McQuay MPC-HPC200 Installation Manual

Installation, Operation and Maintenance Manual
Group:
IM 856-1
Aftermarket Products
©
2008 McQuay International
Part Number: IM 856-1 Date: January 2009 Supersedes: IM 856 dated April 2007
For Models: MPC-LPC200-11/113 MPC-LPC200-123 MPC-HPC200
Table Of Contents
Hazardous Identification Information............................3
Installation......................................................................4
PureCharge Specifications .............................................4
Average refrigerant/oil mixture in tank per distillation..4
Contents of the PureCharge Installation Kit..................4
Field-Provided Items......................................................4
Preliminary Inspection ...................................................4
PureCharge Unit Operational Overview.........................5
How It Works.................................................................5
How the PureCharge Unit Transfers Oil to the Chiller’s
Oil Sump ........................................................................5
Operating Parameters.....................................................5
Operational LED Indicators ...........................................6
Diagnostic LED indicators.............................................6
Fault LED indicators......................................................6
Installing the PureCharge Unit.......................................8
Location and Mounting ..................................................8
Plumbing the PureCharge Unit.......................................8
Liquid Refrigerant Fill Line (with Strainer)...................9
Vapor Return Line..........................................................9
Oil Return Line and Oil Filter-Drier installation............9
Option 1 Oil Line Piping Instructions..........................11
Option 2 Oil Line Piping Instructions..........................11
Electrical Connection...................................................13
Power Requirement......................................................13
Optional Chiller Run Signal.........................................13
Connecting Power........................................................ 13
Initial Start-Up............................................................. 14
Start-Up Procedure ...................................................... 14
Description Of PureCharge Components..................... 15
Safety Features............................................................. 16
Electrical Control Box.................................................16
Logic Board Relays and Dip Switches ........................ 17
Switches (SW1) & (SW2) (Dip Switches)...................17
Maintenance................................................................. 21
EZ-Change Refrigerant Filter Drier Replacement
Instructions .................................................................. 21
Steps for Changing EZ Change Filter Drier................. 21
Periodic Maintenance .................................................. 22
Control Calibration...................................................... 22
Leak Testing Procedures.............................................. 22
PureCharge Evacuation Procedure .............................. 23
Troubleshooting........................................................... 24
Using Switch SW2 Dip Switches as a diagnostic aid.. 24
Troubleshooting Chart.................................................24
Switch light defective. ................................................. 24
Replace switch............................................................. 24
Troubleshooting the Liquid Level Sensor.................... 28
Liquid Level Sensor Replacement Instructions........... 28
Replacing Level Sensor Switch Electronic Module.....28
Procedure to Clear Oil Logged Distillation Tank ........ 29
2 IM 856-1
Introduction
The McQuay PureCharge unit is designed to remove oil, acid & moisture from the refrigerant charge of a centrifugal chiller and automatically return the oil to the chiller’s oil sump. The PureCharge unit may be used with centrifugal chillers using the following refrigerants: R-11. R-113, R-114, R-123, R-12, R-22 and R-134a.

Hazardous Identification Information

! DANGER
Dangers indicate a hazardous situation which will result in death or serious injury if not avoided.
! WARNING
Warnings indicate potentially hazardous situations which can result in property damage, severe personal injury, or death if not avoided.
! CAUTION
Cautions indicate potentially hazardous situations, which can result in personal injury or equipment damage if not avoided.
IM 856-1 3

Installation

! WARNING
Installing or servicing refrigerant support equipment can be hazardous due to system pressures and dangerous voltages. Only qualified service personnel should work on such equipment.

PureCharge Specifications

Electrical power requirements:
Remote alarm relay (rly) contact rating
Operating environment: 70°F to 105°F, 5% to 80% relative
Storage environment: 0°F to 120°F, 5% to 80% relative
Dimensions (approximate):
Weight (approximate): 60 pounds Shipping weight
(approximate): Operating distillation
temperature: Operating pressures: 30 to 250 psi Distillation tank factory
pressure tested at: Average refrigerant/oil
mixture in tank per distillation
(varies depending upon installation and refrigerant level in chiller):
Average rate of refrigerant/oil mixture processed (depends upon installation, refrigerant level in chiller, and whether chiller is Running or Off):
Note: The PureCharge unit comes
equipped with a remote alarm capability.

