McQuay MPS015AGDL25E Installation Manual

Page 1
Maverick I™ Commercial Packaged Rooftop System Heating & Cooling
Gas/Electric
Models MPS015AG - 020AG 15 to 20 Tons
Installat
ion and Maintenance Manual
Group: Applied Systems
Part Number: 92-102421-08-00
Date: March 2007
© 2007 McQuay International
ARI Standard 210/240 UAC
Page 2
2 IM 863
Table of Contents
Table of Contents. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Checking Product Received . . . . . . . . . . . . . . . . . . . . 3
Equipment Protection . . . . . . . . . . . . . . . . . . . . . . . . . 3
Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Major Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-7
General Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-12
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Location Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Outside Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Attaching Exhaust and Combustion Air Inlet Hoods . . . . . . . . . 13
Cover Panel Installation/Conversion Procedure . . . . . . . . . . . . 14
Filter Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Rooftop Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Ducting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Return Air . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Gas Supply, Condensate Drain and Piping. . . . . . . 17
Gas Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
LP Conversion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Adjusting or Checking Furnace Input. . . . . . . . . . . . . . . . . . . . . 19
Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Hook-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Internal Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
208 Volt Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Furnace Section Controls and Ignition System . . . 22
Normal Operating Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Normal Heat Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Operating Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
To Start Furnace. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
To Shut Down Furnace. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Burners. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Manual Reset Overtemperature Control . . . . . . . . . . . . . . . . . . 24
Pressure Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Limit Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Cooling Section Operation . . . . . . . . . . . . . . . . . . . . 24
Cooling Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Continuous Fan Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
System Operating Information . . . . . . . . . . . . . . . . . 25
Advise The Customer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Furnace Section Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Lubrication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Cooling Section Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . 26
To Inspect The Evaporator Coil . . . . . . . . . . . . . . . . . . . . . . . 26
Cleaning Evaporator Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Cleaning Condenser Coil, Condenser Fan,
Circulation Air Blower and Venturi . . . . . . . . . . . . . . . . . . . 26
Re-Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Replacement Parts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Wiring Diagrams. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Charging. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Air-Flow Performance Charts . . . . . . . . . . . . . . . 27-28
Electrical Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . 29-30
Trouble Shooting . . . . . . . . . . . . . . . . . . . . . . . . . 31-33
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . 34-39
Charging Charts . . . . . . . . . . . . . . . . . . . . . . . . . . 40-41
Page 3
IM 863
3
Introduction
This manual contains the installation and operating instruc­tions for your packaged rooftop system. There are a few pre­cautions that should be taken to derive maximum satisfaction from it. Improper installation can result in unsatisfactory operation or dangerous conditions.
Read this manual and any instructions packaged with separate equipment required to make up the system prior to installa­tion. Give this manual to the owner and explain its provisions. The owner should retain this manual for future reference.
Checking Product Received
This manual contains the installation and operating instruc­tions for your combination gas heating/electric cooling unit. There are some precautions that should be taken to derive maximum satisfaction from it. Improper installation can result in unsatisfactory operation or dangerous conditions.
Read this manual and any instructions packaged with separate equipment required to make up the system prior to installa­tion. Give this manual to the owner and explain its provisions. The owner should retain this manual for future reference.
Equipment Protection From The Environment
Upon receiving the unit, inspect it for any damage from ship­ment. Claims for damage, either shipping or concealed, should be filed immediately with the shipping company.
IMPORTANT: Check the unit model number, heating size, elec­trical characteristics, and accessories to determine if they are correct.
Specifications
General
The unit is available in 250,000 AND 350,000 BTUH heating input with nominal cooling capacity of 15 tons. 300,000 and 400,000 BTUH heating inputs are available in nominal cool­ing capacity of 20 tons. Units are convertible from bottom supply and return to side supply and return by relocation of supply and return air cover panels. See cover installation detail and Figures 10 &11.
The units are weatherized for mounting outside of the build­ing.
Major Components
The unit includes a hermetically-sealed refrigerating system consisting of a scroll compressor, condenser coil, evaporator coil with capillary tube assembly, a supply air fan, a condens­er fan, a heat exchanger assembly, gas burner and control assembly, combustion air motors and fan, and all necessary internal electrical wiring. The cooling system of these units is factory-evacuated, charged and performance tested. Refrigerant amount and type are indicated on rating plate.
The manufacturer’s warranty does not cover any damage or defect to the air conditioner caused by the attachment or use of any components, accessories or devices (other than those authorized by the manufacturer) into, onto or in con­junction with the air conditioner. You should be aware that the use of unauthorized components, accessories or devices may adversely affect the operation of the air condi­tioner and may also endanger life and property. The manu­facturer disclaims any responsibility for such loss or injury resulting from the use of such unauthorized components, accessories or devices.
DANGER
!
Units are not design certified to be installed inside the structure. Doing so can cause inadequate unit performance as well as property damage and carbon monoxide poison­ing resulting in personal injury or death.
DANGER
!
Page 4
4 IM 863
Safety Information
Use only with type of gas approved for this unit. Refer to the unit rating plate.
WARNING
!
Install this unit only in a location and position as specified in the location requirements and considerations section of these instructions. Provide adequate combustion and venti­lation air to the unit space as specified in the venting sec­tion of these instructions.
WARNING
!
Provide adequate combustion and ventilation air to the unit space as specified in the combustion and ventilation air section of these instructions.
WARNING
!
Combustion products must be discharged outdoors. Connect this unit to an approved vent system only, as specified in vent Pipe Installation section of these instruc­tions.
WARNING
!
Never test for gas leaks with an open flame. It can cause an explosion or fire resulting in property damage, personal injury or death. Use a commercially available soap solution made specifically for the detection of leaks to check all con­nections, as specified in the Gas Supply and Piping section of these instructions.
DANGER
!
Always install unit to operate within the unit's intended tem­perature-rise range with a duct system which has an exter­nal static pressure within the allowable range, as specified in ducting section of these instructions. See also unit rating plate.
WARNING
!
When a unit is installed so that supply ducts carry air circu­lated by the unit to areas outside the space containing the unit, the return air shall also be handled by duct(s) sealed to the unit casing and terminating outside the space con­taining the unit.
WARNING
!
This unit may be used to heat the building or structure dur­ing construction if the following installation requirements are met. installation must comply with all installation instruc­tions including:
• proper vent installation;
• furnace operating under thermostatic control;
• return air duct sealed to the furnace;
• air filters in place;
• set furnace input rate and temperature rise per rating plate marking;
• means of providing outdoor air required for combustion;
• return air temperature maintained between 55°F (13°C) and 80°F (27°C); and
• installation of exhaust and combustion air inlet hoods completed;
• clean furnace, duct work and components upon substan­tial completion of the construction process, and verify fur­nace operating conditions including ignition, input rate, temperature rise and venting according to the instruc­tions.
WARNING
!
Page 5
IM 863
5
Figure 1: Unit Dimensions - Bottom View
Figure 2: Supply and Return Dimensions for Downflow Applications - Bottom View
Unit Dimensions
FOR CLEARANCES SEE PAGE 28, FIGURE 12.
IMPORTANT: THIS UNIT MUST BE MOUNTED LEVEL IN BOTH DIRECTIONS TO ALLOW WATER TO DRAIN FROM THE CONDENSER SECTION AND CONDENSATE PAN.
ST-A0886-02
ST-A0886-07
SUPPLY
AIR
RETURN
AIR
Page 6
6 IM 863
Figure 3: Component Locations & Dimensions
ST-A0886-04
Figure 4: Component Locations & Dimensions
ST-A0886-06
Figure 5: Component Locations
ST-A0886-27
GAS SUPPLY
(SIDE ENTRY)
3/4” INLET
FILTER OPENING
BLOWERS
FURNACE
INDOOR MOTOR
COMPRESSOR #1
COMPRESSOR #2
INDOOR COIL
OUTDOOR FAN #1
OUTDOOR FAN #2
BLOWER ACCESS
FLUE HOODS
POWER ENTRY
CONDENSATE DRAIN 1” FNPT
COMBUSTION AIR INLETS
COMPRESSOR ACCESS
CONTROL/FILTER ACCESS
FURNACE ACCESS
33.250
5.625
144.750
OPTIONAL OUTDOOR AIR HOOD LOCATION
DISCONNECT
LOCATION
OPTIONAL EXHAUST
HOOD LOCATION
50.000
50.000
17.708
5.625
33.250
44.651
146.094
CONDENSATE DRAIN
HIGH/LOW CIRCUIT #1
HIGH/LOW CIRCUIT #3
HIGH/LOW CIRCUIT #2
HIGH/LOW CIRCUIT #4
HIGH PRESSURE SWITCH
CRKT #1
HIGH PRESSURE SWITCH
CRKT #3
HIGH PRESSURE SWITCH
CRKT #2
HIGH PRESSURE SWITCH
CRKT #4
57.438
OUTDOOR FAN #4
OUTDOOR FAN #3
CONTROL COMPARTMENT
DISCONNECT
LOCATION
Page 7
IM 863
7
Figure 7: Component Access Locations & Dimensions
ST-A0886-05
ST-A0886-03
Figure 8: Component Locations
ST-A0886-28
Figure 6: Dimensions – Back View
OUTDOOR FAN #4
SUPPLY COVER
RETURN COVER
COMPRESSOR ACCESS
146.094
3.815
46.185
58.836
4.610
6.843
13.719
19.594
24.319
25.869
6.230
REMOVE COVER PLATE WHEN
CONVERTING FROM DOWNFLOW
TO HORIZONTAL CONFIGURATION.
OUTDOOR FAN #3
OUTDOOR COIL
COMPRESSOR #4
COMPRESSOR #3
HEAT EXCHANGER
FILTER RACK
RETURN COMPARTMENT
OUTDOOR FAN #1
OUTDOOR FAN #2
42.750
146.094
18.443
5.876
20.000
4.483
13.344
7.220
47.221
50.000
3.730
Page 8
8 IM 863
General Data
[] Designates Metric Conversions
NOM. SIZES 15 & 20 TON S [52.8-70.3 kW] ASHRAE 90.1-2004 COMPLIANT MODELS
NOTES:
1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to
20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner Equipment
certification program, which is based on ARI Standard 210/240 or 360.
2. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures.
3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80° F ambient, 80° F entering dry bulb, and 67° F entering wet bulb a
t ARI rated cfm.
4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions
using American National Standard Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet ab
ove sea level.
5. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270.
Model MPS- 015AGCL25E 015AGCL35E 015AGCM25E 015AGCM35E Cooling Performance
1
CONTINUED
Gross Cooling Capacity Btu [kW] 188,000 [55.1] 188,000 [55.1] 188,000 [55.1] 188,000 [55.1]
2
EER/SEER
10.2/NA 10.2/NA 10.2/NA 10.2/NA Nominal CFM/ARI Rated CFM [L/s] 6000/6000 [2831/2831] 6000/6000 [2831/2831] 6000/6000 [2831/2831] 6000/6000 [2831/2831] ARI Net Cooling Capacity Btu [kW] 180,000 [52.7] 180,000 [52.7] 180,000 [52.7] 180,000 [52.7] Net Sensible Capacity Btu [kW] 134,000 [39.3] 134,000 [39.3] 134,000 [39.3] 134,000 [39.3] Net Latent Capacity Btu [kW] 46,000 [13.5] 46,000 [13.5] 46,000 [13.5] 46,000 [13.5] Integrated Part Load Value
3
10.4 10.4 10.4 10.4
Net System Power kW 17.6 17.6 17.6 17.6
Heating Performance (Package Gas/Electric)
4
Heating Input Btu [kW] (1st Stage /2nd Stage) 125,000/250,000 175,000/350,000 125,000/250,000 175,000/350,000 Heating Output Btu [kW] (1st Stage /2nd Stage) 101,500/203,000 142,000/284,000 [41.6/83.2] 101,500/203,000 142,000/284,000 [41.6/83.2] Temperature Rise Range °F [°C] 15-45 [8.3/25] 30-60 [16.7/33.3] 15-45 [8.3/25] 30-60 [16.7/33.3] Steady State Efficiency (%) 81 81 81 81 No. Burners 10 14 10 14 No. Stages 2 2 2 2 Gas Connection Pipe Size in. [mm] 0.75 [19.05] 0.75 [19.05] 0.75 [19.05] 0.75 [19.05]
Compressor
Qty./Type 4/Scroll 4/Scroll 4/Scroll 4/Scroll
Outdoor Sound Rating (dB)
5
91 91 91 91
Outdoor Coil—Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled Tube Size in. [mm] OD 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 36 [3.34] 36 [3.34] 36 [3.34] 36 [3.34] Rows / FPI [FPcm] 1 / 22 [9] 1 / 22 [9] 1 / 22 [9] 1 / 22 [9]
Indoor Coil—Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 15.75 [1.46] 15.75 [1.46] 15.75 [1.46] 15.75 [1.46] Rows / FPI [FPcm] 4 / 13 [5] 4 / 13 [5] 4 / 13 [5] 4 / 13 [5] Refrigerant Control Capillary Tubes Capillary Tubes Capillary Tubes Capillary Tubes Drain Connection No./Size in. [mm] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4]
Outdoor Fan—Type Propeller Propeller Propeller Propeller
No. Used/Diameter in. [mm] 4/24 [609.6] 4/24 [609.6] 4/24 [609.6] 4/24 [609.6] Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1 CFM [L/s] 16000 [7550] 16000 [7550] 16000 [7550] 16000 [7550] No. Motors/HP 4 at 1/3 HP 4 at 1/3 HP 4 at 1/3 HP 4 at 1/3 HP Motor RPM 1075 1075 1075 1075
Indoor Fan—Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal
No. Used/Diameter in. [mm] 2/18x9 [457.2x228.6] 2/18x9 [457.2x228.6] 2/18x9 [457.2x228.6] 2/18x9 [457.2x228.6] Drive Type/No. Speeds Belt/Variable Belt/Variable Belt/Variable Belt/Variable No. Motors 1 1 1 1 Motor HP 3 3 5 5 Motor RPM 1725 1725 1725 1725 Motor Frame Size 56 56 184 184
Filter—Type Disposable Disposable Disposable Disposable
Furnished Yes Yes Yes Yes (No.) Size Recommended in. [mm] (3)2x18x18 [51x457x457] (3)2x18x18 [51x457x457] (3)2x18x18 [51x457x457] (3)2x18x18 [51x457x457]
(3)2x18x24 [51x457x610] (3)2x18x24 [51x457x610] (3)2x18x24 [51x457x610] (3)2x18x24 [51x457x610]
Refrigerant Charge Oz. (Sys. 1/Sys. 2) [g] 82/72 [2325/2041] 82/72 [2325/2041] 82/72 [2325/2041] 82/72 [2325/2041] Weights
Net Weight lbs. [kg] 1790 [812] 1817 [824] 1820 [826] 1847 [838] Ship Weight lbs. [kg] 2010 [912] 2037 [924] 2040 [925] 2067 [938]
Page 9
IM 863
9
General Data
[] Designates Metric Conversions
NOM. SIZES 15 & 20 TONS [52.8-70.3 kW] ASHRAE 90.1-2004 COMPLIANT MODELS
NOTES:
1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to
20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner Equipment
certification program, which is based on ARI Standard 210/240 or 360.
2. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures.
3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80° F ambient, 80° F entering dry bulb, and 67° F entering wet bulb a
t ARI rated cfm.
4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions
using American National Standard Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet ab
ove sea level.
5. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270.
Model MPS- 015AGDL25E 015AGDL35E 015AGDM25E 015AGDM35E Cooling Performance
1
Gross Cooling Capacity Btu [kW] 188,000 [55.1] 188,000 [55.1] 188,000 [55.1] 188,000 [55.1]
2
EER/SEER
10.2/NA 10.2/NA 10.2/NA 10.2/NA Nominal CFM/ARI Rated CFM [L/s] 6000/6000 [2831/2831] 6000/6000 [2831/2831] 6000/6000 [2831/2831] 6000/6000 [2831/2831] ARI Net Cooling Capacity Btu [kW] 180,000 [52.7] 180,000 [52.7] 180,000 [52.7] 180,000 [52.7] Net Sensible Capacity Btu [kW] 134,000 [39.3] 134,000 [39.3] 134,000 [39.3] 134,000 [39.3] Net Latent Capacity Btu [kW] 46,000 [13.5] 46,000 [13.5] 46,000 [13.5] 46,000 [13.5] Integrated Part Load Value
3
10.4 10.4 10.4 10.4
Net System Power kW 17.6 17.6 17.6 17.6
Heating Performance (Package Gas/Electric)
4
Heating Input Btu [kW] (1st Stage /2nd Stage) 125,000/250,000 [36.6/73.2]175,000/350,000 [51.3/102.6]125,000/250,000 [36.6/73.2]175,000/350,000 [51.3/102.6] Heating Output Btu [kW] (1st Stage /2nd Stage) 101,500/203,000 [29.7/59.5] 142,000/284,000 [41.6/83.2] 101,500/203,000 [29.7/59.5] 142,000/284,000 [41.6/83.2] Temperature Rise Range °F [°C] 15-45 [8.3/25] 30-60 [16.7/33.3] 15-45 [8.3/25] 30-60 [16.7/33.3] Steady State Efficiency (%) 81 81 81 81 No. Burners 10 14 10 14 No. Stages 2 2 2 2 Gas Connection Pipe Size in. [mm] 0.75 [19.05] 0.75 [19.05] 0.75 [19.05] 0.75 [19.05]
Compressor
Qty./Type 4/Scroll 4/Scroll 4/Scroll 4/Scroll
Outdoor Sound Rating (dB)
5
91 91 91 91
Outdoor Coil—Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled Tube Size in. [mm] OD 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 36 [3.34] 36 [3.34] 36 [3.34] 36 [3.34] Rows / FPI [FPcm] 1 / 22 [9] 1 / 22 [9] 1 / 22 [9] 1 / 22 [9]
Indoor Coil—Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 15.75 [1.46] 15.75 [1.46] 15.75 [1.46] 15.75 [1.46] Rows / FPI [FPcm] 4 / 13 [5] 4 / 13 [5] 4 / 13 [5] 4 / 13 [5] Refrigerant Control Capillary Tubes Capillary Tubes Capillary Tubes Capillary Tubes Drain Connection No./Size in. [mm] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4]
Outdoor Fan—Type Propeller Propeller Propeller Propeller
No. Used/Diameter in. [mm] 4/24 [609.6] 4/24 [609.6] 4/24 [609.6] 4/24 [609.6] Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1 CFM [L/s] 16000 [7550] 16000 [7550] 16000 [7550] 16000 [7550] No. Motors/HP 4 at 1/3 HP 4 at 1/3 HP 4 at 1/3 HP 4 at 1/3 HP Motor RPM 1075 1075 1075 1075
Indoor Fan—Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal
No. Used/Diameter in. [mm] 2/18x9 [457.2x228.6] 2/18x9 [457.2x228.6] 2/18x9 [457.2x228.6] 2/18x9 [457.2x228.6] Drive Type/No. Speeds Belt/Variable Belt/Variable Belt/Variable Belt/Variable No. Motors 1 1 1 1 Motor HP 3 3 5 5 Motor RPM 1725 1725 1725 1725 Motor Frame Size 56 56 184 184
Filter—Type Disposable Disposable Disposable Disposable
Furnished Yes Ye s Yes Ye s (No.) Size Recommended in. [mm] (3)2x18x18 [51x457x457] (3)2x18x18 [51x457x457] (3)2x18x18 [51x457x457] (3)2x18x18 [51x457x457]
(3)2x18x24 [51x457x610] (3)2x18x24 [51x457x610] (3)2x18x24 [51x457x610] (3)2x18x24 [51x457x610]
Refrigerant Charge Oz. (Sys. 1/Sys. 2) [g] 82/72 [2325/2041] 82/72 [2325/2041] 82/72 [2325/2041] 82/72 [2325/2041] Weights
Net Weight lbs. [kg] 1806 [819] 1841 [835] 1836 [833] 1871 [849] Ship Weight lbs. [kg] 2026 [919] 2061 [935] 2056 [933] 2091 [948]
CONTINUED
Page 10
10 IM 863
General Data
[] Designates Metric Conversions
NOM. SIZES 15 & 20 TON S [52.8-70.3 kW] ASHRAE 90.1-2004 COMPLIANT MODELS
NOTES:
1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to
20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner Equipment
certification program, which is based on ARI Standard 210/240 or 360.
2. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures.
3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80° F ambient, 80° F entering dry bulb, and 67° F entering wet bulb a
t ARI rated cfm.
4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions
using American National Standard Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet ab
ove sea level.
5. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270.
Model MPS- 015AGYL35E 015AGYM35E 020AGCL30E 020AGCL40E Cooling Performance
1
CONTINUED
Gross Cooling Capacity Btu [kW] 188,000 [55.1] 188,000 [55.1] 246,000 [72.1] 246,000 [72.1]
2
EER/SEER
10.2/NA 10.2/NA 9.7/NA 9.7/NA Nominal CFM/ARI Rated CFM [L/s] 6000/6000 [2831/2831] 6000/6000 [2831/2831] 7700/7400 [3634/3492] 7700/7400 [3634/3492] ARI Net Cooling Capacity Btu [kW] 180,000 [52.7] 180,000 [52.7] 232,000 [68] 232,000 [68] Net Sensible Capacity Btu [kW] 134,000 [39.3] 134,000 [39.3] 168,000 [49.2] 168,000 [49.2] Net Latent Capacity Btu [kW] 46,000 [13.5] 46,000 [13.5] 64,000 [18.8] 64,000 [18.8] Integrated Part Load Value
3
10.4 10.4 9.9 9.9
Net System Power kW 17.6 17.6 23.9 23.9
Heating Performance (Package Gas/Electric)
4
Heating Input Btu [kW] (1st Stage /2nd Stage) 175,000/350,000 [51.3/102.6] 175,000/350,000 [51.3/102.6] 150,000/300,000 [44/87.9] 200,000/400,000 [58.6/117.2] Heating Output Btu [kW] (1st Stage /2nd Stage) 142,000/284,000 [41.6/83.2] 142,000/284,000 [41.6/83.2] 121,500/243,000 [35.6/71.2] 162,000/324,000 [47.5/94.9] Temperature Rise Range °F [°C] 30-60 [16.7/33.3] 30-60 [16.7/33.3] 15-45 [8.3/25] 25-55 [13.9/30.6] Steady State Efficiency (%) 81 81 81 81 No. Burners 14 14 12 14 No. Stages 2 2 2 2 Gas Connection Pipe Size in. [mm] 0.75 [19.05] 0.75 [19.05] 0.75 [19.05] 0.75 [19.05]
Compressor
Qty./Type 4/Scroll 4/Scroll 4/Scroll 4/Scroll
Outdoor Sound Rating (dB)
5
91 91 91 91
Outdoor Coil—Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled Tube Size in. [mm] OD 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 36 [3.34] 36 [3.34] 36 [3.34] 36 [3.34] Rows / FPI [FPcm] 1 / 22 [9] 1 / 22 [9] 2 / 22 [9] 2 / 22 [9]
Indoor Coil—Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 15.75 [1.46] 15.75 [1.46] 15.75 [1.46] 15.75 [1.46] Rows / FPI [FPcm] 4 / 13 [5] 4 / 13 [5] 4 / 13 [5] 4 / 13 [5] Refrigerant Control Capillary Tubes Capillary Tubes Capillary Tubes Capillary Tubes Drain Connection No./Size in. [mm] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4]
Outdoor Fan—Type Propeller Propeller Propeller Propeller
No. Used/Diameter in. [mm] 4/24 [609.6] 4/24 [609.6] 4/24 [609.6] 4/24 [609.6] Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1 CFM [L/s] 16000 [7550] 16000 [7550] 16000 [7550] 16000 [7550] No. Motors/HP 4 at 1/3 HP 4 at 1/3 HP 4 at 1/3 HP 4 at 1/3 HP Motor RPM 1075 1075 1075 1075
Indoor Fan—Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal
No. Used/Diameter in. [mm] 2/18x9 [457.2x228.6] 2/18x9 [457.2x228.6] 2/18x9 [457.2x228.6] 2/18x9 [457.2x228.6] Drive Type/No. Speeds Belt/Variable Belt/Variable Belt/Variable Belt/Variable No. Motors 1 1 1 1 Motor HP 3 5 5 5 Motor RPM 1725 1725 1725 1725 Motor Frame Size 56 184 184 184
Filter—Type Disposable Disposable Disposable Disposable
Furnished Yes Ye s Yes Ye s (No.) Size Recommended in. [mm] (3)2x18x18 [51x457x457] (3)2x18x18 [51x457x457] (3)2x18x18 [51x457x457] (3)2x18x18 [51x457x457]
(3)2x18x24 [51x457x610] (3)2x18x24 [51x457x610] (3)2x18x24 [51x457x610] (3)2x18x24 [51x457x610]
Refrigerant Charge Oz. (Sys. 1/Sys. 2) [g] 82/72 [2325/2041] 82/72 [2325/2041] 117/107 [3317/3033] 117/107 [3317/3033] Weights
Net Weight lbs. [kg] 1841 [835] 1871 [849] 1972 [894] 1988 [902] Ship Weight lbs. [kg] 2061 [935] 2091 [948] 2192 [994] 2208 [1002]
Page 11
IM 863
11
General Data
[] Designates Metric Conversions
NOM. SIZES 15 & 20 TONS [52.8-70.3 kW] ASHRAE 90.1-2004 COMPLIANT MODELS
NOTES:
1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to
20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner Equipment
certification program, which is based on ARI Standard 210/240 or 360.
2. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures.
3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80° F ambient, 80° F entering dry bulb, and 67° F entering wet bulb a
t ARI rated cfm.
4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions
using American National Standard Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet ab
ove sea level.
5. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270.
