 23.92 23.92
Net Weight lbs. [kg] 1677 [761] 1707 [774] 1843 [836] 1864 [846]
Integrated Part Load Value
3
10.4 10.4 9.9 9.9
Compressor
No./Type 4/Scroll 4/Scroll 4/Scroll 4/Scroll
Outdoor Sound Rating (dB)
4
91 91 91 91
Outdoor Coil—Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled Tube Size in. [mm] OD 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 36 [3.34] 36 [3.34] 36 [3.34] 36 [3.34] Rows / FPI [FPcm] 1 / 22 [9] 1 / 22 [9] 2 / 22 [9] 2 / 22 [9]
Net Latent Capacity Btu [kW] 46,000 [13.48] 46,000 [13.48] 64,000 [18.75] 64,000 [18.75]
Indoor Coil—Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 15.75 [1.46] 15.75 [1.46] 15.75 [1.46] 15.75 [1.46] Rows / FPI [FPcm] 4 / 13 [5] 4 / 13 [5] 4 / 13 [5] 4 / 13 [5] Refrigerant Control Capillary Tubes Capillary Tubes Capillary Tubes Capillary Tubes Drain Connection No./Size in. [mm] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4]
Outdoor Fan—Type Propeller Propeller Propeller Propeller
No. Used/Diameter in. [mm] 4/24 [609.6] 4/24 [609.6] 4/24 [609.6] 4/24 [609.6] Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1 CFM [L/s] 16000 [7550] 16000 [7550] 16000 [7550] 16000 [7550] No. Motors/HP 4 at 1/3 HP 4 at 1/3 HP 4 at 1/3 HP 4 at 1/3 HP Motor RPM 1075 1075 1075 1075
Indoor Fan—Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal
No. Used/Diameter in. [mm] 2/15x15 [381x381] 2/15x15 [381x381] 2/15x15 [381x381] 2/15x15 [381x381] Drive Type/No. Speeds Belt/Variable Belt/Variable Belt/Variable Belt/Variable No. Motors 1 1 1 1 Motor HP 3 5 5 7.5 Motor RPM 1725 1725 1725 1725 Motor Frame Size 56 184 184 0
Filter—Type Disposable Disposable Disposable Disposable
Furnished Yes Ye s Yes Yes (No.) Size Recommended in. [mm] (3)2x18x18 [51x457x457] (3)2x18x18 [51x457x457] (3)2x18x18 [51x457x457] (3)2x18x18 [51x457x457]
Refrigerant Charge Oz. (Sys. 1/Sys. 2) [g] 82/72 [2325/2041] 82/72 [2325/2041] 117/107 [3317/3033] 117/107 [3317/3033] Weights
Ship Weight lbs. [kg] 1897 [860] 1927 [874] 2063 [936] 2084 [945]
9.7/NA
(3)2x18x24 [51x457x610] (3)2x18x24 [51x457x610] (3)2x18x24 [51x457x610] (3)2x18x24 [51x457x610]
CONTINUED
[ ] Designates Metric Conversions
General Data
NOM. SIZES 15 & 20 TONS [52.8-70.3 kW] ASHRAE 90.1-2004 COMPLIANT MODELS
Page 9
IM 867
9
NOTES:
1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner Equipment certification program, which is based on ARI Standard 210/240 or 360.
2. EER and/or SEER are rated at ARI conditions a
nd in accordance with DOE test procedures.
3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80° F ambient, 80° F entering dry bulb, and 67° F entering wet bulb at ARI rated cfm.
4. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270.
[ ] Designates Metric Conversions
General Data
NOM. SIZES 15 & 20 TONS [52.8-70.3 kW] ASHRAE 90.1-2004 COMPLIANT MODELS
McQuay MPS Series 020AYDL 020AYDM 020AYYL 020AYYM Cooling Performance
Gross Cooling Capacity Btu [kW] 246,000 [72.08] 246,000 [72.08] 246,000 [72.08] 246,000 [72.08] EER/SEER Nominal CFM/ARI Rated CFM [L/s] 8000/7400 [3775/3492] 8000/7400 [3775/3492] 8000/7400 [3775/3492] 8000/7400 [3775/3492] ARI Net Cooling Capacity Btu [kW] 232,000 [67.98] 232,000 [67.98] 232,000 [67.98] 232,000 [67.98] Net Sensible Capacity Btu [kW] 168,000 [49.22] 168,000 [49.22] 168,000 [49.22] 168,000 [49.22] Net Latent Capacity Btu [kW] 64,000 [18.75] 64,000 [18.75] 64,000 [18.75] 64,000 [18.75] Integrated Part Load Value Net System Power kW 23.92 23.92 23.92 23.92
Compressor
No./Type 4/Scroll 4/Scroll 4/Scroll 4/Scroll
Outdoor Sound Rating (dB) Outdoor Coil—Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled Tube Size in. [mm] OD 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 36 [3.34] 36 [3.34] 36 [3.34] 36 [3.34] Rows / FPI [FPcm] 2 / 22 [9] 2 / 22 [9] 2 / 22 [9] 2 / 22 [9]
