This manual contains the installation and operating
instructions for your packaged rooftop system. There are some
precautions that should be taken to derive maximum
satisfaction from it. Improper installation can result in
unsatisfactory operation or dangerous conditions.
Introduction
WARNING
Install this unit only in a location and position as specified in
the Mechanical Installation section of these instructions.
Provide adequate combustion and ventilation air to the unit
space as specified in the venting section of these instructions.
Read this manual and any instructions packaged with separate
equipment prior to installation. Give this manual to the owner
and explain its provisions. The owner should retain this
manual for future reference.
This product line does have an optional DDC controller. For
operation and information on using and programming the
MicroTech II unit controller, refer to the appropriate operation
manual (see Table 1).
For a description of operation and information on using the
keypad to view data and set parameters, refer to the
appropriate program-specific operation manual (see Table 1).
Table 1: Operation, Installation and Maintenance
Resources
UnitManual
Rooftop unit control configuration
DDC Unit ControllerOM 1077
BACnet Communication ModuleIM 1000
LonWorks Communication ModuleIM 999
Operation manual bulletin
number
Checking Product Received
Upon receiving the unit, inspect it for any damage from
shipment. Claims for damage, either shipping or concealed,
should be filed immediately with the shipping company.
IMPORTANT: Check the unit model number, heating size,
electrical characteristics, and accessories to determine if they
are correct.
Safety Information
DANGER
WARNING
Combustion products must be discharged outdoors. Connect
this unit to an approved vent system only, as specified in
Mechanical Installation section of these instructions.
WARNING
Use only with type of gas approved for this unit. Refer to the
unit rating plate.
DANGER
Never test for gas leaks with an open flame. It can cause an
explosion or fire resulting in property damage, personal injury
or death. Use a commercially available soap solution made
specifically for the detection of leaks to check all connections,
as specified in the Mechanical Installation section of these
instructions.
WARNING
Always install unit to operate within the unit's intended
temperature-rise range with a duct system which has an
external static pressure within the allowable range, as
specified in the Mechanical Installation section of these
instructions. See also unit rating plate.
DANGER
Units are not design certified to be installed inside the
structure. Doing so can cause inadequate unit performance
as well as property damage and carbon monoxide poisoning
resulting in personal injury or death.
The manufacturer’s warranty does not cover any damage or
defect to the air conditioner caused by the attachment or use
of any components, accessories or devices (other than those
authorized by the manufacturer) into, onto, or in conjunction
with the air conditioner. you should be aware that the use of
unauthorized components, accessories or devices may
adversely affect the operation of the air conditioner and may
also endanger life and property. The manufacturer disclaims
any responsibility for such loss or injury resulting from the use
of such unauthorized components, accessories or devices.
WARNING
Provide adequate combustion and ventilation air to the unit
space as specified in the combustion and ventilation air
section of these instructions.
Major Components
The unit includes a hermetically-sealed refrigerating system
consisting of a scroll compressor, condenser coil, evaporator
coil with capillary tube assembly, circulation air blower,
condenser fan, heat exchanger assembly, gas burner and
control assembly, combustion air motor and fan, and all
necessary internal electrical wiring. The unit’s cooling system
is factory-evacuated, charged and performance tested.
Refrigerant amount and type are indicated on rating plate.
The unit is available in 150,000, 225,000 and 252,000 BTUH
heating input. Cooling capacity is 6.5, 7.5, 8.5, 10 and 12
nominal tons. Units are convertible from bottom supply and
return to side supply and return by relocation of supply and
return air cover panels. The units are weatherized for mounting
outside of the building.
McQuay IM 971-13
Mechanical Installation
Mechanical Installation
General
WARNING
When a unit is installed so that supply ducts carry air
circulated by the unit to areas outside the space containing
the unit, the return air shall also be handled by duct(s) sealed
to the unit casing and terminating outside the space
containing the unit.
Install this unit in accordance with The American National
Standard Z223.1-latest edition manual entitled “National Fuel
Gas Code,” and the requirements or codes of the local utility or
other authority having jurisdiction.
Additional helpful publications available from the “National
Fire Protection Association” are: sNFPA-90A - Installation of
Air Conditioning and Ventilating Systems 1985 or latest
edition. NFPA-90B - Warm Air Heating and Air Conditioning
Systems 1984.