Contents of the PureCharge Installation Kit

Each kit includes:
One Installation, Operation and Maintenance Manual. One PureCharge unit with EZ-Change refrigerant
filter attached. One oil filter/drier (for use in oil return line).
One liquid-line strainer (for use in refrigerant fill line).
120 VAC, 50/60 Hz., 1-Phase, 15­amp fused circuit
Actual current draw approximately 4 Amps
120 VAC; 15 Amp
humidity, non condensing
humidity, non condensing 33" height x 16" length x 12" depth
95 pounds
155 F degrees
350 psig
10 to 20 lbs
850 to 1250 lbs. per week 44000 to 65000 lbs per year
One 1/4’ sweat check valve (with spring) (for use in
oil return line). One 3/8” charging valve adapter with copper ferrules
and cap. One 1/2” charging valve adapter with copper ferrules
and cap. Two 5/8” charging valve adapters with copper ferrules
and cap. One 3/4” to 5/8” reducing flare union (for use with
charging valve adapter if necessary). One 5/8” to 1/2” reducing flare union (for use with
charging valve adapter if necessary). One 1/2” to 3/8” reducing flare union (for use with
charging valve adapter if necessary). One 1/4” NPT run brass fitting (fitting with Schrader
valve for use with oil adapter fitting for leak testing.) One plastic tool for inserting power line into electrical
terminal block. One brass three-way internal branch tee and copper
ferrule. Two 1/4” NPT to 1/4” brass flare fittings.
Two 1/4” NPT to 1/4” brass 90-degree flare fittings.
Two 1/4” NPT pipe plugs
Twelve 1/4” flare nuts
One six feet length of 3/8” ID 3/4” line insulation
One ten feet length of 1/8” adhesive-backed insulation
tape. One 18” x 24”x 1/2” sheet of adhesive-backed
insulation

Field-Provided Items

To be furnished by the installer:
PureCharge unit mounting hardware.
Electrical conduit and wiring materials.
1/4-inch copper refrigerant tubing.
Refrigerant cylinder (for collection of excess oil if
excess oil is not initially returned directly to the chiller’s oil sump.

Preliminary Inspection

Before installing the PureCharge unit, check the data on the unit nameplate and verify that it is the appropriate model for the refrigerant in the chiller it is to be installed on. Make sure the voltage is correct for the application. Visually inspect all components for damage in shipment before installing. Pay particular attention to the Temperature Sensor (TS-1) capillary tube.
4 IM 856-1

