McQuay MPS003 Installation Manual

Installation and Maintenance Manual IM 921-1
Accessories for Maverick™ I Commercial Packaged Rooftop Systems
Models MPS003 – 025 3 to 25 Tons R-410A Refrigerant
Group: Applied Systems
Part Number: IM 921-1
Date: May 2010
Note: This manual is a collection of various installation manuals for accessories that may be purchased separately. To print this manual with
page numbers showing, choose “Documents and Markups” from the Adobe
© 2010 McQuay International
®
Reader® print option settings.
INSTALLATION INSTRUCTIONS
MODELS (-)XRX-BGF03 & (-)XRX-BGF04/BGF06
ECONOMIZER POWER EXHAUST
WARN ING
This installation shall be carried out by a manufacturer's authorized representative, in accordance with the requirements of the manufacturer. Failure to follow instructions can result in fire or explosion, causing property damage, severe personal injury, or death. The qualified service personnel performing this work assumes responsibility for this installation.
IM POR TANT
Damage to the product, resulting from failure to follow instructions or use of unauthorized parts, may be exclude from the manufacturer's product warranty coverage.
WARN ING
Turn off electrical power and turn off main gas supply before beginning modification. Failure to do so can cause electrical shock, explosion, or fire, resulting in property damage, personal injury, or death.
TOOLS RE QUIRED FOR IN STAL LA TION:
3
" electric drill with
8
1
" diameter drill bit for sheet metal.
8
5
" socket
16
(-)XRX-BGF04
PACK AGE CON TENTS
ITEM DE SCRIP TION PART No. PART No.
1 Power Exhaust Assembly 6046520 / PEA 6046508 / PEA
2 Fan Blade 6046520 / 3464 6046508 / 3464
3 Fan Motor 208-230 volt / 1 phase (C) 6046520 / 3675 6046508 / 3675
4 Fan Motor 460 volt / 1 phase (D) 6046520 / 3675 6046508 / 3675
5 Fan Motor 575 volt / 1 phase (Y) 6046520 / 3698 6046508 / 3968
6 Relay (R1) 6046520 / 3400 6046508 / 3400
7 Fuse Block 6046520 / 3370 6046508 / 3370
8 Barometric Relief Adaptor 6046520 / ADP 6046508 / ADP
(-)XRX-BGF06 Power Exhaust C, D, Y Voltage
(-)XRX-BGF03 Power Exhaust C, D, Y Voltage
Step 1:
Remove lower barometric relief hood. Remove relief damper section from economizer or duct work.
Step 2:
Place relief damper section onto barometric relief damper adapter and secure with screws provided with power exhaust.
Step 3: Place relief damper assembly into lower hood assembly where prepunched holes are in hood sides with screws from Step
1.
Horizontal Application:
Step 4: Place power exhaust over hole in duct work and secure to duct work. Adjust support legs to level power exhaust. See Figure 1.
Vertical Application:
Step 5:
Place over hole where hood was located and secure. See Figure 2.
MODEL "A"
3 - 6 TON 23.750 REF
7 ½ TON 29.750 REF.
RETURN DUCT TO BE PROPERLY SIZED FOR AIRFLOW OF SPECIFIC INSTALLATION
A
FIGURE1
2
SECURE TO DUCT WORK
PREPUNCHED HOLE FOR
RELIEF DAMPER
BAROMETRIC RELIEF DAMPER & HOOD TO BE RELOCATED FROM ECONOMIZER TO POWER EXHAUST
SECURE TO HOOD EXTENSION
PREPUNCHED HOLE FOR RELIEF DAMPER
NOTE: COIL NOT SHOWN FOR CLARITY
FIGURE 2
HARNESS DETAIL
COMPONENT CODE WIRE COLOR CODE
BLK Black BLU Blue BRN Brown GRN Green GRY Gray ORG Orange RED Red VIO Violet YEL Yellow
Notes:
230 Volt 1-Phase Power Ex haust for
RXRX-BGF03C / RXRX-BGF04C
RKKA/JKA/LKA/KMA/JMA/LMA/KNL/LNL/JNL 036-072
Roof top Sys tems, Inc. 2405 McIver Lane Car roll ton, Texas 75006 Phone(972) 247- 7447 Fax (972) 243- 0940
RKNA/LNA/JNA 036-060
Date: June 17, 2009 Supersedes: 05-17-06 Drawn by: MGL Unit #:60-465-20/08-21 Di a gram#: 4652021W Ap proved by:
3
HARNESS DETAIL
COMPONENT CODE
WIRE COLOR CODE
BLK Black BLU Blue BRN Brown GRN Green GRY Gray ORG Orange RED Red VIO Violet WHT White YEL Yellow
Notes:
HARNESS DETAIL
COMPONENT CODE
460 Volt 1-Phase Power Ex haust for
(-)XRX-BGF03D / (-)XRX-BGF04D/BGF06
RKKA/JKA/LKA/KMA/JMA/LMA/KNL/LNL/JNL 036-072
Roof top Sys tems, Inc. 2405 McIver Lane Car roll ton, Texas 75006 Phone(972) 247- 7447 Fax (972) 243- 0940
BLK Black BLU Blue BRN Brown GRN Green GRY Gray ORG Orange RED Red VIO Violet WHT White YEL Yellow
RKNA/LNA/JNA 036-060
Date: June 17, 2009 Supersedes: 05-17-06 Drawn by: MGL Unit #:60-465-20/08-31 Di a gram#: 4652031W Ap proved by:
WIRE COLOR CODE
Notes:
SUPERSEDES 05-28-09 JUNE 17, 2009
575 Volt 1-Phase Power Ex haust for
(-)XRX-BGF03Y / (-)XRX-BGF04Y/BGF06
RKKA/JKA/LKA/KMA/JMA/LMA/KNL/LNL/JNL 036-072
Roof top Sys tems, Inc. 2405 McIver Lane Car roll ton, Texas 75006 Phone(972) 247- 7447 Fax (972) 243- 0940
RKNA/LNA/JNA 036-060
Date: June 17, 2009 Supersedes: 05-17-06 Drawn by: MGL Unit #:60-465-20/08-41 Di a gram#: 4652041W Ap proved by:
RMIPE20
INSTALLATION INSTRUCTIONS
MODELS (-)XRX-BGF05
ECONOMIZER POWER EXHAUST
WARN ING
This installation shall be carried out by a manufacturer's authorized representative, in accordance with the requirements of the manufacturer. Failure to follow instructions can result in fire or explosion, causing property damage, severe personal injury, or death. The qualified service personnel performing this work assumes responsibility for this installation.
IM POR TANT
Damage to the product, resulting from failure to follow instructions or use of unauthorized parts, may be exclude from the manufacturer's product warranty coverage.
WARN ING
Turn off electrical power and turn off main gas supply before beginning modification. Failure to do so can cause electrical shock, explosion, or fire, resulting in property damage, personal injury, or death.
TOOLS RE QUIRED FOR IN STAL LA TION:
3
" electric drill with
8
1
" diameter drill bit for sheet metal.
8
5
" socket
16
(-)XRX-BGF05
PACK AGE CON TENTS
ITEM DE SCRIP TION PART No.