Indoor Coil—Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 15.75 [1.46] 15.75 [1.46] 15.75 [1.46] 15.75 [1.46] Rows / FPI [FPcm] 4 / 13 [5] 4 / 13 [5] 4 / 13 [5] 4 / 13 [5] Refrigerant Control Capillary Tubes Capillary Tubes Capillary Tubes Capillary Tubes Drain Connection No./Size in. [mm] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4]
Outdoor Fan—Type Propeller Propeller Propeller Propeller
No. Used/Diameter in. [mm] 4/24 [609.6] 4/24 [609.6] 4/24 [609.6] 4/24 [609.6] Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1 CFM [L/s] 16000 [7550] 16000 [7550] 16000 [7550] 16000 [7550] No. Motors/HP 4 at 1/3 HP 4 at 1/3 HP 4 at 1/3 HP 4 at 1/3 HP Motor RPM 1075 1075 1075 1075
Indoor Fan—Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal
No. Used/Diameter in. [mm] 2/15x15 [381x381] 2/15x15 [381x381] 2/15x15 [381x381] 2/15x15 [381x381] Drive Type/No. Speeds Belt/Variable Belt/Variable Belt/Variable Belt/Variable No. Motors 1 1 1 1 Motor HP 5 7.5 5 7.5 Motor RPM 1725 1725 1725 1725 Motor Frame Size 184 0 184 0
Filter—Type Disposable Disposable Disposable Disposable
Furnished Yes Ye s Yes Yes (No.) Size Recommended in. [mm] (3)2x18x18 [51x457x457] (3)2x18x18 [51x457x457] (3)2x18x18 [51x457x457] (3)2x18x18 [51x457x457]
Refrigerant Charge Oz. (Sys. 1/Sys. 2) [g] 117/107 [3317/3033] 117/107 [3317/3033] 117/107 [3317/3033] 117/107 [3317/3033] Weights
Net Weight lbs. [kg] 1843 [836] 1864 [846] 1843 [836] 1864 [846] Ship Weight lbs. [kg] 2063 [936] 2084 [945] 2063 [936] 2084 [945]
1
2
3
4
9.7/NA 9.7/NA 9.7/NA
9.9 9.9 9.9 9.9
91 91 91 91
(3)2x18x24 [51x457x610] (3)2x18x24 [51x457x610] (3)2x18x24 [51x457x610] (3)2x18x24 [51x457x610]
9.7/NA
Page 10
10 IM 867
ELECTRICAL DATA
ELECTRICAL DATA
Minimum Circuit Ampacity 74/74
Unit Information
Unit Operating Voltage Range
187-253
Minimum Overcurrent Protection Device Size
80/80
Maximum Overcurrent Protection Device Size
80/80
Compressor Motor
No. 4
Volts 200/240
Phase 3
HP 3 1/3
RPM 3450 Amps (RLA) 12.4/12.4 Amps (LRA) 88/88
Condenser Motor
No. 4
Volts 208/230
Phase 1
HP 1/3 Amps (FLA) 9.6 Amps (LRA) 4.7
Evaporator Fan
No. 1
Volts 208/230
Phase 3
HP 3 Amps (FLA) 11.5 Amps (LRA) 74.5 82.6
14.7
5
3
208/230
1
4.7
9.6
1/3
1
208/230
4
88/88
12.4/12.4
3450
3 1/3
3
200/240
4
90/90
90/90
78/78
187-253
38.1
7
3
3
460
1
2.4
8
1/3
1
460
4
44
6.4
3450
3 1/2
3
460
4
45
45
43
414-506
41.3
10
5
3
460
1
2.4
8
1/3
1
460
4
44
6.4
3450
3 1/2
3
460
4
50
50
47
414-506
20
8
3
3
575
1
1.5
4
1/3
1
575
4
34
5
3450
3 1/2
3
575
4
40
40
34
518-632
33
8
5
3
575
1
1.5
4
1/3
1
575
4
34
5
3450
3 1/2
3
575
4
40
40
34
518-632
015AYCL 015AYCM 015AYDL 015AYDM 015AYYL 015AYYM
1. Horsepower Per Compressor.
2. Amp Draw Per Motor. Multiply Value By Number of Motors to Determine Total Amps.
Table A1
ELECTRICAL DATA
Minimum Circuit Ampacity 99/99
Unit Information
Unit Operating Voltage Range
187-253
Minimum Overcurrent Protection Device Size
110/110
Maximum Overcurrent Protection Device Size
110/110
Compressor Motor
No. 4
Volts 200/240
Phase 3
HP 3 1/3
RPM 3450 Amps (RLA) 17.5/17.5 Amps (LRA) 123/123
Condenser Motor
No. 4
Volts 208/230
Phase 1
HP 1/3 Amps (FLA) 9.6 Amps (LRA) 4.7
Evaporator Fan
No. 1
Volts 208/230
Phase 3
HP 5 Amps (FLA) 14.7 Amps (LRA) 82.6 136
22.3
7.5
3
208/230
1
4.7
9.6
1/3
1
208/230
4
123/123
17.5/17.5
3450
3 1/3
3
200/240
4
125/125
100/100
108/108
187-253
41.3
10
5
3
460
1
2.4
8
1/3
1
460
4
62
9
3450
3 1/2
3
460
4
60
60
57
414-506
68
11.2
7.5
3
460
1
2.4
8
1/3
1
460
4
62
9
3450
3 1/2
3
460
4
60
60
58
414-506
33
8
5
3
575
1
1.5
4
1/3
1
575
4
50
7.1
3450
4
3
575
4
50
50
43
518-632
53.8
8.8
7.5
3
575
1
1.5
4
1/3
1
575
4
50
7.1
3450
4
3
575
4
50
50
44
518-632
020AYCL 020AYCM 020AYDL 020AYDM 020AYYL 020AYYM
1. Horsepower Per Compressor.
2. Amp Draw Per Motor. Multiply Value By Number of Motors to Determine Total Amps.
Table A2
Page 11
IM 867
11
Installation
General
1 PRE-INSTALLATION CHECK-POINTS
Before attempting any installation, the following points should be carefully considered:
a Structural strength of supporting members.