These publications are available from:
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
Pre-Installation Check-Points
1 Before attempting any installation, carefully consider the
following points:
a Structural strength of supporting members (rooftop
installation)
b Clearances and provision fo r servi cing power supply
and wiring
c Gas supply and piping
d Air duct connections and sizing
e Drain facilities and connections
f Location for minimum noise and vibration - away
from bedroom windows
Location Considerations
The metal parts of this unit may be subject to rust or
deterioration in adverse environmental conditions. This
oxidation could shorten the equipment’s useful life. Salt spray,
fog or mist in seacoast areas, sulphur or chlorine from lawn
watering systems, and various chemical contaminants from
industries such as paper mills and petroleum refineries are
especially corrosive.
If the unit is to be installed in an area where contaminants are
likely to be a problem, give special attention to the equipment
location and exposure.
1 Avoid having lawn sprinkler heads spray directly on the
unit cabinet.
2 In coastal areas, locate the unit on the side of the building
away from the waterfront.
3 Shielding by a fence or shrubs may give some protection.
4 Frequent washing of the cabinet, fan blade and coil with
fresh water will remove most of the salt or other
contaminants that build up on the unit.
5 Regular cleaning and waxing of the cabinet with a good
automobile polish will provide some protection.
6 A good liquid cleaner may be used several times a year
to remove matter that will not wash off with water.
Several different types of protective coatings are offered in
some areas. These coatings may provide some benefit, but the
effectiveness of such coating materials cannot be verified by
the equipment manufacturer.
The best protection is frequent cleaning, maintenance, and
minimal exposure to contaminants.
WARNING
This unit may be used to heat the building or structure during
construction if the following installation requirements are met.
Installation must comply with all install ation instructions
including:
• Proper vent installation
• Furnace operating under thermostatic control
• Return air duct sealed to the furnace
• Air filters in place
• Set furnace input rate and temperature rise per rating plate
marking
• Means of providing outdoor air required for combustion
• Return air temperature maintained between 55°F (13°C )
and 80°F (27°C)
• Installation of exhaust and combustion air inl e t hoods
completed
• Clean furnace, duct work and components upon
substantial completion of the construction process, and
verify furnace operating conditions including ignition,
input rate, temperature rise and venting, according to the
instructions.
4McQuay IM 971-1
Mechanical Installation
Outside Installation
DANGER
These units are designed certified for outdoor installation
only. Installation inside any part of a structure can result in
inadequate unit performance as well as property damage.
Installation inside can also cause recirculation of flue
products into the conditioned space resulting in personal
injury or death.
(Typical outdoor slab installation is show n in Figure 1.)
1 Select a location where external water drainage cannot
collect around unit.
2 Provide a level slab sufficiently high enough above grade
to prevent surface water from entering the unit
3 Locate the unit to provide proper access for inspection
and servicing as shown in Figure 3, page 6.
4 Locate unit where operating sounds will not disturb
owner or neighbors.
Figure 1: Outside Slab Installation
8 Remove compressor shipping supports (if so equipped)
after installation.
Attaching Exhaust and Combustion Air Inlet
Hoods
IMPORTANT: Do not operate this unit without the exhaust/
combustion air inlet hood properly installed. This hood is
shipped in a carton in the blower compartment inside the unit
and must be attached when the unit is installed. See Figure 34,
page 42.
To attach exhaust/combustion air inlet hood:
1 Remove screws securing blower access panel and
remove access panel. For location of blower access
panel, see Figure 26, page 34 .
2 Remove exhaust/combustion air inlet hood from the
carton, located inside the blower compartment.
3 Attach blower access panel.
4 Attach the combustion air inlet/exhaust hood with
screws. Reference Figure 26, page 34 for proper
location. Screws are in carton with the hood.
5 Vent the unit using the flue exhaust hood, as supplied
from the factory, without alteration or addition. The only
exception is with factory approved additions. Consult
your local utility or other authority having jurisdiction
for accepted venting techniques.
5
Locate unit so roof runoff water does not pour directly on
the unit. Provide gutter or other shielding at roof
level.Do not locate unit in an area where excessive snow
drifting may occur or accumulate.
6 Where snowfall is anticipated, the height of the unit
above the ground level must be considered. Mount unit
high enough to be above anticipated maximum area
snowfall and to allow combustion air to enter the
combustion air inlet.
7 Select an area which will keep the areas of the vent, air
intake, and A/C condenser fins free and clear of
obstructions such as weeds, shrubs, vines, snow,
etc.Inform the user accordingly.