1 Power Exhaust Assembly 6046516 / PEA
2 Fan Blade 6046516 / 3465
3 Fan Motor 208-230 volt / 1 phase(C) 6046516 / 3677
4 Fan Motor 460 volt / 1 phase (D) 6046516 / 3694
5 Fan Motor 575 volt / 1 phase (Y) 6046516 / 3690
6 Relay (R1) 6046516 / 3400
7 Fuse Block 6046516 / 3370
8 Barometric Relief Adaptor 6046516 / ADP
Power Exhaust C, D, Y Voltage
INSTALLATION
1. Remove return cover. See Figure 1.
2. Connect new wire harness in control box back (View A) and route above economizer. See Figure 2.
FILTERS
EXISTING WIRE HARNESS
VIEW A
NEW WIRE HARNESS
ECONOMIZER
RETURN COVER
FIGURE 1
REMOVE PLUG IN BULKHEAD BEFORE INSTALLING NEW WIRE HARNESS
INSTALL FUSES IN FUSEHOLDERS
VIEW A
CONNECT WIRE HARNESS TERMINALS TO ANY TWO OF THE THREE SUPPLY FAN CONTACTOR TERMINALS.
FIGURE 2
2
3. Remove relief dampers from economizer. See
Figure 3.
4. Connect power exhaust wiring:
Plug in control connections from power exhausts to existing connections provided on economizer.
Remove small rectangular cover beside control connections on economizer and discard
(Figure 2).
Use screw that was removed in previous step to attach ground terminals on wire harness.
Plug in power connections through the rectangular holes revealed when the cover was removed.
5. Route power and control connections under divider panel using line clamps provided to take up excess slack in wiring harness and avoid contact between fan blades and wiring harness during operation (Figure 4). secure each power exhaust with (4) screws (2 in top flange and 2 in bottom flange).
POWER EXHAUST
RELIEF DAMPERS
6. Connect ends of new wire harness to power connections. See Figure 4.
7. Reinstall relief dampers.
8. Reinstall return cover.
9. All units are factory shipped for high speed. for changing to low speed, see notes section on wiring diagram.
POWER CONNECTIONS
FIGURE 3
(5) LINE CLAMPS
DIVIDER PANEL
CONTROL CONNECTIONS
FIGURE 4
SUPERSEDES 08-19-09 AUGUST 25, 2009
RMIPE16
E# = WIRE END DESIGNATION
E2 STUD #6 18 Ga. Wire E3 Female ¼ Quick Disc. E4 Male ¼ Quick Disc. Insul E6 Wire Nut Size 73B
HAR NESS LEADS
ARE 14 GA. WIRE
WITH NO END
DES IG NA TION
COMPONENT CODE
WIRE COLOR CODE
BLK Black BLU Blue BRN Brown GRN Green GRY Gray ORG Orange RED Red VIO Violet YEL Yellow
Re vi sion Change Date
ECN 3032 Changed wir ing diagram 08-18-09
CON NEC TOR & CON TACT CON FIG U RA TION
P1 (303903) PLUG - (303912) PIN
S1 (303904) CAP - (303913) SOCKET
Notes:
1. Con nect J12 to S12 at economizer. High volt age har ness.
2. A. Power Ex haust wired for High speed. B. For Med speed dis con nect BLK at re lay (3). C. For Low speed dis con nect BLK at re lay (3).
3. Be sure all leads from mo tor have been cov ered with tape.
4. Con nect J2 to S2 at economizer. Low volt age har ness.
208-230/460/575 Volt 1 Phase Power Ex haust for
RKNL / RLNL 180-300
Date: August 18, 2009 Supercedes: 06-29-09 Drawn by: MGL Unit #: 60-465-16-21/31/41 Di a gram#: 604651641w Ap proved by:
INSTALLATION INSTRUCTIONS
MODELS (-)XRD-RGCM3
HORIZONTAL AIRFLOW ECONOMIZERS
WARN ING
THIS ACCESSORY IS TO BE INSTALLED BY A QUALIFIED, LICENSED SERVICE PERSON. TO AVOID UNSATISFACTORY OPERATION OR DAMAGE TO THE PRODUCT AND POSSIBLE UNSAFE CONDITIONS, INCLUDING ELECTRICAL SHOCK, REFRIGERANT LEAKAGE AND FIRE, THE INSTALLATION INSTRUCTIONS PROVIDED WITH THIS ACCESSORY MUST BE STRICTLY FOLLOWED AND THE PARTS SUPPLIED USED WITHOUT SUBSTITUTION. DAMAGE TO THE PRODUCT RESULTING FROM NOT FOLLOWING THE INSTRUCTIONS OR USING UNAUTHORIZED PARTS MAY BE EXCLUDED FROM THE MANUFACTURER’S WARRANTY COVERAGE.
WARN ING
DISCONNECT ELECTRICAL POWER TO THE UNI T. FAILURE TO DO S O CAN CAUSE ELE CTRICAL SHOCK RESULTING IN PERSONAL INJURY OR DEATH.
TOOLS RE QUIRED FOR IN STAL LA TION:
3
" elec tric drill with
8
Wa ter proof ex te rior duct seal ant Sheet metal tools (e.g. shears)
5
" socket Small flat blade (0.125" wide) screw driver
16
TABLE 1
PACK AGE CON TENTS
ITEM DE SCRIP TION PART No.
1 2 3 4 5 6 7 8
9 10 11 12 13 14
Discharge Air Sensor (Hardware Bag) (2) Permanent Filters (2) Spotweld Assy - Bird Screen (2) Exhaust Air Rainhood - Top OA Rainhood Assy - Left Side OA Rainhood Assy - Right Side (2) Exhaust Air Rainhood - Left Side (2) Exhaust Air Rainhood – Right Side OA Rainhood Assy - Filter Bracket Strip OA Rainhood Assy – Top OA Rainhood - Front Filter Support OA Filter Rail Hardware Bag Exhaust Air Rain Hood Spacer
(-)XRD-RGCM3 economizer with controller,
actuator, and outside enthalpy sensor attached
6039416 / 3112
6039416 / 8568 (23.875" X 23.875")
6039416 / BSWA
6039416 / EHT2 6039416 / EHSL
6039416 / EHSR 6039416 / EHS3L 6039416 / EHS3R
6039416 / ADP
6039416 / EHT 6039416 / EHB 6039416 / FCH
6039416 / HDW
6039416 / ADP2
FIGURE 1
PANEL - TOP LEFT
PANEL - LEFT BOTTOM SECTION
RETURN COVER
STEP 1:
Immediately upon receipt, all cartons and contents should be inspected for transit damage. Units with damaged cartons should be opened immediately. If damage is found, it should be noted on the delivery papers and a damage claim filed with the last carrier.
STEP 2:
Remove RETURN COVER, PANEL – TOP LEFT, and PANEL – LEFT BOTTOM SECTION from the unit and retain for reuse (SEE FIGURE 1). Retain screws.
STEP 3:
Fasten RETURN COVER (SEE FIGURE 2) over bottom return opening using 4 retained screws.
STEP 4:
Remove screws from 3 sides of ROOF PANEL so that it can be raised during economizer insertion.
STEP 5:
Remove jumper plug PL7 and connect unit ECONOMIZER PLUG to economizer mating plug and slide economizer into unit. Reinstall jumper plug PL7to PL21 located on economizer.
FIGURE 2
RE TURN COVER
ECONOMIZER
(SEE BILL OF MA TE RIAL)
A1005-01
ROOF PANEL
ECONOMIZER PLUG
A1005-01
2
STEP 6: Mount PANEL – LEFT BOTTOM SECTION to unit (SEE FIGURE 3). Use only 2 screws (one on each side) for easy removal during calibration.
