This manual contains the installation and operating instructions for your packaged rooftop system. There are a few precautions that should be taken to derive maximum satisfaction
from it. Improper installation can result in unsatisfactory
operation or dangerous conditions.
Read this manual and any instructions packaged with separate
equipment required to make up the system prior to installation. Give this manual to the owner and explain its provisions.
The owner should retain this manual for future reference.
Checking Product Received
This manual contains the installation and operating instructions for your combination gas heating/electric cooling unit.
There are some precautions that should be taken to derive
maximum satisfaction from it. Improper installation can result
in unsatisfactory operation or dangerous conditions.
Read this manual and any instructions packaged with separate
equipment required to make up the system prior to installation. Give this manual to the owner and explain its provisions.
The owner should retain this manual for future reference.
Equipment Protection From The
Environment
Upon receiving the unit, inspect it for any damage from shipment. Claims for damage, either shipping or concealed,
should be filed immediately with the shipping company.
IMPORTANT: Check the unit model number, heating size, electrical characteristics, and accessories to determine if they are
correct.
Specifications
General
The unit is available in 250,000 AND 350,000 BTUH heating
input with nominal cooling capacity of 15 tons. 300,000 and
400,000 BTUH heating inputs are available in nominal cooling capacity of 20 tons. Units are convertible from bottom
supply and return to side supply and return by relocation of
supply and return air cover panels. See cover installation
detail and Figures 10 &11.
The units are weatherized for mounting outside of the building.
Major Components
The unit includes a hermetically-sealed refrigerating system
consisting of a scroll compressor, condenser coil, evaporator
coil with capillary tube assembly, a supply air fan, a condenser fan, a heat exchanger assembly, gas burner and control
assembly, combustion air motors and fan, and all necessary
internal electrical wiring. The cooling system of these units is
factory-evacuated, charged and performance tested.
Refrigerant amount and type are indicated on rating plate.
The manufacturer’s warranty does not cover any damage
or defect to the air conditioner caused by the attachment or
use of any components, accessories or devices (other than
those authorized by the manufacturer) into, onto or in conjunction with the air conditioner. You should be aware that
the use of unauthorized components, accessories or
devices may adversely affect the operation of the air conditioner and may also endanger life and property. The manufacturer disclaims any responsibility for such loss or injury
resulting from the use of such unauthorized components,
accessories or devices.
▲▲
DANGER
!
Units are not design certified to be installed inside the
structure. Doing so can cause inadequate unit performance
as well as property damage and carbon monoxide poisoning resulting in personal injury or death.
▲▲
DANGER
!
Page 4
4IM 863
Safety Information
Use only with type of gas approved for this unit. Refer to
the unit rating plate.
▲▲
WARNING
!
Install this unit only in a location and position as specified in
the location requirements and considerations section of
these instructions. Provide adequate combustion and ventilation air to the unit space as specified in the venting section of these instructions.
▲▲
WARNING
!
Provide adequate combustion and ventilation air to the unit
space as specified in the combustion and ventilation air
section of these instructions.
▲▲
WARNING
!
Combustion products must be discharged outdoors.
Connect this unit to an approved vent system only, as
specified in vent Pipe Installation section of these instructions.
▲▲
WARNING
!
Never test for gas leaks with an open flame. It can cause
an explosion or fire resulting in property damage, personal
injury or death. Use a commercially available soap solution
made specifically for the detection of leaks to check all connections, as specified in the Gas Supply and Piping section
of these instructions.
▲▲
DANGER
!
Always install unit to operate within the unit's intended temperature-rise range with a duct system which has an external static pressure within the allowable range, as specified
in ducting section of these instructions. See also unit rating
plate.
▲▲
WARNING
!
When a unit is installed so that supply ducts carry air circulated by the unit to areas outside the space containing the
unit, the return air shall also be handled by duct(s) sealed
to the unit casing and terminating outside the space containing the unit.
▲▲
WARNING
!
This unit may be used to heat the building or structure during construction if the following installation requirements are
met. installation must comply with all installation instructions including:
• proper vent installation;
• furnace operating under thermostatic control;
• return air duct sealed to the furnace;
• air filters in place;
• set furnace input rate and temperature rise per rating
plate marking;
• means of providing outdoor air required for combustion;
• return air temperature maintained between 55°F (13°C)
and 80°F (27°C); and
• installation of exhaust and combustion air inlet hoods
completed;
• clean furnace, duct work and components upon substantial completion of the construction process, and verify furnace operating conditions including ignition, input rate,
temperature rise and venting according to the instructions.
▲▲
WARNING
!
Page 5
IM 863
5
Figure 1: Unit Dimensions - Bottom View
Figure 2: Supply and Return Dimensions for Downflow Applications - Bottom View
Unit Dimensions
FOR CLEARANCES SEE PAGE 28, FIGURE 12.
IMPORTANT: THIS UNIT MUST BE MOUNTED LEVEL IN
BOTH DIRECTIONS TO ALLOW WATER TO DRAIN FROM
THE CONDENSER SECTION AND CONDENSATE PAN.
ST-A0886-02
ST-A0886-07
SUPPLY
AIR
RETURN
AIR
Page 6
6IM 863
Figure 3: Component Locations & Dimensions
ST-A0886-04
Figure 4: Component Locations & Dimensions
ST-A0886-06
Figure 5: Component Locations
ST-A0886-27
GAS SUPPLY
(SIDE ENTRY)
3/4” INLET
FILTER OPENING
BLOWERS
FURNACE
INDOOR MOTOR
COMPRESSOR #1
COMPRESSOR #2
INDOOR COIL
OUTDOOR FAN #1
OUTDOOR FAN #2
BLOWER ACCESS
FLUE HOODS
POWER ENTRY
CONDENSATE DRAIN
1” FNPT
COMBUSTION
AIR INLETS
COMPRESSOR ACCESS
CONTROL/FILTER
ACCESS
FURNACE ACCESS
33.250
5.625
144.750
OPTIONAL OUTDOOR
AIR HOOD LOCATION
DISCONNECT
LOCATION
OPTIONAL EXHAUST
HOOD LOCATION
50.000
50.000
17.708
5.625
33.250
44.651
146.094
CONDENSATE DRAIN
HIGH/LOW CIRCUIT #1
HIGH/LOW CIRCUIT #3
HIGH/LOW CIRCUIT #2
HIGH/LOW CIRCUIT #4
HIGH PRESSURE SWITCH
CRKT #1
HIGH PRESSURE SWITCH
CRKT #3
HIGH PRESSURE SWITCH
CRKT #2
HIGH PRESSURE SWITCH
CRKT #4
57.438
OUTDOOR FAN #4
OUTDOOR FAN #3
CONTROL COMPARTMENT
DISCONNECT
LOCATION
Page 7
IM 863
7
Figure 7: Component Access Locations & Dimensions
ST-A0886-05
ST-A0886-03
Figure 8: Component Locations
ST-A0886-28
Figure 6: Dimensions – Back View
OUTDOOR FAN #4
SUPPLY COVER
RETURN COVER
COMPRESSOR ACCESS
146.094
3.815
46.185
58.836
4.610
6.843
13.719
19.594
24.319
25.869
6.230
REMOVE COVER PLATE WHEN
CONVERTING FROM DOWNFLOW
TO HORIZONTAL CONFIGURATION.
OUTDOOR FAN #3
OUTDOOR COIL
COMPRESSOR #4
COMPRESSOR #3
HEAT EXCHANGER
FILTER RACK
RETURN COMPARTMENT
OUTDOOR FAN #1
OUTDOOR FAN #2
42.750
146.094
18.443
5.876
20.000
4.483
13.344
7.220
47.221
50.000
3.730
Page 8
8IM 863
General Data
[] Designates Metric Conversions
NOM. SIZES 15 & 20 TON S [52.8-70.3 kW] ASHRAE 90.1-2004 COMPLIANT MODELS
NOTES:
1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does
not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Unitsare suitable
for operation to
20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner Equipment
certification program, which isbased on ARI Standard 210/240 or 360.
2. EER and/or SEER are rated at ARI conditionsand in accordance with DOE test procedures.
3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80° F ambient,80° F entering dry bulb, and 67° F entering wet bulba
t ARI rated cfm.
4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions
using American National Standard Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations
above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet ab
ove sea level.
5. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270.
Model MPS-015AGCL25E015AGCL35E015AGCM25E015AGCM35E
Cooling Performance
No. Used/Diameter in. [mm]4/24 [609.6]4/24 [609.6]4/24 [609.6]4/24 [609.6]
Drive Type/No. SpeedsDirect/1Direct/1Direct/1Direct/1
CFM [L/s]16000 [7550]16000 [7550]16000 [7550]16000 [7550]
No. Motors/HP4 at 1/3 HP4 at 1/3 HP4 at 1/3 HP4 at 1/3 HP
Motor RPM1075107510751075
No. Used/Diameter in. [mm]2/18x9 [457.2x228.6]2/18x9 [457.2x228.6]2/18x9 [457.2x228.6]2/18x9 [457.2x228.6]
Drive Type/No. SpeedsBelt/VariableBelt/VariableBelt/VariableBelt/Variable
No. Motors1111
Motor HP3355
Motor RPM1725172517251725
Motor Frame Size5656184184
1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does
not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Unitsare suitable
for operation to
20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner Equipment
certification program, which isbased on ARI Standard 210/240 or 360.