(rooftop installation)
b Clearances and provision for servicing.
c Power supply and wiring.
d Air duct connections.
e Drain facilities and connections.
f Location for minimum noise.
2 LOCATION
These units are designed for outdoor installations. They can be mounted on a slab or rooftop. They are not to be installed within any part of a structure such as an attic, crawl space, closet, or any other place where condenser air flow is restricted or other than outdoor ambient condi­tions prevail. Since the application of the units is of the outdoor type, it is important to consult your local code authorities at the time the first installation is made.
Outside Slab Installation
(Typical outdoor slab installations are shown in Figures 9 and
10.)
1 Select a location where external water drainage cannot
collect around the unit.
2 Provide a level concrete slab extending 3" beyond all
four sides of the unit. The slab should be sufficient above grade to prevent ground water from entering the unit.
IMPORTANT: To prevent transmission of noise or vibration,
slab should not be connected to building structure.
3 The location of the unit should be such as to provide
proper access for inspection and servicing.
4 Locate unit where operating sounds will not disturb
owner or neighbors.
5 Locate unit so roof runoff water does not pour directly on
the unit. Provide gutter or other shielding at roof level. Do not locate unit in an area where excessive snow drift­ing may occur or accumulate.
Clearances
The following minimum clearances must be observed for proper unit performance and serviceability.
1 Provide 48" minimum clearance at the front of the unit.
Provide 18" minimum clearance at all other sides of the unit.
2 Provide 60" minimum clearance between top of unit and
maximum 3 foot overhang.
3 Unit is design certified for application on combustible
flooring with 0" minimum clearance.
4 See Figure 9 for illustration of minimum installation-
service clearances.
Rooftop Installation
1 Before locating the unit on the roof, make sure that the
strength of the roof and beams is adequate at that point to support the weight involved. This is very important and user’s responsibility.
Figure 9: Outside Slab Installation, Basement or Crawl Space Distribution System
A0886-22
A0886-23
Figure 10: Outside Slab Installation, Closet Distribution System. Slab Floor Construction
Page 12
12 IM 867
2 For rigging and roofcurb details, see Figures 11 and 12.
Use field-furnished spreaders.
3 For roofcurb assembly, see Roofcurb Installation Instruc-
tions.
4 If the roofcurb is not used, provisions for disposing of
condensate water runoff must be provided.
5 The unit should be placed on a solid and level roofcurb
or platform of adequate strength. See Figure 13.
6 The location of the unit on the roof should be such as to
provide proper access for inspection and servicing.
IMPORTANT: If unit will not be put into service immediately, cover supply and return openings to prevent excessive conden­sation.
Figure 11: Rigging for Liftiing
A0888-02
A0888-02
Figure 12: Roofcurb Installation
ST-A0886-12
CENTER OF
GRAVITY
CENTER OF
GRAVITY
32.9
835.6 mm
67.1
1704.3 mm
Page 13
IM 867
13
Ductwork
Ductwork should be fabricated by the installing contractor in accordance with local codes and NFPA90A. Industry manuals may be used as a guide when sizing and designing the duct system - contact Air Conditioning Contractors of America, 1513 16th St. N.W., Washington, D.C. 20036.
The unit should be placed as close to the space to be air con­ditioned as possible allowing clearance dimensions as indicat­ed. Ducts should be run as directly as possible to supply and return outlets. Use of non-flammable waterproof flexible con­nectors on both supply and return connections at the unit to reduce noise transmission is recommended. It is preferable to install the unit on the roof of the structure if the registers or diffusers are located on the wall or in the ceil­ing. A slab installation could be considered when the registers are low on a wall or in the floor.
On ductwork exposed to outside air conditions of temperature and humidity, use a minimum of 2" of insulation and a vapor barrier. Distribution system in attic, furred space or crawl space should be insulated with at least 2" of insulation with vapor barrier. One-half to 1" thickness of insulation is usually sufficient for ductwork inside the air conditioned space.
Balancing dampers should be provided for each branch duct in the supply system. Ductwork should be properly supported from the structure.
When installing ductwork, consider the following items:
1 Noncombustible flexible connectors should be used
between ductwork and unit to reduce noise and vibration transmission into the ductwork.
2 When auxiliary heaters are installed, use noncombustible
flexible connectors and clearance to combustible material of 0" for the first 3 feet of discharge duct. Clearance to unit top and side is 0".
Filters
This unit is provided with 3 - 18" x 18" x 2" and 3 - 18" x 24" x 2" disposable filters. When replacing filters, ensure they are inserted fully to the back to prevent bypass. See Figure 8.
Recommended supplier of this filter is:
AAF International Part #: 54-42541-01 (18” x 18” x 2”)
Part #: 54-42541-03 (18” x 24” x 2”)
Horizontal Conversion Procedure
Downflow to Horizontal
1 Remove the screws and covers from the outside of the
supply and return sections. Also remove and discard cover plate. See Figure 3.
2 Install the covers over the bottom supply and return
openings, painted side up, inserting the leading flange under the bracket provided. Place the back flange to top of the front bracket provided. See Figure 14.
3 Secure the return and supply cover to front bracket with
two (2) screws.
Condensate Drain
The condensate drain connection of the evaporator is 1" nom­inal male pipe thread. IMPORTANT: Install a condensate trap to
ensure proper condensate drainage. See Figure 15.
Figure 13: Flat rooftop installation, attic or drop ceiling distribution system. Mounted on roofcurb. Curb must be level.
Figure 14: Cover Gasket Detail
A0886-24
Page 14
14 IM 867
Electrical Wiring
Field wiring must comply with the National Electrical Code* and local ordinances that may apply.