STEP 11: Fasten 11 OA RA INHOOD - FRONT FILTER SUPPORT to PANEL – TOP LEFT. The bottom lip should support the PERMANENT FILTERS.
STEP 7: Fasten  FILTER BRACKET STRIP to unit using 2 screws (one on each side). See Table 1 for identification.
STEP 8: Fasten 12 OA FILTER RAIL to FILTER BRACKET STRIP with 4 screws. Fasten FILTER BRACKET STRIP to economizer with 4 neoprene washer head screws provided.
STEP 9: Fasten OA RAINHOOD - LEFT SIDE and OA RAINHOOD - RIGHT SIDE to unit using 3 screws provided.
STEP 10: Slide PERMANENT FILTERS between OA RAINHOOD - LEFT SIDE and OA RAINHOOD - RI GHT SIDE back into the 12 OA FILTER RAIL.
STEP 12: Fasten PANEL – TOP LEFT to OA RAINHOOD - LEFT SIDE and OA RAINHOOD - RIGHT SIDE and 11 OA RAINHOOD - FRONT FILTER SUPPORT using 16 screws.
STEP 13:
Position the OA RAINHOOD ASSY – TOP under edge of ROOF PANEL.
STEP 14: Re-secure ROOF PANEL using existing screws.
FIGURE 3
PANEL - LEFT BOTTOM SECTION
ROOF PANEL (REF.)
12
PANEL - TOP LEFT
11
A1012-01
3
STEP 15:
Provide opening in return air duct to mount the two barometric relief dampers and hoods (SEE FIGURE 4). Locate a convenient distance from unit.
STEP 16:
Using self-drilling screws provided, assemble exhaust air rain hoods ( EXHAUST AIR RAINHOOD – TOP, EXHAUST AIR RAINHOOD - LEFT SIDE, EXHAUST AIR RAINHOOD - RIGHT SIDE, SPOTWELD ASSY ­BIRD SCREEN) and install in return air duct. Use sealant (not provided) as required.
STEP 17: Remove the blower motor access panel (SEE FIGURE 5).
STEP 18:
Connect the DISCHARGE AIR SENSOR to wires 51 and 52 located in the blower motor compartment.
NOTE:
Mixed air sensor should be secured with the included wire tie to avoid entanglement with the blower and direct contact with any sheet metal surfaces.
STEP 19:
Replace the blower motor access panel.
FIGURE 4
SUPPLY AIR
25.250
RETURN AIR
DUCT
PANEL - LEFT BOTTOM SECTION
STEP 20:
Upon start-up check the economizer sequence of operation using the steps provided in these instructions. After testing unit operation and setting outside air damper minimum position, secure PANEL – LEFT BOTTOM SECTION (SEE FIGURE 3) with remaining screws.
FIGURE 5
WIRE TIE
25.250
47.250
A1005-01
INDOOR MOTOR
A1006-01
4
DI RECT MOUNT ECONOMIZER SE QUENCE OF OP ER A TION
GEN ERAL
This accessory economizer package is designed to save energy costs by using outdoor air for cooling and ventilation in place of mechanical cooling whenever possible. The economizer continuously monitors indoor and outdoor air conditions and compares them to a user-selected setpoint to determine if free cooling is available.
AC CES SO RIES
RXRX-AV02 — Dual Enthalpy Up grade Kit
For maximum energy savings, this upgrade kit will allow the economizer to compare the outdoor air enthalpy to the return air enthalpy, instead of a user-selected setpoint to determine if "free cooling" is available.
RXRX-AR02 - Wall-Mounted Car bon Di ox ide Sen sor
For installations requiring Demand Control Ventilation (DCV) based upon indoor air levels of carbon dioxide (CO2). When the unit supply fan is running, the CO2 sensor modulates the outside air damper to maintain a user-selected CO2 level inside the occupied space. Energy savings are achieved by not bringing in excessive amounts of outdoor air when the indoor air conditions are suitable. Energy savings can be substantial on buildings with highly variable occupancy rates.
Wall-Mounted Remote Potentiometer
For installations requiring remote adjustment of damper minimum position by the occupants, a remote potentiometer, such as the Honeywell S963B1128 can be used.
RXRX-BFF02C, RXRX-BFF02D, RXRX-BFF02Y — Power Exhaust Kit
For installations requiring more space static pressure relief than can be obtained with the standard barometric relief damper included with the economizer, a power exhaust kit can be added.
B. Range of adjustment is from 0-100% (2-10V); in
most applications the minimum position is adjusted to allow 10% to 25% outside air to enter the system.
C. The Outside Air Damper Minimum Position
potentiometer can be adjusted at any time.
D. Whenever the "G" (supply fan) signal is present,
the damper will open to this minimum position unless:
a. It may modulate to a greater position if
overridden by the CO2 sensor (DCV).
b. It may not open if overridden by the discharge
air temperature sensor (Freeze Protect Mode).
3. DCV Max — Demand Control Ventilation (DCV) Maximum Setpoint
A. The DCV maximum position potentiometer allows
the installer to limit the amount of outdoor air flow into the building when the DCV overrides the mixed air sensor.
B. Setting the DCV maximum position of the damper
prevents the introduction of large amounts of hot or cold air into the space.
C. Note: If the DCV maximum position is set below
the outside air damper minimum position, the minimum position overrides the DCV maximum position (negating the function of the DCV).
4. DCV Set — Demand Control Ventilation (DCV) Setpoint
A. The DCV can be any sensor that provides a
2-10Vdc output. The DCV modulates the outdoor damper to provide ventilation based on occupancy. Typically, a carbon dioxide (CO2) sensor is used to indirectly monitor occupancy level.
B. No cooling signal (e.g.Y1, Y2) is required for the
DCV to override the outdoor air damper when ventilation requires outdoor air.
C. The controller must receive a "G" (supply fan)
signal to open the damper. D. Range of adjustment is from 2 Volts to 10 Volts. E. The DCV setpoint can be adjusted at any time.
FIGURE 6
STARTUP
Attach connector from Economizer Controller to Rooftop Control Panel Connector and install discharge/mixed air temperature sensor per installation guide.
AD JUST MENTS
5 po ten ti om eters with screw driver ad just ment slots, start ing from top of con trol ler
1. EXH Set — Adjustments for (optional) power ex haust A. The outside air damper position at which the
power exhaust fan(s) will engage. The LED labeled EXH below the potentiometer adjustment will indicate when power exhaust is available. When the power exhaust call is made, the controller provides a 60 ±30 second delay before exhaust fan activation to allow the damper to reach the appropriate position.
B. Range of adjustment is from 0-100% (2-10V); in
most applications the power exhaust is set to engage at about 70% outside air.
5
F. The controller compares the CO2 sensor input to
the setpoint setting to determine the damper minimum position.
a. If the actual CO2 level is below the setpoint,
then the damper minimum position is determined by the damper minimum position potentiometer setting.
b. If the actual CO2 level rises above the
setpoint, then the damper minimum position is overridden proportionally more open.
c. If the discharge air temperature drops below
48°F (Freeze Protect Mode), the DCV input will be overridden and the damper may not open.
G. Compatible CO2 sensors will have a 2-10Vdc
output for a 0-1500 ppm CO2 input.
H. Ensure proper polarity of the sensor wires when
connecting to the economizer controller. Incorrect polarity negates the sensor signal.
5. Economizer Setpoint A. Only the coolest, driest outside air is used for
economizer operation when the potentiometer is on setting "D". For greatest energy savings, the potentiometer is on setting "A".