Cover Panel Installation/Conversion
Procedure
Downflow To Horizontal
1 Remove the screws and covers from the outside of the
supply and return sections. See Figure 2.
2 Install the covers over the bottom supply and return
openings, painted side up, inserting the leading flange
under the bracket provided. Place the back flange to top
of the front bracket provided. See Figure 2.
3 Secure the return and supply cover to front bracket with
one (1) screw .
Figure 2: Cover Gasket Detail, Downflow to Horizontal
McQuay IM 971-15
Mechanical Installation
Filter Replacement
This unit is provided with 6 - 18” × 18” × 2” disposable filters.
When replacing filters, ensure they are inserted fully to the
back to prevent bypass.
Clearances
The following minimum clearances must be observed for
proper unit performance and serviceability (also see Figure 3).
Table 2: Recommended Clearances
Recommended
Clearance
48”A- Fr ont
18”B - Condenser Coil
18”C - Duct Side
18”D - Evaporator End
60”E - Above
*Without Economizer. 48” With Economizer
Figure 3: Clearances
Location
Figure 4: Flat Rooftop Installation, With Attic or Drop
Ceiling Distributing System
Rooftop Installation
1 Before locating the unit on the roof, make sure that the
roof structure is adequate to support the weight involved.
(See Electrical & Physical Tables in this manual.) THIS
IS VERY IMPORTANT AND THE INSTALLER'S
RESPONSIBILITY.
2 For rigging and roofcurb details, see Figure 5 through
Figure 7.
3 The location of the unit on the roof should be such as to
provide proper access for inspection and servicing.
IMPORTANT: If unit will not be put into service
immediately, block off supply and return air openings to
prevent excessive condensation.
Ductwork
The installing contractor should fabricate ductwork in
accordance with local codes. Use industry manuals as a guide
when sizing and designing the duct system. Contact Air
Conditioning Contractors of America, 1513 16th St. N.W.,
Washington, D.C. 20036.
DANGER
Never connect return ductwork to any other heat producing
device such as fireplace insert, stove, etc. Unauthorized use
of such devices may result in fire, carbon monoxide
poisoning, explosion, personal injury, property damage or
death.
Place the unit as close to the conditioned space as possible
allowing clearances as indicated. Run ducts as directly as
possible to supply and return outlets. Use of non-flammable
weatherproof flexible connectors on both supply and return
connections at unit to reduce noise transmission is
recommended.
6McQuay IM 971-1
Mechanical Installation
On ductwork exposed to outside temperature and humidity, use
a minimum of 2" of insulation and a vapor barrier. Distribution
system in attic, furred space or crawl space should be insulated
with at least 2" of insulation. 1/2" to 1" thick insulation is
usually sufficient for ductwork inside the air conditioned
space.
Provide balancing dampers for each branch duct in the supply
system. Properly support ductwork from the structure.
IMPORTANT: In the event that the return air ducts must be
run through an “unconfined” space containing other fuel
burning equipment, it is imperative that the user be informed
against future changes in construction which might change this
to a “confined space.” Also, caution the user against any future
installation of additional equipment (such as power
ventilators), within the existing unconfined and/or confined
space which might create a negative pressure within the
vicinity of other solid, liquid, or gas fueled units.
Return Air
DANGER
Never allow products of combustion or the flue products to
enter the return air ductwork, or the circulating air supply. All
return ductwork must be adequately sealed and secured to
the furnace with sheet metal screws and joints must be taped.
All other duct joints must be secured with approved
connections and sealed airtight.
Failure to prevent products of combustion from being
circulated into the living space can create potentially
hazardous conditions, including carbon monoxide poisoning
that could result in personal injury or death.
Figure 5: Rigging Detail
A074403
Capacity Tons [kW]
7.5-12.5 [26.4-44.0]
Corner Weights by Percentage
ABCD
33% 27% 17% 23%
Figure 6: Shipping Board Removal
Illustration
ST-A0744-03
[ ] Designates Metric Conversions
Figure 7: Roofcurb
Remove Shipping Boards
Before Installing Unit
McQuay IM 971-17
Mechanical Installation
Gas Supply, Condensate Drain
Gas Connection
IMPORTANT: Connect this unit only to gas supplied by a
commercial utility.
1 Install gas piping in accordance with local codes and
regulations of the local utility company. In the absence
of local codes, the installation must conform to the
specifications of the National Fuel Gas Code, ANSI
Z223.1 - latest edition.
