McQuay MPS006AYCL Installation Manual

Maverick I™ Commercial Packaged Rooftop System Cooling Only or Heating & Cooling
Electric/Electric
Model MPS006AY 6 Tons
Installat
ion and Maintenance Manual
Group: Applied Systems
Part Number: 92-102421-04-00
Date: March 2007
© 2007 McQuay International
2 IM 865
Table of Contents
Table of Contents. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Checking Product Received . . . . . . . . . . . . . . . . . . . . 3
Equipment Protection . . . . . . . . . . . . . . . . . . . . . . . . . 3
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Pre-Installation Check Points . . . . . . . . . . . . . . . . . . . . . . . . 6
Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Outside Slab Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Rooftop Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
General Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-9
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Ductwork. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Conversion Procedure . . . . . . . . . . . . . . . . . . . . . . . 11
Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Downflow to Horizontal. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Electrical Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Control Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Internal Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Grounding. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Indoor Air Flow Data . . . . . . . . . . . . . . . . . . . . . . . . . 13
Pre-Start Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Auxiliary Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Control System Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Replacement Parts. . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Charge Information . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
IM 865
3
Introduction
This manual contains the installation and operating instruc­tions for your packaged rooftop unit. There are a few precau­tions that should be taken to derive maximum satisfaction from it. Improper installation can result in unsatisfactory oper­ation or dangerous conditions.
Read this manual and any instructions packaged with separate equipment required to make up the system prior to installation. Give this manual to the owner and explain its provisions. The owner should retain this manual for future reference.
Checking Product Received
Upon receiving the unit, inspect it for any damage from ship­ment. Claims for damage, either shipping or concealed, should be filed immediately with the shipping company. Check the unit model number, electrical characteristics, and accessories to determine if they are correct.
Equipment Protection From The Environment
The metal parts of this unit may be subject to rust or deteriora­tion in adverse environmental conditions. This oxidation could shorten the equipment’s useful life. Salt spray, fog or mist in seacoast areas, sulphur or chlorine from lawn watering sys­tems, and various chemical contaminants from industries such as paper mills and petroleum refineries are especially corro­sive.
If the unit is to be installed in an area where contaminants are likely to be a problem, special attention should be given to the equipment location and exposure.
1 Avoid having lawn sprinkler heads spray directly on the
unit cabinet.
2 In coastal areas, locate the unit on the side of the building
away from the waterfront.
3 Shielding provided by a fence or shrubs may give some
protection.
Regular maintenance will reduce the buildup of contami­nents and help to protect the unit’s finish.
1 Frequent washing of the cabinet, fan blade and coil with
fresh water will remove most of the salt or other contami­nants that build up on the unit.
2 Regular cleaning and waxing of the cabinet with a good
automobile polish will provide some protection.
3 A good liquid cleaner may be used several times a year to
remove matter that will not wash off with water.
Several different types of protective coatings are offered in some areas. These coatings may provide some benefit, but the effectiveness of such coating materials cannot be verified by the equipment manufacturer.
The best protection is frequent cleaning, maintenance and minimal exposure to contaminants.
Recognize this symbol as an indication of Important Safety Information!
!
The manufacturer’s warranty does not cover any damage or defect to the air conditioner caused by the attachment or use of any components, accessories or devices (other than those authorized by the manufacturer) into, onto or in con­junction with the air conditioner. You should be aware that the use of unauthorized components, accessories or devices may adversely affect the operation of the air condi­tioner and may also endanger life and property. The manu­facturer disclaims any responsibility for such loss or injury resulting from the use of such unauthorized components, accessories or devices.
DANGER
!
Proposition 65: This unit contains fiberglass insulation. Respirable particles of fiberglass are known to the state of California to cause cancer.
WARNING
!
Disconnect all power to the unit before starting mainte­nance. Failure to do so can result in severe electrical shock or death.
DANGER
!
4 IM 865
Figure 1: Unit Dimensions Bottom View
Figure 2: Unit Dimensions
ILL 1316
ILL1305
26
78.25
81.53
2
2
2
30.25
BASE ELECTRICAL ENTRY
CONDENSER COIL
CONDENSER COIL
CONROL ENTRY
COMPRESSOR/
CONTROL BOX
ACCESS
ELECTRIC HEAT ACCESS
CONDENSER FAN DISCHARGE GRILLE
POWER ENTRY
RETURN
AIR
SUPPLY
AIR
9.56
44.13
46.5
4.5
3.25
4.5
13.13
20
13.13
2.25
4.63
14.44
2
35
11.13
18.19
7.22
IM 865
5
Figure 3: Unit Dimensions
Figure 4: Unit Dimensions – Back View
ILL 1304
ILL 1288
82.25
25.13
12.25
5.5
19.13
4.94
6.84
13.72
12.25
35
31.22
3.81
82.25
24.03
48.06
5.34
COIL/FILTER
ACCESS
BLOWER
ACCESS
CONDENSATE DRAIN
3/4” NPT FEMALE
RETURN COVER/
OPTIONAL OUTDOOR
AIR HOOD LOCATION
SUPPLY COVER
6 IM 865
Installation
General
1 PRE-INSTALLATION CHECK-POINTS
Before attempting any installation, the following points should be carefully considered:
a Structural strength of supporting members.