PureCharge Unit Operational Overview

The PureCharge unit is designed to remove oil, acids and moisture from a centrifugal chiller’s refrigerant. However, its main purpose is to remove oil from the refrigerant and return it to the chiller’s lubrication circuit (oil sump) where it belongs. Initial oil stripping is accomplished in two phases. The first phase, or initial oil stripping process, occurs at initial start-up of the PureCharge unit. This is when all the excess oil that has been added to the system over time is removed from the oil sump and discarded. Often times the initial stripping process can yield several gallons to multiple tens of gallons, depending on how severely the refrigerant is saturated with oil.
The second phase begins when all excess oil has been removed from the refrigerant. The PureCharge unit will, from that point on, maintain the system in lubrication balance. Lubrication balance meaning virtually 100 percent of the compressor’s lubricating oil is kept in the oil sump.
Operation of the PureCharge unit is accomplished by a patented process utilizing gravity, heat and pressure in conjunction with special high capacity desiccants to completely remove oil, acids and moisture from a chiller’s refrigerant charg e.
The PureCharge unit works by repeatedly drawing 10 to 20 pounds (depending upon the refrigerant level available in the chiller evaporator) of refrigerant for processing from the chiller for each extract cycle. The oil-contaminated refrigerant is heated by means of a flexible band electric heater and the liquid refrigerant is vaporized off. As the refrigerant vaporizes it passes through the special E-Z Change high capacity moisture/acid filter-drier where it is cleaned before returning to the chiller evaporator.
At the end of the distillation phase, any distilled oil is automatically returned to the chiller’s oil sump through an in-line high acid capacity filter-drier where any residual acids are removed.
The PureCharge unit is able to process between 850 and 1250 pounds of refrigerant per week.
Three Operational Phases:
1. Fill Phase (Phase 1): Refrigerant contaminated with
oil, acid and moisture flows by gravity from the chiller’s evaporator into the PureCharge distillation tank. The Fill Cycle terminates automatically when liquid refrigerant is sensed by the optical level sensor, or after 75 minutes fill time, whichever comes first. At the end of the Fill Phase, Distillation (Phase 2) is initiated.
2. Distillation (Phase 2): During the distillation phase the
distillation heater is energized, heating the refrigerant­oil mixture and causing the liquid refrigerant to vaporize. The vaporized refrigerant vapor flows from the distillation tank to the chiller evaporator through an integral high capacity moisture/acid filter-drier.
Once all refrigerant is vaporized, any distilled oil remaining accumulates at the bottom of the PureCharge distillation tank where it is further heated. Upon reaching 155 F degrees an Oil Return Phase (Phase 3) is initiated. Average duration of a typical Distillation Phase is approximately 1-1/2 to 2-1/4 hours, depending upon the refrigerant level in the distillation tank at the start of the distillation phase.
3. Oil Transfer (Phase 3): During the oil return phase
distilled oil is automatically transferred from the Distillation Tank to the chiller’s oil sump. The returning oil flows through an in-line high acid capacity filter where residual acids are removed before entering the oil sump.

How the PureCharge Unit Transfers Oil to the Chiller’s Oil Sump

During the Distillation Phase, vaporized refrigerant is returned to the chiller evaporator through a 10-psid check valve. Therefore, at the conclusion of the distillation phase, the vapor pressure in the distillation tank will be at a pressure 10 psi higher than the chiller evaporator / oil sump pressure. This pressure is used to push accumulated oil from the tank back to the oil sump.

How It Works

PureCharge operation is cyclic and non-stop as long as power is applied. Each complete extract cycle comprises three operational phases and is approximately 2-1/2 to 3­1/2 hours in duration.
IM 856-1 5

Operating Parameters

1. Fill Phase: 75 minutes maximum. (Controlled by
either programmed time or liquid level sensor.)
2. Distillation Phase: Duration of the Distillation Phase
is dependant upon the amount of refrigerant in the tank at the conclusion of the Fill Phase and will vary from approximately 1-1/2 to 2-1/4 hours.
3. Oil Transfer Phase: The Oil Transfer Phase is a six-
minute timed cycle.
4. Oil Temperature: The temperature of the distilled oil
is limited to 155 F degrees by Temperature Sensor (TS-1). This setting can be calibrated in the field when necessary. However, do not change the factory setting unless calibration is absolutely necessary. Refer to the Maintenance section for calibration instructions.
5. Refrigerant Process Capacity: The PureCharge unit ,
on average, processes approximately 850 to 1250 pounds of refrigerant per week. The chiller’s total refrigerant charg e is processed and made progressively cleaner until all oil, acids and moisture have been removed. To completely clean the refrigerant, the chiller’s total refrigerant charge must be processed several times (at least 4 or 5 times).
6. Oil-Refrigerant Separation Efficiency: The amount of
refrigerant and oil being returned to the oil sump at the completion each cycle is proportionate to the level of oil concentration in the refrigerant. The higher the oil concentration, the more refrigerant will be returned with the oil to the oil sump. However, under any condition, the amount of refrigerant reaching the oil sump is insignificant. For example, a chiller with a 500-pound charge containing an average of 12% oil by weight means that the PureCharge unit will return approximately one pound of oil and approximately two ounces of refrigerant to the chiller oil sump on any given cycle. This is only during the initial clean­up period.
7. Once the excess oil is removed, only trace amounts of
refrigerant (if any) will ever reach the oil sump because only a small amount of oil will be returned during each return cycle (again that is once the excess oil has been removed). The approximately two ounces of refrigerant that does reach the chiller oil sump every 2-1/2 to 3-1/2 hours is inconsequential and will have no bearing on chiller operation if the chiller’s oil sump heater is on. If on, the chiller’s oil sump heater will quickly vaporize such a miniscule amount of refrigerant long before the next PureCharge unit’s oil transfer cycle occurs.
8. Power Consumption: Distillation is accomplished by
means of a 350-watt electric heater. However, because the heater is only energized approximately 60% of the time, power consumption is approximately that of a 250-watt light bulb.