2. EER and/or SEER are rated at ARI conditionsand in accordance with DOE test procedures.
3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80° F ambient,80° F entering dry bulb, and 67° F entering wet bulba
t ARI rated cfm.
4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions
using American National Standard Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations
above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet ab
ove sea level.
5. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270.
Model MPS-015AGDL25E015AGDL35E015AGDM25E015AGDM35E
Cooling Performance
No. Used/Diameter in. [mm]4/24 [609.6]4/24 [609.6]4/24 [609.6]4/24 [609.6]
Drive Type/No. SpeedsDirect/1Direct/1Direct/1Direct/1
CFM [L/s]16000 [7550]16000 [7550]16000 [7550]16000 [7550]
No. Motors/HP4 at 1/3 HP4 at 1/3 HP4 at 1/3 HP4 at 1/3 HP
Motor RPM1075107510751075
No. Used/Diameter in. [mm]2/18x9 [457.2x228.6]2/18x9 [457.2x228.6]2/18x9 [457.2x228.6]2/18x9 [457.2x228.6]
Drive Type/No. SpeedsBelt/VariableBelt/VariableBelt/VariableBelt/Variable
No. Motors1111
Motor HP3355
Motor RPM1725172517251725
Motor Frame Size5656184184
NOM. SIZES 15 & 20 TON S [52.8-70.3 kW] ASHRAE 90.1-2004 COMPLIANT MODELS
NOTES:
1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does
not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Unitsare suitable
for operation to
20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner Equipment
certification program, which isbased on ARI Standard 210/240 or 360.
2. EER and/or SEER are rated at ARI conditionsand in accordance with DOE test procedures.
3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80° F ambient,80° F entering dry bulb, and 67° F entering wet bulba
t ARI rated cfm.
4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions
using American National Standard Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations
above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet ab
ove sea level.
5. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270.
Model MPS-015AGYL35E015AGYM35E020AGCL30E020AGCL40E
Cooling Performance
No. Used/Diameter in. [mm]4/24 [609.6]4/24 [609.6]4/24 [609.6]4/24 [609.6]
Drive Type/No. SpeedsDirect/1Direct/1Direct/1Direct/1
CFM [L/s]16000 [7550]16000 [7550]16000 [7550]16000 [7550]
No. Motors/HP4 at 1/3 HP4 at 1/3 HP4 at 1/3 HP4 at 1/3 HP
Motor RPM1075107510751075
No. Used/Diameter in. [mm]2/18x9 [457.2x228.6]2/18x9 [457.2x228.6]2/18x9 [457.2x228.6]2/18x9 [457.2x228.6]
Drive Type/No. SpeedsBelt/VariableBelt/VariableBelt/VariableBelt/Variable
No. Motors1111
Motor HP3555
Motor RPM1725172517251725
Motor Frame Size56184184184
1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does
not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Unitsare suitable
for operation to
20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner Equipment
certification program, which isbased on ARI Standard 210/240 or 360.
2. EER and/or SEER are rated at ARI conditionsand in accordance with DOE test procedures.
3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80° F ambient,80° F entering dry bulb, and 67° F entering wet bulba
t ARI rated cfm.
4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions
using American National Standard Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations
above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet ab
ove sea level.
5. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270.
Model MPS-020AGCM30E020AGCM40E020GDL30E020AGDL40E
Cooling Performance
No. Used/Diameter in. [mm]4/24 [609.6]4/24 [609.6]4/24 [609.6]4/24 [609.6]
Drive Type/No. SpeedsDirect/1Direct/1Direct/1Direct/1
CFM [L/s]16000 [7550]16000 [7550]16000 [7550]16000 [7550]
No. Motors/HP4 at 1/3 HP4 at 1/3 HP4 at 1/3 HP4 at 1/3 HP
Motor RPM1075107510751075
No. Used/Diameter in. [mm]2/18x9 [457.2x228.6]2/18x9 [457.2x228.6]2/18x9 [457.2x228.6]2/18x9 [457.2x228.6]
Drive Type/No. SpeedsBelt/VariableBelt/VariableBelt/VariableBelt/Variable
No. Motors1111
Motor HP7.57.555
Motor RPM1725172517251725
Motor Frame Size213213184184
1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does
not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Unitsare suitable
for operation to
20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner Equipment
certification program, which isbased on ARI Standard 210/240 or 360.
2. EER and/or SEER are rated at ARI conditionsand in accordance with DOE test procedures.
3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80° F ambient,80° F entering dry bulb, and 67° F entering wet bulba
t ARI rated cfm.
4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions
using American National Standard Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations
above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet ab
ove sea level.
5. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270.
Model MPS-020AGDM30E020AGDM40E
Cooling Performance
9.7/NA9.7/NA
Nominal CFM/ARI Rated CFM [L/s]7700/7400 [3634/3492]7700/7400 [3634/3492]
ARI Net Cooling Capacity Btu [kW]232,000 [68]232,000 [68]
Net Sensible Capacity Btu [kW]168,000 [49.2]168,000 [49.2]
Net Latent Capacity Btu [kW]64,000 [18.8]64,000 [18.8]
Integrated Part Load Value
3
9.99.9
Net System Power kW23.923.9
Heating Performance (Package Gas/Electric)
4
Heating Input Btu [kW] (1st Stage /2nd Stage)150,000/300,000 [44/87.9] 200,000/400,000 [58.6/117.2]
Heating Output Btu [kW] (1st Stage /2nd Stage) 121,500/243,000 [35.6/71.2] 162,000/324,000 [47.5/94.9]
Temperature Rise Range °F [°C]15-45 [8.3/25]25-55 [13.9/30.6]
Steady State Efficiency (%)8181
No. Burners1214
No. Stages22
Gas Connection Pipe Size in. [mm]0.75 [19.05]0.75 [19.05]
020AGYL40E
246,000 [72.1]
9.7/NA
7700/7400 [3634/3492]
232,000 [68]
168,000 [49.2]
64,000 [18.8]
9.9
23.9
200,000/400,000
162,000/324,000 [47.5/94.9]
25-55 [13.9/30.6]
81
14
2
0.75 [19.05]
020AGYM40E
246,000 [72.1]
7700/7400 [3634/3492]
232,000 [68]
168,000 [49.2]
64,000 [18.8]
200,000/400,000 [58.6/117.2]
162,000/324,000 [47.5/94.9]
25-55 [13.9/30.6]
0.75 [19.05]
Compressor
Qty./Type4/Scroll4/Scroll
Outdoor Sound Rating (dB)
5
9191
Outdoor Coil—Fin TypeLouveredLouvered
Tube TypeRifledRifled
Tube Size in. [mm] OD0.375 [9.5]0.375 [9.5]
Face Area sq. ft. [sq. m]36 [3.34]36 [3.34]
Rows / FPI [FPcm]2 / 22 [9]2 / 22 [9]
Indoor Coil—Fin TypeLouveredLouvered
Tube TypeRifledRifled
Tube Size in. [mm]0.375 [9.5]0.375 [9.5]
Face Area sq. ft. [sq. m]15.75 [1.46]15.75 [1.46]
Rows / FPI [FPcm]4 / 13 [5]4 / 13 [5]
Refrigerant ControlCapillary TubesCapillary Tubes
Drain Connection No./Size in. [mm]1/1 [25.4]1/1 [25.4]
Outdoor Fan—TypePropellerPropeller
No. Used/Diameter in. [mm]4/24 [609.6]4/24 [609.6]
Drive Type/No. SpeedsDirect/1Direct/1
CFM [L/s]16000 [7550]16000 [7550]
No. Motors/HP4 at 1/3 HP4 at 1/3 HP
Motor RPM10751075
Indoor Fan—TypeFC CentrifugalFC Centrifugal
No. Used/Diameter in. [mm]2/18x9 [457.2x228.6]2/18x9 [457.2x228.6]
Drive Type/No. SpeedsBelt/VariableBelt/Variable
No. Motors11
Motor HP7.57.5
Motor RPM17251725
Motor Frame Size213213
Filter—TypeDisposableDisposable
FurnishedYesYe s
(No.) Size Recommended in. [mm](3)2x18x18 [51x457x457] (3)2x18x18 [51x457x457]
(3)2x18x24 [51x457x610] (3)2x18x24 [51x457x610]
Refrigerant Charge Oz. (Sys. 1/Sys. 2) [g]117/107 [3317/3033]117/107 [3317/3033]
1 INSTALLATION — Install this unit in accordance with
The American National Standard Z223.1-latest edition
manual entitled “National Fuel Gas Code,” and the
requirements or codes of the local utility or other authority having jurisdiction.
Additional helpful publications available from the
“National Fire Protection Association” are: NFPA-90A Installation of Air Conditioning and Ventilating Systems
1985 or latest edition. NFPA-90B - Warm Air Heating
and Air Conditioning Systems 1984.
These publications are available from:
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
2 PRE-INSTALLATION CHECK-POINTS — Before
attempting any installation, carefully consider the following points:
Structural strength of supporting members
(Rooftop Installation)
Clearances and provision for servicing
Power supply and wiring
Gas supply and piping
Air duct connections and sizing
Drain facilities and connections
Location for minimum noise and vibration - away from
bedroom windows
IMPORTANT: Before operating unit, remove compressor shipping supports from the compressor base. Failure to remove supports will casue noise and vibration.