Model MPS- 020AGCM30E 020AGCM40E 020GDL30E 020AGDL40E Cooling Performance
1
Gross Cooling Capacity Btu [kW] 246,000 [72.1] 246,000 [72.1] 246,000 [72.1] 246,000 [72.1]
2
EER/SEER
9.7/NA 9.7/NA 9.7/NA 9.7/NA Nominal CFM/ARI Rated CFM [L/s] 7700/7400 [3634/3492] 7700/7400 [3634/3492] 7700/7400 [3634/3492] 7700/7400 [3634/3492] ARI Net Cooling Capacity Btu [kW] 232,000 [68] 232,000 [68] 232,000 [68] 232,000 [68] Net Sensible Capacity Btu [kW] 168,000 [49.2] 168,000 [49.2] 168,000 [49.2] 168,000 [49.2] Net Latent Capacity Btu [kW] 64,000 [18.8] 64,000 [18.8] 64,000 [18.8] 64,000 [18.8] Integrated Part Load Value
3
9.9 9.9 9.9 9.9
Net System Power kW 23.9 23.9 23.9 23.9
Heating Performance (Package Gas/Electric)
4
Heating Input Btu [kW] (1st Stage /2nd Stage) 150,000/300,000 [44/87.9] 200,000/400,000 [58.6/117.2] 150,000/300,000 [44/87.9] 200,000/400,000 [58.6/117.2] Heating Output Btu [kW] (1st Stage /2nd Stage) 121,500/243,000 [35.6/71.2] 162,000/324,000 [47.5/94.9] 121,500/243,000 [35.6/71.2] 162,000/324,000 [47.5/94.9] Temperature Rise Range °F [°C] 15-45 [8.3/25] 25-55 [13.9/30.6] 15-45 [8.3/25] 25-55 [13.9/30.6] Steady State Efficiency (%) 81 81 81 81 No. Burners 12 14 12 14 No. Stages 2 2 2 2 Gas Connection Pipe Size in. [mm] 0.75 [19.05] 0.75 [19.05] 0.75 [19.05] 0.75 [19.05]
Compressor
Qty./Type 4/Scroll 4/Scroll 4/Scroll 4/Scroll
Outdoor Sound Rating (dB)
5
91 91 91 91
Outdoor Coil—Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled Tube Size in. [mm] OD 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 36 [3.34] 36 [3.34] 36 [3.34] 36 [3.34] Rows / FPI [FPcm] 2 / 22 [9] 2 / 22 [9] 2 / 22 [9] 2 / 22 [9]
Indoor Coil—Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 15.75 [1.46] 15.75 [1.46] 15.75 [1.46] 15.75 [1.46] Rows / FPI [FPcm] 4 / 13 [5] 4 / 13 [5] 4 / 13 [5] 4 / 13 [5] Refrigerant Control Capillary Tubes Capillary Tubes Capillary Tubes Capillary Tubes Drain Connection No./Size in. [mm] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4]
Outdoor Fan—Type Propeller Propeller Propeller Propeller
No. Used/Diameter in. [mm] 4/24 [609.6] 4/24 [609.6] 4/24 [609.6] 4/24 [609.6] Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1 CFM [L/s] 16000 [7550] 16000 [7550] 16000 [7550] 16000 [7550] No. Motors/HP 4 at 1/3 HP 4 at 1/3 HP 4 at 1/3 HP 4 at 1/3 HP Motor RPM 1075 1075 1075 1075
Indoor Fan—Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal
No. Used/Diameter in. [mm] 2/18x9 [457.2x228.6] 2/18x9 [457.2x228.6] 2/18x9 [457.2x228.6] 2/18x9 [457.2x228.6] Drive Type/No. Speeds Belt/Variable Belt/Variable Belt/Variable Belt/Variable No. Motors 1 1 1 1 Motor HP 7.5 7.5 5 5 Motor RPM 1725 1725 1725 1725 Motor Frame Size 213 213 184 184
Filter—Type Disposable Disposable Disposable Disposable
Furnished Yes Ye s Yes Ye s (No.) Size Recommended in. [mm] (3)2x18x18 [51x457x457] (3)2x18x18 [51x457x457] (3)2x18x18 [51x457x457] (3)2x18x18 [51x457x457]
(3)2x18x24 [51x457x610] (3)2x18x24 [51x457x610] (3)2x18x24 [51x457x610] (3)2x18x24 [51x457x610]
Refrigerant Charge Oz. (Sys. 1/Sys. 2) [g] 117/107 [3317/3033] 117/107 [3317/3033] 117/107 [3317/3033] 117/107 [3317/3033] Weights
Net Weight lbs. [kg] 1994 [904] 2010 [912] 1996 [905] 2020 [916] Ship Weight lbs. [kg] 2214 [1004] 2230 [1012] 2216 [1005] 2240 [1016]
CONTINUED
Page 12
12 IM 863
General Data
[] Designates Metric Conversions
NOM. SIZES 15 & 20 TONS [52.8-70.3 kW] ASHRAE 90.1-2004 COMPLIANT MODELS
NOTES:
1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to
20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner Equipment
certification program, which is based on ARI Standard 210/240 or 360.
2. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures.
3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80° F ambient, 80° F entering dry bulb, and 67° F entering wet bulb a
t ARI rated cfm.
4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions
using American National Standard Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet ab
ove sea level.
5. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270.
Model MPS- 020AGDM30E 020AGDM40E Cooling Performance
1
Gross Cooling Capacity Btu [kW] 246,000 [72.1] 246,000 [72.1]
2
EER/SEER
9.7/NA 9.7/NA Nominal CFM/ARI Rated CFM [L/s] 7700/7400 [3634/3492] 7700/7400 [3634/3492] ARI Net Cooling Capacity Btu [kW] 232,000 [68] 232,000 [68] Net Sensible Capacity Btu [kW] 168,000 [49.2] 168,000 [49.2] Net Latent Capacity Btu [kW] 64,000 [18.8] 64,000 [18.8] Integrated Part Load Value
3
9.9 9.9
Net System Power kW 23.9 23.9
Heating Performance (Package Gas/Electric)
4
Heating Input Btu [kW] (1st Stage /2nd Stage) 150,000/300,000 [44/87.9] 200,000/400,000 [58.6/117.2] Heating Output Btu [kW] (1st Stage /2nd Stage) 121,500/243,000 [35.6/71.2] 162,000/324,000 [47.5/94.9] Temperature Rise Range °F [°C] 15-45 [8.3/25] 25-55 [13.9/30.6] Steady State Efficiency (%) 81 81 No. Burners 12 14 No. Stages 2 2 Gas Connection Pipe Size in. [mm] 0.75 [19.05] 0.75 [19.05]
020AGYL40E
246,000 [72.1]
9.7/NA
7700/7400 [3634/3492]
232,000 [68]
168,000 [49.2]
64,000 [18.8]
9.9
23.9
200,000/400,000
162,000/324,000 [47.5/94.9]
25-55 [13.9/30.6]
81 14
2
0.75 [19.05]
020AGYM40E
246,000 [72.1]
7700/7400 [3634/3492]
232,000 [68]
168,000 [49.2]
64,000 [18.8]
200,000/400,000 [58.6/117.2]
162,000/324,000 [47.5/94.9]
25-55 [13.9/30.6]
0.75 [19.05]
Compressor
Qty./Type 4/Scroll 4/Scroll
Outdoor Sound Rating (dB)
5
91 91
Outdoor Coil—Fin Type Louvered Louvered
Tube Type Rifled Rifled Tube Size in. [mm] OD 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 36 [3.34] 36 [3.34] Rows / FPI [FPcm] 2 / 22 [9] 2 / 22 [9]
Indoor Coil—Fin Type Louvered Louvered
Tube Type Rifled Rifled Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 15.75 [1.46] 15.75 [1.46] Rows / FPI [FPcm] 4 / 13 [5] 4 / 13 [5] Refrigerant Control Capillary Tubes Capillary Tubes Drain Connection No./Size in. [mm] 1/1 [25.4] 1/1 [25.4]
Outdoor Fan—Type Propeller Propeller
No. Used/Diameter in. [mm] 4/24 [609.6] 4/24 [609.6] Drive Type/No. Speeds Direct/1 Direct/1 CFM [L/s] 16000 [7550] 16000 [7550] No. Motors/HP 4 at 1/3 HP 4 at 1/3 HP Motor RPM 1075 1075
Indoor Fan—Type FC Centrifugal FC Centrifugal
No. Used/Diameter in. [mm] 2/18x9 [457.2x228.6] 2/18x9 [457.2x228.6] Drive Type/No. Speeds Belt/Variable Belt/Variable No. Motors 1 1 Motor HP 7.5 7.5 Motor RPM 1725 1725 Motor Frame Size 213 213
Filter—Type Disposable Disposable
Furnished Yes Ye s (No.) Size Recommended in. [mm] (3)2x18x18 [51x457x457] (3)2x18x18 [51x457x457]
(3)2x18x24 [51x457x610] (3)2x18x24 [51x457x610]
Refrigerant Charge Oz. (Sys. 1/Sys. 2) [g] 117/107 [3317/3033] 117/107 [3317/3033]
4/Scroll
91
Louvered
Rifled
0.375 [9.5] 36 [3.34]
2 / 22 [9]
Louvered
Rifled
0.375 [9.5]
15.75 [1.46] 4 / 13 [5]
Capillary Tubes
1/1 [25.4]
Propeller
4/24 [609.6]
Direct/1
16000 [7550]
4 at 1/3 HP
1075
FC Centrifugal
2/18x9 [457.2x228.6]
Belt/Variable
1 5
1725
184
Disposable
Yes (3)2x18x18 [51x457x457] (3)2x18x24 [51x457x610]
117/107 [3317/3033]
4/Scroll
Louvered
0.375 [9.5] 36 [3.34] 2 / 22 [9] Louvered
0.375 [9.5]
15.75 [1.46] 4 / 13 [5]
Capillary Tubes
1/1 [25.4]
Propeller
4/24 [609.6]
Direct/1
16000 [7550]
4 at 1/3 HP
FC Centrifugal
2/18x9 [457.2x228.6]
Belt/Variable
Disposable
(3)2x18x18 [51x457x457] (3)2x18x24 [51x457x610]
117/107 [3317/3033]
Weights
Net Weight lbs. [kg] 2018 [915] 2042 [926] Ship Weight lbs. [kg] 2238 [1015] 2262 [1026]
2020 [916]
2240 [1016]
2042 [926]
2262 [1026]
9.7/NA
9.9
23.9
81 14
2
91
Rifled
Rifled
1075
1
7.5
1725
213
Yes
Page 13
IM 863
13
Installation
General
1 INSTALLATION — Install this unit in accordance with
The American National Standard Z223.1-latest edition manual entitled “National Fuel Gas Code,” and the requirements or codes of the local utility or other author­ity having jurisdiction.
Additional helpful publications available from the “National Fire Protection Association” are: NFPA-90A ­Installation of Air Conditioning and Ventilating Systems 1985 or latest edition. NFPA-90B - Warm Air Heating and Air Conditioning Systems 1984.
These publications are available from:
National Fire Protection Association, Inc. Batterymarch Park Quincy, MA 02269
2 PRE-INSTALLATION CHECK-POINTS — Before
attempting any installation, carefully consider the follow­ing points:
Structural strength of supporting members
(Rooftop Installation) Clearances and provision for servicing Power supply and wiring Gas supply and piping Air duct connections and sizing Drain facilities and connections Location for minimum noise and vibration - away from
bedroom windows
IMPORTANT: Before operating unit, remove compressor ship­ping supports from the compressor base. Failure to remove sup­ports will casue noise and vibration.
Location Consideratons
The metal parts of this unit may be subject to rust or deterio­ration in adverse environmental conditions. This oxidation could shorten the equipment’s useful life. Salt spray, fog or mist in seacoast areas, sulphur or chlorine from lawn watering systems, and various chemical contaminants from industries such as paper mills and petroleum refineries are especially corrosive.
If the unit is to be installed in an area where contaminants are likely to be a problem, give special attention to the equipment location and exposure.
1 Avoid having lawn sprinkler heads spray directly on the
unit cabinet.
2 In coastal areas locate the unit on the side of the building
away from the waterfront.
3 Shielding by a fence or shrubs may give some protection.
4 Frequent washing of the cabinet, fan blade and coil with
fresh water will remove most of the salt or other contam­inants that build up on the unit.
5 Regular cleaning and waxing of the cabinet with an auto-
mobile polish will provide some protection.
6 A liquid cleaner may be used several times a year to
remove matter that will not wash off with water.
Several different types of protective coatings are offered in some areas. These coatings may provide some benefit, but the effectiveness of such coating materials cannot be verified by the equipment manufacturer.
The best protection is frequent cleaning, maintenance and minimal exposure to contaminants.
Outside Installation
(Typical outdoor slab installation is shown in Figure 9.)
1 Select a location where external water drainage cannot
collect around unit.
2 Provide a level slab sufficiently high enough above grade
to prevent surface water from entering the unit
3 Locate the unit to provide proper access for inspection
and servicing as shown in Figure 12.
4 Locate unit where operating sounds will not disturb
owner or neighbors.
5 Locate unit so roof runoff water does not pour directly on
the unit. Provide gutter or other shielding at roof level. Do not locate unit in an area where excessive snow drift­ing may occur or accumulate.