B. Adjustment range is A, B, C, or D
a. Setting "A" = 73F db or 27 Btu/lbm @ 50% RH b. Setting "B" = 70F db or 25 Btu/lbm @ 50% RH c. Setting "C" = 67F db or 23 Btu/lbm @ 50% RH d. Setting "D" = 63F db or 22 Btu/lbm @ 50% RH
C. Economizer Setpoint potentiometer can be
adjusted at any time.
D. The controller compares the enthalpy sensor input
with the economizer setpoint to determine if free cooling is available.
a. Single enthalpy strategy: If outdoor air
enthalpy is lower than the setpoint, then free cooling is available. Note: The factory-installed 620-ohm resistor must be in place across terminals SR and SR+.
b. Dual enthalpy strategy: If outdoor air enthalpy
is lower than return air enthalpy, then free cooling is available.
1. Note: If using dual enthalpy, the Economizer Setpoint must be at the "D" setting.
2. The factory-installed 620-ohm jumper must be removed to install the dual enthalpy upgrade kit.
NOR MAL OP ER A TION
1. Fan Only (G) A. Damper will go to minimum position (in 90
seconds or less) whenever the "G" (supply fan) signal is present.
B. When "G" signal is removed, the outside air
damper closes against blade seals for tight shutoff of outside air.
C. If the discharge air temperature drops below 48ºF,
then the control will override the minimum position setting and will modulate the outside air damper closed.
2. Call for First Stage of Cooling (Y1) A. Economizer Unavailable (warm outdoor air).
Compressor 1 is commanded on without delay.
B. Economizer Available (free cooling). The
controller tries to maintain a discharge air temperature of 53ºF ± 5 by modulating the outside air damper position.
FIGURE 7
3. Call for Second Stage of Cooling (Y2) A. Economizer Unavailable (warm outdoor air).
Compressor 2 is commanded on without delay.
B. Economizer Available (free cooling). Compressor
1 is commanded on without delay. The controller tries to maintain a discharge air temperature of 53ºF ± 5 by modulating the outside air damper position. Compressor 2 is not activated in the economizer mode.
4. Call for Heat A. Standard Air Conditioner with electric or gas heat.
(W1 & W2) a. The Thermostat controls the stages of heating
directly.
b. If the control detects that the supply fan is on
(through its "G" input), then the control will open the damper to minimum position.
c. If the discharge air temperature drops below
48ºF, then the control will override the minimum position setting and will modulate the outdoor damper closed.
B. Heat Pump Operation (B)
a. The "B" signal from the Thermostat allows
operation of the compressors to provide heating without delay.
b If the control detects that the supply fan is on
(through its "G" input), then the control can open the damper to minimum position.
c. If the discharge air temperature drops below
48ºF, then the control will override the minimum position setting and will modulate the outdoor damper closed.
5. Low Ambient Compressor Lockout – None present.
6
TROU BLE SHOOT ING
1. Checkout requires a handheld multimeter, 9V battery, a 5.6k ohm .25 watt resistor, a 1.2k ohm .25 watt resistor, a jumper wire with .25" quick connect terminals, and the 620 ohm resistor that is factory-installed across terminals SR+ and SR. The terminal names below reference the economizer controller. Use the following flowcharts for to diagnose unit.
2. a. Disconnect power to the unit.
b. Jumper P to P1 (factory installed jumper is
normally present).
c. Remove outdoor air enthalpy sensor from
terminals SO+ and SO and install the 1.2k ohm resistor.
d. Put 620 ohm resistor across terminals SR+ and
SR (factory installed 620 ohm resistor is normally present and can be used).
e. Put 5.6k ohm resistor across T and T1.
3. a. Turn (EXH Set) Exhaust fan Setpoint
potentiometer fully CCW.
b. Turn (Min Pos) Minimum Outside Air Damper
potentiometer fully CCW.
c. Turn (DCV Max) Demand Control Ventilation
Maximum potentiometer fully CW.
d. Turn (DCV Set) Demand Control Ventilation
Setpoint potentiometer fully CCW.
e. Turn enthalpy potentiometer to "D".
7
BASIC ECONOMIZER OPERATION
START Perform STEP 2 Perform STEP 3
Put thermostat fan setting to "CONTINUOUS FAN"
Reapply Power to the Unit
Set thermostat so neither heating or cooling is called
Connect Economizer Wire Harness to Unit
Check Thermostat Connections
Check for 24 VAC at Unit Transformer
Check Unit Wire Harness
Check Economizer Controller Model Number
Perform STEP 2 & STEP 3 again.
If problem continues, replace controller
Unplug Economizer Wire Harness from Unit Wire harness and Install
Jumper Plug (Jumpers Y1 Thermostat to Y1 Compressor and Jumpers
Y2 Thermostat to Y2 Compressor)
If one stage of cooling is called by the
thermostat, do first stage
compressor(s) run? If both stages
are called, do both stages
of compressors
run?
NO
Check Thermostat Wiring
Check Unit Wiring Harness
The "Free Cooling" LED turns on & the EXH LED turns on.
If only one stage of cooling is called by the thermostat, then that stage
will turn off. If two stages are called by the thermostat, then only the
second stage will turn off. The power exhaust (optional) contacts will
close after 60 +/- 30 seconds. The outside air damper opens
approximately 50% (this position is determined by the actual resistance
of the 5.6k ohm resistor placed across terminals T and T1).
Set enthalpy potentiometer to D (fully CW).
The "Free Cooling" LED turns off & the EXH LED turns off.
If only one stage of cooling is called by the thermostat, then that stage
will turn back on. If two stages are called by the thermostat, then both stages will turn on. The power exhaust (optional) contacts open & the
outside air damper fully closes.
Set enthalpy potentiometer back to A (fully CCW).
Remove 5.6k ohm resistor and jumper terminals T to T1.
(W7213A1016)
YES
Check Economizer Wiring
Harness. Check Unit wiring
harness at economizer
connection for proper terminal
location
YES
YES
NO
NO
Turn down thermostat setting so that a call for cooling is present.
NO
Set enthalpy potentiometer on economizer controller to A (fully CCW).
NO
Recheck STEP 2 and STEP 3. If LED’s turn on and damper motor
does not operate, measure voltage between terminals 24V COM and
(+ (white wire)). If approximately 6 VDC is present, replace damper
actuator. If voltage not present, or LED’s do not light replace controller.
NO
Recheck STEP 2 and STEP 3.
If problem continues replace controller
24 VAC power
available between terminal TR and
TR1?
YES
Are all LED's off &
outside air damper fully closed?
YES
If one stage of cooling is called by the
thermostat, do first stage
compressor(s) run? If both stages
are called, do both stages
of compressors
run?
YES
The "Free Cooling" LED turns on & the EXH LED turns on. If only one
stage of cooling is called by the thermostat, then that stage will turn off.
If two stages of cooling are called by the thermostat, then only the
second stage will turn off. The power exhaust (optional) contacts will
close after 60 +/- 30 seconds. The outside air damper fully opens
YES
Remove jumper from terminals T to T1 and leave open (simulates the
The "Free Cooling" LED remains on & the EXH LED turns off.
If only one stage of cooling is called by the thermostat, then that stage
will remain off. If two stages of cooling are called by the thermostat,
then only the second stage will remain off. The power exhaust
(optional) contacts opens & the outside air damper fully closes
Economizer Controller, Actuator, Wiring are correct.
Remove resistors, reconnect wires, and set up
Freeze Protect mode).