Location Consideratons
The metal parts of this unit may be subject to rust or deterioration in adverse environmental conditions. This oxidation
could shorten the equipment’s useful life. Salt spray, fog or
mist in seacoast areas, sulphur or chlorine from lawn watering
systems, and various chemical contaminants from industries
such as paper mills and petroleum refineries are especially
corrosive.
If the unit is to be installed in an area where contaminants
are likely to be a problem, give special attention to the
equipment location and exposure.
1 Avoid having lawn sprinkler heads spray directly on the
unit cabinet.
2 In coastal areas locate the unit on the side of the building
away from the waterfront.
3 Shielding by a fence or shrubs may give some protection.
4 Frequent washing of the cabinet, fan blade and coil with
fresh water will remove most of the salt or other contaminants that build up on the unit.
5 Regular cleaning and waxing of the cabinet with an auto-
mobile polish will provide some protection.
6 A liquid cleaner may be used several times a year to
remove matter that will not wash off with water.
Several different types of protective coatings are offered in
some areas. These coatings may provide some benefit, but the
effectiveness of such coating materials cannot be verified by
the equipment manufacturer.
The best protection is frequent cleaning, maintenance and
minimal exposure to contaminants.
Outside Installation
(Typical outdoor slab installation is shown in Figure 9.)
1 Select a location where external water drainage cannot
collect around unit.
2 Provide a level slab sufficiently high enough above grade
to prevent surface water from entering the unit
3 Locate the unit to provide proper access for inspection
and servicing as shown in Figure 12.
4 Locate unit where operating sounds will not disturb
owner or neighbors.
5 Locate unit so roof runoff water does not pour directly on
the unit. Provide gutter or other shielding at roof level.
Do not locate unit in an area where excessive snow drifting may occur or accumulate.
6 Where snowfall is anticipated, the height of the unit
above the ground level must be considered. Mount unit
high enough to be above anticipated maximum area
snowfall and to allow combustion air to enter the combustion air inlet.
7 Select an area which will keep the areas of the vent, air
intake, and A/C condenser fins free and clear of obstructions such as weeds, shrubs, vines, snow, etc. Inform the
user accordingly.
Attaching Exhaust and Combustion Air
Inlet Hoods
IMPORTANT: Do not operate this unit without the exhaust/combus-
tion air inlet hood properly installed. These hoods are shipped in
cartons in the blower compartment inside the unit and must be
attached when the unit is installed. See Figure 4.
Power supply to unit must be disconnected before making
field connections. To avoid electrical shock, personal injury
or death, be sure to rigorously adhere to field wiring procedures regarding proper lockout and tagout of components.
▲▲
DANGER
!
These units are designed certified for outdoor installation
only. Installation inside any part of a structure can result in
inadequate unit performance as well as property damage.
Installation inside can also cause recirculation of flue products into the conditioned space resulting in personal injury
or death.
▲▲
DANGER
!
Page 14
14IM 863
To attach exhaust/combustion air inlet hood:
1 Remove screws securing blower access panel and remove
access panel. For location of blower access panel, see Figure
3.
2 Remove exhaust/combustion air inlet hoods from the car-
tons, located inside the blower compartment.
3 Attach blower access panel.
4 Attach the combustion air inlet/exhaust hoods with screws.
Reference Figure 4 for proper location. Screws are in carton
with the hood.
5 Vent the unit using the flue exhaust hood, as supplied from
the factory, without alteration or addition. The only exception is with factory approved additions.
Horizontal Conversion Procedure
Downflow to Horizontal
1 Remove the screws and covers from the outside of the
supply and return sections. Also remove and discard
cover plate. See Figure 7.
2 Install the covers over the bottom supply and return
openings, painted side up, inserting the leading flange
under the bracket provided. Place the back flange to top
of the front bracket provided. See Figures 10
and 11.
3 Secure the return and supply cover to front bracket with
two (2) screws.
Filter Replacement
This unit is provided with 3 - 18” X 18” X 2” and 3 - 18” X
24” X 2” disposable filters. When replacing filters, ensure
they are inserted fully to the back to prevent bypass. See
Figure 5.
Recommended supplier of this filter is:
AAF International
Part #: 54-42541-01 (18" x 18" x 2")
Part #: 54-42541-03 (18" x 24" x 2")
Figure 9: Outside Slab Installation. Closet Distribution
System. Slab Floor Construction
ST-A0886-25
Figure 10: Horizontal Conversion Detail
ST-A0886-30
Figure 11: Horizontal Conversion Detail
ST-A0886-31
Page 15
IM 863
15
Figure 12: Clearances
ST-A0886-09
FIGURE 13: Flat Rooftop Installation, Attic or Drop Ceiling Distributing System.
Mounted on Roofcurb. Curb must be level.
ST-A0886-10
Clearances
The following minimum clearances must be observed for proper unit performance and serviceability. Reference Figure 12.
Page 16
16IM 863
Rooftop Installation
1 Before locating the unit on the roof, make sure that the
roof structure is adequate to support the weight involved.
(See Electrical & Physical Tables in this manual.) THIS
IS VERY IMPORTANT AND THE INSTALLER’S
RESPONSIBILITY.
2 For rigging and roofcurb details, see Figures 14, 15, 16
and 17.
3 The location of the unit on the roof should be such as to
provide proper access for inspection and servicing.
IMPORTANT: If unit will not be put into service immediately,
block off supply and return air openings to prevent excessive
condensation.
Ducting
The installing contractor should fabricate ductwork in accordance with local codes. Use industry manuals as a guide when
sizing and designing the duct system. Contact Air
Conditioning Contractors of America, 1513 16th St. N.W.,
Washington, D.C. 20036.
Place the unit as close to the conditioned space as possible
allowing clearances as indicated. Run ducts as directly as possible to supply and return outlets. Use of non-flammable
weatherproof flexible connectors on both supply and return
connections at unit to reduce noise transmission is recommended.
On ductwork exposed to outside temperature and humidity,
use a minimum of 2” of insulation and a vapor barrier.
Distribution system in attic, furred space or crawl space
should be insulated with at least 2” of insulation.
1
⁄2” to 1”
thick insulation is usually sufficient for ductwork inside the
air conditioned space.
Provide balancing dampers for each branch duct in the supply
system. Properly support ductwork from the structure.
IMPORTANT: In the event that the return air ducts must be run
through an “unconfined” space containing other fuel burning
equipment, it is imperative that the user/building owner must be
informed against changes in construction which might change
this to a “confined space.” Also, caution the user/building owner
against installation of additional equipment, such as power ventilators, within the existing unconfined and/or confined space
which might create a negative pressure within the vicinity of
other solid, liquid, or gas fueled units.
Return Air
Do not, under any circumstances, connect return ductwork
to any other heat producing device such as fireplace insert,
stove, etc. Unauthorized use of such devices may result in
fire, carbon monoxide poisoning, explosion, personal injury,
property damage or death.
▲▲
DANGER
!
Never allow products of combustion or the flue products to
enter the return air ductwork, or the circulating air supply.
all return ductwork must be adequately sealed and secured
to the furnace with sheet metal screws, and joints taped. All
other duct joints must be secured with approved connections and sealed airtight.
Failure to prevent products of combustion from being circulated into the living space can create potentially hazardous
conditions, including carbon monoxide poisoning that could
result in personal injury or death.
▲▲
DANGER
!
ST-A0886-12
Figure 15: Lifting Detail
ST-A1084-01
Figure 14: Shipping Board Removal
REMOVE SHIPPING BOARDS
BEFORE INSTALLING UNIT.
CENTER OF
GRAVITY
CENTER OF
GRAVITY
32.9ⴖ
835.6 mm
67.1ⴖ
1704.3 mm
Page 17
IM 863
17
Gas Supply, Condensate Drain
and Piping
Gas Connection
IMPORTANT: Connect this unit only to gas supplied by a com-
mercial utility.
1 Install gas piping in accordance with local codes and reg-
ulations of the local utility company. In the absence of
local codes, the installation must conform to the specifications of the National Fuel Gas Code, ANSI Z223.1 latest edition.
NOTE: The use of flexible gas connectors is not permitted.
2 Connect the gas line to the gas valve supplied with unit.
Routing can be through the gas pipe opening shown in
Figures 9 or 13A or 13B or through the base as shown in
Figure 22.
3 Size the gas line to the furnace adequate enough to pre-
vent undue pressure drop and never less than 1/2”.
4 Install a drip leg or sediment trap in the gas supply line
as close to the unit as possible.
5 Install an outside ground joint union to connect the gas
supply to the control assembly at the burner tray.
6 Gas valves have been factory installed. Install a manual
gas valve where local codes specify a shut-off valve outside the unit casing. (See Figure 18.)
7 Make sure piping is tight. A pipe compound resistant to
the action of liquefied petroleum gases must be used
at all threaded pipe connections.
8 IMPORTANT: any additions, changes or conversions
required for the furnace to satisfactorily meet the application should be made by a qualified installer, service agency
or the gas supplier, using factory-specified or approved
parts. In the commonwealth of Massachusetts, installation
must be performed by a licensed plumber or gas fitter for
appropriate fuel.
IMPORTANT: Disconnect the furnace and its individual shutoff
valve from the gas supply piping during any pressure testing of
that system at test pressures in excess of 1/2 pound per square
inch gauge or isolate the system from the gas supply piping system by closing its individual manual shutoff valve during any
pressure testing of this gas supply system at pressures equal to
or less than 1/2 PSIG.