Operational LED Indicators

A series of six LED indicators located on the upper right side of the solid state logic board are provided as a means of monitoring unit operation. See Figure 6 o n page
Operation LED indicators
D1, D2, D3, D4, D5 Green LED Blinking Indicates 5 second delay before program starts.
D1 Green LED Blinking Indicates unit is in Fill Phase 1 and the distillation tank is currently being filled from the chiller evaporator. The Fill Phase is either a 75­minute timed period
6 IM 856-1
or until a liquid level high signal is
18.
received from the optical level sensor of the PureCharge unit, whichever comes first.
D2 Green LED Blinking Indicates the cycle has advanced to Distillation Phase 2 and is currently in the process of vaporizing the refrigerant from the refrigerant/oil mixture.
D3 Green LED Blinking Indicates the liquid refrigerant has vaporized, distilled oil temperature has reached 155 F degrees and is currently in the Oil Transfer Phase 3.
D4 Green LED ON Solid Anytime the heater is on, the green LED D5 will be on solid. This is simply for informational purposes.
D5 Green LED On Solid Anytime the liquid level high sensor senses a liquid level the green D5 LED is on solid. This is simply for information.

Diagnostic LED indicators

When diagnosing unit problems it is helpful to be able to verify various system components for proper operation. (See the section titled Using Switch SW2 Dip Switches as Diagnostic Aid on page
24.)

Fault LED indicators

The LED indicators are also used to indicate certain Fault conditions. (Refer to the Troubleshooting Section starting on page fault conditions:
D6 Red LED Blinking with D1 Green LED ON Solid: Indicates temperature in the distillation tank did not
drop below 155 F degrees within a pre-programmed time limit of 20 minutes after initiating a Fill Phase. Refer to Troubleshooting Section starting on page cause.
D6 Red LED Blinking with D2 Green LED ON Solid: Indicates temperature failed to reach 155 degrees F.
within a pre-programmed 6 hour time limit after initiation of the Distillation Phase. Refer to Troubleshooting Section starting on page
D6 Red LED Blinking with D3 Green LED ON Solid: Indicates that the unit prematurely reached a
temperature of 155 F degrees during the distillation phase. This would indicate that the distillation tank is not filling with refrigerant properly or is losing the distillation charge prior to proper distillation. Refer to Troubleshooting Section on page
D6 Red LED Blinking with D4 Green LED ON Solid: Logic board received a signal from the Liquid
Level High Optical sensor for a period of 2 hours straight indicating a problem Refer to Troubleshooting Section on page
24.) The following is a description of the possible
24 for probable
24 for probable cause.
24 for probable cause.
24 for probable cause.
Recording the LED Lights During a Fault
When you see the red FAULT light ON, do not immediately turn the power switch OFF. First, remove the cover from the control box and observe and record which of the LED light(s) are ON. This will tell you the kind of fault that has occurred. Turning the switch OFF resets the logic board, terminating the Fault indicator. Record the type of fault. Examine the unit for any apparent problems, and check the troubleshooting section for possible causes of the fault. If there is no readily apparent problem, reset the unit. After reset, allow unit to operate normally to see if the fault repeats.
IM 856-1 7