Note: The use of flexible gas connectors is not permitted.
Connect the gas line to the gas valve supplied with unit.
2
Routing can be through the gas pipe opening shown in
Figure 26, page 34 or through the base as shown in
Figure 1 1, page 12.
3 Size the gas line to the furnace adequate enough to
prevent undue pressure drop and never less than 1/2".
4 Install a drip leg or sediment trap in the gas supply line
as close to the unit as possible.
5 Install an outside ground joint union to connect the gas
supply to the control assembly at the burner tray.
6 Gas valves have been factory installed. Install a manual
gas valve where local codes specify a shut-off valve
outside the unit casing (Figure 8).
7 Make sure piping is tight. A pipe compound resistant
to the action of liquefied petroleum gases must be
used at all threaded pipe connections.
Figure 8: Suggested Gas Piping
IMPORTANT: Disconnect the furnace and its individual
shutoff valve from the gas supply piping during any pressure
testing of that system at test pressures in excess of 1/2 pound
per square inch gauge or isolate the system from the gas
supply piping system by closing its individual manual shutoff
valve during any pressure testing of this gas supply system at
pressures equal to or less than 1/2 PSIG.
DANGER
Never test for gas leaks with an open flame. It can cause an
explosion or fire resulting in property damage, personal injury
or death. Use a commercially available soap solution made
specifically for the detection of leaks to check all connections
as specified in the “Mechanical Installation” section of these
instructions.
IMPORTANT: Check the rating plate to make certain the unit
is equipped to burn the type of gas supplied. Care should be
taken after installation of th is equipment that the gas control
valve not be subjected to high gas supply line pressure.In
making gas connections, avoid strains as they may cause noise
and damage the controls. A backup wrench is required to be
required for the furnace to satisfactorily meet the
application should be made by a qualified installer,
service agency or the gas supplier, using factoryspecified or approved parts. In the commonwealth of
Massachusetts, installation must be performed by a
licensed plumber or gas fitter for appropriate fuel.
The capacities of gas pipe of different diameters and lengths in
cu.ft. per hr. with pressure drop of 0.3 in. and specific gravity
of 0.60 (natural gas) are shown in Table 1.
After determining the pipe length, select the pipe size which
will provide the minimum cubic feet per hour required for the
gas input rating of the furnace. By formula:
Cu. Ft. per Hr. Required =
Gas Input of Furnace (BTU/Hr)
Heating Value of Gas (BTU/Ft3)
The gas input of the furnace is marked on the furnace rating
3
plate. The heating value of the gas (BTU/Ft
) may be
determined by consulting the local natural gas utility or the LP
gas supplier.
8McQuay IM 971-1
Mechanical Installation
LP Conversion
Use a properly calibrated manometer gauge for accurate gas
pressure readings.
DANGER
Only small variations in the gas flow should be made by
means of the pressure regulator adjustment. Furnaces
This unit is equipped at the factory for use with natural gas
only. Conversion to LP gas requires a special kit supplied by
the distributor or manufacturer. Mailing addresses are listed
on the furnace rating plate, parts list and warranty. Failure to
use the proper conversion kit can cause fire, carbon
monoxide poisoning, explosion, personal injury, property
damage, or death.
functioning on LP gas must be set by means of the tank or
branch supply regulators. The furnace manifold pressure
should be set at 10" W.C. at the gas control valve.
To adjust the pressure regulator, remove the regulator cap and
turn the adjustment screw clockwise to increase pressure or
counterclockwise to decrease pressure. Then replace the
regulator cap securely.
Convert the unit to use liquefied petroleum (LP) gas by
replacing with the gas valve supplied in the conversion kit.
Any necessary major changes in the gas flow rate should be
made by changing the size of the burner orifices. To change
The LP gas valve maintains the proper manifold pressure for
LP gas. The correct burner LP orifices are included in the kit.
IMPORTANT: To remove the natural gas valve, remove the
four screws securing the manifold pipe to the burner tray.
Remove the manifold pipe with gas valve attached.
Note: Order the correct LP conversion kit from the furnace
manufacturer. See Conversion Kit Index shipped with
unit for proper LP kit number. Furnace conversion to LP
gas must be performed by a qualified technician.
orifice spuds, shut off the manual main gas valve and remove
the gas manifold.
For elevations up to 2,000 feet, rating plate input ratings apply.