6 Where snowfall is anticipated, the height of the unit
above the ground level must be considered. Mount unit high enough to be above anticipated maximum area snowfall and to allow combustion air to enter the com­bustion air inlet.
7 Select an area which will keep the areas of the vent, air
intake, and A/C condenser fins free and clear of obstruc­tions such as weeds, shrubs, vines, snow, etc. Inform the user accordingly.
Attaching Exhaust and Combustion Air Inlet Hoods
IMPORTANT: Do not operate this unit without the exhaust/combus-
tion air inlet hood properly installed. These hoods are shipped in cartons in the blower compartment inside the unit and must be attached when the unit is installed. See Figure 4.
Power supply to unit must be disconnected before making field connections. To avoid electrical shock, personal injury or death, be sure to rigorously adhere to field wiring proce­dures regarding proper lockout and tagout of components.
DANGER
!
These units are designed certified for outdoor installation only. Installation inside any part of a structure can result in inadequate unit performance as well as property damage. Installation inside can also cause recirculation of flue prod­ucts into the conditioned space resulting in personal injury or death.
DANGER
!
Page 14
14 IM 863
To attach exhaust/combustion air inlet hood:
1 Remove screws securing blower access panel and remove
access panel. For location of blower access panel, see Figure
3.
2 Remove exhaust/combustion air inlet hoods from the car-
tons, located inside the blower compartment.
3 Attach blower access panel.
4 Attach the combustion air inlet/exhaust hoods with screws.
Reference Figure 4 for proper location. Screws are in carton with the hood.
5 Vent the unit using the flue exhaust hood, as supplied from
the factory, without alteration or addition. The only excep­tion is with factory approved additions.
Horizontal Conversion Procedure
Downflow to Horizontal
1 Remove the screws and covers from the outside of the
supply and return sections. Also remove and discard cover plate. See Figure 7.
2 Install the covers over the bottom supply and return
openings, painted side up, inserting the leading flange under the bracket provided. Place the back flange to top of the front bracket provided. See Figures 10
and 11.
3 Secure the return and supply cover to front bracket with
two (2) screws.
Filter Replacement
This unit is provided with 3 - 18” X 18” X 2” and 3 - 18” X 24” X 2” disposable filters. When replacing filters, ensure they are inserted fully to the back to prevent bypass. See Figure 5.
Recommended supplier of this filter is:
AAF International Part #: 54-42541-01 (18" x 18" x 2")
Part #: 54-42541-03 (18" x 24" x 2")
Figure 9: Outside Slab Installation. Closet Distribution System. Slab Floor Construction
ST-A0886-25
Figure 10: Horizontal Conversion Detail
ST-A0886-30
Figure 11: Horizontal Conversion Detail
ST-A0886-31
Page 15
IM 863
15
Figure 12: Clearances
ST-A0886-09
FIGURE 13: Flat Rooftop Installation, Attic or Drop Ceiling Distributing System. Mounted on Roofcurb. Curb must be level.
ST-A0886-10
Clearances
The following minimum clearances must be observed for prop­er unit performance and serviceability. Reference Figure 12.
Page 16
16 IM 863
Rooftop Installation
1 Before locating the unit on the roof, make sure that the
roof structure is adequate to support the weight involved. (See Electrical & Physical Tables in this manual.) THIS
IS VERY IMPORTANT AND THE INSTALLER’S RESPONSIBILITY.
2 For rigging and roofcurb details, see Figures 14, 15, 16
and 17.
3 The location of the unit on the roof should be such as to
provide proper access for inspection and servicing.
IMPORTANT: If unit will not be put into service immediately, block off supply and return air openings to prevent excessive condensation.
Ducting
The installing contractor should fabricate ductwork in accor­dance with local codes. Use industry manuals as a guide when sizing and designing the duct system. Contact Air Conditioning Contractors of America, 1513 16th St. N.W., Washington, D.C. 20036.
Place the unit as close to the conditioned space as possible allowing clearances as indicated. Run ducts as directly as pos­sible to supply and return outlets. Use of non-flammable weatherproof flexible connectors on both supply and return connections at unit to reduce noise transmission is recom­mended.
On ductwork exposed to outside temperature and humidity, use a minimum of 2” of insulation and a vapor barrier. Distribution system in attic, furred space or crawl space should be insulated with at least 2” of insulation.
1
2” to 1” thick insulation is usually sufficient for ductwork inside the air conditioned space.
Provide balancing dampers for each branch duct in the supply system. Properly support ductwork from the structure.
IMPORTANT: In the event that the return air ducts must be run through an “unconfined” space containing other fuel burning equipment, it is imperative that the user/building owner must be informed against changes in construction which might change this to a “confined space.” Also, caution the user/building owner against installation of additional equipment, such as power venti­lators, within the existing unconfined and/or confined space which might create a negative pressure within the vicinity of other solid, liquid, or gas fueled units.
Return Air
Do not, under any circumstances, connect return ductwork to any other heat producing device such as fireplace insert, stove, etc. Unauthorized use of such devices may result in fire, carbon monoxide poisoning, explosion, personal injury, property damage or death.
DANGER
!
Never allow products of combustion or the flue products to enter the return air ductwork, or the circulating air supply. all return ductwork must be adequately sealed and secured to the furnace with sheet metal screws, and joints taped. All other duct joints must be secured with approved connec­tions and sealed airtight.
Failure to prevent products of combustion from being circu­lated into the living space can create potentially hazardous conditions, including carbon monoxide poisoning that could result in personal injury or death.
DANGER
!
ST-A0886-12
Figure 15: Lifting Detail
ST-A1084-01
Figure 14: Shipping Board Removal
REMOVE SHIPPING BOARDS BEFORE INSTALLING UNIT.
CENTER OF
GRAVITY
CENTER OF
GRAVITY
32.9
835.6 mm
67.1
1704.3 mm
Page 17
IM 863
17
Gas Supply, Condensate Drain and Piping
Gas Connection
IMPORTANT: Connect this unit only to gas supplied by a com-
mercial utility.
1 Install gas piping in accordance with local codes and reg-
ulations of the local utility company. In the absence of local codes, the installation must conform to the specifi­cations of the National Fuel Gas Code, ANSI Z223.1 ­latest edition.
NOTE: The use of flexible gas connectors is not permit­ted.
2 Connect the gas line to the gas valve supplied with unit.
Routing can be through the gas pipe opening shown in Figures 9 or 13A or 13B or through the base as shown in Figure 22.
3 Size the gas line to the furnace adequate enough to pre-
vent undue pressure drop and never less than 1/2”.
4 Install a drip leg or sediment trap in the gas supply line
as close to the unit as possible.
5 Install an outside ground joint union to connect the gas
supply to the control assembly at the burner tray.
6 Gas valves have been factory installed. Install a manual
gas valve where local codes specify a shut-off valve out­side the unit casing. (See Figure 18.)
7 Make sure piping is tight. A pipe compound resistant to
the action of liquefied petroleum gases must be used at all threaded pipe connections.
8 IMPORTANT: any additions, changes or conversions
required for the furnace to satisfactorily meet the applica­tion should be made by a qualified installer, service agency or the gas supplier, using factory-specified or approved
parts. In the commonwealth of Massachusetts, installation must be performed by a licensed plumber or gas fitter for appropriate fuel.
IMPORTANT: Disconnect the furnace and its individual shutoff valve from the gas supply piping during any pressure testing of that system at test pressures in excess of 1/2 pound per square inch gauge or isolate the system from the gas supply piping sys­tem by closing its individual manual shutoff valve during any pressure testing of this gas supply system at pressures equal to or less than 1/2 PSIG.
IMPORTANT: Check the rating plate to make certain the unit is equipped to burn the type of gas supplied. Care should be taken after installation of this equipment that the gas control valve not be subjected to high gas supply line pressure.
Nominal
Iron Pipe
Size,
Inches
Equivalent Length of Pipe, Feet
10 20 30 40 506070 80
1
/2 1329273 63 56 50 46 43
3
/4 278 190 152 130 115 105 96 90
1 520 350 285 245 215 195 180 170 11/4 1,050 730 590 500 440 400 370 350 11/2 1,600 1,100 890 760 670 610 560 530
Table 3: Gas Pipe Capacity Table (Cu. Ft./Hr.)
Figure 16: Roofcurb Figure 17: Roofcurb
ST-A0888-02
ST-A0888-02
Never test for gas leaks with an open flame. It can cause an explosion or fire resulting in property damage, personal injury or death. Use a commercially available soap solution made specifically for the detection of leaks to check all con­nections, as specified in the Gas Supply and Piping section of these instructions.
DANGER
!
Page 18
18 IM 863
In making gas connections, avoid strains as they may cause noise and damage the controls. A backup wrench is required to be used on the valve to avoid damage.
The capacities of gas pipe of different diameters and lengths in cu. ft. per hr. with pressure drop of 0.3 in. and specific gravity of 0.60 (natural gas) are shown in Table 3.
After determining the pipe length, select the pipe size which will provide the minimum cubic feet per hour required for the gas input rating of the furnace. By formula:
Gas Input of Furnace (BTU/HR)
Cu. Ft. Per Hr. Required =
Heating Value of Gas (BTU/FT3)
The gas input of the furnace is marked on the furnace rating plate. The heating value of the gas (BTU/FT3) may be deter­mined by consulting the local natural gas utility or the L.P. gas supplier.
LP Conversion
Convert the unit to use liquefied petroleum (LP) gas by replacing with the stem/spring assembly supplied in the con­version kit. The LP gas valve maintains the proper manifold pressure for LP gas. The correct burner LP orifices are includ­ed in the kit.
See Figure 19A for component locations.
NOTE: Order the correct LP conversion kit from the furnace manufacturer. See Conversion Kit Index shipped with unit for
proper LP kit number. Furnace conversion to LP gas must be performed by a qualified technician.
This unit is equipped at the factory for use on natural gas only. Conversion to LP gas requires a special kit supplied by the distributor or manufacturer. Mailing addresses are listed on the furnace rating plate, parts list and warranty. Failure to use the proper conversion kit can cause fire, carbon monox­ide poisoning, explosion, personal injury, property damage or death.
DANGER
!
Figure18: Suggested Gas Piping
FROM GAS METER
*
Factory supplied grommet must be utilized.
MANUAL GAS SHUT-OFF VALV E
UNIT GAS SUPPLY CONNECTION
*
ROOF OR GROUND LEVEL INSTALLATION
Figure 19A: Heat Exchanger Component Identification
ST-A0886-29
Page 19
IM 863
19
Maximum capacity of pipe in thousands of BTU per hour of undiluted liquefied petrole­um gases (at 11 inches water column inlet pressure).
(Based on a Pressure Drop of 0.5 Inch Water Column)
Table 4: LP Gas Pipe Capacity Table (Cu. Ft./Hr.)
Nominal Iron Pipe Size, Inches
10 20 30 40 50 60 70 80 90 100 125 150
275 189 152 129 114 103 96 89 83 78 69 63
567 393 315 267 237 217 196 182 173 162 146 132 1,071 732 590 504 448 409 378 346 322 307 275 252 2,205 1,496 1,212 1,039 913 834 771 724 677 630 567 511 3,307 2,299 1,858 1,559 1,417 1,275 1,181 1,086 1,023 976 866 787 6,221 4,331 3,465 2,992 2,646 2,394 2,205 2,047 1,921 1,811 1,606 1,496
1/2 3/4
1 1-1/4 1-1/2
2
Length of Pipe, Feet
Example (LP): Input BTU requirement of unit, 150,000
Equivalent length of pipe, 60 ft. = 3/4IPS required.
Figure 19B: Honeywell VR8305Q4120 Two Stage Gas Valve
OUTLET PRESSURE TAP-1/8 NPT
2-STAGE OPERATOR
INLET PRESSURE TAP-1/8 NPT
GROUND TERMINAL
LOW STAGE ADJUSTMENT UNDER VENT CAP
HIGH STAGE ADJUSTMENT UNDER VENT CAP
Adjusting or Checking Furnace Input
– Natural Gas Line Pressure 5” - 10.5” W.C. – LP Gas Line Pressure 11” - 13” W.C.
– Natural Gas Manifold Pressure 3.5” W.C – LP Gas Manifold Pressure - 10” W.C.
Supply and manifold pressure taps are located on the gas valve body 1/8” N.P.T. and on the manifold. See Figure 19B.
Use a properly calibrated manometer gauge for accurate gas pressure readings.
Only small variations in the gas flow should be made by means of the pressure regulator adjustment. Furnaces func­tioning on LP gas must be set by means of the tank or branch supply regulators. The furnace manifold pressure should be set at 10” W.C. at the gas control valve.
To adjust the pressure regulator, remove the regulator vent cover and turn the adjustment screw clockwise to increase pressure or counterclockwise to decrease pressure. See Figure 19B. Then replace the regulator vent cover securely.
Any necessary major changes in the gas flow rate should be made by changing the size of the burner orifices. To change orifice spuds, shut off the manual main gas valve and remove the gas manifold.