Installing the PureCharge Unit

3. The unit
(vertical) position.
must be installed standing in an upright

Location and Mounting

The PureCharge unit comes mounted on its own integral base sufficient for proper support. Unit piping normally provides adequate support to stabilize the unit. Additional support may be provided as deemed necessary.
1. The unit
chiller’s refrigerant charging valve or other appropriate valve located near the bottom of the evaporator. The liquid refrigerant Fill Line is to be connected at this point.
2. The unit should be mounted directly on the flo or so
the liquid refrigerant Fill inlet port is as low as possible relative to the refrigerant level in the evaporator. When the chiller is mounted on a pad, the unit still should sit on the floor. The extra height of the pad provides additional liquid head to aid in gravity flow of liquid refrigerant from the chiller. The unit cannot overfill because of a Liquid Level High optical sensor. When the sensor is reached, the fill phase is terminated.
During a Fill Phase, if the refrigerant level in the distillation tank does not reach at minimum the middle sight glass, the PureCharge unit is not filling to an acceptable operating level.
Figure 1 – PureCharge Unit Hook-up
must be located within four (4) feet of the
! WARNING

Plumbing the Unit

To facilitate connection of the refrigerant Fill line and the Oil Return line, to their respective chiller valves, special brass valve adapter fittings and copper ferrules have been provided in the Installation Kit. These special adapters allow hook-up to the chiller’s valves without interfering with normal service access.
Determining Which Side Port to Use
Each valve adapter has opposing 1/4-inch FNPT side ports. To determine which of the ports to use, temporarily screw the valve adapter onto the charging valve hand tight. Usually only one of these ports will be accessible. This is the port you will use. The other port will be plugged. Select the appropriate fitting from the Kit, as called for in the piping instructions, and install in this port. Then, using a 1/4-inch pipe plug from the Kit, plug the unused side port. Each valve adapter comes with flare cap and ferrule to cap off the adapter’s charging access port. Be sure to always use a ferrule when installing the valve adapter and cap.
! CAUTION
Complete Fill Line and fittings from evaporator to the PureCharge unit must be completely insulated to avoid vapor locking, which will prevent filling.
1/4" Vapor Return Line
(Equalization Line)
Equalization Solenoid Valve (SOL-2)
Valve Adapter
1/4" Fitting
Refrigerant Charging Valve
1/4" Refrigerant "Fill" Line
Cap
Inlet Strainer
Evaporator Gauge Line
1/4" Internal Flare Branch Tee
Insulation
Fill Solenoid Valve (SOL-1)
EVAPORATOR
Oil Return Solenoid Valve (SOL-3)
"High Acid Capacity"
Oil Filter
1/4" Oil Return Line
Oil Sump
Oil Charging
Valve
Adapter
Valve
Shrader Fitting
Cap
Oil Line Check Valve
8 IM 856-1

Liquid Refrigerant Fill Line (with Strainer)