*C.E.C. in Canada
Power Wiring
1 This unit incorporates single-point electrical connections
for the unit and electric heat accessory.
2 It is important that proper electrical power is available to
the unit. Voltage should not vary more than 10% from the values marked on the unit rating plate. Phase voltages must be balanced within 3%.
3 For branch circuit wiring (main power supply to unit dis-
connect), the minimum wire size can be determined from Table B using the circuit ampacity found on the unit nameplate or from Tables A and G.
4 The branch circuit wire must be sized in accordance with
the National Electrical Code (C.E.C. in Canada) and local ordinances that may apply using the minimum cir­cuit ampacity found on the unit rating plate.
5 Field-installed power wiring must be run through ground-
ed rain-tight conduit attached to the unit power entry panel and connected as follows:
Units Without Electric Heat - Connect power wiring to the power terminal block located on the left side of the electric heat compartment. Connect the ground wire to the adjacent ground lug.
Units with Factory Installed Electric Heat - Connect power wiring to the power terminal block located on the
electric heater kit. Connect the ground wire to the adja­cent ground lug. DO NOT connect aluminum wiring directly to the electric heater terminal block. Wiring to the unit contactors is factory-connected.
6 For field installation of an electric heater kit, follow the
instructions below. Refer to the information supplied with the kit.
a Removing screws as required, open heater access door
and detach adjacent power entry panel.
b Remove unit contactor wires (1L1, 1L2, 1L3) from
unit terminal block on the left side of the electric heat compartment. Remove and discard the terminal block and the adjacent ground lug.
c Remove the heater kit block-off panel and install the
heater kit in its place using the screws previously removed.
d Connect the unit contactor wires (1L1, 1L2, 1L3) to
the compressor fuse block on the heater kit.
e Re-install the power entry panel & run conduit and the
proper size field wiring through the opening in the panel.
f Connect field wiring to the power terminal block
located on the electric heater kit. Connect ground wire to the adjacent ground lug.
g Connect heater kit control plug to the receptacle on the
control wiring harness.
h Close heater access door and secure with screws previ-
ously removed.
Control Wiring (Class II)
1 Low voltage wiring should not be run in conduit with
power wiring.
2 Control wiring is routed through the 7/8" hole in the
unit side panel. See Figure 7. Use a minimum #18 AWG thermostat wire. For wire lengths exceeding 50', use #16 AWG thermostat wire. Connect the control wiring to the low voltage terminal block located below the unit control box.
3 It is necessary that only approved thermostats be used.
Please contact your McQuay Representative.
4 Figure 18 shows representative low voltage connection
diagrams. Read your thermostat installation instructions for any special requirements for your specific thermo­stat.
Figure 15: Condensate Drain
TABLE B: COPPER WIRE SIZE — AWG (1% VOLTAGE DROP)
300 250 200 150 100
50
Supply
Wire
Length
Feet
4 4 6
8
10 14
15
3
4 4 6
8
12
20
2
3
4 6
8
10
25
2
3
4 4 6
10
30
1 2
3
4 6
8
35
1/0
1 2 4 6
8
40
1/0
1 2
3
4 6
45
2/0 1/0
1
3
4 6
50
2/0 1/0
1 2 4 6
55
3/0 2/0 1/0
2
3
4
60
3/0 2/0 1/0
1
3
4
65
3/0 2/0 1/0
1 2 4
70
4/0 3/0 2/0 1/0
2
3
75
4/0 3/0 2/0 1/0
2
3
80
4/0 3/0 2/0 1/0
1
3
85
4/0 4/0 3/0 1/0
1 2
90
250 4/0 3/0 2/0
1 2
95
250 4/0 3/0 2/0
1 2
100
250
4/0 3/0 2/0
1 2
105
250
4/0 3/0 2/0 1/0
2
110
300 250
4/0 2/0 1/0
1
115
300 250
4/0 3/0 1/0
1
120
300 250
4/0 3/0 1/0
1
125
Circuit Ampacity
NOTE:
1. Wire size based on 60ºC type copper conductors below 100 ampacity. 2. Wire size based on 75ºC type copper conductors for 100 ampacity and above.
Page 15
IM 867
15
NOTE: Units installed in Canada require that an outdoor thermostat (30,000 min. cycles of endurance) be installed and be wired with C.E.C. Class I wiring.
Internal Wiring
1 A diagram of the internal wiring of this unit is located on
the inside of the electrical access panel. If any of the original wire, as supplied with the unit must be replaced, the wire gauge and insulation must be the same as origi­nal wiring.
208 Volt Applications
Transformer is factory-wired for 220 volts on 200/220 volt models and must be changed for 200-volt applications. See unit wiring diagram for 200-volt wiring.
Grounding
GROUNDING MAY ALSO BE ACCOMPLISHED BY GROUNDING THE POWER LINE CONDUIT TO THE UNIT. MAKE SURE THE CONDUIT NUT LOCKING TEETH HAVE PIERCED THE INSULATING PAINT FILM OF THE SIDE PANEL.
Thermostat
The thermostat should be mounted on an inside wall about five feet above the floor in a location where it will not be affected by unconditioned air, sun, or drafts from open doors or other sources. The low voltage wiring should be sized as shown in Table B.
Install the room thermostat in accordance with the instruction sheet packed in the box with the thermostat.
Indoor Air Flow Data
Belt-drive blower models have motor sheaves set for proper CFM at a typical external static. See Tables D and E for blower performance.
The unit must be permanently grounded. A grounding lug is provided in the electric heat access area for a ground wire. Failure to ground this unit can result in fire or electrical shock causing property damage, severe personal injury or death.
