McQuay MicroTech 2000 Installation Manual

Installation and Maintenance IM 660-3
Group: WSHP Part Number: 106018961 Date: May 2005
MicroTech 2000™ Water Source Heat Pump Unit Controller
© 2005 McQuay International
Contents
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Component Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Microprocessor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Yellow Status LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Service Pin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Red Service LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Temperature Sensing . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Standard Control Features . . . . . . . . . . . . . . . . . . . . . . . . 3
Compressor Short Cycle Protection . . . . . . . . . . . . . . . . . . . . 3
Random Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Delayed Reversing Valve De-energization . . . . . . . . . . . . . . . 3
Condensate Overflow Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Brownout Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
High Pressure Refrigerant Alarm . . . . . . . . . . . . . . . . . . . . . . 3
Low Temperature Refrigerant Alarm . . . . . . . . . . . . . . . . . . . . 3
Low Pressure Refrigerant Alarm . . . . . . . . . . . . . . . . . . . . . . . 3
Change Filter Notification (network units only) . . . . . . . . . . . . 3
Configurable Relay Outputs . . . . . . . . . . . . . . . . . . . . . . . 4
Boilerless System/Auxiliary Heat Relay (LonWorks only) . . . . 4
Boilerless System/Auxiliary Heat Relay (LonMark only) . . . . . 4
MotorizeD Valve Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Fresh Air Damper Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Timed Output Relay (LonWorks only) . . . . . . . . . . . . . . . . . . . 4
Interface Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
MicroTech Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Wall-Mounted Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Remote Room Set Point Adjustment . . . . . . . . . . . . . . . . . . . . 5
Tenant Override . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Pre-Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Required tools and literature . . . . . . . . . . . . . . . . . . . . . . 6
Water Source Heat Pump Identification . . . . . . . . . . . . . 6
Field Wiring Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Wall Sensor Packages . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Network Communications Units . . . . . . . . . . . . . . . . . . . 6
Set Points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Procedure for WSHP . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Description of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Fan Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Unoccupied Operating Mode . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Cooling Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Heating Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Occupied Operating Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Cooling Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Heating Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Holding Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Tenant Override Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Load Shed Mode (LonWorks only) . . . . . . . . . . . . . . . . . . . . . 9
Optimal Start (LonWorks only) . . . . . . . . . . . . . . . . . . . . . . . . . 9
Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Diagnostic Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Unit Identification (Wink) Command . . . . . . . . . . . . . . . . . . . 10
Alarm Monitoring and Control . . . . . . . . . . . . . . . . . . . . . . . . 10
Clearing Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Alarm Fault Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
High Pressure Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Low Temperature Fault . . . . . . . . . . . . . . . . . . . . . . . . .10
Low Pressure Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Condensate Overflow Fault . . . . . . . . . . . . . . . . . . . . . . 11
Brownout Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Change Filter Notification (network units only) . . . . . . . . . . . 11
Service Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Inputs and Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Analog Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Digital Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Input/Output Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Test Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Microprocessor Problems . . . . . . . . . . . . . . . . . . . . . . . 12
Power Supply Problems . . . . . . . . . . . . . . . . . . . . . . . . . 12
Erroneous Temperature Readings . . . . . . . . . . . . . . . . . 13
Digital Input Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Brownout Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
WSHP Controller Replacement . . . . . . . . . . . . . . . . . . . 13
Copyright © 2005 McQuay International. All rights reserved throughout the world.
Introduction
This manual provides informat ion about the MicroTech 2000™ Water Source Heat Pump (WSHP) controller and control system used in the McQuay International WSHP product lines. The manual describes the controller’s components, input/output configurations, and service procedures.