For high altitudes (elevations over 2,000 ft.), contact McQuay
Parts. see conversion kit index 92-21519-XX for derating and
orifice spud sizes.
Check of input is important to prevent over-firing of the
furnace beyond its design-rated input. NEVER SET INPUT
ABOVE THAT SHOWN ON THE RATING PLATE. Use the
Adjusting or Checking Furnace Input
Gas TypeLine pressure (in wc)Manifold Pressure
Natural Gas5 - 10.53.5
LP Gas11-1310
following table or formula to determine input rate.
Cu. Ft./Hr. Required =
Heating Value of Gas (BTU/CuFt) x 3600
Time in Seconds for 1 Cu. Ft. of Gas
Supply and manifold pressure taps are located on the gas valve
body 1/8" N.P.T. and on the manifold.
Table 4: Meter Time In Minutes And Seconds For Normal Input Rating Of Furnaces Using Natural Or Lp Gas
Input
Btu/hr
40,000
60,000
80,000
100,000
Meter Size
Cu. Ft.
One
Ten
One
Ten
One
Ten
One
Ten
900 1000 1040 1100 2500
Min. Sec. Min. Sec. Min. Sec. Min. Sec. Min. Sec.
1
13
0
9
0
6
0
5
21
30
54
0
41
45
33
24
Table 5: LP Gas Pipe Capacity (Cubic feet per hour)
Start the furnace and measure the time required to burn one
cubic foot of gas. Prior to checking the furnace input, make
certain that all other gas units are shut off, with the exception
of pilot burners. Time the meter with only the furnace in
operation.
IMPORTANT NOTE FOR ALTITUDES ABOVE 2,000
FEET (610 METERS): The main burner orifices in your
furnace and in these kits are sized for the nameplate input and
intended for installations at elevations up to 2,000 feet in the
USA or Canada, or for elevations of 2,000 - 4,500 feet (610 -
McQuay IM 971-19
Mechanical Installation
1,373 meters) in Canada if the unit has been derated at the
factory. For elevations above 2,000 feet (610 meters) IN THE USA ONLY (see ANSIZ223.1), the burner orifices must be
sized to reduce the input 4% for each 1,000 feet (305 meters)
above sea level.
NOTICE: Derating of the heating input for high altitude in the
field is unlawful in Canada (refer to CAN/CGA 2.17). Units
installed in altitudes greater than 2,000 feet (610 meters) must
be shipped from the factory or from a factory authorized
conversion station with the heating input derated by 10% so as
to operate properly in altitudes from 2,000 - 4,500 feet (610
1,373 meters).
Condensate Drain
The condensate drain connection of the evaporator is threaded
1" nominal iron pipe. IMPORTANT: Install a condensate trap
to ensure proper condensate drainage. See Figure 9.
Figure 9: Condensate Drain
10McQuay IM 971-1
Electrical Installation
Electrical Installation
Wiring
Power Supply
DANGER
Power supply to the unit must be disconnected before making
field connections. To avoid electrical shock, personal injury or
death, be sure to rigorously adhere to field wiring procedures
regarding proper lockout and tagout of components.
1 All wiring should be made in accordance with the
National Electrical Code. Consult the local power
company to determine the availability of sufficient
power to operate the unit. Check the voltage at power
supply to make sure it corresponds to the unit's RATED
VOLTAGE REQUIREMENT. Install a branch circuit
disconnect near the rooftop, in accordance with the
N.E.C., C.E.C. or local codes.
2 It is important that proper electrical power is available at
the unit. Voltage should not vary more than 10% from
that stamped on the unit nameplate. On three phase units,
phases must be balanced within 3%.
3 For branch circuit wiring (main power supply to unit
disconnect), the minimum wire size for the length of run
can be determined fromTable 6 using the circuit
ampacity found on the unit rating plate.
4 For through the base wiring entry reference Figure 18.
All fittings and conduit are field supplied for this
application. Reference the chart with Figure 26, page 34
For branch circuit wiring (main power supply to unit
disconnect), the minimum wire size for the length of run
can be determined from this table using the circuit
ampacity found on the unit rating plate. From the unit
disconnect to unit, the smallest wire size allowable in
Table 6 may be used, as the disconnect must be in sight
of the unit.
2 Wire size based on 75°C rated wire insulation for 1%
voltage drop.
3 For more than 3 conductors in a raceway or cable, see the
N.E.C. (C.E.C. in Canada) for derating the ampacity of
each conductor.