(rooftop installation)
b Clearances and provision for servicing. c Power supply and wiring. d Air duct connections. e Drain facilities and connections. f Location for minimum noise.
2 LOCATION
These units are designed for outdoor installations. They can be mounted on a slab or rooftop. They are not to be installed within any part of a structure such as an attic, crawl space, closet, or any other place where condenser air flow is restricted or other than outdoor ambient condi­tions prevail. Since the application of the units is of the outdoor type, it is important to consult your local code authorities at the time the first installation is made.
Outside Slab Installation
(Typical outdoor slab installations are shown in Figures 5 and 6.)
1 Select a location where external water drainage cannot
collect around the unit.
2 Provide a level concrete slab extending 3" beyond all four
sides of the unit. The slab should be sufficient above grade to prevent ground water from entering the unit.
IMPORTANT: To prevent transmission of noise or vibration, slab should not be connected to building structure.
3 The location of the unit should be such as to provide
proper access for inspection and servicing.
4 Locate unit where operating sounds will not disturb owner
or neighbors.
5 Locate unit so roof runoff water does not pour directly on
the unit. Provide gutter or other shielding at roof level. Do not locate unit in an area where excessive snow drifting may occur or accumulate.
Clearances
The following minimum clearances must be observed for proper unit performance and serviceability.
1 Provide 12" minimum clearance at the front of the unit.
Provide 36" minimum clearance at the left and 18" on the right side of the unit for service access.
2 Provide 60" minimum clearance between top of unit and
maximum 3 foot overhang.
3 Unit is design certified for application on combustible
flooring with 0" minimum clearance.
4 See Figure 5 for illustration of minimum installation-ser-
vice clearances.
*5 When used with economizer, 12" minimum dimension at
unit front becomes 57".
Figure 5: Outside Slab Installation, Basement or Crawl Space Distribution System
Figure 6: Outside Slab Installation, Closet Distribution System. Slab Floor Construction
ILL I308
ILL I309
*12
18
*
IM 865
7
Rooftop Installation
1 Before locating the unit on the roof, make sure that the
strength of the roof and beams is adequate at that point to support the weight involved. (See specification sheet for weight of unit.) This is very important and user’s respon­sibility.
2 For rigging and roofcurb details, see Figures 7 and 8. Use
field-furnished spreaders.
NOTE: Remove shipping boards from unit before installing on the roofcurb.
3 For roofcurb assembly, see Roofcurb Installation Instruc-
tions.
4 If the roofcurb is not used, provisions for disposing of
condensate water runoff must be provided.
5 The unit should be placed on a solid and level roofcurb or
platform of adequate strength. See Figure 9.
6 The location of the unit on the roof should be such as to
provide proper access for inspection and servicing.
IMPORTANT: If unit will not be put into service immediately, cover supply and return openings to prevent excessive condensation.
Figure 8: Packaged Air Conditioner Roofcurb Installation
Figure 7: Packaged Air Conditioner Rigging For Lifting
CORNER WEIGHTS BY PERCENTAGE
ABCD
23% 29% 21% 27%
I296
SPREADER BAR
A
C
B
LIFTING BEAM
5/8SHACKLE
(EACH CORNER)
39
26-1/8
CENTER OF
GRAVITY
D
SUPPLY
RETURN
NAILING STRIP
OVERHANG
THIS END
ONLY
6-1/4
*
NOTE
RETURN DUCT*
UNIT
SUPPLY DUCT*
INSULATION PANELS (4) SUPPLIED
ST-A0801-20-01
GASKET (FULL PERIMETER AND ON DIVIDERS. MUST BE ABOVE DUCT AND INSULATION PANEL FLANGES.)
ST-A0801-20-01
ROOFTOP UNIT
COUNTER FLASHING*
INSULATION*
1/4TYP (3) SIDES *SEE NOTE
CANT STRIP*
ROOF FELT*
INSULATION*
ROOF DECK*
*BY CONTRACTOR
ROOF
STRUCTURAL
MEMBER*
ROOFCURB
DUCT*
NAILER STRIP
GASKET
HOLD DOWN BRACKET TYP. (4) PLCS.