Although the following instructs you to connect the Liquid Refrigerant Fill Line to the chiller’s refrigerant charging valve, this is not always best. Some chillers have the charging valve located very close to where liquid refrigerant from the condenser enters the evaporator.
Usually, when this is the case, the chiller manufacturer provides an alternate access valve elsewhere near the bottom of evaporator. When this is the case, you should connect to the alternate valve. If the chiller currently has an oil recovery eductor system, it probably will be necessary to disconnect the eductor and make the connection there. Wherever the connection is made, as long as sufficient refrigerant from the evaporator is available to the unit, it will function and remove oil from the refrigerant. However, connecting to the optimum location assures optimal oil removal.
Carrier Series D™ Centrifugal Chiller Instructions
On some Carrier Series D centrifugal chillers, the refrigerant charging valve is located about even with the refrigerant level in the cooler. Therefore, for the unit to fill by gravity, it will be necessary to cut into the horizontal section of the refrigerant charging line where it exits the bottom of the cooler and add a fitting and valve for connection of the unit Fill Line.
1. Select the appropriate size valve adapter from the
Installation Kit that fits the chiller’s refrigerant charging valve. Depending on how the Fill Line is to run, select either a straight (U1-4B) or 90 degree (E1­4B) brass 1/4” NPT x 1/4” flare fitting from the Kit and install in the appropriate side port. Install a 1/4” pipe plug from the Kit into the opposite side port.
2. Using the appropriate copper ferrule, permanently
install the valve adapter onto the chiller’s refrigerant charging valve. (See Figure 1, page
3. Using 1/4” O.D. copper tubing, run a 1/4” copper line
to the Fill Solenoid Valve (SOL-1) from the valve adapter fitting. (See Figure 1, page
4. Be absolutely sure to keep the Fill Line lower than the
Liquid Fill Inlet connection on the distillation tank. If any part of the Fill Line rises higher than the Fill Inlet, liquid refrigerant may not flow by gravity from the chiller into the distillation tank.
5. Next, from the Installation Kit select the Fill line
strainer and two 1/4” flare nuts and install anywhere in the Fill Line. Make certain the connections to the strainer are leak tight.
6. Before making final connection to the unit, insulate
the entire refrigerant fill line and strainer. Insulation materials have been included in the Installation Kit.
IM 856-1 9
8.)
8.)
The entire Fill Line, Strainer, the refrigerant charging valve and all interconnecting piping up to the evaporator shell must be insulated. Failure to properly insulate these items may cause vapor lock preventing the PureCharge unit from functioning. (See Figure 1, on page
7. Do not open the refrigerant charging valve at this
time.

Vapor Return Line

Note: When connecting the vapor return line to a Schrader valve fitting, the valve stem
1. Close the evaporator gauge stop valve.
2. Disconnect the gauge line from valve.
3. From the Installation Kit, select the1/4”brass T6-4
three-way internal branch tee and copper ferrule. Connect the tee to the gauge stop valve 1/4” port. (See Figure 1, page
4. Re-connect gauge line to one end of tee.
5. From the other end of the tee, run a 1/4” copper line
to the Equalization Solenoid Valve (SOL-2). (See Figure 1, page
Avoid sagging or traps in the Vapor Return (Equalization) Line where vapor can condense and accumulate causing a blockage
6. Do Not re-open evaporator gauge valve at this time.