IMPORTANT: Check the rating plate to make certain the unit is
equipped to burn the type of gas supplied. Care should be taken
after installation of this equipment that the gas control valve not
be subjected to high gas supply line pressure.
Never test for gas leaks with an open flame. It can cause
an explosion or fire resulting in property damage, personal
injury or death. Use a commercially available soap solution
made specifically for the detection of leaks to check all connections, as specified in the Gas Supply and Piping section
of these instructions.
▲▲
DANGER
!
Page 18
18IM 863
In making gas connections, avoid strains as they may cause
noise and damage the controls. A backup wrench is required
to be used on the valve to avoid damage.
The capacities of gas pipe of different diameters and lengths
in cu. ft. per hr. with pressure drop of 0.3 in. and specific
gravity of 0.60 (natural gas) are shown in Table 3.
After determining the pipe length, select the pipe size which
will provide the minimum cubic feet per hour required for the
gas input rating of the furnace. By formula:
Gas Input of Furnace
(BTU/HR)
Cu. Ft. Per Hr. Required =
Heating Value of Gas
(BTU/FT3)
The gas input of the furnace is marked on the furnace rating
plate. The heating value of the gas (BTU/FT3) may be determined by consulting the local natural gas utility or the L.P.
gas supplier.
LP Conversion
Convert the unit to use liquefied petroleum (LP) gas by
replacing with the stem/spring assembly supplied in the conversion kit. The LP gas valve maintains the proper manifold
pressure for LP gas. The correct burner LP orifices are included in the kit.
See Figure 19A for component locations.
NOTE: Order the correct LP conversion kit from the furnace
manufacturer. See Conversion Kit Index shipped with unit for
proper LP kit number. Furnace conversion to LP gas must
be performed by a qualified technician.
This unit is equipped at the factory for use on natural gas
only. Conversion to LP gas requires a special kit supplied by
the distributor or manufacturer. Mailing addresses are listed
on the furnace rating plate, parts list and warranty. Failure to
use the proper conversion kit can cause fire, carbon monoxide poisoning, explosion, personal injury, property damage or
death.
Example (LP): Input BTU requirement of unit, 150,000
Equivalent length of pipe, 60 ft. = 3/4” IPS required.
Figure 19B: Honeywell VR8305Q4120 Two Stage Gas Valve
OUTLET PRESSURE
TAP-1/8 NPT
2-STAGE
OPERATOR
INLET PRESSURE
TAP-1/8 NPT
GROUND
TERMINAL
LOW STAGE ADJUSTMENT
UNDER VENT CAP
HIGH STAGE ADJUSTMENT
UNDER VENT CAP
Adjusting or Checking Furnace Input
– Natural Gas Line Pressure 5” - 10.5” W.C.
– LP Gas Line Pressure 11” - 13” W.C.
– Natural Gas Manifold Pressure 3.5” W.C
– LP Gas Manifold Pressure - 10” W.C.
Supply and manifold pressure taps are located on the gas
valve body 1/8” N.P.T. and on the manifold. See Figure 19B.
Use a properly calibrated manometer gauge for accurate gas
pressure readings.
Only small variations in the gas flow should be made by
means of the pressure regulator adjustment. Furnaces functioning on LP gas must be set by means of the tank or branch
supply regulators. The furnace manifold pressure should be
set at 10” W.C. at the gas control valve.
To adjust the pressure regulator, remove the regulator vent
cover and turn the adjustment screw clockwise to increase
pressure or counterclockwise to decrease pressure. See Figure
19B. Then replace the regulator vent cover securely.
Any necessary major changes in the gas flow rate should be
made by changing the size of the burner orifices. To change
orifice spuds, shut off the manual main gas valve and remove
the gas manifold.
For elevations up to 2,000 feet, rating plate input ratings
apply. For high altitudes (elevations over 2,000 ft.), see conversion kit index 92-21519-XX for derating and orifice spud
sizes.
Check of input is important to prevent over-firing of the
furnace beyond its design-rated input. NEVER SET
INPUT ABOVE THAT SHOWN ON THE RATING
PLATE. Use the following table or formula to determine
input rate.
Heating Value of Gas
(BTU/Cu. Ft.) x 3600
Cu. Ft. Per Hr. Required =
Time in Seconds
(for 1 Cu. Ft.) of Gas
Start the furnace and measure the time required to burn one
cubic foot of gas. Prior to checking the furnace input, make
certain that all other gas units are shut off, with the exception
of pilot burners. Time the meter with only the furnace in
operation.
IMPORTANT NOTE FOR ALTITUDES ABOVE 2,000 FEET
(610 METERS): The main burner orifices in your furnace and in
these kits are sized for the nameplate input and intended for
installations at elevations up to 2,000 feet in the USAor
Canada, or for elevations of 2,000 - 4,500 feet (610 -1,373
meters) in Canada if the unit has been derated at the factory.
For elevations above 2,000 feet (610 meters) IN THE USAONLY (see ANSI-Z223.1), the burner orifices must be sized to
reduce the input 4% for each 1,000 feet (305 meters) above sea
level.
NOTICE: Derating of the heating input for high altitude in the
field is unlawful in Canada (refer to can/cga 2.17). Units installed
in altitudes greater than 2,000 feet (610 meters) must be
shipped from the factory or from a factory authorized conversion
station with the heating input derated by 10% so as to operate
properly in altitudes from 2,000 - 4,500 feet (610 - 1,373
meters).
Condensate Drain
The condensate drain connection of the evaporator is
threaded 1” NPT. IMPORTANT: Install a condensate trap to
ensure proper condensate drainage. See Figure 20.
250,000ONE13.0 14.415.015.8 36.0
TEN2102242302 386 0
ONE10.812.012.513.230.0
300,000
TEN148202521250
ONE9.3 10.310.71.325.7
350,000
TEN1331431471 53417
ONE8.19.09.369 .922.5
400,000
TEN121130136139345
METER TIME IN MINUTES AND SECONDS FOR NORMAL
INPUT RATING OF FURNACES EQUIPPED FOR NATURAL
OR LP GAS
INPUT
BTU/HR
METER
SIZE
CU. FT.
HEATING VALUE OF GAS BTU PER CU. FT.
9001000104011002500
MIN. SEC. MIN. SEC. MIN. SEC. MIN. SEC. MIN. SEC.
Table 5
Page 20
20IM 863
Wiring
Power Supply
1 All wiring should be made in accordance with the
National Electrical Code. Consult the local power company to determine the availability of sufficient power to
operate the unit. Check the voltage at power supply to
make sure it corresponds to the unit’s RATED VOLTAGE REQUIREMENT. Install a branch circuit disconnect near the rooftop, in accordance with the N.E.C.,
C.E.C. or local codes.
2 It is important that proper electrical power is available at
the unit. Voltage should not vary more than 10% from
that stamped on the unit nameplate. On three phase units,
phases must be balanced within 3%.
3 For branch circuit wiring (main power supply to unit dis-
connect), the minimum wire size for the length of run
can be determined from Table 6 using the circuit ampacity found on the unit rating plate. Use the smallest wire
size allowable from the unit disconnect to unit.
4 For through the base wiring entry reference Figure 22.
All fittings and conduit are field supplied for this application. Reference the chart with Figure 22 for proper hole
and conduit size.
NOTES:
1 For branch circuit wiring (main power supply to unit discon-
nect), the minimum wire size for the length of run can be
determined from this table using the circuit ampacity found
on the unit rating plate. From the unit disconnect to unit, the
smallest wire size allowable in Table 6 may be used, as the
disconnect must be in sight of the unit.
2 Wire size based on 75°C rated wire insulation for 1% volt-
age drop.
3 For more than 3 conductors in a raceway or cable, see the
N.E.C. (C.E.C. in Canada) for derating the ampacity of
each conductor.
IMPORTANT: THIS UNIT IS APPROVED FOR USE WITH
COPPER CONDUCTORS ONL
Y CONNECTED TO UNIT CON-
TACTOR.
WARRANTY WILL BE VOIDED IF ALUMINUM WIRE IS CON-
NECTED TO UNIT CONTACTOR.
Figure 20: Condensate Drain
Power supply to unit must be disconnected before making
field connections. To avoid electrical shock, personal injury
or death, be sure to rigorously adhere to field wiring procedures regarding proper lockout and tagout of components.
To wire unit, refer to the following hook-up diagram.
Refer to Figures 2 and 22 for location of wiring entrances.
Wiring to be done in the field between the unit and devices
not attached to the unit, or between separate devices which
are field installed and located, shall conform with the temperature limitation for Type T wire [63°F rise (35°C)] when
installed in accordance with the manufacturer’s instructions.
Internal Wiring
A diagram of the internal wiring of this unit is located on the
inside of control access panel and in this manual. If any of the
original wire as supplied with the unit must be replaced, the
wire gauge and insulation must be same as original wiring.
208 Volt Applications
Transformer is factory wired for 230 volts on 208/230 volt
models and must be changed for 208 volt applications. See
unit wiring diagram for 208 volt wiring.
Thermostat
The room thermostat must be compatible with the spark ignition control on the unit. Generally, all thermostats that are not
of the “current robbing” type are compatible with the integrated furnace control. The low voltage wiring should be sized as
shown in Table 7.
Install the room thermostat in accordance with the instruction
sheet packed in the box with the thermostat.