For network installation or commissioning instructions for new projects, refer to the protocol information document ED
14954. For general information on a particular WSHP unit, refer to the model-specific installation manual (see Table 1).
Table 1: Model-specific water source heat pump installation literature
Document number WSHP unit model
lM 407 Vertical WSHP (007 to 060) lM 439 Large Vertical WSHP (070 to 290) IM 447 Console Units WSHP lM 494 WMH/CWH (007 to 019) lM 526 Horizontal WSHP (007 to 120) lM 544 CCH/HWH (006 to 060)* lM 656 Horizontal WSHP (019 to 060) IM 742 Enfinity Horizontal WSHP (007 to 060) IM 778 Enfinity Vertical WSHP (007 to 060)
*50 Hz only
WARNING
Electric shock hazard. Can cause equipment damage, personal injury, or death.
Properly ground equipment. Connections and service to the MicroTech WSHP controller control panel must be performed only by personnel knowledgeable in the operation of the equipment being controlled.
WARNING
Moisture in the control panel can cause personal injury and improper equipment operation.
When servicing this equipment during rainy weather or high humidity conditions, protect the electrical components in the main control panel.
CAUTION
Temperature hazard. Can cause damage to system components.
The controller is designed to operate in ambient temperatures from 32°F to 140°F (O°C to 60°C), and in relative humidity up to 95% (noncondensing). The controller can be stored in ambient temperatures from 40°F to 176°F (40°C to 80°C), and in relative humidity up to 95% (noncondensing).
CAUTION
Properly commission (page 6) the water source heat pump before using for temporary heating or cooling. Failure to properly commission can cause equipment damage not covered by warranty.
CAUTION
Static sensitive components. Static discharge while handling electronic circuit boards can cause damage to the components.
Discharge any static electrical charge by touching the bare metal inside the main control panel before performing any service work. Never unplug cables, circuit board terminal blocks, relay modules, or power plugs while power is applied to the panel.
CAUTION
This equipment generates and uses radio frequency energy. If not installed and used in accordance with this manual, it can cause interference to radio communications. It has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC rules. Operation is subject to the following conditions:
1. This device may not cause harmful interference.
2. This device must accept any interference received, including interference that may cause undesired operation.
These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. Operation of this equipment in a residential area is likely to cause harmful interference, in which case users are required to correct the interference at their own expense. McQuay International disclaims any liability resulting from any interference or for the correction thereof.
McQuay IM 660-3 1
General Information
The MicroTech 2000™ WSHP unit controller provides control of McQuay and AAF water source heat pumps. The controller enables the mode of operation, monitors the water and air temperatures, and indicates fault conditions. Each unit controller is factory programmed, wired, and tested for effective operation of your McQuay WHSP.
The MicroTech 2000 WSHP controller uses LONW
ORKS
®
technology. One of the following two versions of the application software is loaded into the controller at the factory.
LONMARK® 3.3 certified application code is the current standard application code for MicroTech 2000 units. Use L
ONMARK application code in new applications including:
Units that operate stand alone.
Units that are integrated into a L
ONWORKS communication
network for communicating with a building automation system (BAS) of your choice.
For network integration information, refer to the Protocol Information document ED 15054. Unit controllers with L
ONMARK application code have a software identification of
WHPE2E or higher.
LonTalk
®
application code was designed prior to
certification. Use this application software only in existing systems where an existing MicroTech Communications Gateway (MCG) or MicroTech Comm uni cations Gateway for Open Protocol (MCGOP) panel is installed. Use LonTalk application code in existing systems where:
MicroTech 2000 WSHPs connect to a McQuay MicroTech
monitor through a MicroTech Communication Gateway (MCG panel).
MicroTech 2000 WSHPs connect to a third par ty BAS
system through a MicroTech Communications Gateway for Open Protocol (MCGOP) panel.
If you choose to upgrade your heat pumps, the other application code can be installed in the field.
Component Data
Microprocessor
The MicroT ech 200 0 WSHP unit co ntroller is a preprogrammed microprocessor containing the software required to monitor and control the unit. The controller supports a minimum of six analog inputs, four digital inputs and five digital outputs (including the LED). All electrical connections to the board are provided by three mass termination style headers. Two of the headers are designated strictly for factory wiring, the other for a field wiring harness that terminates to a screw-type terminal strip on the unit’s exterior.