IMPORTANT: This unit is approved for use with copper
conductors only connected to unit contactor.
Warranty will be voided if aluminum wire is connected to unit
contactor.
To wire unit, refer to the following hook-up diagram. Refer to
Figure 11, page12 and Figure 26, page 34 for location of
wiring entrances. Wiring to be done in the field between the
unit and devices not attached to the unit, or between separate
devices which are field installed and located, shall conform
The customer supplied room thermostat must be compatible
with the spark ignition control on the unit. Generally, all
thermostats that are not of the “current robbing” type are
compatible with the integrated furnace control. The low
voltage wiring should be sized as shown in Table 8.
with the temperature limitation for Type T wire [63°F rise
(35°C)] when installed in accordance with the manufacturer's
instructions.
Internal Wiring
A diagram of the internal wiring of this unit is located on the
inside of control access panel and in this manual. If any of the
original wire as supplied with the unit must be replaced, the
wire gauge and insulation must be same as original wiring.
208 Volt Applications
Transformer is factory wired for 230 volts on 208/230 volt
models and must be changed for 208 volt applications. See
unit wiring diagram for 208 volt wiring.
Table 8: Field Wire Size for 24 Volt Thermostat
Solid Copper Wire, AWG
3.0
16
14
12
10
10
10
2.5
16
14
12
12
10
2.0
18
16
14
12
Thermostat
Load Amps
Note: (1) The total wire length is the distance from the furnace to the
thermostat and back to the furnace.
Note: DO NOT USE CONTROL WIRING SMALLER THAN NO. 18 AWG.
50100150200250300
Length of Run -Feet (1)
12
10
10
Install the room thermostat in accordance with the instruction
sheet packed in the box with the thermostat.
See Figure 13, page 14 for an example of a typical customer
supplied wiring diagram.
12McQuay IM 971-1
Electrical Installation
Optional Factory Supplied Thermostat
Figure 12: Optional Thermostat
The optional factory supplied, touch screen, commercial
setback digital thermostat (Figure 12) uses microcomputer
technology to provide precise time and temperature control.
This thermostat offers the flexibility to design heating and
cooling programs that fit building needs (Table 9). This
thermostat is adaptable to most residential 24 volt forced air
multi-stage systems with electric or fossil fuel auxiliary and is
the ultimate for comfort, convenience, and performance.
See Figure 14, page 14 for an optional factory supplied
thermostat wiring diagram.
1.5 A per terminal, 2.5 A max. combined
45° to 99°F (7° to 37°C)
Adjustable
Adjustable
Heat 0.6°F, Cool 1.2°F
Heat 0.6°F, Cool 1.2°F
32° to +105°F (0° to +41°C)
90% non-condensing max.
-4° to 150°F (-20° to 65°C)
4.6” x 5.9” x 1.2”
Table 10: Thermostat Terminal Functions
Y22nd Stage Compressor
YCompressor Relay
GFan Relay
RCPower for Cooling
RHPower for Heating
C Common wire from secondary side of cooling (Optional). Required for
fault indication, continuous backlight operation or remote temperature
sensor operation
LMalfunction indicator for systems with malfunction connection
W/EHeat Relay/Emergency Heat Relay (Stage 1)
W22nd Stage Heat (3rd Stage Heat in HP2)
Blank Blank
-Common (DC) for wired remote temperature sensor
SFrequency signal from remote temperature sensor
+Power (DC) to remote temperature sensor
1) On 3 to 5 ton units, a terminal block is not supplied. Use a wirenut to extend from the leads provided in the unit to the thermostat.
W1, W2, and Y2 are optional depending upon the size and selected options of the unit. Colors shown above are typical for the MPS I.
2) For wiring with DDC control option, see OM 1077 for wiring instructions.
14McQuay IM 971-1
Electrical Installation
Figure 15: Wiring Diagram: MPS 006B – 007B, 208-230/460 Volt (Cooling Only – Single Stage)
McQuay IM 971-115
Electrical Installation
Figure 16: Wiring Diagram: MPS 006B – 007B, 208-230/460 Volt (Gas Heat – Single Stage)
16McQuay IM 971-1
Figure 17: Wiring Diagram: MPS 006B – 007B, 575 Volt (Cooling Only – Single Stage)
Electrical Installation
McQuay IM 971-117
Electrical Installation
Figure 18: Wiring Diagram: MPS 006B – 007B, 575 V (Gas Heat – Single Stage)