IM 863
21
Figure 22: Base Entry Locations
ST-A0886-14
Figure 23: Typical Thermostat Wiring
WIRE SIZE, AWG
14
1/2ⴖ
7/8ⴖ
12
1/2ⴖ
7/8ⴖ
10
1/2ⴖ
7/8ⴖ
8
3/4ⴖ
1-31/32ⴖ
6
1ⴖ
1-23/64ⴖ
4
1ⴖ
1-23/64ⴖ
3
1-1/4ⴖ
1-23/32ⴖ
2
1-1/4ⴖ
1-23/32ⴖ
1
1-1/2ⴖ
1-31/32ⴖ
0
1-1/2ⴖ
1-31/32ⴖ
00
2ⴖ
2-15/32ⴖ
000
2ⴖ
2-15/32ⴖ
CONDUIT SIZE
HOLE SIZE
NOTES: 1. DETERMINE REQUIRED WIRE SIZE FROM MINIMUM CIRCUIT AMPACITY SHOWN IN INSTALLATION & OPERATING INSTRUCTION.
2. BOTTOM POWER ENTRY WILL NOT ACCOMMODATE WIRE LARGER THAN #2 AWG (SHADED AREA).
(1) The total wire length is the distance from the furnace to the thermostat and back to the furnace.
NOTE: DO NOT USE CONTROL WIRING SMALLER THAN NO. 18
AWG.
FIELD GAS
CONNECTIONS
STRAIGHT CONDUIT
FITTING SIZED
PER CHART
CONDUIT FROM
POWER SUPPLY
SIZED PER CHART
WIRE SIZE FROM
MIN. CIRCUIT AMPACITY
CUT HOLE
SIZED PER CHART
OR USE KNOCK OUT
CONTROL VOLTAGE
KNOCKOUT
POWER WIRES
FROM DISCONNECT
TO CONTACTOR
POWER WIRES
TO DISCONNECT
WIRE FROM
ZONE THERMOSTAT
STRAIGHT CONDUIT
FITTING
CONDUIT FROM
ZONE THERMOSTAT
WASHERS
Page 22
Furnace Section Controls and
Ignition Systems
Normal Furnace Operating Sequence
This unit has a two stage gas furnace which employs an integrated furnace control with self diagnostics located in the control box. The furnace is composed of induced draft blowers,
negative pressures switches, two stage gas valve, manifold
orifices, inshot burners, direct spark ignitor, remote flame
sense, tubular heat exchanger, high limit switch and rollout
switches. See Figure 24.
Normal Heat Mode
Call For First Stage (low fire) Only:
1 Zone thermostat contacts close, a call for first stage
(low fire) heat is initiated.
2 Control runs self check.
3 Control checks the high-limit switch for normally
closed contacts, each pressure switch for normally open
contacts, and all flame rollout switches for continuity.
4 Control energizes each inducer.
5 Control checks each pressure switch for closure.
6 If each pressure switch is closed, the control starts a 30
second prepurge and energizes W2. If any pressure
switch is still open, the inducers will continue to be
energized until closure.
7 After prepurge timeout, control energizes W1 and con-
tinues to energize W2, initiates spark for 2 seconds
minimum, 7 second maximum ignition trial, initiates
120 second, second stage (high fire) warm up timing.
8 Control detects flame, de-energizes spark and initiates
45 second delay on blower timing.
9 After a fixed 45 seconds indoor blower delay on, the
control energizes the indoor blower.
10 After a fixed 120 seconds second stage warmup period
control checks thermostat input. If only W1 is called
for, W2 is de-energized and the control starts a 30 second off delay on the W2 inducer(s).
11 After fixed 30 seconds the W2 inducers is de-ener-
gized.
12 Control enters normal operating loop where all inputs
are continuously checked.
13 Zone thermostat is satisfied.
14 Control de-energizes gas valve.
15 Control senses loss of flame.
16 Control initiates 5 second inducer postpurge and 90
second indoor blower delay off.
17 Control de-energizes inducer blower(s).
18 Control de-energizes indoor blower.
19 Control in the stand by mode with solid red LED.
Call For Second Stage, After First Stage
Established; Starting from A.11:
1 If a call for second stage (high fire) is initiated after a
call for first stage heat is established, the control verifies W2 pressure switches for normally open contacts.
The control energizes the W2 inducers and energizes
the second stage of the gas valve.
2 Control enters normal operating loop where all inputs
are continuously checked.
Second Stage Satisfied; First Stage Still Called For;
Star
ting From B.3:
1 Once the call for second stage is satisfied, the control
starts a 30 second off delay on W2 inducers and
reduces the gas valve to first stage.
2 Control enters normal operating loop where all inputs
are continuously checked.
First Stage Satisfied:
1 Zone thermostat is satisfied.
2 Control de-energizes gas valve.
3 Control senses loss of flame.
4 Control initiates 5 second inducer postpurge and 90
second indoor blower delay off.
5 Control de-energizes inducer blower.
6 Control de-energizes indoor blower.
7 Control in the stand by mode with solid red LED.
22IM 863
Figure 24
ST-A0886-29
Page 23
IM 863
23
First Stage and Second Stage Called
Simultaneously:
1 Zone thermostat contacts close, a call for first stage
(low fire) and second stage (high fire) heat is initiated.
2 Control runs self check.
3 Control checks the high-limit switch for normally
closed contacts, each pressure switch for normally open
contacts, and all flame rollout switches for continuity.
4 Control energizes each inducer.
5 Control checks each pressure switch for closure.
6 If each pressure switch is closed, the control starts a 30
second prepurge and energizes W2. If either switch is
still open, the inducers will continue to be energized
until closure.
7 After prepurge timeout, control energizes W1 and con-
tinues to energize W2, initiates spark for 2 seconds
minimum, 7 second maximum ignition trial, and initi-
ates 120 second stage warm up timing.
8 Control detects flame, de-energizes spark and starts a
45 second indoor blower delay on timing.
9 After a fixed 45 seconds indoor blower delay on, the
control energizes the indoor blower.
10 After a fixed 120 seconds second stage warmup period
control checks the thermostat input. If W1 and W2 is
present control enters normal operating loop where all
inputs are continuously checked.
First Stage and Second Stage Removed Simultaneously:
1 Upon a loss of W1 and W2 the gas valve is de-ener-
gized.
2 Upon a loss of flame, each inducer will complete a 5
second postpurge and the indoor blower will complete a
90 second delay off.
3 Control in the stand by mode with solid red LED.
The integrated control is a three ignition system.
After a total of three cycles without sensing main burner
flame, the system goes into a 100% lockout mode. After one
hour, the ignition control repeats the prepurge and ignition
cycles for 3 tries and then goes into 100% lockout mode
again. It continues this sequence of cycles and lockout each
hour until ignition is successful or power is interrupted.
During the lockout mode, neither the ignitor or gas valve will
be energized until the system is reset by turning the thermostat to the “OFF” position or interrupting the electrical power
to the unit for 3 seconds or longer.
The circulating air blower will start and run on the heating
speed if the thermostat fan switch is in the “ON” position.
The integrated furnace control is equipped with diagnostic
LED. The LED is lit continuously when there is power to the
control, with or without a call for heat. If the LED is not lit,
there is either no power to the control or there is an internal
component failure within the control, and the control should
be replaced.
If the control detects the following failures, the LED will
flash on for approximately 1/4 second, then off for 3/4 second
for designated failure detections.
1 Flash: Failed to detect flame within the three tries for igni-
tion.
2 Flash: Pressure switch or induced draft blower problem
detected.
3 Flash: High limit or auxiliary limit open.
4 Flash: Flame sensed and gas valve not energized or flame
sensed with no “W” signal.
5 Flash: Overtemperature switch open.
Operating Instructions
This unit is equipped with integrated furnace control. This
device lights the main burners each time the room thermostat
(closes) calls for heat. See operating instructions on the back
of the furnace/controls access panel.
To Start The Furnace
1 Set the thermostat to its lowest setting.
2 Turn off all electric power to the unit.
3 This unit does not have a pilot. It is equipped with an
ignition device which automatically lights the burner.
Do not try to light the burner by hand.
4 Remove control door.
5 Move control knob to the “OFF” position. Turn the
knob by hand only, do not use any kind of tool.
6 Wait five (5) minutes to clear out any gas. Then smell
for gas, including near the floor. If you smell gas,
STOP! Follow B in the safety information on the
Operating Instructions located on the back of the controls/access panel. If you don’t smell gas, go to the next
step.
7 Move the gas control knob from “OFF” position to
“ON” position. Operate this unit with the gas control
Never test for gas leaks with an open flame. It can cause
an explosion or fire resulting in property damage, personal
injury or death. Use a commercially available soap solution
made specifically for the detection of leaks to check all connections, as specified in the Gas Supply and Piping section
of these instructions.
▲▲
DANGER
!
The spark ignitor and ignition lead from the ignition control
are high voltage. Keep hands or tools away to prevent electrical shock. Shut off electrical power before servicing any
of the controls. Failure to adhere to this warning can result
in personal injury or death.
▲▲
DANGER
!
Should overheating occur or the gas supply fail to shut off,
shut off the manual gas valve to the unit before shutting off
the electrical supply. Failure to do so can result in an explosion or fire causing property damage, severe personal
injury or death!
▲▲
DANGER
!
Page 24
24IM 863
knob in the “ON” position only. Do not use the gas
control knob as a means for throttling the burner input
rate.