YES
potentiometers per jobsite requirements.
8
NO
NO
HEAT PUMP OPERATION
(Perform BASIC ECONOMIZER OPERATI ON check first)
START
Perform STEP 2
Perform STEP 3
Put thermostat fan setting to "CONTINUOUS FAN"
Reapply Power to the Unit
Turn down thermostat setting so that a call for cooling is present.
Set enthalpy potentiometer on economizer controller to A (fully CCW).
The "Free Cooling" LED turns on & the EXH LED turns on.
If only one stage of cooling is called by the thermostat, then that stage will turn off.
If two stages are called by the thermostat, then only the second stage will turn off.
The power exhaust (optional) contacts will close after 60 +/- 30 seconds.
The outside air damper opens approximately 50% (this position is determined by
the actual resistance of the 5.6k ohm resistor placed across terminals T and T1).
YES
Reset the thermostat setting so that a call for heating is present.
The "Free Cooling" LED turns off & the EXH LED turns off.
If only one stage of heating is called by the thermostat, then that stage will turn on.
If two stages are called by the thermostat, then both stages will turn on.
The power exhaust (optional) contacts will open The outside air damper fully
closes.
NO
Perform Basic Economizer Operation
check first. Recheck STEP 2 and
STEP 3
NO
YES
Turn Min Pos potentiometer fully CW.
The outside air damper drives fully open.
The EXH LED turns on.
The power exhaust (optional) contacts will close after
approximately 60 +/- 30 seconds.
YES
Heat Pump Operation is Correct.
Remove resistors, reconnect wires, and set up
potentiometers per jobsite requirements.
Check for 24 VAC at B terminal.
Check for B signal at thermostat.
Check Unit wire harness.
Check Economizer Wire harness.
NO
Replace controller.
9
Use the following graph and the multimeter to verify proper operation of the mixed air / discharge air temperature sensor.
Measure the resistance (ohms) of the mixed air / discharge air temperature sensor with the multimeter. Look up the equivalent temperature on the graph. This should be the same as temperature the mixed air / discharge air sensor is detecting. If it is not, replace the mixed air /discharge air sensor.
NOTES
1. The mist eliminator (Permanent Outdoor Air Filter), is of aluminum mesh construction and should be cleaned by flushing regularly with warm soapy water. The replacement mist eliminator size is listed on the first page of these instructions.
2. When diagnosing the system, the best results are obtained by first putting the fan setting on the Thermostat to the "Continuous Fan" mode.
3. Operation of the optional power exhaust only depends upon the supply fan running and the damper position (it is possible to set the minimum position high enough to engage the power exhaust in the heating mode).
4. This economizer requires a two-stage thermostat.
5. Upon loss of power to the unit or economizer, the outside air damper will spring close shut in about 5 seconds.
6. Compressor Time Delays, Compressor Interstage Delays, Compressor Low Ambient Lockouts, etc. are not provided by the economizer controller.
10
HARNESS ENDS AT PL6 & PL7
COMPONENT CODE
C7400A Fresh Air Sensor 9RT1H Mixed Air Sensor J2 Power Exhaust Cap MS7106K Damper Actuator 24v PL6 Male A/C Unit Plug PL7 Female A/C Unit Plug PL20 Female Economizer Cap PL21 Male Smoke Plug W7213A Logic Module
WIRE COLOR CODE
BLK Black BLU Blue BRN Brown GRN Green GRY Gray ORG Orange PNK Pink RED Red TAN Tan VIO Violet WHT White YEL Yellow
Re vi sion Change Date
ECN 2259 Change brown wire length 07/09/09
CONNECTOR & CONTACT CONFIGURATION
PL7 (303917) CAP - (303902) SOCKET
J2 (303909) CAP - (303902) SOCKET
Notes:
1. Unit wir ing shown as ref er ence only. Check unit wir ing for ac tual unit wir ing.
2. Re lays 1K and 2K ac tu ate when the Out door Air Enthalpy is lower than the Re turn Air Enthalpy.
3. 1S is an elec tronic switch which closes when pow ered by a 24 VAC in put.
4. Fac tory in stalled re sis tor should be re moved only if C7400 Dif fer en tial Enthalpy Sen sor is added.
5. Y2 must be en er gized for the com pres sor to op er ate.
Hor i zon tal Mod u lat ing Gear Economizer
RKNL / RLNL 180-300
Date: July 9, 2009 Supercedes: 03-19-09 Drawn by: MGL Unit #: 60-394-16 Di a gram#: 6039416W Ap proved by:
SUPERSEDES 06-04-09 JULY 15, 2009
RMIHE16
INSTALLATION INSTRUCTIONS
MODELS (-)XRD-PDCM3 & (-)XRD-SDCM3
VERTICAL AIRFLOW ECONOMIZERS
WARN ING
THIS ACCESSORY IS TO BE INSTA LLED BY A QUA LIFIED, LICENSED SERVICE PERSON. TO A VOID UNSATISFA CTORY OPERATION OR DA MAGE TO THE PRODUCT A ND POSSIBLE UNSAFE CONDITIONS, INC LUDING ELECTRICAL SHOCK, REFRIGERANT LEAKAGE AND FIRE, THE INSTALLATION INSTRUCTIONS PROVIDED WITH THIS ACCESSORY MUST BE STRICTLY FOLLOWED AND THE PARTS SUPPLIED USED WITHOUT SUBSTITUTION. DAMAGE TO THE PRODUCT RESULTING FROM NOT FOLLOWING THE INSTRUCTIONS OR USING UNAUTHORIZED PARTS MAY BE EXCLUDED FROM THE MANUFACTURER’S WARRANTY COVERAGE.
WARN ING
DISCONNECT ELECTRICAL POWER TO TH E UNIT. FA ILURE TO DO SO CA N CA USE ELECTRIC A L SHOCK RESULTING IN PERSONAL INJURY OR DEATH.
WARN ING
THE SMOKE DETECTOR MUST NOT BE RELIED UPON AS THE PRIMARY SMOKE DETECTION IN BUILDING SAFETY. THE ECONOMIZER SMOKE DETECTOR DE-ENERGIZES THE SUPPLY FAN AND CLOSES THE OUTSIDE AIR DAMPER WHEN SMOKE IS DETECTED. REFER TO ENCLOSED SMOKE DETECTOR INSTRUCTIONS (SECTION 7) FOR TESTING OF ADEQUATE SMOKE SENSOR AIRFLOW UPON INSTALLATION OF (-)XRD-SDCM3 ECONOMIZER WITH SMOKE DETECTOR CAPA BILITIES. SUFFICIENT DUCTED AIR VELOC ITY MUST BE PRESENT ACROSS THE SMOKE DETEC TOR SAMPLING TUBE TO ENSURE PROPER OPERATION. ADDING POWERED EXHAUST MAY BE REQUIRED IN BUILDINGS WITH EXCESSIVE ENVELOPE AIR LOSSES AND/OR RESTRICTIVE RETURN AIR CONDITIONS TO THE UNIT PREVENTING ADEQUATE RETURN AIR TO THE UNIT WHEN ECONOMIZER IS OPEN TO OUTSIDE AIR.
TOOLS RE QUIRED FOR IN STAL LA TION:
3
" electric drill with
8
5
" socket Small flat blade (0.125" wide) screwdriver
16
TABLE 1
(-)XRD-SDCM3
economizer with smoke
detector, con trol ler,
ac tu a tor, and out side
enthalpy sen sor at tached
PACK AGE CON TENTS
(-)XRD-PDCM3
economizer with con trol ler,
ac tu a tor, and out side
enthalpy sen sor at tached
ITEM DE SCRIP TION PART No. PART No.