For elevations up to 2,000 feet, rating plate input ratings apply. For high altitudes (elevations over 2,000 ft.), see con­version kit index 92-21519-XX for derating and orifice spud sizes.
Check of input is important to prevent over-firing of the furnace beyond its design-rated input. NEVER SET INPUT ABOVE THAT SHOWN ON THE RATING PLATE. Use the following table or formula to determine input rate.
Heating Value of Gas (BTU/Cu. Ft.) x 3600
Cu. Ft. Per Hr. Required =
Time in Seconds
(for 1 Cu. Ft.) of Gas
Start the furnace and measure the time required to burn one cubic foot of gas. Prior to checking the furnace input, make certain that all other gas units are shut off, with the exception of pilot burners. Time the meter with only the furnace in operation.
IMPORTANT NOTE FOR ALTITUDES ABOVE 2,000 FEET (610 METERS): The main burner orifices in your furnace and in
these kits are sized for the nameplate input and intended for installations at elevations up to 2,000 feet in the USAor Canada, or for elevations of 2,000 - 4,500 feet (610 -1,373 meters) in Canada if the unit has been derated at the factory. For elevations above 2,000 feet (610 meters) IN THE USA ONLY (see ANSI-Z223.1), the burner orifices must be sized to reduce the input 4% for each 1,000 feet (305 meters) above sea level.
NOTICE: Derating of the heating input for high altitude in the field is unlawful in Canada (refer to can/cga 2.17). Units installed in altitudes greater than 2,000 feet (610 meters) must be shipped from the factory or from a factory authorized conversion station with the heating input derated by 10% so as to operate properly in altitudes from 2,000 - 4,500 feet (610 - 1,373 meters).
Condensate Drain
The condensate drain connection of the evaporator is threaded 1” NPT. IMPORTANT: Install a condensate trap to
ensure proper condensate drainage. See Figure 20.
250,000 ONE 13.0 14.4 15.0 15.8 36.0
TEN 2 10 2 24 2 302 386 0
ONE 10.8 12.0 12.5 13.2 30.0
300,000
TEN 1 48 2 0 2 5 2 12 5 0
ONE 9.3 10.3 10.7 1.3 25.7
350,000
TEN 1 33 143 1471 53 417
ONE 8.1 9.0 9.36 9 .9 22.5
400,000
TEN 1 21 1 30136139 3 45
METER TIME IN MINUTES AND SECONDS FOR NORMAL INPUT RATING OF FURNACES EQUIPPED FOR NATURAL
OR LP GAS
INPUT
BTU/HR
METER
SIZE
CU. FT.
HEATING VALUE OF GAS BTU PER CU. FT.
900 1000 1040 1100 2500
MIN. SEC. MIN. SEC. MIN. SEC. MIN. SEC. MIN. SEC.
Table 5
Page 20
20 IM 863
Wiring
Power Supply
1 All wiring should be made in accordance with the
National Electrical Code. Consult the local power com­pany to determine the availability of sufficient power to operate the unit. Check the voltage at power supply to make sure it corresponds to the unit’s RATED VOLT­AGE REQUIREMENT. Install a branch circuit discon­nect near the rooftop, in accordance with the N.E.C., C.E.C. or local codes.
2 It is important that proper electrical power is available at
the unit. Voltage should not vary more than 10% from that stamped on the unit nameplate. On three phase units, phases must be balanced within 3%.
3 For branch circuit wiring (main power supply to unit dis-
connect), the minimum wire size for the length of run can be determined from Table 6 using the circuit ampaci­ty found on the unit rating plate. Use the smallest wire size allowable from the unit disconnect to unit.
4 For through the base wiring entry reference Figure 22.
All fittings and conduit are field supplied for this applica­tion. Reference the chart with Figure 22 for proper hole and conduit size.
NOTES:
1 For branch circuit wiring (main power supply to unit discon-
nect), the minimum wire size for the length of run can be determined from this table using the circuit ampacity found on the unit rating plate. From the unit disconnect to unit, the smallest wire size allowable in Table 6 may be used, as the disconnect must be in sight of the unit.
2 Wire size based on 75°C rated wire insulation for 1% volt-
age drop.
3 For more than 3 conductors in a raceway or cable, see the
N.E.C. (C.E.C. in Canada) for derating the ampacity of each conductor.
IMPORTANT: THIS UNIT IS APPROVED FOR USE WITH COPPER CONDUCTORS ONL
Y CONNECTED TO UNIT CON-
TACTOR.
WARRANTY WILL BE VOIDED IF ALUMINUM WIRE IS CON- NECTED TO UNIT CONTACTOR.
Figure 20: Condensate Drain
Power supply to unit must be disconnected before making field connections. To avoid electrical shock, personal injury or death, be sure to rigorously adhere to field wiring proce­dures regarding proper lockout and tagout of components.
DANGER
!
Figure 21: Recommended Branch Circuit Disconnect Location
ST-A0886-11
DO NOT OVERTIGHTEN DRAIN FITTING
Page 21
Hook-Up
To wire unit, refer to the following hook-up diagram.
Refer to Figures 2 and 22 for location of wiring entrances.
Wiring to be done in the field between the unit and devices not attached to the unit, or between separate devices which are field installed and located, shall conform with the temper­ature limitation for Type T wire [63°F rise (35°C)] when installed in accordance with the manufacturer’s instructions.
Internal Wiring
A diagram of the internal wiring of this unit is located on the inside of control access panel and in this manual. If any of the original wire as supplied with the unit must be replaced, the wire gauge and insulation must be same as original wiring.
208 Volt Applications
Transformer is factory wired for 230 volts on 208/230 volt models and must be changed for 208 volt applications. See unit wiring diagram for 208 volt wiring.
Thermostat
The room thermostat must be compatible with the spark igni­tion control on the unit. Generally, all thermostats that are not of the “current robbing” type are compatible with the integrat­ed furnace control. The low voltage wiring should be sized as shown in Table 7.
Install the room thermostat in accordance with the instruction sheet packed in the box with the thermostat.
IM 863
21
Figure 22: Base Entry Locations
ST-A0886-14
Figure 23: Typical Thermostat Wiring
WIRE SIZE, AWG
14
1/2 7/8
12
1/2 7/8
10
1/2 7/8
8
3/4
1-31/32
6
1
1-23/64
4
1
1-23/64
3
1-1/4
1-23/32
2
1-1/4
1-23/32
1
1-1/2
1-31/32
0
1-1/2
1-31/32
00
2
2-15/32
000
2
2-15/32
CONDUIT SIZE
HOLE SIZE
NOTES: 1. DETERMINE REQUIRED WIRE SIZE FROM MINIMUM CIRCUIT AMPACITY SHOWN IN INSTALLATION & OPERATING INSTRUCTION.
2. BOTTOM POWER ENTRY WILL NOT ACCOMMODATE WIRE LARGER THAN #2 AWG (SHADED AREA).
Table 6: Branch Circuit Wire Size
COPPER
WIRE SIZE—AWG
SUPPLY WIRE LENGTH—FEET
50 100 150 200 250 300
20 10 8 6 4 4 4 25 10 8 6 4 4 3
308644 3 2 358643 21
408643 21 45 8 4 3 2 1 1/0 50 6 4 3 2 1 1/0 60 6 4 2 1 1/0 2/0 70 4 3 2 1/0 2/0 3/0
80 4 3 1 1/0 2/0 3/0
90 3 2 1/0 2/0 3/0 4/0 100 3 2 1/0 2/0 3/0 4/0 110 2 1 2/0 3/0 4/0 250 125 1 1 2/0 3/0 4/0 25
UNIT MCA
Table 7
FIELD WIRE SIZE FOR 24 VOLT THERMOSTAT CIRCUITS
SOLID COPPER WIRE - AWG.
3.0 16 14 12 10 10 10
2.5 16 14 12 12 12 10
2.0 18 16 14 12 12 10
50 100 150 200 250 300
Length of Run – Feet (1)
Thermostat Load -
Amps
(1) The total wire length is the distance from the furnace to the thermo­stat and back to the furnace.
NOTE: DO NOT USE CONTROL WIRING SMALLER THAN NO. 18 AWG.
FIELD GAS CONNECTIONS
STRAIGHT CONDUIT
FITTING SIZED
PER CHART
CONDUIT FROM POWER SUPPLY
SIZED PER CHART
WIRE SIZE FROM
MIN. CIRCUIT AMPACITY
CUT HOLE
SIZED PER CHART
OR USE KNOCK OUT
CONTROL VOLTAGE
KNOCKOUT
POWER WIRES
FROM DISCONNECT
TO CONTACTOR
POWER WIRES TO DISCONNECT
WIRE FROM
ZONE THERMOSTAT
STRAIGHT CONDUIT
FITTING
CONDUIT FROM
ZONE THERMOSTAT
WASHERS
Page 22
Furnace Section Controls and Ignition Systems
Normal Furnace Operating Sequence
This unit has a two stage gas furnace which employs an inte­grated furnace control with self diagnostics located in the con­trol box. The furnace is composed of induced draft blowers, negative pressures switches, two stage gas valve, manifold orifices, inshot burners, direct spark ignitor, remote flame sense, tubular heat exchanger, high limit switch and rollout switches. See Figure 24.
Normal Heat Mode
Call For First Stage (low fire) Only:
1 Zone thermostat contacts close, a call for first stage
(low fire) heat is initiated.
2 Control runs self check.
3 Control checks the high-limit switch for normally
closed contacts, each pressure switch for normally open contacts, and all flame rollout switches for continuity.
4 Control energizes each inducer.
5 Control checks each pressure switch for closure.
6 If each pressure switch is closed, the control starts a 30
second prepurge and energizes W2. If any pressure switch is still open, the inducers will continue to be energized until closure.
7 After prepurge timeout, control energizes W1 and con-
tinues to energize W2, initiates spark for 2 seconds minimum, 7 second maximum ignition trial, initiates 120 second, second stage (high fire) warm up timing.
8 Control detects flame, de-energizes spark and initiates
45 second delay on blower timing.
9 After a fixed 45 seconds indoor blower delay on, the
control energizes the indoor blower.
10 After a fixed 120 seconds second stage warmup period
control checks thermostat input. If only W1 is called for, W2 is de-energized and the control starts a 30 sec­ond off delay on the W2 inducer(s).
11 After fixed 30 seconds the W2 inducers is de-ener-
gized.
12 Control enters normal operating loop where all inputs
are continuously checked.
13 Zone thermostat is satisfied.
14 Control de-energizes gas valve.
15 Control senses loss of flame.
16 Control initiates 5 second inducer postpurge and 90
second indoor blower delay off.
17 Control de-energizes inducer blower(s).
18 Control de-energizes indoor blower.
19 Control in the stand by mode with solid red LED.
Call For Second Stage, After First Stage Established; Starting from A.11:
1 If a call for second stage (high fire) is initiated after a
call for first stage heat is established, the control veri­fies W2 pressure switches for normally open contacts. The control energizes the W2 inducers and energizes the second stage of the gas valve.
2 Control enters normal operating loop where all inputs
are continuously checked.
Second Stage Satisfied; First Stage Still Called For; Star
ting From B.3:
1 Once the call for second stage is satisfied, the control
starts a 30 second off delay on W2 inducers and reduces the gas valve to first stage.
2 Control enters normal operating loop where all inputs
are continuously checked.
First Stage Satisfied:
1 Zone thermostat is satisfied.
2 Control de-energizes gas valve.
3 Control senses loss of flame.
4 Control initiates 5 second inducer postpurge and 90
second indoor blower delay off.
5 Control de-energizes inducer blower.
6 Control de-energizes indoor blower.
7 Control in the stand by mode with solid red LED.
22 IM 863
Figure 24
ST-A0886-29
Page 23
IM 863
23
First Stage and Second Stage Called Simultaneously:
1 Zone thermostat contacts close, a call for first stage
(low fire) and second stage (high fire) heat is initiated.
2 Control runs self check.
3 Control checks the high-limit switch for normally
closed contacts, each pressure switch for normally open contacts, and all flame rollout switches for continuity.
4 Control energizes each inducer.
5 Control checks each pressure switch for closure.
6 If each pressure switch is closed, the control starts a 30
second prepurge and energizes W2. If either switch is still open, the inducers will continue to be energized until closure.
7 After prepurge timeout, control energizes W1 and con-
tinues to energize W2, initiates spark for 2 seconds minimum, 7 second maximum ignition trial, and initi- ates 120 second stage warm up timing.
8 Control detects flame, de-energizes spark and starts a
45 second indoor blower delay on timing.
9 After a fixed 45 seconds indoor blower delay on, the
control energizes the indoor blower.
10 After a fixed 120 seconds second stage warmup period
control checks the thermostat input. If W1 and W2 is present control enters normal operating loop where all inputs are continuously checked.
First Stage and Second Stage Removed Simultaneously:
1 Upon a loss of W1 and W2 the gas valve is de-ener-
gized.
2 Upon a loss of flame, each inducer will complete a 5
second postpurge and the indoor blower will complete a 90 second delay off.
3 Control in the stand by mode with solid red LED.
The integrated control is a three ignition system.