8 Replace the control door.
9 Turn on all electric power to the unit.
10 Set the thermostat to the desired setting.
11 If the unit will not operate, follow the instructions
below on how to shut down the furnace.
The initial start-up on a new installation may require the control system to be energized for some time until air has bled
through the system and fuel gas is available at the burners.
To Shut Down Furnace
1 Set the thermostat to the lowest setting.
2 Turn off all electric power to the unit if service is to be
performed.
3 Remove control door.
4 Move control knob to the “OFF” position.
5 Replace control door.
Burners
Burners for these units have been designed so that field
adjustment is not required. Burners are tray-mounted and
accessible for easy cleaning when required.
Manual Reset Overtemperature Control
Four manual reset overtemperature controls are located on the
burner shield. These devices senses blockage in the heat
exchanger or insufficient combustion air. This shuts off the
main burners if excessive temperatures occur in the burner
compartment.
Operation of this control indicates an abnormal condition.
Therefore, the unit should be examined by a qualified
installer, service agency, or the gas supplier before being
placed back into operation.
Pressure Switch
This furnace has four pressure switches for sensing a blocked
exhaust or a failed induced draft blower. They are normally
open and close when the induced draft blowers start, indicating air flow through the combustion chamber.
Limit Control
The supply air high temperature limit cut-off is set at the factory and cannot be adjusted. It is calibrated to prevent the air
temperature leaving the furnace from exceeding the maximum
outlet air temperature.
IMPORTANT: Replace this control only with the identical
replacement part.
Cooling Section Operation
Cooling Mode
Call for first stage cooling
1 Zone thermostat contacts close and a call for cooling is
initiated.
2 Inputs ‘Y1’ and ‘G’ to the control are energized.
3 Control senses ‘Y1’ and ‘G’. After 1 sec. delay, control
energizes indoor blower and first stage compressor.
4 Control enters normal operating loop where all inputs
are continuously checked.
5 Zone thermostat is satisfied.
6 Control de-energizes indoor blower relay after 80 sec-
ond indoor blower delay off.
7 Control in the stand by mode with solid red LED.
Call for second stage cooling. After first stage cooling established: starting from A4.
1 If a call for second stage cooling is initiated after a call
for first stage cooling is established, the control energizes Y2 and energizes the second stage compressor.
2 Control enters normal operating loop where all inputs
are continuously checked.
Second stage satisfied: first stage still called for:
starting from B2.
1 Y2 is de-energized and second stage compressor is de-
energized.
First stage and second stage called simultaneously.
1 Zone thermostat contacts close, a call for first and sec-
ond stage cooling is initiated.
2 Inputs Y1, Y2 and G to the control are energized.
3 Control senses Y1, Y2 and G, after 1 second delay,
control energizes indoor blower, first and second stage
compressor are energized.
Do not jumper this device! Do not reset the overtemperature control without taking corrective action to
assure that an adequate supply of combustion air is maintained under all conditions of operation. Failure to do so
can result in carbon monoxide poisoning or death. Replace
this control only with the identical replacement part.
▲▲
DANGER
!
Do not jumper this device! Doing so can cause a fire or
explosion resulting in property damage, personal injury or
death.
▲▲
DANGER
!
Page 25
IM 863
25
First stage and second stage removed simultanously.
1 Upon a loss of Y1 and Y2 each compressor is de-ener-
gized. Control either de-energizes indoor blower relay
after 80 second indoor blower delay off.
2 Control in the stand by mode with solid red LED.
Continuous Fan Mode
A ‘G’ input only indicates a zone thermostat call for continuous indoor blower operation.
System Operating Information
Advise the Customer
1 Change the air filters regularly. The heating system
operates better, more efficiently and more economically.
2 Except for the mounting platform, keep all combustible
articles three feet from the unit and exhaust system.
3 IMPORTANT: Replace all blower doors and compartment
cover after servicing the unit. Do not operate the unit
without all panels and doors securely in place.
4 Do not allow snow or other debris to accumulate in the
vicinity of the unit
Furnace Section Maintenance
The unit’s furnace should operate for many years without
excessive scale build-up in flue passageways; however, it is
recommended that a qualified installer, service agency, or the
gas supplier annually inspect the flue passageways, the
exhaust system and the burners for continued safe operation,
paying particular attention to deterioration from corrosion or
other sources.
If during inspection the flue passageways and exhaust system
are determined to require cleaning, the following procedures
should be followed (by a qualified installer, service agency,
or gas supplier):
1 Turn off the electrical power to the unit and set the
thermostat to the lowest temperature.
2 Shut off the gas supply to the unit either at the
meter or at manual valve in the supply piping.
3 Remove the furnace controls access panel and the con-
trol box cover.
4 Disconnect the gas supply piping from the gas valve.
5 Disconnect the wiring to the induced draft blower
motors, gas valve, flame sensor, and flame roll-out control, and ignitor cable. Mark all wires disconnected
for proper reconnection.
6 Remove the screws (4) connecting the burner tray to
the heat exchanger mounting panel.
7 Remove the burner tray and the manifold assembly
from the unit.
8 Remove the screws (10) connecting the two induced
draft blowers to the collector box and screws (12) connecting the inducer mounting plate to the heat exchanger center panel. Remove the induced draft blowers and
the collector box from the unit.
9 Remove the turbulators from inside the heat exchangers
by inserting the blade of a screwdriver under the locking tabs. Pop the tabs out of the expanded grooves of
the heat exchanger. Slide the turbulators out of the heat
exchangers.
10 Direct a water hose into the outlet of the heat exchanger
top. Flush the inside of each heat exchanger tube with
water. Blow out each tube with air to remove excessive
moisture.
11 Reassemble (steps 1 through 9 in reverse order). Be
careful not to strip out the screw holes used to
mount the collector box and inducer blower.
Replace inducer blower gasket and collector box
gasket with factory replacements if damaged.
The manufacturer recommends that a qualified installer, service agency or the gas supplier visually inspect the burner
flames for the desired flame appearance at the beginning of
the heating season and approximately midway in heating season.
The manufacturer also recommends that a qualified installer,
service agency or the gas supplier clean the flame sensor with
steel wool at the beginning of the heating season.
Lubrication
IMPORTANT: DO NOT attempt to lubricate the bearings on the
blower motor or the induced draft blower motor. Addition of lubricants can reduce the motor life and void the warranty.
The blower motor and induced draft blower motor are prelubricated by the manufacturer and do not require further attention.
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous
operation resulting in fire, electrical shock, property damage, personal injury or death.
▲▲
DANGER
!
Holes in the exhaust transition or heat exchanger can
cause toxic fumes to enter the home. The exhaust transition or heat exchanger must be replaced if they have holes
or cracks in them. Failure to do so can cause carbon
monoxide poisoning resulting in personal injury or death.
▲▲
DANGER
!
Power supply to unit must be disconnected before making
field connections. To avoid electrical shock, personal injury
or death, be sure to rigorously adhere to field wiring procedures regarding proper lockout and tagout of components.
▲▲
DANGER
!
Page 26
26IM 863
A qualified installer, service agency or the gas supplier must
periodically clean the motors to prevent the possibility of
overheating due to an accumulation of dust and dirt on the
windings or on the motor exterior. And, as suggested elsewhere in these instructions, the air filters should be kept clean
because dirty filters can restrict air flow and the motor
depends upon sufficient air flowing across and through it to
prevent overheating.
Cooling Section Maintenance
It is recommended that at the beginning of each cooling season a qualified installer or service agency inspect and clean
the cooling section of this unit. The following areas should be
addressed: evaporator coil. condenser coil, condenser fan
motor and venturi area.
To inspect the evaporator coil:
1 Open the control/filter access panel and remove filters.
Also, remove blower access panel. In downflow applications remove the horizontal return to gain access.
2 Shine a flashlight on the evaporator coil (both sides)
and inspect for accumulation of lint, insulation, etc.
3 If coil requires cleaning, follow the steps shown below.
Cleaning Evaporator Coil
1 The coil should be cleaned when it is dry. If the coil is
coated with dirt or lint, vacuum it with a soft brush
attachment. Be careful not to bend the coil fins.
2 If the coil is coated with oil or grease, clean it with a
mild detergent-and-water solution. Rinse the coil thoroughly with water. IMPORTANT: Do not use excessive
water pressure. Excessive water pressure can bend the
fins and tubing of the coil and lead to inadequate unit performance. Be careful not to splash water excessively into
unit.
3 Inspect the drain pan and condensate drain at the same
time the evaporator coil is checked. Clean the drain pan
by flushing with water and removing any matters of
obstructions which may be present.
4 Go to next section for cleaning the condenser coil.
Cleaning Condenser Coil, Condenser Fan,
Circulation Air Blower and Venturi
1 Remove the condenser access end panel and/or com-
pressor access louver panel. Disconnect the wires to the
condenser fan motor in the control box (see wiring diagram).
2 The coil should be cleaned when it is dry. If the coil is
coated with dirt or lint, vacuum it with a soft brush
attachment. Be careful not to bend the coil fins.
3 If the coil is coated with oil or grease, clean it with a
mild detergent-and-water solution. Rinse the coil thoroughly with water.
IMPORTANT: Do not use excessive
water pressure. Excessive water pressure can bend the
fins and tubing of the coil and lead to inadequate unit performance. Be careful not to splash water excessively into
unit.
4 The venturi should also be inspected for items of
obstruction such as collections of grass, dirt or spider
webs. Remove any that are present.