CABLE OR CHAIN
NOTE: Remove shipping boards from unit before installing on the roofcurb.
8 IM 865
General Data
Nominal Sizes 6 Tons [21.1 kW] ASHRAE 90.1-2004 Compliant Models
[] Designates Metric Conversions
McQuay MPS Series 006AYCL 006AYCM 006AYDL 006AYDM Cooling Performance
1
Gross Cooling Capacity Btu [kW] 75,000 [21.97] 75,000 [21.97] 75,000 [21.97] 75,000 [21.97] EER/SEER
2
10.3/9.5 10.3/9.5 10.3/NA Nominal CFM/ARI Rated CFM [L/s] 2000/2400 [944/1133] 2000/2400 [944/1133] 2000/2400 [944/1133] 2000/2400 [944/1133] ARI Net Cooling Capacity Btu [kW] 72,000 [21.1] 72,000 [21.1] 72,000 [21.1] 72,000 [21.1] Net Sensible Capacity Btu [kW] 53,000 [15.53] 53,000 [15.53] 53,000 [15.53] 53,000 [15.53]
Net System Power kW 6.99 6.99 6.99 6.99
Net Weight lbs. [kg] 619 [281] 619 [281] 619 [281] 619 [281]
Integrated Part Load Value
3
11.5 11.5 11.5 11.5
Compressor
No./Type 2/Scroll 2/Scroll 2/Scroll 2/Scroll
Outdoor Sound Rating (dB)
4
83 83 83 83
Outdoor Coil—Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled Tube Size in. [mm] OD 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 16.56 [1.54] 16.56 [1.54] 16.56 [1.54] 16.56 [1.54] Rows / FPI [FPcm] 2 / 22 [9] 2 / 22 [9] 2 / 22 [9] 2 / 22 [9]
Net Latent Capacity Btu [kW] 19,000 [5.57] 19,000 [5.57] 19,000 [5.57] 19,000 [5.57]
Indoor Coil—Fin Type Louvered Louvered Louvered Louvered
Tube Type Rifled Rifled Rifled Rifled Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 6.5 [0.6] 6.5 [0.6] 6.5 [0.6] 6.5 [0.6] Rows / FPI [FPcm] 4 / 12 [5] 4 / 12 [5] 4 / 12 [5] 4 / 12 [5] Refrigerant Control Capillary Tubes Capillary Tubes Capillary Tubes Capillary Tubes Drain Connection No./Size in. [mm] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4]
Outdoor Fan—Type Propeller Propeller Propeller Propeller
No. Used/Diameter in. [mm] 1/24 [609.6] 1/24 [609.6] 1/24 [609.6] 1/24 [609.6] Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1 CFM [L/s] 4000 [1888] 4000 [1888] 4000 [1888] 4000 [1888] No. Motors/HP 1 at 1/3 HP 1 at 1/3 HP 1 at 1/3 HP 1 at 1/3 HP Motor RPM 1075 1075 1075 1075
Indoor Fan—Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal
No. Used/Diameter in. [mm] 1/10x9 [254x229] 1/10x9 [254x229] 1/10x9 [254x229] 1/10x9 [254x229] Drive Type/No. Speeds Belt/Variable Belt/Variable Belt/Variable Belt/Variable No. Motors 1 1 1 1 Motor HP 1 1/2 1 1/2 1 1/2 1 1/2 Motor RPM 1725 1725 1725 1725 Motor Frame Size 0 0 0 0
Filter—Type Disposable Disposable Disposable Disposable
Furnished Yes Yes Yes Yes (No.) Size Recommended in. [mm] (4)2x16x16 [51x406x406] (4)2x16x16 [51x406x406] (4)2x16x16 [51x406x406] (4)2x16x16 [51x406x406]
Refrigerant Charge Oz. (Sys. 1/Sys. 2) [g] 88/88 [2495/2495] 88/88 [2495/2495] 88/88 [2495/2495] 88/88 [2495/2495] Weights
Ship Weight lbs. [kg] 628 [285] 628 [285] 628 [285] 628 [285]
10.3/NA
CONTINUED
NOTES:
1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner Equipment certification program, which is based on ARI Standard 210/240 or 360.
2. EER and/or S
EER are rated at ARI conditions and in accordance with DOE test procedures.
3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80° F ambient, 80° F entering dry bulb, and 67° F entering wet bulb at ARI rated cfm.
4. Outdoor Sound Rating shown is tested in accordance with ARI Sta
ndard 270.
Loading...
+ 16 hidden pages