After a total of three cycles without sensing main burner flame, the system goes into a 100% lockout mode. After one hour, the ignition control repeats the prepurge and ignition cycles for 3 tries and then goes into 100% lockout mode again. It continues this sequence of cycles and lockout each hour until ignition is successful or power is interrupted. During the lockout mode, neither the ignitor or gas valve will be energized until the system is reset by turning the thermo­stat to the “OFF” position or interrupting the electrical power to the unit for 3 seconds or longer.
The circulating air blower will start and run on the heating speed if the thermostat fan switch is in the “ON” position.
The integrated furnace control is equipped with diagnostic LED. The LED is lit continuously when there is power to the control, with or without a call for heat. If the LED is not lit, there is either no power to the control or there is an internal component failure within the control, and the control should be replaced.
If the control detects the following failures, the LED will flash on for approximately 1/4 second, then off for 3/4 second for designated failure detections.
1 Flash: Failed to detect flame within the three tries for igni-
tion.
2 Flash: Pressure switch or induced draft blower problem
detected. 3 Flash: High limit or auxiliary limit open. 4 Flash: Flame sensed and gas valve not energized or flame
sensed with no “W” signal. 5 Flash: Overtemperature switch open.
Operating Instructions
This unit is equipped with integrated furnace control. This device lights the main burners each time the room thermostat (closes) calls for heat. See operating instructions on the back of the furnace/controls access panel.
To Start The Furnace
1 Set the thermostat to its lowest setting.
2 Turn off all electric power to the unit.
3 This unit does not have a pilot. It is equipped with an
ignition device which automatically lights the burner. Do not try to light the burner by hand.
4 Remove control door.
5 Move control knob to the “OFF” position. Turn the
knob by hand only, do not use any kind of tool.
6 Wait five (5) minutes to clear out any gas. Then smell
for gas, including near the floor. If you smell gas, STOP! Follow B in the safety information on the Operating Instructions located on the back of the con­trols/access panel. If you don’t smell gas, go to the next step.
7 Move the gas control knob from “OFF” position to
“ON” position. Operate this unit with the gas control
Never test for gas leaks with an open flame. It can cause an explosion or fire resulting in property damage, personal injury or death. Use a commercially available soap solution made specifically for the detection of leaks to check all con­nections, as specified in the Gas Supply and Piping section of these instructions.
DANGER
!
The spark ignitor and ignition lead from the ignition control are high voltage. Keep hands or tools away to prevent elec­trical shock. Shut off electrical power before servicing any of the controls. Failure to adhere to this warning can result in personal injury or death.
DANGER
!
Should overheating occur or the gas supply fail to shut off, shut off the manual gas valve to the unit before shutting off the electrical supply. Failure to do so can result in an explo­sion or fire causing property damage, severe personal injury or death!
DANGER
!
Page 24
24 IM 863
knob in the “ON” position only. Do not use the gas control knob as a means for throttling the burner input rate.
8 Replace the control door.
9 Turn on all electric power to the unit.
10 Set the thermostat to the desired setting.
11 If the unit will not operate, follow the instructions
below on how to shut down the furnace.
The initial start-up on a new installation may require the con­trol system to be energized for some time until air has bled through the system and fuel gas is available at the burners.
To Shut Down Furnace
1 Set the thermostat to the lowest setting.
2 Turn off all electric power to the unit if service is to be
performed.
3 Remove control door.
4 Move control knob to the “OFF” position.
5 Replace control door.
Burners
Burners for these units have been designed so that field adjustment is not required. Burners are tray-mounted and accessible for easy cleaning when required.
Manual Reset Overtemperature Control
Four manual reset overtemperature controls are located on the burner shield. These devices senses blockage in the heat exchanger or insufficient combustion air. This shuts off the main burners if excessive temperatures occur in the burner compartment.
Operation of this control indicates an abnormal condition. Therefore, the unit should be examined by a qualified installer, service agency, or the gas supplier before being placed back into operation.
Pressure Switch
This furnace has four pressure switches for sensing a blocked exhaust or a failed induced draft blower. They are normally open and close when the induced draft blowers start, indicat­ing air flow through the combustion chamber.
Limit Control
The supply air high temperature limit cut-off is set at the fac­tory and cannot be adjusted. It is calibrated to prevent the air temperature leaving the furnace from exceeding the maximum outlet air temperature.
IMPORTANT: Replace this control only with the identical replacement part.
Cooling Section Operation
Cooling Mode
Call for first stage cooling
1 Zone thermostat contacts close and a call for cooling is
initiated.
2 Inputs ‘Y1’ and ‘G’ to the control are energized.
3 Control senses ‘Y1’ and ‘G’. After 1 sec. delay, control
energizes indoor blower and first stage compressor.
4 Control enters normal operating loop where all inputs
are continuously checked.
5 Zone thermostat is satisfied.
6 Control de-energizes indoor blower relay after 80 sec-
ond indoor blower delay off.
7 Control in the stand by mode with solid red LED.
Call for second stage cooling. After first stage cool­ing established: starting from A4.
1 If a call for second stage cooling is initiated after a call
for first stage cooling is established, the control ener­gizes Y2 and energizes the second stage compressor.
2 Control enters normal operating loop where all inputs
are continuously checked.
Second stage satisfied: first stage still called for: starting from B2.
1 Y2 is de-energized and second stage compressor is de-
energized.
First stage and second stage called simultaneously.
1 Zone thermostat contacts close, a call for first and sec-
ond stage cooling is initiated.
2 Inputs Y1, Y2 and G to the control are energized.
3 Control senses Y1, Y2 and G, after 1 second delay,
control energizes indoor blower, first and second stage compressor are energized.
Do not jumper this device! Do not reset the over­temperature control without taking corrective action to assure that an adequate supply of combustion air is main­tained under all conditions of operation. Failure to do so can result in carbon monoxide poisoning or death. Replace this control only with the identical replacement part.
DANGER
!
Do not jumper this device! Doing so can cause a fire or explosion resulting in property damage, personal injury or death.
DANGER
!
Page 25
IM 863
25
First stage and second stage removed simultan­ously.
1 Upon a loss of Y1 and Y2 each compressor is de-ener-
gized. Control either de-energizes indoor blower relay after 80 second indoor blower delay off.
2 Control in the stand by mode with solid red LED.
Continuous Fan Mode
A ‘G’ input only indicates a zone thermostat call for continu­ous indoor blower operation.
System Operating Information
Advise the Customer
1 Change the air filters regularly. The heating system
operates better, more efficiently and more economical­ly.
2 Except for the mounting platform, keep all combustible
articles three feet from the unit and exhaust system.
3 IMPORTANT: Replace all blower doors and compartment
cover after servicing the unit. Do not operate the unit without all panels and doors securely in place.
4 Do not allow snow or other debris to accumulate in the
vicinity of the unit
Furnace Section Maintenance
The unit’s furnace should operate for many years without excessive scale build-up in flue passageways; however, it is recommended that a qualified installer, service agency, or the gas supplier annually inspect the flue passageways, the exhaust system and the burners for continued safe operation, paying particular attention to deterioration from corrosion or other sources.
If during inspection the flue passageways and exhaust system are determined to require cleaning, the following procedures should be followed (by a qualified installer, service agency,
or gas supplier):
1 Turn off the electrical power to the unit and set the
thermostat to the lowest temperature.
2 Shut off the gas supply to the unit either at the
meter or at manual valve in the supply piping.
3 Remove the furnace controls access panel and the con-
trol box cover.
4 Disconnect the gas supply piping from the gas valve.
5 Disconnect the wiring to the induced draft blower
motors, gas valve, flame sensor, and flame roll-out con­trol, and ignitor cable. Mark all wires disconnected
for proper reconnection.
6 Remove the screws (4) connecting the burner tray to
the heat exchanger mounting panel.
7 Remove the burner tray and the manifold assembly
from the unit.
8 Remove the screws (10) connecting the two induced
draft blowers to the collector box and screws (12) con­necting the inducer mounting plate to the heat exchang­er center panel. Remove the induced draft blowers and the collector box from the unit.
9 Remove the turbulators from inside the heat exchangers
by inserting the blade of a screwdriver under the lock­ing tabs. Pop the tabs out of the expanded grooves of the heat exchanger. Slide the turbulators out of the heat exchangers.
10 Direct a water hose into the outlet of the heat exchanger
top. Flush the inside of each heat exchanger tube with water. Blow out each tube with air to remove excessive moisture.
11 Reassemble (steps 1 through 9 in reverse order). Be
careful not to strip out the screw holes used to mount the collector box and inducer blower. Replace inducer blower gasket and collector box gasket with factory replacements if damaged.
The manufacturer recommends that a qualified installer, serv­ice agency or the gas supplier visually inspect the burner flames for the desired flame appearance at the beginning of the heating season and approximately midway in heating sea­son.
The manufacturer also recommends that a qualified installer, service agency or the gas supplier clean the flame sensor with steel wool at the beginning of the heating season.
Lubrication
IMPORTANT: DO NOT attempt to lubricate the bearings on the blower motor or the induced draft blower motor. Addition of lubri­cants can reduce the motor life and void the warranty.
The blower motor and induced draft blower motor are prelu­bricated by the manufacturer and do not require further atten­tion.
Label all wires prior to disconnection when servicing con­trols. Wiring errors can cause improper and dangerous operation resulting in fire, electrical shock, property dam­age, personal injury or death.
DANGER
!
Holes in the exhaust transition or heat exchanger can cause toxic fumes to enter the home. The exhaust transi­tion or heat exchanger must be replaced if they have holes or cracks in them. Failure to do so can cause carbon monoxide poisoning resulting in personal injury or death.
DANGER
!
Power supply to unit must be disconnected before making field connections. To avoid electrical shock, personal injury or death, be sure to rigorously adhere to field wiring proce­dures regarding proper lockout and tagout of components.
DANGER
!
Page 26
26 IM 863
A qualified installer, service agency or the gas supplier must periodically clean the motors to prevent the possibility of overheating due to an accumulation of dust and dirt on the windings or on the motor exterior. And, as suggested else­where in these instructions, the air filters should be kept clean because dirty filters can restrict air flow and the motor depends upon sufficient air flowing across and through it to prevent overheating.
Cooling Section Maintenance
It is recommended that at the beginning of each cooling sea­son a qualified installer or service agency inspect and clean the cooling section of this unit. The following areas should be addressed: evaporator coil. condenser coil, condenser fan motor and venturi area.
To inspect the evaporator coil:
1 Open the control/filter access panel and remove filters.
Also, remove blower access panel. In downflow appli­cations remove the horizontal return to gain access.
2 Shine a flashlight on the evaporator coil (both sides)
and inspect for accumulation of lint, insulation, etc.
3 If coil requires cleaning, follow the steps shown below.
Cleaning Evaporator Coil
1 The coil should be cleaned when it is dry. If the coil is
coated with dirt or lint, vacuum it with a soft brush attachment. Be careful not to bend the coil fins.
2 If the coil is coated with oil or grease, clean it with a
mild detergent-and-water solution. Rinse the coil thor­oughly with water. IMPORTANT: Do not use excessive
water pressure. Excessive water pressure can bend the fins and tubing of the coil and lead to inadequate unit per­formance. Be careful not to splash water excessively into unit.
3 Inspect the drain pan and condensate drain at the same
time the evaporator coil is checked. Clean the drain pan by flushing with water and removing any matters of obstructions which may be present.
4 Go to next section for cleaning the condenser coil.
Cleaning Condenser Coil, Condenser Fan, Circulation Air Blower and Venturi
1 Remove the condenser access end panel and/or com-
pressor access louver panel. Disconnect the wires to the condenser fan motor in the control box (see wiring dia­gram).
2 The coil should be cleaned when it is dry. If the coil is
coated with dirt or lint, vacuum it with a soft brush attachment. Be careful not to bend the coil fins.
3 If the coil is coated with oil or grease, clean it with a
mild detergent-and-water solution. Rinse the coil thor­oughly with water.
IMPORTANT: Do not use excessive water pressure. Excessive water pressure can bend the fins and tubing of the coil and lead to inadequate unit per­formance. Be careful not to splash water excessively into unit.
4 The venturi should also be inspected for items of
obstruction such as collections of grass, dirt or spider webs. Remove any that are present.
5 Inspect the circulating air blower wheel and motor for
accumulation of lint, dirt or other obstruction and clean it necessary. Inspect the blower motor mounts and the blower housing for loose mounts or other damage. Repair or replace if necessary.
Re-assembly
1 Reconnect fan motor wires per the wiring diagram
attached to the back of the control cover.
2 Replace the control box cover.
3 Close the filter/control access panel and replace the
blower/evaporator coil access panels.
4 Restore electrical power to the unit and check for prop-
er operation, especially the condenser fan motor.
Replacement Parts
To find your local McQuay Certified Parts Distributor, go to www.mcquay.com and select Parts Locator.
Troubleshooting
Refer to Figures 25 and 26 for determining cause of unit problems.
Wiring Diagrams
Figures 27 through 32 are complete wiring diagrams for the unit and its power sources. Also located on back of compres­sor access panel.
Charging
See Figures 33 and 34 for proper charging information.