DANGER
!
Figure 16: Branch Circuit Disconnect Location Table C
FIELD WIRE SIZE FOR 24 VOLT THERMOSTAT CIRCUITS
SOLID COPPER WIRE - AWG.
3.0 16 14 12 10 10 10
2.5 16 14 12 12 12 10
2.0 18 16 14 12 12 10
50 100 150 200 250 300
Length of Run – Feet (1)
Thermostat Load -
Amps
(1) The total wire length is the distance from the furnace to the thermo­stat and back to the furnace.
NOTE: DO NOT USE CONTROL WIRING SMALLER THAN NO. 18 AWG.
A0886-34
Figure 17: Low Voltage Connection Entries
A0886-32
Figure 18: Electric Heat Compartment
Page 16
16 IM 867
E.S.P. - Inches of Water
15 TON PACKAGE UNIT - 60 Hz
———
637
653
669
685
701
717
733
749
765
———
1494
1738
1981
2224
2468
2711
2955
3198
3442
TABLE D: AIR-FLOW PERFORMANCE – 15 TON MODELS
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3
1.4
1.5 1.6 1.7 1.8 1.9 2.0
STD
CFM
RPM RPM
WATTS WATTS
RPM
WATTS
RPM RPM
WATTS WATTS
RPM
WATTS
RPM
WATTS
RPM RPM
WATTS WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM RPM
WATTS WATTS
RPM RPM RPM RPM
WATTS WATTS WATTS WATTS
4800
5000
5200
5400
5600
5800
6000
6200
6400
6600
6800
7000
7200
———
640
656
672
688
704
720
736
752
768
784
———
1394
1638
1881
2125
2368
2611
2855
3098
3342
3585
644
660
676
692
708
724
740
756
772
788
804
1294
1538
1781
2025
2268
2512
2755
2998
3242
3485
3729
631
647
663
679
695
711
727
743
759
775
791
807
877
951
1194
1438
1681
1925
2168
2412
2655
2899
3142
3385
3629
3821
650
666
682
698
714
731
747
763
779
795
811
881
890
1095
1338
1581
1825
2068
2312
2555
2799
3042
3286
3529
3695
4000
670
686
702
718
734
750
766
782
798
814
885
894
903
1238
1482
1725
1968
2212
2455
2699
2942
3186
3429
3569
3874
4179
689
705
721
737
753
769
785
801
817
889
898
907
916
1382
1625
1869
2112
2355
2599
2842
3086
3329
3442
3748
4053
4358
709
725
741
757
773
789
805
821
893
920
911
902
929
1525
1769
2012
2256
2499
2742
2986
3229
3316
3622
3927
4232
4538
728
744
760
776
792
808
888
897
906
915
924
933
942
1669
1912
2156
2399
2643
2886
2885
3190
3495
3801
4106
4411
4717
747
764
780
796
812
892
901
910
919
928
9
37
946
955
1812
2056
2299
2543
2786
2759
3064
3369
3675
3980
4285
4591
4896
767
783
799
815
896
905
914
923
932
941
950
959
968
1956
2199
2443
2686
2632
2938
3243
3548
3854
4159
4464
4770
5075
786
802
818
900
909
918
927
936
945
954
963
972
2100
2343
2586
2506
2812
3117
3422
3727
4033
4338
4643
4949
806
822
904
913
922
931
940
949
958
967
9
76
2243
2487
2380
2685
2991
3296
3601
3907
4212
4517
4823
899
908
917
926
935
944
953
962
971
980
989
1949
2254
2559
2864
3170
3475
3780
4086
4391
4696
5002
912
921
929
936
947
956
965
974
983
992
———
2128
2433
2738
3044
3349
3654
3960
4265
4570
4876
———
924
933
942
951
960
969
978
987
996
1005
———
2307
2612
2917
3223
3528
3833
4139
4444
4749
5055
———
937
946
955
964
973
982
991
1000
1009
———
950
959
968
977
986
995
1004
1013
—————
963
972
981
990
999
1008
1017
—————
976
985
994
1003
1012
1021
———————
2486
2791
3097
3402
3707
4012
4318
4623
4928
———
2665
2970
3276
3581
3886
4192
4497
4802
—————
2844
3149
3455
3760
4065
4371
4876
—————
3023
3329
3634
3939
4245
4550
———————
DRIVE PACKAGE L
3.0 BK-90
1VP-44
123 456
823 787
750
710 670 629
MOTOR HP
BLOWER SHEAVE
MOTOR SHEAVE
TURNS OPEN
RPM
NOTES: 1. Factory sheave settings shown in bold type.
2. Do not set sheave below minimum turns open shown.
3. Re-adjustment of sheave required to achieve rated airflow at ARI minimum E.S.P.
4. Drive data shown is for horizontal airflow with dry coil. Add component resistance
to duct resistance to determine total E.S.P.