1 2 3
4 5
6 7 8
9 10 11 12 13 14 15
Dis charge Air Sen sor (Hardware Bag) (2) Per ma nent Fil ters Spotweld Assy - Bird Screen
Ex haust Air Rainhood Assy – Birdscreen Front Sup port
OA Rainhood Assy - Left Side OA Rainhood Assy - Right Side Ex haust Air Rainhood - Left Side Ex haust Air Rainhood – Right Side OA Fil ter Rail Assy OA Rainhood Assy – Top OA Rainhood - Front Fil ter Sup port Hardware Bag Smoke Detector w/ Harness Sampling Tube Sampling Tube Bracket
6036413B / 3112 6036413S / 3112 6036413B / 8567
(11.875" X 23.875")
6036413S / 8567
(11.875" X 23.875")
6036413B / BSWA 6036413S / BSWA
6036413B / EHB2 6036413S / EHB2 6036413B / EHSL 6036413S / EHSL
6036413B / EHSR 6036413S / EHSR
6036413B / EHS2L 6036413S / EHS2L
6036413B / EHS2R 6036413S / EHS2R
6036413B / EHT2 6036413S / EHT2
6036413B / EHT 6036413S / EHT 6036413B / EHB 6036413S / EHB
6036413B / HDW 6036413S / HDW
------ 6036413S / 3528
------ 6036413S / 3532
------ 6036413S / BRKT
FIGURE 1 (-)XRD-PDCM3 Shown - (-)XRD-SDCM3 Similar
LEAVE THESE
SCREWS ENGAGED
RETURN COVER
FRONT SIDE
ROOF PANEL REMOVE SCREWS FROM THREE SIDES (FRONT, LEFT AND BACK) EXCEPT AS NOTED
FILTERS
LEFT PANEL - UPPER (REMOVE TO BE REUSED IN RAIN HOOD ASSEMBLY
LEFT PANEL - LOWER (REMOVE TO BE REUSED IN RAIN HOOD ASSEMBLY
DOWNFLOW RETURN OPENING
STEP 1:
Immediately upon receipt, all cartons and contents should be inspected for transit damage. Units with damaged cartons should be opened immediately. If damage is found, it should be noted on the delivery papers and a damage claim filed with the last carrier. Compare carton(s) contents to PACKAGE CONTENTS List (TABLE 1) above to note any missing items.
STEP 2:
Remove RETURN COVER, LEFT PANEL – UPPER and LOWER PANELS – LEFT BOTTOM SECTION from the unit and retain for reuse (SEE
FIGURE 1). Retain screws. STEP 3:
Remove screws from 3 sides of ROOF PANEL so that it can be raised during economizer insertion.
NOTE 1:
Remove shipping bracket, PERMANENT FILTERS,  OA RAINHOOD - LEFT SIDE,  OA RAINHOOD - RIGHT SIDE, EXHAUST AIR RAINHOOD - LEFT SIDE and EXHAUST AIR RAINHOOD – RIGHT SIDE from fresh air opening. (SEE FIGURE 2).
STEP 4:
Remove jumper plug and slide economizer into unit return air section (SEE FIGURE 2). After the economizer is installed, connect unit ECONOMIZER PLUG to economizer mating plug. PDCM3 - Reinstall jumper plug PL7 to PL21 (located on economizer). SDCM3 - Save jumper plug PL7 in this compartment for diagnostic purposes.
FIGURE 2
RE TURN COVER
DOWNFLOW RE TURN OPEN ING
ROOF PANEL
PLUG
FIL TERS
WIRE HARNESS
ACTUATOR
CONTROLLER
ECONOMIZER ASSEMBLY
A1010-01
FRONT SIDE
NOTE 1
A1011-01
2
STEP 5:
Secure economizer and SPOTWELD ASSY - BIRD SCREEN along bottom with six screws as shown (SEE
FIGURE 2). See TABLE 1 for identification. STEP 6:
Fasten  EXHAUST AIR RAINHOOD - LEFT SIDE and EXHAUST AIR RAINHOOD – RIGHT SIDE to barometric relief opening (lower opening) on the economizer (SEE FIGURE 3). Fasten with six screws. See FIGURE 4 for identification of EXHAUST AIR RAINHOODS.
STEP 7:
Fasten EXHAUST AIR RAINHOOD ASSY – BIRDSCREEN FRONT SUPPORT under edge of LEFT PANEL – LOWER using six screws. Do not install a screw in the rightmost hole in the panels at this time.
STEP 8:
Fasten LEFT PANEL – LOWER and EXHAUST AIR RAINHOOD ASSY – BIRDSCREEN FRON T SUPPORT to the top of the EXHAUST AIR RAINHOOD - LEFT SIDE and EXHAUST AIR RAINHOOD – RIG HT SIDE which was previously installed on the unit (SEE STEP 7).
STEP 9:
Attach OA FILTER RAIL ASSY to economiz er center support,  EXHAUST AIR RAINHOOD - LEFT SIDE and EXHAUST AIR RAINHOOD – RIGHT SIDE and L EFT PANEL – LOWER using screws provided.
STEP 10:
Position the OA RAINHOOD ASSY – TOP under edge of ROOF PANEL. Do not install screws at this time.
STEP 11:
Fasten OA RAINHOOD - LEFT SIDE and OA RAINHOOD - RIGHT SIDE to unit using screws provided (2 each on (-)XRD-PDCM3, and on (-)XRD-SDCM3).
STEP 12:
Slide PERMANENT FILTERS between OA RAINHOOD - LEFT SIDE and OA RAINHOOD - RI GHT SIDE back into the OA FILTER RAIL ASSY.
STEP 13:
Fasten 11 OA RA INHOOD - FRONT FILTER SUPPORT to LEFT PANEL – UPPER with six screw s. The bottom lip should support the PERMANENT FILTERS. Do not install a screw in the rightmost hole in the panels at this time.
STEP 14:
Fasten LEFT PANEL – UPPER to OA RAINHOOD ­LEFT SIDE and OA RAINHOOD - RIGHT SIDE and 11 OA RAINHOOD - FRONT FILTER SUPPORT using screws (12 on (-)XRD-PDCM3, and on (-)XRD-SDCM3).
STEP 15:
Re-secure ROOF PANEL using the washer head screws that were removed in STEP 3 from the ROOF PANEL.
FIGURE 3 (-)XRD-PDCM3 Shown - (-)XRD-SDCM3 Similar (See Table 1 for identification of parts)
ECON. CENTER
SUPPORT (REF.)
LEFT PANEL - LOWER
ROOF PANEL (REF.)
LEFT PANEL - UPPER
11
A1012-01
3
FIGURE 4
EXHAUST AIR RAIN HOOD
(LOWER LEFT SIDE)
OUTSIDE AIR RAIN HOOD
(UPPER LEFT SIDE)
SEAL STRIP
EXHAUST AIR RAIN HOOD ASSEMBLY
(BIRDSCREEN FRONT SUPPORT)
STEP 16: Remove the BLOWER MOTOR ACCESS PANEL (SEE FIGURE 5).
STEP 17:
Connect the j DISCHARGE AIR SENSOR to wires 51 and 52 located in the blower motor compartment.
NOTE:
Mixed air sensor should be secured with the included wire tie to avoid entanglement with the blower and direct contact with any sheet metal surfaces.
