Figure 12, Unit Control Panel detail....................................................................................26
Figure 13, Unit Control Panel connections..........................................................................27
Figure 14, Compressor Control Panel detail........................................................................28
Figure 15, Compressor Control Panel connections..............................................................29
Manufactured in an ISO Certified Facility
Illustrations and information cover McQuay International products at the time of publication and we reserve the right
to make changes in design and construction at anytime without notice.
IM 786Field Installation Procedure3
2003 McQuay International
4Field Installation ProcedureIM 786
Introduction
These procedures must be performed only by technicians with training and experience on
Westinghouse/McQuay centrifugal water chillers including, but not limited to, MicroTech Series
100 and 200 controllers and MicroTech II (MT II) controllers.
Before commencing any actual replacement work, review the entire procedure, step by step, for the
unit being considered. Also, study the unit to pinpoint the location of the new control components.
This should help prevent difficulties during the procedure.
The procedure consists of:
1. Disassembling of the old control components
2. Installing the MT II control panels
3. Installing new sensors and rewiring.
4. Installing and configuring new software and checking unit operation.
Building Automation Systems (BAS) Interface
Determine if the new chiller controls will be required to tie into the building’s BAS. If so, verify
that the communication protocol is BACnet, L
for these protocols can be obtained separately and field installed on the controller. MicroTech II
cannot talk to an existing BAS through McQuay Open Protocol Master Panels (OPM, CVPC,
CSC, and direct connections) that may be on the job. Communication module part numbers are:
ONTALK, or Modbus. Communication modules
L
ONMARK: 350147401
BACnet: 350147404
Modbus: 350147402
IMPORTANT: Because the new MicroTech II controllers utilizes open, standard protocols listed
above, they are not compatible with legacy MicroTech system controls which utilize legacy,
proprietary McQuay Open Protocol. Therefore, the new MicroTech II chiller unit control panel is
not compatible with the existing MicroTech Chiller System Controller (CSC), Chiller Plant
Controller (CPC), MicroTech Monitor software, MicroTech Network Master Panels (NMP), or
MicroTech Remote Monitoring and Sequencing (RMS) panels. Your McQuay Representative can
help you plan the efficient management of your MicroTech and MicroTech II chiller equipment with
your building’s chiller plant or overall building automation system as your building needs change.
IM 786Field Installation Procedure5
Disassembly
Important Note on Transferring Settings
Record all settings from the existing MicroTech 100 or 200 controller before de-energizing the panel
and removing it. Many of the settings will have to be changed from default later in the MT II
controller to configure the unit correctly. Forms are included on pages 6 and 7 to record settings.
MicroTech 200
Figure 1, MicroTech 200 Panel
Perform the following steps to record setpoint data from the existing MicroTech 200 control. See
manual OM 200 for detailed information.
ActionViewRecord/Ignore
Press Water SetpointsScreen 12, Water SetpointsRecord
Press Next MenuScreen 13, Motor SetpointsRecord
Press Next MenuScreen 14, Time/DateIgnore*
Press Next MenuScreen 15, ScheduleIgnore*
Press Next MenuScreen 16, ScheduleIgnore*
Press Next MenuScreen 17, Timers SetpointsRecord
Press Next MenuScreen 18-20, Tower SetpointsRecord
Press Next MenuScreen 21, Oil SetpointsRecord
Press Next MenuScreen 22, Alarms SetpointRecord
Press Next MenuScreen 23, Lead/Lag, dual compressorsIgnore