Oil Return Line and Oil Filter-Drier installation

Based on the severity of oil contamination in your system, the amount of oil that will be removed by the PureCharge unit on initial start-up could be several gallons more (excess oil) than the capacity of your chiller’s oil sump. For example, a 500-pound refrigerant charge with 12% oil by weight will contain approximately 8.5 gallons of excess oil. Until the chiller’s refrigerant is free of oil, you must decide how you are going to deal with the excess oil before the initial start-up of the PureCharge unit.
The above example is for illustrative purposes only. A smaller refrigerant charge with a higher percent oil concentration, or a larger refrigerant charge with a lower percentage, may yield much more than 8.5 gallons of excess oil. Before proceeding, estimate how much excess oil you will accumulate. To estimate the excess oil you are likely to accumulate, refer to the most recent refrigerant analysis for your chiller. You will also need to know the weight of your chiller’s refrigerant charge. Then refer to Chart 1, Percent of Oil, on page approximately how much excess oil you will be dealing with, you have the following two options as described.
! WARNING
8.)
must be removed.
8.)
8.)
10. Once you know
! CAUTION
It is important to note that the percentage of oil in a sample can vary by as much as 10 percent depending upon where the oil sample is taken from the chiller. For example, if the sample is taken from a location near where the refrigerant is returned from the condenser, mostly pure refrigerant is being returned to the evaporator at that location and the sample will indicate a lower percentage of oil contamination than actually exists in the chiller.
Option 1: Plumb the Oil Return Line per Option 1 piping instructions on page
11. This option allows the excess oil, as it is being stripped from the refrigerant, to flow direct to the chiller’s oil sump where it can accumulate. With Option 1, it will be necessary to periodically monitor the sump’s oil level and remove excess oil as it accumulates. Once the initial oil stripping process is complete and all excess oil has been removed from the oil sump, further monitoring will no longer be necessary.
Advantage: once the initial oil stripping process is complete, no further action is required.
Disadvantage: the main disadvantage to Option 1 is the necessity for someone to periodically monitor and drain­off oil from the oil sump. This may be inconvenient, as the oil-stripping process may take days or weeks to complete.
Option 2: Plumb the Oil Return Line per Option 2 piping instructions on page 11. As determined by previous calculation, install sufficient containment capacity, such as a single 50, 100, 200, etc., pound refrigerant recovery cylinder, in the Oil Return line between the PureCharge unit and the chiller’s oil sump. The cylinder will retain and hold the excess oil as it is stripped from the refrigerant, preventing it from accumulating in the oil sump.
Note that the rated capacity of a refrigerant recovery cylinder is for refrigerant which is heavier than oil; therefore a refrigerant recovery cylinder will not hold the same weight of oil as the rated refrigerant capacity. (See Figures 2 and 3 on page 11 which includes approxi mate oil holding capacities of various size refrigerant recovery cylinders.) Once the stripping process is complete the cylinder and excess oil must be removed from the system.
Advantage: does not require periodic monitoring and draining of oil in order to maintain proper oil level in the oil sump. (Good practice is still to periodically monitor the accumulation of oil in the recovery cylinder in the event that there is more oil recovered than anticipated.)
Disadvantage
: requires temporary installation of a
containment vessel. Also, once the oil stripping process is complete and the excess oil is collected, the containment vessel must be removed from the system.
Use the chart below to estimate the amount of excess oil in the chiller’s refrigerant charge. According to ASHRAE Study 601-TRP, the average chiller has 12% oil by weight in its refrigerant charge. A 500–pound refrigerant charge at 12% by weight contains 60 lbs, or 8.5 gallons of oil.
Chart 1 – Refrigerant-Oil Contamination Chart
100 200 300 400 500 600 700 800 900 1000 1100 1200
% OIL Lbs. Of Oil in Refrigerant Charge based on % by weight
1% 2% 3% 4% 5% 6% 7% 8%
9% 10% 11% 12% 13% 14% 15% 16% 17% 18% 19% 20% 21% 22% 23% 24% 25%
1 2 3 4 2 4 6 8 3 6 9 12 4 8 12 16 5 10 15 20 6 12 18 24 7 14 21 28 8 16 24 32
9 18 27 36 10 20 30 40 11 22 33 44 12 24 36 48 60 72 84 96 108 120 132 144 13 26 39 52 65 78 91 104 117 130 143 156 14 28 42 56 70 84 98 112 126 140 154 168 15 30 45 60 75 90 105 120 135 150 165 180 16 32 48 64 80 96 112 128 144 160 176 192 17 34 51 68 85 102 119 136 153 170 187 204 18 36 54 72 90 108 126 144 162 180 198 216 19 38 57 76 95 114 133 152 171 190 209 228 20 40 60 80 100 120 140 160 180 200 220 240 21 42 63 84 105 126 147 168 189 210 231 252 22 44 66 88 110 132 154 176 198 220 242 264 23 46 69 92 115 138 161 184 207 230 253 276 24 48 72 96 120 144 168 192 216 240 264 288 25 50 75 100 125 150 175 200 225 250 275 300
CHILLER REFRIGERANT CHARGE BY WEIGHT IN Lbs.
5 6 7 8 9 10 11 12 10 12 14 16 18 20 22 24 15 18 21 24 27 30 33 36 20 24 28 32 36 40 44 48 25 30 35 40 45 50 55 60 30 36 42 48 54 60 66 72 35 42 49 56 63 70 77 84 40 48 56 64 72 80 88 96 45 54 63 72 81 90 99 108 50 60 70 80 90 100 110 120 55 66 77 88 99 110 121 132
Oil weighs approximately 7 lbs per gallon
60 Lbs = approximately 8.5 gallons
10 IM 856-1
Loading...
+ 21 hidden pages