Power supply to unit must be disconnected before making field connections. To avoid electrical shock, personal injury or death, be sure to rigorously adhere to field wiring proce­dures regarding proper lockout and tagout of components.
DANGER
!
Label all wires prior to disconnection when servicing the unit. Wiring errors can cause improper and dangerous operation resulting in fire, electrical shock, property dam­age, severe personal injury or death.
DANGER
!
Page 27
IM 863
27
E.S.P. - Inches of Water
15 TON PACKAGE UNIT - 60 Hz
———
637
653
669
685
701
717
733
749
765
———
1494
1738
1981
2224
2468
2711
2955
3198
3442
AIR-FLOW PERFORMANCE – 15 TON MODELS
TABLE 9
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3
1.4
1.5 1.6 1.7 1.8 1.9 2.0
STD
CFM
RPM RPM
WATTS WATTS
RPM
WATTS
RPM RPM
WATTS WATTS
RPM
WATTS
RPM
WATTS
RPM RPM
WATTS WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM RPM
WATTS WATTS
RPM RPM RPM RPM
WATTS WATTS WATTS WATTS
4800
5000
5200
5400
5600
5800
6000
6200
6400
6600
6800
7000
7200
———
640
656
672
688
704
720
736
752
768
784
———
1394
1638
1881
2125
2368
2611
2855
3098
3342
3585
644
660
676
692
708
724
740
756
772
788
804
1294
1538
1781
2025
2268
2512
2755
2998
3242
3485
3729
631
647
663
679
695
711
727
743
759
775
791
807
877
951
1194
1438
1681
1925
2168
2412
2655
2899
3142
3385
3629
3821
650
666
682
698
714
731
747
763
779
795
811
881
890
1095
1338
1581
1825
2068
2312
2555
2799
3042
3286
3529
3695
4000
670
686
702
718
734
750
766
782
798
814
885
894
903
1238
1482
1725
1968
2212
2455
2699
2942
3186
3429
3569
3874
4179
689
705
721
737
753
769
785
801
817
889
898
907
916
1382
1625
1869
2112
2355
2599
2842
3086
3329
3442
3748
4053
4358
709
725
741
757
773
789
805
821
893
920
911
902
929
1525
1769
2012
2256
2499
2742
2986
3229
3316
3622
3927
4232
4538
728
744
760
776
792
808
888
897
906
915
924
933
942
1669
1912
2156
2399
2643
2886
2885
3190
3495
3801
4106
4411
4717
747
764
780
796
812
892
901
910
919
928
937
946
955
1812
2056
2299
2543
2786
2759
3064
3369
3675
3980
4285
4591
4896
767
783
799
815
896
905
914
923
932
941
950
959
968
1956
2199
2443
2686
2632
2938
3243
3548
3854
4159
4464
4770
5075
786
802
818
900
909
918
927
936
945
954
963
972
2100
2343
2586
2506
2812
3117
3422
3727
4033
4338
4643
4949
806
822
904
913
922
931
940
949
958
967
976
2243
2487
2380
2685
2991
3296
3601
3907
4212
4517
4823
899
908
917
926
935
944
953
962
971
980
989
1949
2254
2559
2864
3170
3475
3780
4086
4391
4696
5002
912
921
929
936
947
956
965
974
983
992
———
2128
2433
2738
3044
3349
3654
3960
4265
4570
4876
———
924
933
942
951
960
969
978
987
996
1005
———
2307
2612
2917
3223
3528
3833
4139
4444
4749
5055
———
937
946
955
964
973
982
991
1000
1009
———
950
959
968
977
986
995
1004
1013
—————
963
972
981
990
999
1008
1017
—————
976
985
994
1003
1012
1021
———————
2486
2791
3097
3402
3707
4012
4318
4623
4928
———
2665
2970
3276
3581
3886
4192
4497
4802
—————
2844
3149
3455
3760
4065
4371
4876
—————
3023
3329
3634
3939
4245
4550
———————
DRIVE PACKAGE L
3.0 BK-90
1VP-44
123 456
823 787
750
710 670 629
MOTOR HP
BLOWER SHEAVE
MOTOR SHEAVE
TURNS OPEN
RPM
NOTES: 1. Factory sheave settings shown in bold type.
2. Do not set sheave below minimum turns open shown.
3. Re-adjustment of sheave required to achieve rated airflow at ARI minimum E.S.P.
4. Drive data shown is for horizontal airflow with dry coil. Add component resistance
to duct resistance to determine total E.S.P.
DRIVE PACKAGE M
5
BK-72
1VP-44
1.5 2 3
4
56
1022 1017 1006
933
860 786
MOTOR HP
BLOWER SHEAVE
MOTOR SHEAVE
TURNS OPEN
RPM
COMPONENT RESISTANCE TABLE
CFM WET COIL DOWNFLOW
4800 0.020 0.010
5200 0.040 0.020
5600 0.060 0.030
6000 0.080 0.040
6400 0.100 0.050
6800 0.125 0.060
7200 0.150 0.070
Page 28
28 IM 863
701
717
733
749
765
781
797
813
829
845
861
877
911
920
929
938
947
2468
2711
2955
3198
3442
3685
3929
4172
4415
4659
4902
5146
5726
6032
6337
6642
6948
AIR-FLOW PERFORMANCE – 20 TON MODELS
TABLE 10
E.S.P. - Inches of Water
20 TON PACKAGE UNIT - 60 Hz
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3
1.4
1.5 1.6 1.7 1.8 1.9 2.0
STD
CFM
RPM RPM
WATTS WATTS
RPM
WATTS
RPM RPM
WATTS WATTS
RPM
WATTS
RPM
WATTS
RPM RPM
WATTS WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM RPM
WATTS WATTS
RPM RPM RPM RPM
WATTS WATTS WATTS WATTS
6400
6600
6800
7000
7200
7400
7600
7800
8000
8200
8400
8600
8800
9000
9200
9400
9600
720
736
752
768
784
801
817
833
849
865
881
915
924
933
942
951
960
2611
2855
3098
3342
3585
3829
4072
4316
4559
4802
5046
5600
5905
6211
6516
6821
7127
740
756
772
788
804
820
836
852
868
910
919
928
936
945
954
963
972
2755
2998
3242
3485
3729
3972
4216
4459
4703
5169
5474
5779
6084
6390
6695
7000
7306
759
775
791
807
823
839
855
871
913
922
931
940
949
958
967
976
985
2899
3142
3385
3629
3872
4116
4359
4603
5042
5348
5653
5958
6264
6569
6874
7180
779
795
811
827
843
859
875
917
926
935
944
953
962
971
980
989
3042
3286
3529
3772
4016
4259
4503
4916
5221
5527
5832
6137
6443
6748
7053
7359
798
814
830
846
862
878
921
930
939
948
957
966
975
984
993
3186
3429
3673
3916
4160
4403
4790
5095
5401
5706
6011
6317
6622
6927
7233
817
834
850
866
882
925
934
943
952
961
970
979
988
997
1006
3329
3573
3816
4060
4303
4664
4696
5274
5580
5885
6190
6496
6801
7106
7412
837
853
869
920
929
938
947
956
965
974
983
992
1001
1010
———
3473
3716
3960
4232
4538
4843
5148
5454
5759
6064
6369
6675
6980
7285
———
856
872
924
933
942
951
960
969
978
987
996
1005
1014
———
3616
3860
4106
4411
4717
5022
5327
5633
5938
6243
6549
6854
7159
———
876
928
937
946
955
964
973
982
991
1000
1009
1018
1027
———
3760
3980
4285
4591
4896
5201
5506
5812
6117
6422
6728
7033
7338
———
932
941
950
959
968
977
986
995
1004
1013
1022
1031
—————
3854
4159
4464
4770
5075
5380
5686
5991
6296
6602
6907
7212
—————
945
954
963
972
981
990
999
1008
1017
1026
1035
1044
—————
4033
4338
4643
4949
5254
5559
5865
6170
6475
6781
7086
7391
—————
958
967
976
985
994
1003
1012
1021
1030
1039
1048
—————
4212
4517
4823
5128
5433
5739
6044
6349
6655
6960
7265
—————
971
980
989
998
1007
1015
1024
1033
1042
1051
———————
4391
4696
5002
5307
5612
5918
6223
6528
6834
7139
———————
983
992
1001
1010
1019
1028
1037
1046
1055
1064
———————
4570
4876
5181
5486
5791
6097
6402
6707
7013
7318
———————
996
1005
1014
1023
1032
1041
1050
1059
1068
———————
4749
5055
5360
5665
5971
6276
6581
6887
7192
———————
1009
1018
1027
1036
1045
1054
1063
1072
1081
———————
1022
1031
1040
1049
1058
1067
1076
1085
—————————
1035
1044
1053
1062
1071
1080
1089
1098
—————————
1048
1057
1066
1075
1084
1093
1102
—————————
4928
5234
5539
5844
6150
6455
6760
7066
7371
———————
5108
5413
5718
6024
6329
6634
6940
7245
—————————
5287
5592
5897
6203
6508
6813
7119
7424
—————————
5466
5771
6076
6382
6687
6992
7298
—————————
DRIVE PACKAGE L
5.0 BK-95
1VP-50
1 2 3 456
882 846 810 773 736 700
MOTOR HP
BLOWER SHEAVE
MOTOR SHEAVE
TURNS OPEN
RPM
NOTES: 1. Factory sheave settings shown in bold type.
2. Do not set sheave below minimum turns open shown.
3. Re-adjustment of sheave required to achieve rated airflow at ARI minimum E.S.P.
4. Drive data shown is for horizontal airflow with dry coil. Add component resistance
to duct resistance to determine total E.S.P.
DRIVE PACKAGE M
7.5 BK-90
1VP-60
123
4
56
1102 1075 1047
1006
964 922
MOTOR HP
BLOWER SHEAVE
MOTOR SHEAVE
TURNS OPEN
RPM
COMPONENT RESISTANCE TABLE
CFM WET COIL DOWNFLOW
6400 0.100 0.030
6800 0.125 0.043
7200 0.150 0.055
7600 0.175 0.068
8000 0.200 0.080
8400 0.225 0.093
8800 0.250 0.105
9200 0.275 0.118
9600 0.300 0.130
Page 29
IM 863
29
ELECTRICAL DATA
Minimum Circuit Ampacity
Minimum Overcurrent Protection Device Size
34
40
Maximum Overcurrent Protection Device Size
40
Compressor Motor
No.
4
Volts
575
Phase
3
HP
3 1/2
RPM
3450
Amps (RLA)
5
Amps (LRA)
Unit Information
Unit Operating Voltage Range
34
518-632
Condenser Motor
No.
4
Volts
575
Phase
1
HP
1/3
Amps (FLA)
4
Amps (LRA)
1.5
Evaporator Fan
No.
1
Volts
575
Phase
3
HP
3
Amps (FLA)
8
Amps (LRA)
20 33
8
5
3
575
1
1.5
4
1/3
1
575
4
34
5
3450
3 1/2
3
575
4
40
40
34
518-632
82.6
14.7
5
3
208/230
1
4.7
9.6
1/3
1
208/230
4
123/123
17.5/17.5
3450
4 3/4
3
200/230
4
110/110
110/110
99/99
187-253
82.6
14.7
5
3
208/230
1
4.7
9.6
1/3
1
208/230
4
123/123
17.5/17.5
3450
4 3/4
3
200/230
4
110/110
110/110
99/99
187-253
136
22.3
7.5
3
208/230
1
4.7
9.6
1/3
1
208/230
4
123/123
17.5/17.5
3450
4 3/4
3
200/230
4
125/125
125/125
108/108
187-253
136
22.3
7.5
3
208/230
1
4.7
9.6
1/3
1
208/230
4
123/123
17.5/17.5
3450
4 3/4
3
200/230
4
125/125
125/125
108/108
187-253
41.3
10
5
3
460
1
2.4
8
1/3
1
460
4
62
9
3450
4 3/4
3
460
4
60
60
57
414-506
41.3
10
5
3
460
1
2.4
8
1/3
1
460
4
62
9
3450
4 3/4
3
460
4
60
60
57
414-506
Model MPS-
015AGYL35E 015AGYM35E 020AGCL30E 020AGCL40E 020GCM30E 020GCM40E A020AGDL30E A020AGDL40E
1. Horsepower Per Compressor.
2. Amp Draw Per Motor. Multiply Value By Number of Motors to Determine Total Amps.
ELECTRICAL DATA
ELECTRICAL DATA
Minimum Circuit Ampacity
Minimum Overcurrent
Protection Device Size
74/74
80/80
Maximum Overcurrent Protection Device Size
80/80
Compressor Motor
No.
4
Volts
200/230
Phase
3
HP
3 1/3
RPM
3450
Amps (RLA)
12.4/12.4
Amps (LRA)
Unit Information
Unit Operating Voltage Range
88/88
187-253
Condenser Motor
No.
4
Volts
208/230
Phase
1
HP
1/3
Amps (FLA)
9.6
Amps (LRA)
4.7
Evaporator Fan
No.