*The schedule function is not avaliable in the MTII
6Field Installation ProcedureIM 786
Figure 2, Existing Data Record: MicroTech 200
MicroTech 200
SettingValueSettingValue
Menu 12, Water Setpoints S creen 2
Screen 1 Stage 1 On
Spt Source Stage 4 on
Local Spt Stage 2 On
Startup DT Stage 3 On
Shutdn DTMenu 20 Tower Valve Control
Screen 2 Screen1
Chw Reset Valve control
Max lvg Spt Valve Spt
Return Spt Valve Deadb
No Reset at 70°F
Reset Signal Max position
Max reset
Screen 3
Pulldn Rate Sample Time
Amb Lockout
Menu 13, Motor Setpoints PA Time
Screen 1 Screen 3
Amp Reset Min Start Position
Active Spt Max Start Position
Reset Signal
Min Amp Spt Max Pos At
Network Spt
Max Amp Spt Screen 1
Screen 2 Feed Spt
Soft load No Start Diff
Begin Amp Lim Htr On Diff
Ramp TimeMenu 22, Alarms Setpoint
Menu 14, Time/Date
Screen 1 Low Evap Press Shutdown
Hh;mm;ss
Day
mm-dd-yy
Menu 15, Schedule High Discharge Temp Shutdown
Start-stop schedule
Menu 16, Schedule High Condenser Press Shutdown
Start-stop schedule
Menu 17, Timers Setpoints Motor Current Thres hol d
Screen 1 High Oil Feed Temp
Start to Start Low Oil Delta Temp
Evap recirc Screen 4
Stop to Start Low Net Oil Pressure
Menu 18 Pump Setpoints Low Disch Superht at Min RLA
Screen 1 High Disch Superht at Min RLA
Evap Pmp Screen 5
Cond Pmp Low Disch Superht at Max RLA
Menu 19 Cooling Tower Control High Disch Superht at Max RLA
Screen 1 Surge-High Suct Superht-St artinf
Tower Control Screen 6
Tower Stages Surge-High Suct Superht-Running
Stageup Time Evap Water Freeze
Stage Dn Time Cond Water Freeze
Stage Differential
N/A on MTII
N/A on MTII
N/A on MTII
N/A on MTII
N/A on MTII
N/A on MTII
N/A on MTII
N/A on MTII
N/A on MTII
N/A on MTII
Min position
Screen 2
Valve Type
Mod Limit
Max Change
Min Pos At
Menu 21, Oil Setpoints
Screen 1
Low Evap Press Unload
Low Evap Press Hold
Screen 2
High Discharge Temp Load
Screen 3
N/A on MTII
N/A on MTII
N/A on MTII
N/A on MTII
N/A on MTII
N/A on MTII
IM 786Field Installation Procedure7
MicroTech 100
Setpoints reside in three locations on the MicroTech control. There are eight buttons under
the “SETPOINT” heading, only three of which have information to be recorded as shown
below. The buttons are pressed three times to access three different sets of data. Refer to
manual IM 403.
Setpoint
Menus
Set-up
Options
Service
Setpoint
Menus
1. There are thirteen settings under the Service Setpoint button, accessed by repeatedly
pressing the button.
2. There are 18 settings under the Set-up Options button.
ActionViewAction
SETPOINTS
Press WATE R TEMPERATUREView LWT, Reset, Res etRecord Data
Press MAXIMUM AMP LIMITView Amp Limit, Remote Limit, Si gnalRecord Data
Press SOFT LOADView Soft Load, Beginning Amps , Ramp TimeRecord Data
SERVICE SETPOINTS
Press 13 timesView SetpointsRec ord 2-13
SET-UP O PTIONS
Press 18 timesView setpoint sRecord 1-18
8Field Installation ProcedureIM 786
Figure 3, Existing Data Record: MicroTech 100
MicroTech 100
SettingValue
SETPOINTS, Password Required
Press WATER TEMPERATURE
LLVG EVAP SPT
RESET LVG SIGThis is a Read Only Value
RMT RESET SIGThis is a Read Only Value
Press MA XI MU M AMP LIMIT
MAX AMP LIM
REMOT AMP LINThis is a Read Only Value
REMOT AMP SIG
Press SOFT LOAD
SOFT LOAD AMP
BEG AMP LIMIT
RAMP UP TIME
SET-UP OPTIONS, Password Required
RESET OPTIONS
MAX CHW RESET
ENT EVAP SPT
ENT EVAP TIMER
START MODE
START UP DELTA –T
SHUTDOWN DELTA -T
STARTTO START TIME
STOP TO START TIME
LOAD DELAY
COND PUMP TMR
TWR STG 1 ON
TWR STG 1 OFF
TWR STG 2 ON
TWR STG 2 OFF
ENABLE LAG
DISABLE LAG
DELAY TIMER
SERVICE SET-POINTS, Service Password Req’d
LOW MTR CURR
HOT GAS SPT
LOW OIL DELTA
CALC OIL STP
HIGH OIL FEED
LOW EVAP PRESS
LP OVERRIDE
HI DISCHARGE
HIGH SUCT RUN
HIGH SUCT OFF
HI COND PRESS
N/A on MTII
N/A on MTII
N/A on MTII
N/A on MTII
N/A on MTII
IM 786Field Installation Procedure9
WARNING
Electric shock hazard. Disconnect all power sources to the control box.