DRIVE PACKAGE M
5
BK-72
1VP-44
1.5 2 3
4
56
1022 1017 1006 933 860 786
MOTOR HP
BLOWER SHEAVE
MOTOR SHEAVE
TURNS OPEN
RPM
COMPONENT RESISTANCE TABLE
CFM WET COIL DOWNFLOW
4800 0.020 0.010
5200 0.040 0.020
5600 0.060 0.030
6000 0.080 0.040
6400 0.100 0.050
6800 0.125 0.060
7200 0.150 0.070
Page 17
IM 867
17
TABLE E: AIR-FLOW DATA 20 TON MODELS
701
717
733
749
765
781
797
813
829
845
861
877
911
920
929
938
947
2468
2711
2955
3198
3442
3685
3929
4172
4415
4659
4902
5146
5726
6032
6337
6642
6948
E.S.P. - Inches of Water
20 TON PACKAGE UNIT - 60 Hz
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3
1.4
1.5 1.6 1.7 1.8 1.9 2.0
STD
CFM
RPM RPM
WATTS WATTS
RPM
WATTS
RPM RPM
WATTS WATTS
RPM
WATTS
RPM
WATTS
RPM RPM
WATTS WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM RPM
WATTS WATTS
RPM RPM RPM RPM
WATTS WATTS WATTS WATTS
6400
6600
6800
7000
7200
7400
7600
7800
8000
8200
8400
8600
8800
9000
9200
9400
9600
720
736
752
768
784
801
817
833
849
865
881
915
924
933
942
951
960
2611
2855
3098
3342
3585
3829
4072
4316
4559
4802
5046
5600
5905
6211
6516
6821
7127
740
756
772
788
804
820
836
852
868
910
919
928
936
945
954
963
972
2755
2998
3242
3485
3729
3972
4216
4459
4703
5169
5474
5779
6084
6390
6695
7000
7306
759
775
791
807
823
839
855
871
913
922
931
940
949
958
967
976
9
85
2899
3142
3385
3629
3872
4116
4359
4603
5042
5348
5653
5958
6264
6569
6874
7180
779
795
811
827
843
859
875
917
926
935
944
953
962
971
980
989
3042
3286
3529
3772
4016
4259
4503
4916
5221
5527
5832
6137
6443
6748
7053
7359
798
814
830
846
862
878
921
930
939
948
957
966
975
984
993
3186
3429
3673
3916
4160
4403
4790
5095
5401
5706
6011
6317
6622
6927
7233
817
834
850
866
882
925
934
943
952
961
970
979
988
997
1006
3329
3573
3816
4060
4303
4664
4696
5274
5580
5885
6190
6496
6801
7106
7412
837
853
869
920
929
938
947
956
965
974
983
992
1001
1010
———
3473
3716
3960
4232
4538
4843
5148
5454
5759
6064
6369
6675
6980
7285
———
856
872
924
933
942
951
960
969
978
987
996
1005
1014
———
3616
3860
4106
4411
4717
5022
5327
5633
5938
6243
6549
6854
7159
———
876
928
937
946
955
964
973
982
991
1000
1009
1018
1027
———
3760
3980
4285
4591
4896
5201
5506
5812
6117
6422
6728
7033
7338
———
932
941
950
959
968
977
986
995
1004
1013
1022
1031
—————
3854
4159
4464
4770
5075
5380
5686
5991
6296
6602
6907
7212
—————
945
954
963
972
981
990
999
1008
1017
1026
1035
1044
—————
4033
4338
4643
4949
5254
5559
5865
6170
6475
6781
7086
7391
—————
958
967
976
985
994
1003
1012
1021
1030
1039
1048
—————
4212
4517
4823
5128
5433
5739
6044
6349
6655
6960
7265
—————
971
980
989
998
1007
1015
1024
1033
1042
1051
———————
4391
4696
5002
5307
5612
5918
6223
6528
6834
7139
———————
983
992
1001
1010
1019
1028
1037
1046
1055
1064
———————
4570
4876
5181
5486
5791
6097
6402
6707
7013
7318
———————
996
1005
1014
1023
1032
1041
1050
1059
1068
———————
4749
5055
5360
5665
5971
6276
6581
6887
7192
———————
1009
1018
1027
1036
1045
1054
1063
1072
1081
———————
1022
1031
1040
1049
1058
1067
1076
1085
—————————
1035
1044
1053
1062
1071
1080
1089
1098
—————————
1048
1057
1066
1075
1084
1093
1102
—————————
4928
5234
5539
5844
6150
6455
6760
7066
7371
———————
5108
5413
5718
6024
6329
6634
6940
7245
———————
5287
5592
5897
6203
6508
6813
7119
7424
—————————
5466
5771
6076
6382
6687
6992
7298
—————————
DRIVE PACKAGE L
5.0 BK-95
1VP-50
1
2 3 456
882
846 810 773 736 700
MOTOR HP
BLOWER SHEAVE
MOTOR SHEAVE
TURNS OPEN
RPM
NOTES: 1. Factory sheave settings shown in bold type.
2. Do not set sheave below minimum turns open shown.
3. Re-adjustment of sheave required to achieve rated airflow at ARI minimum E.S.P.
4. Drive data shown is for horizontal airflow with dry coil. Add component resistance
to duct resistance to determine total E.S.P.
DRIVE PACKAGE M
7.5 BK-90
1VP-60
123
4
56
1102 1075 1047 1006 964 922
MOTOR HP
BLOWER SHEAVE
MOTOR SHEAVE
TURNS OPEN
RPM
COMPONENT RESISTANCE TABLE
CFM WET COIL DOWNFLOW
6400 0.100 0.030
6800 0.125 0.043
7200 0.150 0.055
7600 0.175 0.068
8000 0.200 0.080
8400 0.225 0.093
8800 0.250 0.105
9200 0.275 0.118
9600 0.300 0.130
Page 18
18 IM 867
Pre-Start Check
1 Is unit properly located and slightly slanted toward
indoor condensate drain?
2 Is ductwork insulated, weatherproofed, with proper spac-
ing to combustible materials?
3 Is air free to travel to and from outdoor coil? (See Figure
5.)
4 Is the wiring correct, tight, and according to unit wiring
diagram?
5 Is unit grounded?
6 Are field supplied air filters in place and clean?
7 Do the outdoor fan and indoor blower turn freely without
rubbing, and are they tight on the motor shafts?