The controller uses set points and fixed preprogrammed parameters to maintain unit control (many of the set points and
preprogrammed parameters can be adjusted with a PC over the network).
Yellow Status LED
A yellow , on-b oard status L ED aids in diagnostics by indicating the water source heat pump operating mode and alarm conditions. The yellow LED indicates the unit operating mode as shown in Ta ble2. For more information on alarms, refer to the “Alarm monitoring and control” section on page 10.
A remote status LED is provided with all optional wall-mounted temperature sensor packages. It has the same function as the on-board status LED. If used, the remote LED connects to the MicroTech WSHP controller at connection #1 on Terminal Board #1.
Table 2: Status LED indication
Status LED status Mode
On continually Occupied, Occupied Load Shed On 0.5 sec, Off 5.5 sec Unoccupied On 5.5 sec, Off 0.5 sec Tenant Override, Override Load Shed On 0.1 sec, Off 0.1 sec Alarm Condition (Condensate Overflow,
Brownout, Compressor Fault)
Service Pin
A service pin (button) is provided that can be used to cause the Neuron network containing its unique 48-bit Neuron ID. This ID is useful during network commissioning. For another method of forcing the controller to broadcast its Neuron ID, see “Tenant override” on page 5.
®
chip to broadcast a message over the LONWORKS
Red Service LED
A red on-board service LED provides diagnostics by indicating the Neuron chip status. The red LED indicates the Neuron chip status as shown in Table 3 below.
Table 3: Service LED indication
Service LED status Mode
Off continually (Normal) The Neuron has an application
On continually The Neuron does not have an application
Blink slowly The Neuron has an application but is
and is configured.
or is damaged. (Downloading an application may correct this.)
unconfigured.
Temperature Sensing
The MicroTech 2000 WSHP unit controller uses negative temperature coefficient (NTC) thermistors for temperature sensing. A thermistor chart, which provides voltage-to­temperature and resistance-to-temperature conversion data, is included in Table 9 on page 12. The discharge air temperature sensor is located at the inlet to the fan. The leaving water temperature sensor is located in the leaving water line.
2 McQuay IM 660-3
Standard Control Features
Standard features of the MicroTech 2000 WSHP control include:
Heating and cooling control from a room sensor
Monitoring of all equipment protection controls
Fan and compressor operation
Monitoring of discharge air temperature
Monitoring of leaving water temperature
Status of all vital unit functions
Optional control outputs
Additional standard features of the MicroTech 2000 control are provided below.
Compressor Short Cycle Protection
When a compressor is energized, it remains energized for at least 2 minutes before the temperature control sequence is allowed to de-energize it. An alarm condition can override this “minimum-on” timer and stop the compressor if necessary . When a compressor is de-energized, it remains de-energized for at least 5 minutes before the temperature control sequence is allowed to energize it again.
Random Start
The random start feature prevents simultaneous compressor startup that could otherwise occur after the following events:
Unit powerup
Unoccupied to occupied changeover
Brownout condition
The compressor start delay can be from 5 to 37 seconds and is determined by the unique 48-bit Neuron chip ID.
Delayed Reversing Valve De-energization
This feature is provided to delay “swishing.” It prevents the reversing valve from returning to its normal (cooling) position for a period of approximately 10 seconds after the compressor is re-energized when the unit is in the heating mode. If necessary , an alarm condition can override the delay timer and de-energize the reversing valve with the compressor.
Brownout Alarm
The on-board brownout feature is meant to protect the compressor contactors from low voltage or “brownout” conditions. If the supply voltage to the water source heat pumps is below 82% of the nameplate value, the WSHP controller detects it, indicates it, and de-energizes the compressor. After rectifying the browno ut condition (when supply voltage remains above 90% of nameplate) normal unit operation resumes.