STEP 18:
Replace the BLOWER MOTOR ACCESS PANEL.
STEP 19:
Upon start-up check the economizer sequence of operation using the steps provided in these instructions. After testing unit operation and setting outside air damper minimum position, replace RETURN COVER with remaining screws.
END VIEW
A1005-01
FIGURE 5
WIRE TIE
INDOOR MOTOR
A1006-01
4
DI RECT MOUNT ECONOMIZER SE QUENCE OF OP ER A TION
GEN ERAL
This accessory economizer package is designed to save energy costs by using outdoor air for cooling and ventilation in place of mechanical cooling whenever possible. The economizer continuously monitors indoor and outdoor air conditions and compares them to a user-selected setpoint to determine if free cooling is available.
AC CES SO RIES
(-)XRX-AV02 — Dual Enthalpy Up grade Kit
For maximum energy savings, this upgrade kit will allow the economizer to compare the outdoor air enthalpy to the return air enthalpy, instead of a user-selected setpoint to determine if "free cooling" is available.
(-)XRX-AR02 - Wall-Mounted Car bon Di ox ide Sen sor
For installations requiring Demand Control Ventilation (DCV) based upon indoor air levels of carbon dioxide (CO2). When the unit supply fan is running, the CO2 sensor modulates the outside air damper to maintain a user-selected CO2 level inside the occupied space. Energy savings are achieved by not bringing in excessive amounts of outdoor air when the indoor air conditions are suitable. Energy savings can be substantial on buildings with highly variable occupancy rates.
Wall-Mounted Remote Potentiometer
For installations requiring remote adjustment of damper minimum position by the occupants, a remote potentiometer, such as the Honeywell S963B1128 can be used.
(-)XRX-BFF02C, (-)XRX-BFF02D, (-)XRX-BFF02Y — Power Exhaust Kit
For installations requiring more space static pressure relief than can be obtained with the standard barometric relief damper included with the economizer, a power exhaust kit can be added.
B. Range of adjustment is from 0-100% (2-10V); in
most applications the power exhaust is set to engage at about 70% outside air.
2. Min Pos — Outside Air Damper minimum position A. Adjust the minimum position potentiometer to
allow the minimum amount of outdoor air, as required by local codes, to enter the building.
B. Range of adjustment is from 0-100% (2-10V); in
most applications the minimum position is adjusted to allow 10% to 25% outside air to enter the system.
C. The Outside Air Damper Minimum Position
potentiometer can be adjusted at any time.
D. Whenever the "G" (supply fan) signal is present,
the damper will open to this minimum position unless:
a. It may modulate to a greater position if
overridden by the CO2 sensor (DCV).
b. It may not open if overridden by the discharge
air temperature sensor (Freeze Protect Mode).
3. DCV Max — Demand Control Ventilation (DCV) Maximum Setpoint
A. The DCV maximum position potentiometer allows
the installer to limit the amount of outdoor air flow into the building when the DCV overrides the mixed air sensor.
B. Setting the DCV maximum position of the damper
prevents the introduction of large amounts of hot or cold air into the space.
C. Note: If the DCV maximum position is set below
the outside air damper minimum position, the minimum position overrides the DCV maximum position (negating the function of the DCV).
STARTUP
Operational Note
For (-) XRD-SDCM3 economizer. After these startup adjustments have been completed, perform airflow measurement tests on the smoke detector to ensure adequate smoke detector sensing air. Refer to enclosed smoke detector instructions (section 7).
Attach connector from Economizer Controller to Rooftop Control Panel Connector and install discharge/mixed air temperature sensor per installation guide.
AD JUST MENTS
5 po ten ti om eters with screw driver ad just ment slots, start ing from top of con trol ler
1. EXH Set — Adjustments for (optional) power ex haust A. The outside air damper position at which the
power exhaust fan(s) will engage. The LED labeled EXH below the potentiometer adjustment will indicate when power exhaust is available. When the power exhaust call is made, the controller provides a 60 ±30 second delay before exhaust fan activation to allow the damper to reach the appropriate position.
FIGURE 6
5
4. DCV Set — Demand Control Ventilation (DCV) Setpoint
A. The DCV can be any sensor that provides a
2-10Vdc output. The DCV modulates the outdoor damper to provide ventilation based on occupancy. Typically, a carbon dioxide (CO2) sensor is used to indirectly monitor occupancy level.
B. No cooling signal (e.g.Y1, Y2) is required for the
DCV to override the outdoor air damper when ventilation requires outdoor air.
C. The controller must receive a "G" (supply fan)
signal to open the damper. D. Range of adjustment is from 2 Volts to 10 Volts. E. The DCV setpoint can be adjusted at any time. F. The controller compares the CO2 sensor input to
the setpoint setting to determine the damper
minimum position.
a. If the actual CO2 level is below the setpoint,
then the damper minimum position is determined by the damper minimum position potentiometer setting.
b. If the actual CO2 level rises above the
setpoint, then the damper minimum position is overridden proportionally more open.
c. If the discharge air temperature drops below
48°F (Freeze Protect Mode), the DCV input will be overridden and the damper may not open.
G. Compatible CO2 sensors will have a 2-10Vdc
output for a 0-1500 ppm CO2 input. H. Ensure proper polarity of the sensor wires when
connecting to the economizer controller. Incorrect
polarity negates the sensor signal.
5. Economizer Setpoint A. Only the coolest, driest outside air is used for
economizer operation when the potentiometer is on setting "D". For greatest energy savings, the potentiometer is on setting "A".
B. Adjustment range is A, B, C, or D
a. Setting "A" = 73F db or 27 Btu/lbm @ 50% RH b. Setting "B" = 70F db or 25 Btu/lbm @ 50% RH c. Setting "C" = 67F db or 23 Btu/lbm @ 50% RH d. Setting "D" = 63F db or 22 Btu/lbm @ 50% RH
C. Economizer Setpoint potentiometer can be
adjusted at any time.
D. The controller compares the enthalpy sensor input
with the economizer setpoint to determine if free cooling is available.
a. Single enthalpy strategy: If outdoor air
enthalpy is lower than the setpoint, then free cooling is available. Note: The factory-installed 620-ohm resistor must be in place across terminals SR and SR+.
b. Dual enthalpy strategy: If outdoor air enthalpy
is lower than return air enthalpy, then free cooling is available.
FIGURE 7
1. Note: If using dual enthalpy, the Economizer Setpoint must be at the "D" setting.
2. The factory-installed 620-ohm jumper must be removed to install the dual enthalpy upgrade kit.
NOR MAL OP ER A TION
1. Fan Only (G) A. Damper will go to minimum position (in 90
seconds or less) whenever the "G" (supply fan) signal is present.
B. When "G" signal is removed, the outside air
damper closes against blade seals for tight shutoff of outside air.
C. If the discharge air temperature drops below 48ºF,
then the control will override the minimum position setting and will modulate the outside air damper closed.
2. Call for First Stage of Cooling (Y1) A. Economizer Unavailable (warm outdoor air).
Compressor 1 is commanded on without delay.
B. Economizer Available (free cooling). The
controller tries to maintain a discharge air temperature of 53ºF ± 5 by modulating the outside air damper position.
3. Call for Second Stage of Cooling (Y2) A. Economizer Unavailable (warm outdoor air).
Compressor 2 is commanded on without delay.
B. Economizer Available (free cooling). Compressor
1 is commanded on without delay. The controller tries to maintain a discharge air temperature of 53ºF ± 5 by modulating the outside air damper position. Compressor 2 is not activated in the economizer mode.