5 Inspect the circulating air blower wheel and motor for
accumulation of lint, dirt or other obstruction and clean
it necessary. Inspect the blower motor mounts and the
blower housing for loose mounts or other damage.
Repair or replace if necessary.
Re-assembly
1 Reconnect fan motor wires per the wiring diagram
attached to the back of the control cover.
2 Replace the control box cover.
3 Close the filter/control access panel and replace the
blower/evaporator coil access panels.
4 Restore electrical power to the unit and check for prop-
er operation, especially the condenser fan motor.
Replacement Parts
To find your local McQuay Certified Parts Distributor, go to
www.mcquay.com and select Parts Locator.
Troubleshooting
Refer to Figures 25 and 26 for determining cause of unit
problems.
Wiring Diagrams
Figures 27 through 32 are complete wiring diagrams for the
unit and its power sources. Also located on back of compressor access panel.
Charging
See Figures 33 and 34 for proper charging information.
Power supply to unit must be disconnected before making
field connections. To avoid electrical shock, personal injury
or death, be sure to rigorously adhere to field wiring procedures regarding proper lockout and tagout of components.
▲▲
DANGER
!
Label all wires prior to disconnection when servicing the
unit. Wiring errors can cause improper and dangerous
operation resulting in fire, electrical shock, property damage, severe personal injury or death.
▲▲
DANGER
!
Page 27
IM 863
27
E.S.P. - Inches of Water
15 TON PACKAGE UNIT - 60 Hz
———
—
637
653
669
685
701
717
733
749
765
———
—
1494
1738
1981
2224
2468
2711
2955
3198
3442
AIR-FLOW PERFORMANCE – 15 TON MODELS
TABLE 9
0.10.20.30.40.50.60.70.80.91.01.11.21.3
1.4
1.51.61.71.81.92.0
STD
CFM
RPMRPM
WATTSWATTS
RPM
WATTS
RPMRPM
WATTSWATTS
RPM
WATTS
RPM
WATTS
RPMRPM
WATTSWATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPMRPM
WATTSWATTS
RPMRPMRPMRPM
WATTSWATTSWATTSWATTS
4800
5000
5200
5400
5600
5800
6000
6200
6400
6600
6800
7000
7200
———
640
656
672
688
704
720
736
752
768
784
———
1394
1638
1881
2125
2368
2611
2855
3098
3342
3585
—
—
644
660
676
692
708
724
740
756
772
788
804
—
—
1294
1538
1781
2025
2268
2512
2755
2998
3242
3485
3729
631
647
663
679
695
711
727
743
759
775
791
807
877
951
1194
1438
1681
1925
2168
2412
2655
2899
3142
3385
3629
3821
650
666
682
698
714
731
747
763
779
795
811
881
890
1095
1338
1581
1825
2068
2312
2555
2799
3042
3286
3529
3695
4000
670
686
702
718
734
750
766
782
798
814
885
894
903
1238
1482
1725
1968
2212
2455
2699
2942
3186
3429
3569
3874
4179
689
705
721
737
753
769
785
801
817
889
898
907
916
1382
1625
1869
2112
2355
2599
2842
3086
3329
3442
3748
4053
4358
709
725
741
757
773
789
805
821
893
920
911
902
929
1525
1769
2012
2256
2499
2742
2986
3229
3316
3622
3927
4232
4538
728
744
760
776
792
808
888
897
906
915
924
933
942
1669
1912
2156
2399
2643
2886
2885
3190
3495
3801
4106
4411
4717
747
764
780
796
812
892
901
910
919
928
937
946
955
1812
2056
2299
2543
2786
2759
3064
3369
3675
3980
4285
4591
4896
767
783
799
815
896
905
914
923
932
941
950
959
968
1956
2199
2443
2686
2632
2938
3243
3548
3854
4159
4464
4770
5075
786
802
818
900
909
918
927
936
945
954
963
972
—
2100
2343
2586
2506
2812
3117
3422
3727
4033
4338
4643
4949
—
806
822
904
913
922
931
940
949
958
967
976
—
—
2243
2487
2380
2685
2991
3296
3601
3907
4212
4517
4823
—
—
899
908
917
926
935
944
953
962
971
980
989
—
—
1949
2254
2559
2864
3170
3475
3780
4086
4391
4696
5002
—
—
912
921
929
936
947
956
965
974
983
992
———
2128
2433
2738
3044
3349
3654
3960
4265
4570
4876
———
924
933
942
951
960
969
978
987
996
1005
———
2307
2612
2917
3223
3528
3833
4139
4444
4749
5055
———
937
946
955
964
973
982
991
1000
1009
———
—
950
959
968
977
986
995
1004
1013
—————
963
972
981
990
999
1008
1017
—————
—
976
985
994
1003
1012
1021
———————
2486
2791
3097
3402
3707
4012
4318
4623
4928
———
—
2665
2970
3276
3581
3886
4192
4497
4802
—————
2844
3149
3455
3760
4065
4371
4876
—————
—
3023
3329
3634
3939
4245
4550
———————
DRIVE PACKAGEL
3.0
BK-90
1VP-44
123456
823787
750
710670629
MOTOR HP
BLOWER SHEAVE
MOTOR SHEAVE
TURNS OPEN
RPM
NOTES: 1. Factory sheave settings shown in bold type.
2. Do not set sheave below minimum turns open shown.
3. Re-adjustment of sheave required to achieve rated airflow at ARI minimum E.S.P.
4. Drive data shown is for horizontal airflow with dry coil. Add component resistance
to duct resistance to determine total E.S.P.
DRIVE PACKAGEM
5
BK-72
1VP-44
1.523
4
56
102210171006
933
860786
MOTOR HP
BLOWER SHEAVE
MOTOR SHEAVE
TURNS OPEN
RPM
COMPONENT RESISTANCE TABLE
CFMWET COILDOWNFLOW
48000.0200.010
52000.0400.020
56000.0600.030
60000.0800.040
64000.1000.050
68000.1250.060
72000.1500.070
Page 28
28IM 863
701
717
733
749
765
781
797
813
829
845
861
877
911
920
929
938
947
2468
2711
2955
3198
3442
3685
3929
4172
4415
4659
4902
5146
5726
6032
6337
6642
6948
AIR-FLOW PERFORMANCE – 20 TON MODELS
TABLE 10
E.S.P. - Inches of Water
20 TON PACKAGE UNIT - 60 Hz
0.10.20.30.40.50.60.70.80.91.01.11.21.3
1.4
1.51.61.71.81.92.0
STD
CFM
RPMRPM
WATTSWATTS
RPM
WATTS
RPMRPM
WATTSWATTS
RPM
WATTS
RPM
WATTS
RPMRPM
WATTSWATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPMRPM
WATTSWATTS
RPMRPMRPMRPM
WATTSWATTSWATTSWATTS
6400
6600
6800
7000
7200
7400
7600
7800
8000
8200
8400
8600
8800
9000
9200
9400
9600
720
736
752
768
784
801
817
833
849
865
881
915
924
933
942
951
960
2611
2855
3098
3342
3585
3829
4072
4316
4559
4802
5046
5600
5905
6211
6516
6821
7127
740
756
772
788
804
820
836
852
868
910
919
928
936
945
954
963
972
2755
2998
3242
3485
3729
3972
4216
4459
4703
5169
5474
5779
6084
6390
6695
7000
7306
759
775
791
807
823
839
855
871
913
922
931
940
949
958
967
976
985
2899
3142
3385
3629
3872
4116
4359
4603
5042
5348
5653
5958
6264
6569
6874
7180
—
779
795
811
827
843
859
875
917
926
935
944
953
962
971
980
989
—
3042
3286
3529
3772
4016
4259
4503
4916
5221
5527
5832
6137
6443
6748
7053
7359
—
798
814
830
846
862
878
921
930
939
948
957
966
975
984
993
—
—
3186
3429
3673
3916
4160
4403
4790
5095
5401
5706
6011
6317
6622
6927
7233
—
—
817
834
850
866
882
925
934
943
952
961
970
979
988
997
1006
—
—
3329
3573
3816
4060
4303
4664
4696
5274
5580
5885
6190
6496
6801
7106
7412
—
—
837
853
869
920
929
938
947
956
965
974
983
992
1001
1010
———
3473
3716
3960
4232
4538
4843
5148
5454
5759
6064
6369
6675
6980
7285
———
856
872
924
933
942
951
960
969
978
987
996
1005
1014
———
—
3616
3860
4106
4411
4717
5022
5327
5633
5938
6243
6549
6854
7159
———
—
876
928
937
946
955
964
973
982
991
1000
1009
1018
1027
———
—
3760
3980
4285
4591
4896
5201
5506
5812
6117
6422
6728
7033
7338
———
—
932
941
950
959
968
977
986
995
1004
1013
1022
1031
—————
3854
4159
4464
4770
5075
5380
5686
5991
6296
6602
6907
7212
—————
945
954
963
972
981
990
999
1008
1017
1026
1035
1044
—————
4033
4338
4643
4949
5254
5559
5865
6170
6475
6781
7086
7391
—————
958
967
976
985
994
1003
1012
1021
1030
1039
1048
—————
—
4212
4517
4823
5128
5433
5739
6044
6349
6655
6960
7265
—————
—
971
980
989
998
1007
1015
1024
1033
1042
1051
———————
4391
4696
5002
5307
5612
5918
6223
6528
6834
7139
———————
983
992
1001
1010
1019
1028
1037
1046
1055
1064
———————
4570
4876
5181
5486
5791
6097
6402
6707
7013
7318
———————
996
1005
1014
1023
1032
1041
1050
1059
1068
———————
—
4749
5055
5360
5665
5971
6276
6581
6887
7192
———————
—
1009
1018
1027
1036
1045
1054
1063
1072
1081
———————
—
1022
1031
1040
1049
1058
1067
1076
1085
—————————
1035
1044
1053
1062
1071
1080
1089
1098
—————————
1048
1057
1066
1075
1084
1093
1102
—————————
—
4928
5234
5539
5844
6150
6455
6760
7066
7371
———————
—
5108
5413
5718
6024
6329
6634
6940
7245
—————————
5287
5592
5897
6203
6508
6813
7119
7424
—————————
5466
5771
6076
6382
6687
6992
7298
—————————
—
DRIVE PACKAGEL
5.0
BK-95
1VP-50
123456
882846810773736700
MOTOR HP
BLOWER SHEAVE
MOTOR SHEAVE
TURNS OPEN
RPM
NOTES: 1. Factory sheave settings shown in bold type.