High Pressure Refrigerant Alarm
If excessive pressure in the refrigeration circuit is detected by the high pressure switch, the compressor and reversing valve de-energizes immediately. If the high pressure alarm disappears, manually reset the unit controller by disconnecting and reconnecting power to the unit.
Low Temperature Refrigerant Alarm
Upon detection of a low temperature refrigerant alarm, the unit controller immediately puts the reversing valve in the cooling position for 60 seconds. After 60 seconds, the compressor is disabled. If the low temperature alarm disappears, manually reset the unit controller by disconnecting and reconnecting power to the unit. The low temperature alarm occurs only when the unit is in heating mode.
Low Pressure Refrigerant Alarm
Upon detection of a low pressure refrigerant alarm, the unit controller immediately disables the compressor. If the low pressure alarm disappears, manually reset the unit controller by disconnecting and reconnecting power to the unit.
Change Filter Notification (network units only)
When the water source heat pump fan run time exceeds a network-adjustable set point, a change filter notification is indicated locally and over the MicroTech network.
Condensate Overflow Alarm
If a condensate overflow alarm is detected, the unit controller immediately disables the compressor . Once the overflow alarm disappears, the unit controller automatically resets the WSHP unit. The condensate overflow sensor is an exposed ring terminal located in the condensate drain pan. The condensate overflow alarm occurs only when the unit is in cooling mode.
McQuay IM 660-3 3
Configurable Relay Outputs
The MicroTech 2000 WSHP controller provides one relay output that can be configured for the following four options:
Boilerless system (skin heat) relay
Motorized water valve relay
Fresh air damper relay
Timed output relay (L
ONWORKS only)
These options can affect installation requirements and unit control. If more than one configurable relay output option is required, the MicroTech 2000 WSHP auxiliary board is required to provide the other three outputs. The MicroTech 2000 WSHP auxiliary board typically is factory mounted only in 2-compressor-circuit WSHP units. Only three relay outputs are available for use as configurable relay outputs in 2-circuit WSHP units. All configurable relay outputs are set to “no function” by default and must be field configured. A description of the four relay options follows.
Boilerless System/Auxiliary Heat Relay (LONWORKS only)
The relay receives loop water temperature input from the MicroTech Loop Water Controller through the gateway panel and provides relay output to electric heat on a call for heat after loop temperature falls.
Boilerless System/Auxiliary Heat Relay (LONMARK only)
The relay output energizes when the space temperature reaches the heating set point and de-energizes when the space temperature exceeds the heating set point plus a configurable differential set point (defaulted to 3°F).
Motorized Valve Relay
Figure 1: First control signal output
Terminal boards
(located externally on the WSHP chassis)
12345 67
IMPORTANT: To use onboard 24 VAC, change the jumper PF1 on the MicroTech 2000 controller from factory default pins 1 and 2 to pins 2 and 3.
Figure 2: Second control signal output
Terminal located on
MicroTech 2000 auxilliary board
J6
pilot duty relay
4321
24 VAC
pilot duty relay
(by others)
Use contacts as needed for option.
Figure 3: Third control signal output
Terminal located on
MicroTech 2000 auxilliary board
J7
4321
24 VAC
pilot duty relay
(by others)
EL UPC
24 VAC
(by others)
(by others)
24 VAC24 VAC
(by others)
24 VAC
The relay provides output to the motorized valve to shut off water through the unit when the compressor is not operating.
Fresh Air Damper Relay
The relay provides output to the open damper whenever the fan is operating in the occupied cycle.
Timed Output Relay (LONWORKS only)
The relay provides output to an auxiliary load to control its operation based on a specific time schedule different from that of the heat pump unit.
4 McQuay IM 660-3
Use contacts as needed for option.
Figure 4: Fourth control signal output
Terminal located on
MicroTech 2000 auxilliary board
J10
4321
24 VAC
pilot duty relay
(by others)
Use contacts as needed for option.
(by others)
24 VAC
Loading...
+ 14 hidden pages