6
4. Call for Heat A. Standard Air Conditioner with electric or gas heat.
(W1 & W2) a. The Thermostat controls the stages of heating
directly.
b. If the control detects that the supply fan is on
(through its "G" input), then the control will open the damper to minimum position.
c. If the discharge air temperature drops below
48ºF, then the control will override the minimum position setting and will modulate the outdoor damper closed.
B. Heat Pump Operation (B)
a. The "B" signal from the Thermostat allows
operation of the compressors to provide heating without delay.
b If the control detects that the supply fan is on
(through its "G" input), then the control can open the damper to minimum position.
c. If the discharge air temperature drops below
48ºF, then the control will override the minimum position setting and will modulate the outdoor damper closed.
5. Low Ambient Compressor Lockout – None
present.
TROU BLE SHOOT ING
1. Checkout requires a handheld multimeter, 9V battery, a 5.6k ohm .25 watt resistor, a 1.2k ohm .25 watt resistor, a jumper wire with .25" quick connect terminals, and the 620 ohm resistor that is factory-installed across terminals SR+ and SR. The terminal names below reference the economizer controller. Use the following flowcharts for to diagnose unit.
2. a. Disconnect power to the unit. b. Jumper P to P1 (factory installed jumper is
normally present).
c. Remove outdoor air enthalpy sensor from
terminals SO+ and SO and install the 1.2k ohm resistor.
d. Put 620 ohm resistor across terminals SR+ and
SR (factory installed 620 ohm resistor is normally present and can be used).
e. Put 5.6k ohm resistor across T and T1.
3. a. Turn (EXH Set) Exhaust fan Setpoint
potentiometer fully CCW.
b. Turn (Min Pos) Minimum Outside Air Damper
potentiometer fully CCW.
c. Turn (DCV Max) Demand Control Ventilation
Maximum potentiometer fully CW.
d. Turn (DCV Set) Demand Control Ventilation
Setpoint potentiometer fully CCW.
e. Turn enthalpy potentiometer to "D".
7
BASIC ECONOMIZER OPERATION
START Perform STEP 2 Perform STEP 3
Put thermostat fan setting to "CONTINUOUS FAN"
Set thermostat so neither heating or cooling is called
Reapply Power to the Unit
Connect Economizer Wire Harness to Unit
Check Thermostat Connections
Check for 24 VAC at Unit Transformer
Ensure power is available from smoke detector (-)XRD-SSDCM3 at PL20-2 with
harness connected. Push reset at the smoke detector if power is not present
(refer to smoke detector instructions if smoke detector is suspect).
Unplug Economizer Wire Harness from Unit Wire harness and Install
Jumper Plug (Jumpers Y1 Thermostat to Y1 Compressor and Jumpers
compressor(s) run? If both stages
Check Thermostat Wiring
Check Unit Wiring Harness
The "Free Cooling" LED turns on & the EXH LED turns on.
If only one stage of cooling is called by the thermostat, then that stage
will turn off. If two stages are called by the thermostat, then only the
second stage will turn off. The power exhaust (optional) contacts will
close after 60 +/- 30 seconds. The outside air damper opens
approximately 50% (this position is determined by the actual resistance
of the 5.6k ohm resistor placed across terminals T and T1).
The "Free Cooling" LED turns off & the EXH LED turns off.
If only one stage of cooling is called by the thermostat, then that stage
will turn back on. If two stages are called by the thermostat, then both stages will turn on. The power exhaust (optional) contacts open & the
Remove 5.6k ohm resistor and jumper terminals T to T1.
Y2 Thermostat to Y2 Compressor)
If one stage of cooling is called by the
thermostat, do first stage
are called, do both stages
of compressors
Set enthalpy potentiometer to D (fully CW).
outside air damper fully closes.
Set enthalpy potentiometer back to A (fully CCW).
Check Unit Wire Harness
Check Economizer Controller Model Number
Perform STEP 2 & STEP 3 again.
If problem continues, replace controller
run?
NO
(W7213A1016)
YES
Check Economizer Wiring
Harness. Check Unit wiring
harness at economizer
connection for proper terminal
YES
YES
location
NO
NO
NO
available between terminal TR and TR1?
NO
Turn down thermostat setting so that a call for cooling is present.
NO
Set enthalpy potentiometer on economizer controller to A (fully CCW).
Recheck STEP 2 and STEP 3. If LED’s turn on and damper motor
does not operate, measure voltage between terminals 24V COM and
(+ (white wire)). If approximately 6 VDC is present, replace damper
actuator. If voltage not present, or LED’s do not light replace controller.
Recheck STEP 2 and STEP 3.
If problem continues replace controller
24 VAC power
YES
Are all LED's off &
outside air damper fully closed?
YES
If one stage of cooling is called by the
thermostat, do first stage
compressor(s) run? If both stages
are called, do both stages
of compressors
run?
YES
The "Free Cooling" LED turns on & the EXH LED turns on. If only one
stage of cooling is called by the thermostat, then that stage will turn off.
If two stages of cooling are called by the thermostat, then only the
second stage will turn off. The power exhaust (optional) contacts will
close after 60 +/- 30 seconds. The outside air damper fully opens
YES
Remove jumper from terminals T to T1 and leave open (simulates the
The "Free Cooling" LED remains on & the EXH LED turns off.
If only one stage of cooling is called by the thermostat, then that stage
will remain off. If two stages of cooling are called by the thermostat,
then only the second stage will remain off. The power exhaust (optional) contacts opens & the outside air damper fully closes
Economizer Controller, Actuator, Wiring are correct.
Remove resistors, reconnect wires, and set up
Freeze Protect mode).
YES
potentiometers per jobsite requirements.
8
NO
NO
HEAT PUMP OPERATION
(Perform BASIC ECONOMIZER OPERATI ON check first)
START
Perform STEP 2
Perform STEP 3
Put thermostat fan setting to "CONTINUOUS FAN"
Reapply Power to the Unit
Turn down thermostat setting so that a call for cooling is present.
Set enthalpy potentiometer on economizer controller to A (fully CCW).
The "Free Cooling" LED turns on & the EXH LED turns on.
If only one stage of cooling is called by the thermostat, then that stage will turn off.
If two stages are called by the thermostat, then only the second stage will turn off.
The power exhaust (optional) contacts will close after 60 +/- 30 seconds.
The outside air damper opens approximately 50% (this position is determined by
the actual resistance of the 5.6k ohm resistor placed across terminals T and T1).
YES
Reset the thermostat setting so that a call for heating is present.
The "Free Cooling" LED turns off & the EXH LED turns off.
If only one stage of heating is called by the thermostat, then that stage will turn on.
If two stages are called by the thermostat, then both stages will turn on.
The power exhaust (optional) contacts will open The outside air damper fully
closes.
NO
Perform Basic Economizer Operation
check first. Recheck STEP 2 and
STEP 3
NO
YES
Turn Min Pos potentiometer fully CW.
The outside air damper drives fully open.
The EXH LED turns on.
The power exhaust (optional) contacts will close after
approximately 60 +/- 30 seconds.
YES
Heat Pump Operation is Correct.
Remove resistors, reconnect wires, and set up
potentiometers per jobsite requirements.
Check for 24 VAC at B terminal.
Check for B signal at thermostat.
Check Unit wire harness.
Check Economizer Wire harness.
NO
Replace controller.
9
Loading...
+ 74 hidden pages