2. Do not set sheave below minimum turns open shown.
3. Re-adjustment of sheave required to achieve rated airflow at ARI minimum E.S.P.
4. Drive data shown is for horizontal airflow with dry coil. Add component resistance
• Improper airflow• Check - should be approximately 400 CFM per ton.
• Incorrect refrigerant charge• Charge per procedure attached to unit service panel.
• Air, non-condensibles or moisture in system• Recover refrigerant, evacuate & recharge, add filter drier
• Incorrect voltage• At compressor terminals, voltage must be within 10% of rating
plate volts when unit is operating.
Compressor short cycles• Incorrect voltage• At compressor terminals, voltage must be ± 10% of
nameplate marking when unit is operating.
• Defective overload protector• Replace - check for correct voltage
• Refrigerant undercharge• Add refrigerant
Registers sweat• Low evaporator airflow• Increase speed of blower or reduce restriction - replace air
filter
High head pressure-• Restriction in liquid line, expansion device or filter drier• Remove or replace defective component
low vapor pressures• Flow check piston size too small• Change to correct size piston
• Incorrect capillary tubes• Change coil assembly
High head pressure-high or• Dirty condenser coil• Clean coil
normal vapor pressure -• Refrigerant overcharge• Correct system charge
Cooling mode• Condenser fan not running• Repair or replace
• Air or non-condensibles in system• Recover refrigerant, evacuate & recharge
Low head pressure-high vapor• Defective Compressor valves• Replace compressor
High vapor pressure• Excessive load• Recheck load calculation
• Defective compressor• Replace
Fluctuating head & vapor• Air or non-condensibles in system• Recover refrigerant, evacuate & recharge
pressures
Gurgle or pulsing noise at• Air or non-condensibles in system• Recover refrigerant, evacuate & recharge
expansion device or liquid line
Figure 25
Cooling Trouble Shooting Chart
Disconnect all power to unit before servicing. Contactor may break only one side. Failure to shut off power can cause electrical
shock resulting in personal injury or death.
▲▲
DANGER
!
Page 32
32IM 863
SET THERMOSTAT TO
CALL FOR HEAT
SET FAN SWITCH TO AUTO
START
FLOW CHART CONTINUED ON NEXT PAGE
NO
YES
YES
YES
YES
NO
NO
NO
INDUCED DRAFT BLOWER
MOTOR STARTS
30 SECOND PREPURGE
REPLACE INTEGRATED
CONTROL BOARD (IFC)
REPLACE INDUCED
DRAFT BLOWER(S)
NO
REPLACE NEGATIVE
PRESSURE SWITCH
REPLACE INTEGRATED
CONTROL BOARD (IFC)
IF WIRING IS OK
CHECK FOR EXHAUST,
INTAKE OR HEAT
EXCHANGER BLOCKAGE
AND RESET CONTROL
NO
REPLACE IGNITION CON-
TROL
YES
REPLACE VALVE
• CHECK LINE VOLTAGE TO IFC
• CHECK LOW VOLTAGE TRANSFORMER
• CHECK WIRING
• CHECK FOR 208-230 VAC TO IDM MOTOR
• CHECK IGNITOR CABLE
• CHECK SPARK IGNITOR POSITION AND CONDITION
• IS EACH NEGATIVE PRESSURE SWITCH CLOSED?
• CHECK FOR OPEN ROLL-OUT CONTROLS
• CHECK FOR OPEN LIMIT
• CHECK IGNITION CONTROL CHASSIS GROUND WIRE
• CHECK WIRING
• CHECK INLET GAS PRESSURE
• CHECK 24 VOLTS TO GAS VALVE
• CHECK FOR GAS FLOW TO AND FROM VALVE
• CHECK BURNER CARRYOVER
NOTE: THE SYSTEM WILL ATTEMPT TO LIGHT 3 TIMES WITH A 60 SECOND INTER-
PURGE BETWEEN TRIES. IF AFTER THE THIRD TIME THE BURNERS
DO NOT LIGHT, THE SYSTEM WILL LOCK OUT. IF THE UNIT IS EQUIPPED WITH
A UNITED TECH. THE SYSTEM WILL ATTEMPT TO LIGHT 3 TIMES EACH HOUR
UNTIL THE BURNERS LIGHT OR THE THERMOSTAT IS RESET OR POWER IS
REMOVED FOR 3 SECONDS OR GREATER.
YES
YES
IGNITOR SPARKS
MAIN BURNER LIGHTS
NO
• CHECK NEGATIVE PRESSURE
SWITCH SENSING TUBE
• CHECK FOR EXHAUST
BLOCKAGE
YES
YES
YES
REPLACE IGNITOR/
CABLE ASSEMBLY
REPLACE LIMIT
IF UNIT IS COLD
NO
Figure 26: Furnace Troubleshooting Guide (Combination Heating and Cooling Units With Direct Spark Ignition)
HAZARDOUS VOLTAGE
LINE VOLTAGE CON-
NECTIONS
DISCONNECT POWER BEFORE
SERVICING.
SERVICE MUST BE BY A TRAINED,
QUALIFIED SERVICE TECHNICIAN.
▲▲
WARNING
!
Page 33
IM 863
33
NOTE: IF THE SYSTEM GOES INTO LOCKOUT, WAIT
30 SECONDS AND RESET THE SYSTEM.
• CHECK FLAME SENSOR POSITION AND CONDITION
• CLEAN FLAME SENSOR WITH STEEL WOOL
• CHECK FLAME SENSOR WIRES AND CONNECTIONS
• CHECK FOR 208-230 VAC ACROSS BLOWER
MOTOR TERMINALS ON CONTROL BOARD
• CHECK FOR LINE VOLTAGE AT LOAD SIDE OF
BLOWER CONTACT.
YES
YES
NO
MAIN BURNER FLAME SUSTAINED
YES
NO
INDOOR BLOWER MOTOR STARTS
AFTER 45 SECONDS
REPLACE SENSOR
NO
REPLACE INTEGRATED
CONTROL BOARD (IFC)
NO
REPLACE IGNITION CON-
TROL
YES
REPLACE BLOWER
MOTOR
• CHECK FOR OPEN LIMIT
• CHECK FOR OPEN ROLL-OUT CONTROL
• CHECK FOR PROPER THERMOSTAT OPERATION
• REMOVE VALVE LEAD AT GAS VALVE
IF VALVE CLOSES, RECHECK THE THERMOSTAT
AND WIRING. IF OK, THEN REPLACE VALVE
YES
NO
SYSTEM RUNS UNTIL
CALL FOR HEAT ENDS
TROUBLESHOOTING ENDS
REPEAT PROCEDURE UNTIL TROUBLE FREE
OPERATION IS OBTAINED.
YES
NO
TURN THERMOSTAT OFF
VALVE SHUTS OFF
FLAME SHUTS OFF
YES
INDUCED DRAFT MOTOR(S) STOPS
AFTER 5 SECOND POSTPURGE
YES
YES
• CHECK FOR DIRTY FILTERS
• CHECK FOR RESTRICTED
AIR-FLOW
CHECK FOR EXHAUST,
INTAKE OR HEAT EXCHANG-
ER BLOCKAGE
CLEAR BLOCKAGE AND
RESET CONTROL
YES
INDOOR BLOWER MOTOR STOPS
AFTER 90 SECONDS
YES
FURNACE STARTS ON HIGH FIRE.
FURNACE SWITCHES TO LOW FIRE
AFTER 120 SECONDS WARMUP IF
THERMOSTAT IS CALLING FOR W1.
FURNACE WILL SWITCH TO HIGH
FIRE IF LOW FIRE DOES NOT SATISFY THERMOSTAT DEMAND FOR HEAT
LOAD.
Now that you have made an investment in modern, efficient McQuay equipment, its care should be a high priority.
For training information on all McQuay HVAC products, please visit us at www.mcquay.com and click on training, or
call 540-248-9646 and ask for the Training Department.
Warranty
All McQuay equipment is sold pursuant to its standard terms and conditions of sale, including Limited Product
Warranty. Consult your local McQuay Representative for warranty details. Refer to Form 933-43285Y. To find your
local McQuay Representative, go to www.mcquay.com.
This document contains the most current product information as of this printing. For the most up-to-date product
information, please go to www.mcquay.com.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.