Existing MicroTech Control Panel
Chiller may need to be pumped down to allow installation of new pressure transducers and new
mechanical high pressure switch before removal of old control panel. As in every case, make sure
there is water flow during pumpdown.
CAUTION
1. Service on this equipment must be performed by trained, experienced refriger ation
personnel familiar with equipment operat ion, maintenance, correct servicing
preocdedures, and the safety hazards inherent in this work.
2.Anyone servicing this equipment must comply with EPA requirements reg arding
refrigerant r eclaim a t ion and venting.
1. De-energize power to existing MicroTech (MT) panel (lock and tag out).
2. Check with VOM for presence of voltage in the MT panel. Isolate and de-energize if present.
3. Check for and disconnect any BAS communication from motherboard or display board.
4. Identify all external wiring to and from the MT panel. Mark as necessary. Factory wiring
should be labeled with wire numbers.
5. Remove all external wiring and conduit.
6. Remove all temperature sensors and discard. MT II uses all new sensors, 10k versus 3k on the
older units.
7. Isolate refrigerant and oil lines connected to MT panel. Remove and cap to prevent loss of
refrigerant and oil. Isolate the oil sump while there is still some pressure in the system to
prevent moisture from entering the tank. This is particularly important on R-134a systems.
8. Remove solenoid coil, wires, and conduit from oil cooler valve, liquid injection valve (if
present), and motor cooling valve (if present). Any valves that are not Sporlan brand will have
to be replaced. Older controllers used 115V solenoids coils, MT II use 24V solenoids coils.
Alternately, 115V to 24V interposing relays can be added to operate the existing valves.
9. Remove old control panel from chiller.
10. In most cases it is easier to leave the existing lube box on the unit and mount the new
compressor control panel adjacent to it. Two pieces of angle iron can be installed on the existing
lube box supports, extending out to provide a mounting location for the new panel.
10Field Installation ProcedureIM 786
Lube Box (MT 100 with PSC oil pump motor shown)
There are two basic types of oil pump motors used on Westinghouse/McQuay centrifugal chillers.
Many early design chillers with all size compressors, and all chillers (including current production)
with compressor sizes CE050 and smaller use a Capacitor Start oil pump motor that has uses a
voltage relay. Chillers from approximately 1981 onward with compressor size CE063 and larger
use a Permanent Split Capacitor (PSC) oil pump motor which does not use the voltage relay. In
addition to the presence or absence of the voltage relay the two style motors use different overload
heaters and different capacitors. The same style oil pump motor will use slightly different value
capacitors when used in a 50 Hz application as opposed to a 60 Hz application.
To account for these differences some changes to the factory assembled compressor control panel
may be necessary as the kit is set up for a 60Hz PSC oil pump motor, and the chiller which the
upgrade kit is being installed in may be different. Details on the necessary changes are documented
in the following section.
1. Remove and discard oil pump contactor
(not shown). MT 200 has the pump
contactor in lube box, . MT 100 has
contactor in the control panel.
2. Remove Voltage Relay (not shown) if
present and discard. This is used only on
Capacitor Start oil pump motors, and not
on PSC oil pump motors. A new one is
included in the kit for mounting in the
compressor control panel.
3
4
6
5
3. Re-use Vane Close (VC) pressure switch.
4. Rewire terminal block as required and
document.
5. Remove and discard oil pump overload A
new overload is included in the
8
compressor control panel. This may need
to have its heater replaced with the
alternate. See following instructions.
6. Re-use SA/SB solenoid valve
7. Remove and discard oil pump capacitor(s) . A new capacitor is included in the compressor
control panel. This may need to be changed for one of the alternate capacitors, depending upon
the oil pump motor type and Hz. See following instructions.
8. Existing Oil Pressure (OP) switch can be re-used if desired. Wire NO contacts in starter MCR
circuit. MT 200 does not have this switch, the microprocessor senses the pressures and performs
this function.
7
IM 786Field Installation Procedure11
Loading...
+ 23 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.