1
Volts
208/230
Phase
3
HP
3
Amps (FLA)
11.5
Amps (LRA)
74.5 74.5
11.5
3
3
208/230
1
4.7
9.6
1/3
1
208/230
4
88/88
12.4/12.4
3450
3 1/3
3
200/230
4
80/80
80/80
74/74
187-253
82.6
14.7
5
3
208/230
1
4.7
9.6
1/3
1
208/230
4
88/88
12.4/12.4
3450
3 1/3
3
200/230
4
90/90
90/90
78/78
187-253
82.6
14.7
5
3
208/230
1
4.7
9.6
1/3
1
208/230
4
88/88
12.4/12.4
3450
3 1/3
3
200/230
4
80/80
80/80
77/77
187-253
38.1
7
3
3
460
1
2.4
8
1/3
1
460
4
44
6.4
3450
3 1/2
3
460
4
45
45
43
414-506
38.1
7
3
3
460
1
2.4
8
1/3
1
460
4
44
6.4
3450
3 1/2
3
460
4
45
45
43
414-506
41.3
10
5
3
460
1
2.4
8
1/3
1
460
4
44
6.4
3450
3 1/2
3
460
4
50
50
47
414-506
41.3
10
5
3
460
1
2.4
8
1/3
1
460
4
44
6.4
3450
3 1/2
3
460
4
50
50
47
414-506
Model MPS-
015AGCL25E 015AGCL35E 015AGCM25E 015AGCM35E 015AGDL25E 015AGDL35E 015AGDM25E 015AGDM35E
1. Horsepower Per Compressor.
2. Amp Draw Per Motor. Multiply Value By Number of Motors to Determine Total Amps.
Page 30
30 IM 863
ELECTRICAL DATA
ELECTRICAL DATA
Minimum Circuit Ampacity 58
Unit Information
Unit Operating Voltage Range
414-506
Minimum Overcurrent Protection Device Size
60
Maximum Overcurrent
Protection Device Size
60
Compressor Motor
No. 4
Volts 460
Phase 3
HP
4 3/4
RPM 3450 Amps (RLA) 9 Amps (LRA) 62
Condenser Motor
No. 4
Volts 460
Phase 1
HP 1/3 Amps (FLA) 8 Amps (LRA) 2.4
Evaporator Fan
No. 1
Volts 460
Phase 3
HP 7.5 Amps (FLA) 11.2 Amps (LRA) 68 68
11.2
7.5
3
460
1
2.4
8
1/3
1
460
4
62
9
3450
4 3/4
3
460
4
60
60
58
414-506
33
8
5
3
575
1
1.5
4
1/3
1
575
4
50
7.1
3450
4
3
575
4
50
45
43
518-632
53.8
8.8
7.5
3
575
1
1.5
4
1/3
1
575
4
50
7.1
3450
4
3
575
4
50
50
44
518-632
Model MPS-
020AGDM30E 020AGDM40E 020AGYL40E 020AGYM40E
1. Horsepower Per Compressor.
2. Amp Draw Per Motor. Multiply Value By Number of Motors to Determine Total Amps.
Page 31
IM 863
31
SYMPTOM POSSIBLE CAUSE REMEDY
Unit will not run • Power off or loose electrical connection • Check for correct voltage at compressor contactor in control
box
• Thermostat out of calibration-set too high • Reset
• Failed contactor • Check for 24 volts at contactor coil - replace if contacts are open
• Blown fuses • Replace fuses
• Transformer defective • Check wiring-replace transformer
• High pressure control open (if provided) • Reset-also see high head pressure remedy-The high pressure control opens at 450 PSIG
• Interconnecting low voltage wiring damaged • Replace thermostat wiring
Condenser fan runs, compressor • Loose connection • Check for correct voltage at compressor -
doesn’t check & tighten all connections
• Compressor stuck, grounded or open motor winding • Wait at least 2 hours for overload to reset.
open internal overload. If still open, replace the compressor.
• Low voltage condition At compressor terminals, voltage must be within 10% of rating plate volts when unit is operating.
• Low voltage condition • Add start kit components
Insufficient cooling • Improperly sized unit • Recalculate load
• Improper airflow • Check - should be approximately 400 CFM per ton.
• Incorrect refrigerant charge • Charge per procedure attached to unit service panel.
• Air, non-condensibles or moisture in system • Recover refrigerant, evacuate & recharge, add filter drier
• Incorrect voltage • At compressor terminals, voltage must be within 10% of rating plate volts when unit is operating.
Compressor short cycles • Incorrect voltage • At compressor terminals, voltage must be ± 10% of
nameplate marking when unit is operating.
• Defective overload protector • Replace - check for correct voltage
• Refrigerant undercharge • Add refrigerant
Registers sweat • Low evaporator airflow • Increase speed of blower or reduce restriction - replace air
filter
High head pressure- • Restriction in liquid line, expansion device or filter drier • Remove or replace defective component low vapor pressures • Flow check piston size too small • Change to correct size piston
• Incorrect capillary tubes • Change coil assembly
High head pressure-high or • Dirty condenser coil • Clean coil
normal vapor pressure - • Refrigerant overcharge • Correct system charge
Cooling mode • Condenser fan not running • Repair or replace
• Air or non-condensibles in system • Recover refrigerant, evacuate & recharge
Low head pressure-high vapor • Defective Compressor valves • Replace compressor
pressures • Incorrect capillary tubes • Replace coil assembly
Low vapor pressure - • Low evaporator airflow • Increase speed of blower or reduce restriction - replace air
cool compressor - filter
iced evaporator coil • Operating below 65°F outdoors • Add Low Ambient Kit
• Moisture in system • Recover refrigerant - evacuate & recharge - add filter drier
High vapor pressure • Excessive load • Recheck load calculation
• Defective compressor • Replace
Fluctuating head & vapor • Air or non-condensibles in system • Recover refrigerant, evacuate & recharge
pressures
Gurgle or pulsing noise at • Air or non-condensibles in system • Recover refrigerant, evacuate & recharge
expansion device or liquid line
Figure 25
Cooling Trouble Shooting Chart
Disconnect all power to unit before servicing. Contactor may break only one side. Failure to shut off power can cause electrical shock resulting in personal injury or death.
DANGER
!
Page 32
32 IM 863
SET THERMOSTAT TO
CALL FOR HEAT
SET FAN SWITCH TO AUTO
START
FLOW CHART CONTINUED ON NEXT PAGE
NO
YES
YES
YES
YES
NO
NO
NO
INDUCED DRAFT BLOWER
MOTOR STARTS
30 SECOND PREPURGE
REPLACE INTEGRATED CONTROL BOARD (IFC)
REPLACE INDUCED
DRAFT BLOWER(S)
NO
REPLACE NEGATIVE PRESSURE SWITCH
REPLACE INTEGRATED CONTROL BOARD (IFC)
IF WIRING IS OK
CHECK FOR EXHAUST,
INTAKE OR HEAT
EXCHANGER BLOCKAGE
AND RESET CONTROL
NO
REPLACE IGNITION CON-
TROL
YES
REPLACE VALVE
• CHECK LINE VOLTAGE TO IFC
• CHECK LOW VOLTAGE TRANSFORMER
• CHECK WIRING
• CHECK FOR 208-230 VAC TO IDM MOTOR
• CHECK IGNITOR CABLE
• CHECK SPARK IGNITOR POSITION AND CONDITION
• IS EACH NEGATIVE PRESSURE SWITCH CLOSED?
• CHECK FOR OPEN ROLL-OUT CONTROLS
• CHECK FOR OPEN LIMIT
• CHECK IGNITION CONTROL CHASSIS GROUND WIRE
• CHECK WIRING
• CHECK INLET GAS PRESSURE
• CHECK 24 VOLTS TO GAS VALVE
• CHECK FOR GAS FLOW TO AND FROM VALVE
• CHECK BURNER CARRYOVER
NOTE: THE SYSTEM WILL ATTEMPT TO LIGHT 3 TIMES WITH A 60 SECOND INTER-
PURGE BETWEEN TRIES. IF AFTER THE THIRD TIME THE BURNERS DO NOT LIGHT, THE SYSTEM WILL LOCK OUT. IF THE UNIT IS EQUIPPED WITH A UNITED TECH. THE SYSTEM WILL ATTEMPT TO LIGHT 3 TIMES EACH HOUR UNTIL THE BURNERS LIGHT OR THE THERMOSTAT IS RESET OR POWER IS REMOVED FOR 3 SECONDS OR GREATER.
YES
YES
IGNITOR SPARKS
MAIN BURNER LIGHTS
NO
• CHECK NEGATIVE PRESSURE SWITCH SENSING TUBE
• CHECK FOR EXHAUST BLOCKAGE
YES
YES
YES
REPLACE IGNITOR/ CABLE ASSEMBLY
REPLACE LIMIT IF UNIT IS COLD
NO
Figure 26: Furnace Troubleshooting Guide (Combination Heating and Cooling Units With Direct Spark Ignition)
HAZARDOUS VOLTAGE
LINE VOLTAGE CON-
NECTIONS
DISCONNECT POWER BEFORE SERVICING. SERVICE MUST BE BY A TRAINED, QUALIFIED SERVICE TECHNICIAN.
WARNING
!
Page 33
IM 863
33
NOTE: IF THE SYSTEM GOES INTO LOCKOUT, WAIT
30 SECONDS AND RESET THE SYSTEM.
• CHECK FLAME SENSOR POSITION AND CONDITION
• CLEAN FLAME SENSOR WITH STEEL WOOL
• CHECK FLAME SENSOR WIRES AND CONNECTIONS
• CHECK FOR 208-230 VAC ACROSS BLOWER MOTOR TERMINALS ON CONTROL BOARD
• CHECK FOR LINE VOLTAGE AT LOAD SIDE OF BLOWER CONTACT.
YES
YES
NO
MAIN BURNER FLAME SUSTAINED
YES
NO
INDOOR BLOWER MOTOR STARTS
AFTER 45 SECONDS
REPLACE SENSOR
NO
REPLACE INTEGRATED CONTROL BOARD (IFC)
NO
REPLACE IGNITION CON-
TROL
YES
REPLACE BLOWER
MOTOR
• CHECK FOR OPEN LIMIT
• CHECK FOR OPEN ROLL-OUT CONTROL
• CHECK FOR PROPER THERMOSTAT OPERATION
• REMOVE VALVE LEAD AT GAS VALVE IF VALVE CLOSES, RECHECK THE THERMOSTAT AND WIRING. IF OK, THEN REPLACE VALVE
YES
NO
SYSTEM RUNS UNTIL
CALL FOR HEAT ENDS
TROUBLESHOOTING ENDS
REPEAT PROCEDURE UNTIL TROUBLE FREE
OPERATION IS OBTAINED.
YES
NO
TURN THERMOSTAT OFF
VALVE SHUTS OFF
FLAME SHUTS OFF
YES
INDUCED DRAFT MOTOR(S) STOPS
AFTER 5 SECOND POSTPURGE
YES
YES
• CHECK FOR DIRTY FILTERS
• CHECK FOR RESTRICTED AIR-FLOW
CHECK FOR EXHAUST,
INTAKE OR HEAT EXCHANG-
ER BLOCKAGE
CLEAR BLOCKAGE AND
RESET CONTROL
YES
INDOOR BLOWER MOTOR STOPS
AFTER 90 SECONDS
YES
FURNACE STARTS ON HIGH FIRE. FURNACE SWITCHES TO LOW FIRE AFTER 120 SECONDS WARMUP IF THERMOSTAT IS CALLING FOR W1. FURNACE WILL SWITCH TO HIGH FIRE IF LOW FIRE DOES NOT SATIS­FY THERMOSTAT DEMAND FOR HEAT LOAD.
Page 34
34 IM 863
Figure 27
WIRING DIAGRAM
208-230, 3 PH, 60 HZ.
VOLTAGES
ROOFTOP
Page 35
IM 863
35
Figure 28
WIRING SCHEMATIC
208 - 230, 3 PH, 60 HZ.
ROOFTOP
Page 36
36 IM 863
Figure 29
WIRING DIAGRAM
460V, 3 PH, 60 HZ.
Page 37
IM 863
37
Figure 30
WIRING SCHEMATIC
460V, 3 PH, 60 HZ.
Page 38
38 IM 863
Figure 31
Page 39
IM 863
39
Figure 32
Page 40
40 IM 863
Figure 33
Page 41
IM 863
41
Figure 34
Page 42
42 IM 863
Page 43
IM 863
43
Page 44
44 IM 863
McQuay Training and Development
© 2007 McQuay International • www.mcquay.com • 800-432-1342
Now that you have made an investment in modern, efficient McQuay equipment, its care should be a high priority. For training information on all McQuay HVAC products, please visit us at www.mcquay.com and click on training, or call 540-248-9646 and ask for the Training Department.
Warranty
All McQuay equipment is sold pursuant to its standard terms and conditions of sale, including Limited Product Warranty. Consult your local McQuay Representative for warranty details. Refer to Form 933-43285Y. To find your local McQuay Representative, go to www.mcquay.com.
This document contains the most current product information as of this printing. For the most up-to-date product information, please go to www.mcquay.com.
Loading...