Startup
1 Turn thermostat to “OFF,” turn “on” power supply at dis-
connect switch.
2 Turn temperature setting as high as it will go.
3 Turn fan switch to “ON.”
4 Indoor blower should run. Be sure it is running in the
right direction.
5 Turn fan switch to “AUTO.” Turn system switch to
“COOL” and turn temperature setting below room tem­perature. Unit should run in cooling mode.
6 Is outdoor fan operating correctly in the right direction?
7 Is compressor running correctly.
Record the following after the unit has run some time.
a Operating Mode
b Discharge Pressures (High) _________________PSIG c Vapor Pressure at Compressors (Low)_________PSIG d Vapor Line Temperature at Compressors ________°F. e Indoor Dry Bulb ____________________________°F. f Indoor Wet Bulb____________________________°F. g Outdoor Dry Bulb___________________________°F. h Outdoor Wet Bulb __________________________°F. i Voltage at Contactor_______________________Volts j Current at Contactors______________________Amps k Model Number _______________________________ l Serial Number ________________________________ mLocation_____________________________________ n Owner ______________________________________ o Date ________________________________________
8 Turn thermostat system switch to “HEAT.” Unit com-
pressors should stop. Raise temperature setting to above room temperature. Unit should run in heating mode and auxiliary heaters, if installed, should come on.
9 Check the refrigerant charge using the instructions locat-
ed on unit charging chart. Replace service port caps. Service port cores are for system access only and will leak if not tightly capped.
10 Adjust discharge air grilles and balance system.
11 Check ducts for condensation and air leaks.
12 Check unit for tubing and sheet metal rattles.
13 Instruct the owner on operation and maintenance.
14 Leave “INSTALLATION” and ”USE AND CARE“
instructions with owner
A0823-01
Figure 19
Page 19
IM 867
19
Operation
Cooling Mode
With thermostat in the cool mode, fan auto and the room tem­perature higher than the thermostat setting:
1 Indoor blower contactor is energized through thermostat
contact (G).
2 Compressor contactors are energized through thermostat
contacts (Y1) & (Y2) and high pressure controls.
3 Economizer enthalpy control (if installed) controls opera-
tion of first-stage cooling and positions fresh air damper to maintain mixed air temperature. Second-stage cooling operates normally as required by second stage of thermo­stats.
4 The system will continue in cooling operation as long as
all safety controls are closed, until the thermostat is satis­fied.
Heating Mode
With thermostat in the heat mode, fan auto and the room tem­perature lower than the thermostat setting the indoor blower contactor is energized through thermostat contact (G).
Auxiliary Heat
In the heating mode, the thermostat will energize one or more supplementary resistance heaters.
Replacement Parts
To find your local McQuay Certified Parts Distributor, go to www.mcquay.com and select Parts Locator.
Charge Information
Refer to the appropriate charge chart on the unit, or in this manual.
Troubleshooting
Refer to the troubleshooting chart included in this manual.
Wiring Diagrams
Refer to the appropriate wiring diagram included in this man­ual.
Only electric heater kits supplied by this manufacturer as described in this publication have been designed, tested, and evaluated by a nationally recognized safety testing agency for use with this unit. Use of any other manufactured electric heaters installed within this unit may cause haz­ardous conditions resulting in property damage, fire, bodily injury or death.
DANGER
!
Page 20
20 IM 867
Heater Kit Characteristics
Table F: Auxiliary Heater Kits Characteristics and Application (15 & 20 Ton Models)
MAX. FUSE
UNIT OR CKT. BKR.
MODEL HEATER KIT HEATER KIT UNIT MIN. CKT. SIZE (CKT. BKR.
NUMBER MODEL NO. HEATER KW FLA AMPACITY MUST BE
HACR TYPE
FOR USA)
NONE* 74/74 80/80 CD20C 14.4/19.2 40.0/46.2 74/74 80/80
015AYCL CD40C 28.8/38.4 79.9/92.4 115/130 125/150
CD60C 43.2/57.6 119.9/138.6 165/188 175/200 CD75C 54.0/72.0 149.9/173.3 202/231 225/250
NONE* 43 45 CD20D 19.2 23.1 43 45
015AYDL CD40D 38.4 46.2 67 70
CD60D 57.6 69.3 96 100 CD75D 72.0 86.6 117 125
NONE* 34 35 CD20Y 19.2 18.5 34 35
015AYYL CD40Y 38.4 37.0 57 60
CD60Y 57.6 55.4 80 80 CD75Y 72.0 69.3 97 100
NONE* 77/77 80/80 CD20C 14.4/19.2 40.0/46.2 77/77 80/80
015AYCM CD40C 28.8/38.4 79.9/92.4 119/134 125/150
CD60C 43.2/57.6 119.9/138.6 169/192 175/200 CD75C 54.0/72.0 149.9/173.2 206/235 225/250
NONE* 46 50 CD20D 19.2 23.1 46 50
015AYDM CD40D 38.4 46.2 71 80
CD60D 57.6 69.3 100 100 CD75D 72.0 86.6 121 125
NONE* 34 35 CD20Y 19.2 18.5 34 35
015AYYM CD40Y 38.4 37.0 57 60
CD60Y 57.6 55.4 80 80 CD75Y 72.0 69.3 97 100
NONE* 100/100 110/110 CD20C 14.4/19.2 40.0/46.2 100/100 110/110
020AYCL CD40C 28.8/38.4 79.9/92.4 119/134 125/150
CD60C 43.2/57.6 119.9/138.6 169/192 175/200 CD75C 54.0/72.0 149.9/173.2 206/235 225/250
NONE* 58 60 CD20D 19.2 23.1 58 60
020AYDL CD40D 38.4 46.2 71 80
CD60D 57.6 69.3 100 100 CD75D 72.0 86.6 121 125
NONE* 45 50 CD20Y 19.2 18.5 45 50
020AYYL CD40Y 38.4 37.0 57 60
CD60Y 57.6 55.4 8
0 80
CD75Y 72.0 69.3 97 100 NONE* 108/108 125/125
CD20C 14.4/19.2 40.0/46.2 108/108 125/125
020AYCM CD40C 28.8/38.4 79.9/92.4 128/144 150/150
CD60C 43.2/57.6 119.9/138.6 178/202 200/225 CD75C 54.0/72.0 149.9/173.2 216/245 225/250
NONE* 59 60 CD20D 19.2 23.1 59 60
020AYDM CD40D 38.4 46.2 72 80
CD60D 57.6 69.3 101 110 CD75D 72.0 86.6 123 125
NONE* 46 50 CD20Y 19.2 18.5 46 50
020AYYM CD40Y 38.4 37.0 58 60
CE60Y 57.6 55.4 8190 CD75Y 72.0 69.3 98 100
Page 21
IM 867
21
SYMPTOM POSSIBLE CAUSE REMEDY
Unit will not run • Power off or loose electrical connection • Check for correct voltage at compressor contactor in control
box
• Thermostat out of calibration-set too high • Reset
• Defective contactor • Check for 24 volts at contactor coil - replace if contacts are open
• Blown fuses • Replace fuses
• Transformer defective • Check wiring-replace transformer
• High pressure control open (if provided) • Reset-also see high head pressure remedy-
• Interconnecting low voltage wiring damaged • Replace thermostat wiring
Condenser fan runs, compressor • Run capacitor defective (single phase only) • Replace
doesn’t • Loose connection • Check for correct voltage at compressor -
check & tighten all connections
• Compressor stuck, grounded or open motor winding • Wait at least 2 hours for overload to reset.
open internal overload. If still open, replace the compressor.
• Low voltage condition At compressor terminals, voltage must be within 10% of rating plate volts when unit is operating.
Insufficient cooling • Improperly sized unit • Recalculate load
• Improper airflow • Check - should be approximately 400 CFM per ton.
• Incorrect refrigerant charge • Charge per procedure attached to unit service panel.
• Air, non-condensibles or moisture in system • Recover refrigerant, evacuate & recharge, add filter drier
• Incorrect voltage • At compressor terminals, voltage must be within 10% of rating plate volts when unit is operating.
Compressor short cycles • Incorrect voltage • At compressor terminals, voltage must be ± 10% of
nameplate marking when unit is operating.
• Defective overload protector • Replace - check for correct voltage
• Refrigerant undercharge • Add refrigerant
Registers sweat • Low evaporator airflow • Increase speed of blower or reduce restriction - replace air
filter
High head-low vapor pressures • Restriction in liquid line, expansion device or filter drier • Remove or replace defective component
• Flow check piston size too small • Change to correct size piston
• Incorrect capillary tubes • Change coil assembly
High head-high or normal vapor • Dirty condenser coil • Clean coil
pressure - Cooling mode • Refrigerant overcharge • Correct system charge
• Condenser fan not running • Repair or replace
• Air or non-condensibles in system • Recover refrigerant, evacuate & recharge
High head-high or normal vapor • Low air flow - condenser coil • Check filters - correct to speed
pressure - Heating mode • Refrigerant overcharge • Correct system charge
• Air or non-condensibles in system • Recover refrigerant, evacuate & recharge
• Dirty condenser coil • Check filter - clean coil
Low head-high vapor pressures • Defective Compressor valves • Replace compressor
Low vapor - cool compressor - • Low evaporator airflow • Increase speed of blower or reduce restriction - replace air
iced evaporator coil filter
• Operating below 65°F outdoors • Add Low Ambient Kit
• Moisture in system • Recover refrigerant - evacuate & recharge - add filter drier
High vapor pressure • Excessive load • Recheck load calculation
• Defective compressor • Replace
Fluctuating head & vapor • Air or non-condensibles in system • Recover refrigerant, evacuate & recharge
pressures
Gurgle or pulsing noise at • Air or non-condensibles in system • Recover refrigerant, evacuate & recharge
expansion device or liquid line
TROUBLE SHOOTING CHART
Disconnect all power to unit before servicing. Contactor may break only one side. Failure to shut off power can cause electrical shock resulting in personal injury or death.
DANGER
!
Page 22
22 IM 867
Figure 20: Wiring Diagram for 15 to 20 Tons
Page 23
IM 867
23
Figure 21: Wiring Schematic for 15 to 20 Tons
Page 24
24 IM 867
15 TON
Page 25
IM 867
25
20 TON
Page 26
26 IM 867
Page 27
IM 867
27
Page 28
28 IM 867
McQuay Training and Development
© 2007 McQuay International • www.mcquay.com • 800-432-1342
Now that you have made an investment in modern, efficient McQuay equipment, its care should be a high priority. For training information on all McQuay HVAC products, please visit us at www.mcquay.com and click on training, or call 540-248-9646 and ask for the Training Department.
Warranty
All McQuay equipment is sold pursuant to its standard terms and conditions of sale, including Limited Product Warranty. Consult your local McQuay Representative for warranty details. Refer to Form 933-43285Y. To find your local McQuay Representative, go to www.mcquay.com.
This document contains the most current product information as of this printing. For the most up-to-date product information, please go to www.mcquay.com.
Loading...